1 PS 3 SF6-free 123 kv Substation Solution to meet Axpo s sustainability strategy C. LINDNDER 1), D. GAUTSCHI 2) 1) Axpo Power Ltd. 2) GE Grid Solutions SUMMARY As it is the strategic goal of Axpo Power AG to lower the CO2 footprint of its assets significantly in the future it is one of the primary goals to reduce the amount of SF6 in its network. Together with the transmission system operator EKZ, the Axpo Power AG is installing the world s first 123 kv GIS switchgear which runs with a mixture of C4F7N and CO2 close to the lake of Zurich in Switzerland. The substation is containing 4 bays of GIS of type F35g-145 kv which are connected via double secionalisers on the busbar. The two line bays are connected via high-voltage cables, the two transformers which are installed outdoor are directly connected using gas-insulated busducts and air bushings. The whole switchgear is designed to operate at low temperatures down to -25 C. While the substation is already under construction the release for production of the new type of GIS was given in the manufacturers plant. Gas handling carts, gas analysers and densimeters have been developed in parallel to the development of the switchgear. The gas is delivered on site premixed in bottles and the filling and evacuation process is similar to the one when using SF6. In general, most of the processes which apply to SF6 are also valid when using the new gas. This includes intervention procedures and maintenance cycles. An environmental analysis comparing different type alternative gases and gas mixtures was made and the results show that the new type of switchgear has the lowest CO2 footprint of all analysed types. The reduction in the CO2 footprint is around 70 % to the same switchgear filled with SF6. This leads to a reduction of about 700 t in the lifetime of the switchgear. The installation of this world s first of its type will contribute to achieve Axpo s ambitious goals in terms of CO2 reduction. Keywords Alternative Gases to SF 6 Fluoronited Nitriles GIS and GIB Global warming potential reduction Gas handling of alternative gases Christian Lindner, Christian.lindner@axpo.com David Gautschi, david.gautschi@ge.com 1
2 1. AXPO S SUSTAINABILITY STRATEGY Axpo Power AG has a strategic goal to be the most sustainable Swiss energy company. Besides the continuous increase of energy efficiency in production and distribution of electric energy, the continuous reduction of greenhouse gas emissions is part of Axpo s ecological sustainability goal. Because SF6 has an enormous greenhouse potential which is times higher than CO2 it is also one of the keys to reduce the amount of SF6 installed in the switchgear. In the past major reductions could be achieved by the installation of switchgear with low SF6 volumes and low leakage rates. In Figure 1 the evolution of the gas mass of the circuit-breaker (CB) and the common point (CP) of 145 kv GIS of different generations from the manufacturer GE are presented. The dotted blue line shows an exponential trend line for three-phase encapsulated GIS, the dashed red line the exponential trend line for single-phase encapsulated GIS. SF6 mass of CB & CP in kg Figure 1: Evolution of the SF 6 mass of 145 kv GIS (circuit-breaker and common point) [1] The dramatic decrease of the SF6 mass inside the switchgear and the reduction of the leakage rate lead to lower SF6 emissions in the past. But Axpo did not only take the SF6 emissions into account. For new substations the overall CO2 footprint of the substation over the full lifecycle from production and operation to dismantling was calculated and the results were used for the final product decision [2]. This approach is complex and many details must be provided by the manufacturers to be able to get an accurate picture. This includes for example the determination of the CO2 footprint of frames, heaters, instrument transformer burden etc. 2. SUBSTATION ETZEL For the 123 kv GIS substation Etzel in Switzerland a similar approach was used. But in the first time in history the new gas mixture containing the fluoronitrile C4F7N and CO2 as background gas will be used as insulation, switching and interruption gas. This gas mixture developed by GE and 3M combines the ability to achieve low ambient operating temperatures as today (-25 C) while using the same most compact design and for most components the same enclosures as the switchgear operating with SF6. This leads to the same physical footprint as the SF6 pendant. The substation will consist of 4 bays of 3 phase encapsulated 123 kv GIS (see Figure 2a) which are connected via a single busbar including a double sectionalizer. In addition, 10 bays of 16 kv Duplex Medium voltage cubicles in double bus bar arrangement and two kv / 16 kv power transfomers will be installed. The power transformers, which are installed in 2
3 outdoor condition, are connected with the switchgear using gas-insulated bushings and threephase encapsulated busducts. These components as well as the switchgear can operate at minimum temperatures of -25 C. The substation building is now under construction (see Figure 2b). The GIS will be delivered in autumn 2017 and it will be put in operation by spring a) b) Figures 2: a) 3D view of the GIS substation Etzel with transformer connections via GIL and bushings, b) Picture of the site beginning of June 2017 The substation Etzel is placed and put in operation in the Region Freienbach/Höfe near the lake of Zurich where the demand on electric energy is growing strongly above Switzerland s average growth rate. The project will be realized jointly between Axpo and the DSO EKZ of the region, which provide together electric energy to about 3.5 Million people. Figure 3: Geographic location of the substation Etzel and integration in the existing network During the quotation process, which had been launched in autumn 2015, GE proposed to Axpo the SF6-free GIS using 6 % C4F7N and CO2 as background gas. At that time, several type tests were not yet performed, but within a time frame of about 1 year, GE successfully proofed the design of this new GIS with all relevant type tests for all components (circuitbreaker, disconnector, earthing switches, instrument transformers, bushings and busducts). 3
4 3. BASIC GAS PROPERTIES During more than 20 years of research of alternative gases as a replacement of SF6 many different candidates have been tested. Possible candidate gases were N2, CO2 and O2 and gas mixtures like dry air [3]. The results showed all the same picture: All the candidates are not competitive because they need either much higher operating pressures or bigger dimensions to compensate the lack of dielectric withstand compared to SF6. Significantly higher operating pressures lead to bigger wall thickness which impact mass of enclosure material with negative influence on environmental figures, switchgear cost, etc. The research was therefore extended to gas mixtures based on synthetic gases. The gas which was introduced in the F35g GIS family is based on the fluoronitrile C4F7N and the background gas CO2. Basic data about the gas properties can be found in [4]. a) b) c) Figures 4: a) Breakdown voltage / pressure curve of SF 6 and C 4F 7N, b) Liquefaction curve of C 4F 7N c) Dielectric withstand of C 4F 7N when mixed with the background gas CO2 compared to SF6 The figure 4a shows that the nitrile C4F7N has in pure state around twice the dielectric withstand of SF6. The measurements were taken according to the ASTM D877 method using disk electrodes and a gap with 2.5 mm distance. In Figure 4b the liquefaction curve of C4F7N is presented. Due to the high boiling point of the pure molecule only around 0.5 bar pressure can be filled in when application temperatures down to -25 C are requested. This is the case in the substation Etzel, where the transformers are installed outside in ambient air and where the connection is done with gas insulated lines and air bushings. In Figure 4c the dielectric performance of the nitrile when mixed with the background gas CO2 is presented. Fortunately, the curve is not linearly depending on the mixing ratio. When the mixing ratio is between 4 % and 10 % the dielectric performance is in the range of 70 % to 90 % of SF6 at the same pressure. This lead to the concentration of 6 % C4F7N in 94 % CO2 for the substation Etzel. The missing 20% of the dielectric performance was compensated by a slight operating pressure increase of around 2 bars. Even though the dielectric behaviour of N2 when mixed with C4F7N looks like the curve in Figure 4c CO2 was used as background gas due to its remarkably higher breaking performance in the circuit-breaker. 4
5 4. INFORMATION ABOUT GAS HANDLING AND MAINTENANCE For equipment operators like Axpo it is of key importance to know the differences in gas handling, gas quality check and maintenance when talking about alternative gases. The following chapters answer these questions. In general, the application of the nitrile / CO2 mixture is not more complicated than the use of SF6 today. From the beginning GE had also an eye to develop gas handling equipment always together with at least two independent manufacturers to have a certain competition starting right from the beginning of the introduction of this new type of switchgear. To avoid any mistakes in gas handling the filling valve was adapted using another thread diameter than todays SF6 valves (see Figure 7c). 4.1 General information regarding the gas handling The mixture of the fluorinated nitrile C4F7N and CO2 is used in a closed cycle like SF6. The gas is delivered on site already premixed in bottles (Figure 5a). The mixing ratio of the delivered gas is checked in the manufacturing site. The filling or evacuation procedure is done in a similar way like today with SF6 directly from the bottle. A dedicated gas handling cart is used to fill or recover the gas from / to the GIS compartment. Filling carts are available from two different manufacturers (see Figures 5 b & c). Existing SF6 handling carts cannot be used because of the risk of liquefaction of C4F7N during the pumping operation which could result in a wrong mixing ratio in the equipment. a) b) c) Figures 5: a) Premixed gas in bottles, b) & c) Gas filling and recovery equipment from different manufacturers modified for the use of C 4F 7N The gas registration for example for the transport of the gas mixture is finished for most of the countries. The procedure in case of a major failure when a pressure relief device opens and the gas flows into the substation room remains the same as today with SF6. Also, the neutralisation of byproducts after a major failure or in case of maintenance remains the same. 4.2 Leek seakers and integral tightness test Before the delivery on site the GIS components are subjected to an integral tightness test. Test systems were developed and are existing (see Figure 6a). Multiple leek seekers to detect the exact location of a leek were developed and qualified. In Figure 6b a simple leek detector with acoustic alarm is displayed, in Figure 6c a more advanced handheld device which measures 5
6 also the ppm value of C4F7N. Detection systems for permanent monitoring of the C4F7N and CO2 quantitiy in the substation room are available also. a) b) c) Figures 6: a) Integral tightness test of the first with C 4F 7N and CO 2 filled 245 kv air-insulated current transformer, b) Simple acoustic leek seeker to detect small leaks, c) leak detector with integrated C 4F 7N concentration measurement 4.3 Gas quality check and gas monitoring Specially after the erection the percentage of the gases and the moisture content needs to be checked. In Figure 7a a portable gas quality analyzer is shown. These equipments are based on SF6 analyzers but of course some of the hardware components and the software were adapted to cope with the physical properties of the new gas mixture. a) b) c) a) Figures 7: a) C 4F 7N gas analyser, b) conventional densimeter adapted for the C 4F 7N gas, c) adapted DN20 filling valve For gas monitoring an adapted temperature compensated densimeter is sufficient. The densimeter presented in Figure 7b is used in the substation Etzel to check the gas pressure. These densimeters are available with different alarm contacts and analoge output. Also, pure electronic densimeters are available which can be integrated in an online-monitoring system for permanent temperature, pressure and density observation. For the substation Etzel conventional densimeters per Figure 7b will be installed. To avoid filling the components by mistake with SF6 a filling valve using a different thread diameter is used (Figure 7c). 6
7 4.4 Maintenance Even though that the actual IEC standards would allow higher leakage rates for non-sf6 gases than 0.5 % / year the actual design was made to be below this value. It was decided to follow the same rules as for SF6 today without the need to change the actual maintenance cycles. Tests have also shown that the leakage rate of C4F7N/CO2-switchgear with an adapted sealing system is in the same range as for similar SF6 equipment. The maintenance cycles therefore remain the same as for SF6 switchgear. 5. CO2 FOOTPRINT COMPARISON OF DIFFERENT ALTERNATIVE GASES 5.1. Studied cases As Axpo had already a broad know-how about life-cycle assessments of substations [2] it was clear that not only the CO2 footprint of the gas alone needs to be considered during the assessement of new technologies. As written in chapter 1 the whole life-cycle was illuminated and integrated in the study. The switchgear of type F35g-145kV which is delivered in the substation Etzel was compared with the same switchgear model using SF6. In addition, a switchgear using the alternative gas mixture based on C5-Ketone/CO2/O2 and a switchgear based on dry air and vacuum breaker technology were calculated and compared Calculation basis The CO2-footprint of the following parts were considered in the calculation: Material during the production of the GIS Material used for the substation building Joule losses during the whole life cycle Gas production Gas losses during the life cycle The following parameters were used for the calculation: Operation period: 40 years Nominal current: 2500 A Current profile: 80 % of the time at 625 A (25 % nominal current) 20 % of the time at 1500 A (60 % nominal current) Electricity mix: European electricity mix Leakage rate: 0.2 % / year 5.3. Results of the calculation In Figure 8 the results of the calculation are summarised. It is visible that the CO2-footprint of the new gas mixture F35g-145kv (g3) is around 70 % lower than the SF6 switchgear F35-145kV (SF6). If only the gas losses are compared, then the reduction of the global warming potential impact is more than 99 %. If the leakage rate is increased from 0.2 % / year to the value of 0.5 % / year as stated in IEC then the reduction is even higher. The switchgear of type F35g-145kV has the lowest CO2-footprint of all the compared alternative gases. This is the case because the switchgear using C4F7N has the same size as the equipment filled with SF6. Most of the components are the same. The switchgear of type 7
8 F35g-145kV is the most compact switchgear on the world market. For the other alternatives, additional limitations for example in the operating temperature range may occur in addition. Figure 8: CO 2 footprint comparison of a 145 kv GIS SF 6 switchgear with alternative gas technologies. 6. CONCLUSION AND OUTLOOK The substation Etzel is under construction at the moment. The release for production for the new type of switchgear F35g-145kV was also given in the manufacturing site of GE in Oberentfelden, Switzerland. It will be the first of its kind by using the alternative gas C4F7N and CO2 as background gas. By introducing this type of switchgear, it is possible for the utility Axpo to save around 700 t of CO2 during its lifetime of 40 years when assuming a leakage rate of 0.2 % / year. This corresponds to around 470 flights from Zurich to Miami in eonomy class. The introduction of this pilot project in the network will support to reach the ambitious sustainability strategy of Axpo. BIBLIOGRAPHY [1] D. Gautschi, K. Pohlink, R. Lüscher, Y. Kieffel: Limitations, trends and potentials in the design of modern gas-insulated high voltage switchgear. CIGRE Session 2014, Paper B3-112, Paris, August 2014 [2] C. Lindner et al.: Environmental analysis of different technologies for as Swiss high-voltage substation, CIGRE Session 2010, Paper B3-205, Paris, August 2010 [3] M. Hairbour et al.: Dielectric Withstand of N 2, CO 2 and SF 6 in GIS, CIGRE SC B3, Publication No. 203, Berlin, 2007 [4] Y. Kieffel et al.: SF 6 alternative development for high voltage switchgears. CIGRE Session 2014, Paper D1-305, Paris, August
Innovation Electrical Industry
Position Paper Potential for Optimising the Use of SF6 in Switchgear Automotive Industry 4.0 Energy Efficiency Digitalisation 4.0 Innovation Electrical Industry 16 November 2016 ZVEI German Electrical
More informationLOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES
LOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES Magne SAXEGAARD Elham ATTAR Martin KRISTOFFERSEN ABB - Norway ABB - Norway ABB - Norway magne.saxegaard@no.abb.com elham.attar@no.abb.com martin.kristoffersen@no.abb.com
More informationNordel GRID DISTURBANCE AND FAULT STATISTICS
Nordel GRID DISTURBANCE AND FAULT STATISTICS Table contents Table contents Page 1 Introduction... 3 1.1 Contact persons... 4 1.2 Guidelines the statistics... 4 1.3 Voltage levels in the Nordel network...
More informationTECHNICAL PAPER PRESENTATION
1 W E L C O M E T O A C O M E T 2 0 1 7 TECHNICAL PAPER PRESENTATION 2 INSULATION AND SWITCHING IN ENVIRONMENTALLY FRIENDLY GASES BY JAVIER MANTILLA 3 A B O U T T H E A U T H O R BRIEF BIO JAVIER MANTILLA
More informationNeil Kane Managing Director EMT UK
Neil Kane Managing Director EMT UK SF6 Measurement, Analysis, Diagnostics and Leak Detection Our goals at EMT are to supply Maintenance Operatives with the very best tools to protect both personnel and
More informationSF 6. Gas Handling. DILO. Sustainably tight. Made in Germany
Gas Handling DILO. Sustainably tight. Made in Germany DILO gas handling Zero emissions and maximum gas re-use is our goal For more than 40 years it has been our aim to meet customer requirements for first-class
More informationCOLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE SUMMARY
COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE R. L. Middleton, P. Eng. Manitoba Hydro, Winnipeg, Canada SUMMARY Very low temperatures stress
More informationNORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2014
NORDIC AND BALTIC GRID DISTURBANCE STATISTICS 2014 21.10.2015 REGIONAL GROUP NORDIC 1 INTRODUCTION... 4 1.1 DESCRIPTION OF THE REPORT... 4 1.2 CONTACT PERSONS... 5 1.3 VOLTAGE LEVELS IN THE NORDIC AND
More informationB kv pilot installation with a ketone based insulation gas with first experience from operation in the grid. D. TEHLAR ABB - Switzerland
2016 Paris Session http : //www.cigre.org B3-105 170 kv pilot installation with a ketone based insulation gas with first experience from operation in the grid T. DIGGELMANN ABB - Switzerland D. TEHLAR
More informationSF 6 Product Guide. Gas Analysis Instruments and Accessories
SF 6 Product Guide Gas Analysis Instruments and Accessories Cambridge Sensotec Ltd specialises in the design and manufacture of gas analysis equipment under the Rapidox brand name. Based in the UK, the
More informationGas density monitor With integrated transmitter Model GDM-100-TI
SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed
More informationMITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC
MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC Jérôme DOUCHIN Yann CRESSAULT Raphael Danjoux Schneider Electric France Toulouse University France FLIR France Jerome.douchin@ cressault@laplace.univ-tlse.fr
More informationMicafil RIP bushings High-voltage Resin Impregnated Paper bushings. Power and productivity for a better world TM ABB
Micafil RIP bushings High-voltage Resin Impregnated Paper bushings Power and productivity for a better world TM ABB Leading in Bushings Technology: ABB Micafil ABB Micafil has been closely associated with
More informationMicafil RIP bushings High-voltage Resin-Impregnated Paper bushings. Power and productivity for a better world TM ABB
Micafil RIP bushings High-voltage Resin-Impregnated Paper bushings Power and productivity for a better world TM ABB Leading in Bushings Technology ABB Switzerland Ltd has been closely associated with innovation
More informationInsulating Gas Management Program
DILO 2 nd Annual SF 6 Gas Management Seminar Tampa FL, November 2017 Zero Emissions. No Substitutes. Insulating Gas Management Program Manitoba Hydro November 16, 2017 Doug Dyck Interrupting Equipment
More informationThis multi-functional device allows the determination of up to six quality parameters with only one measurement:
Devices for determination of the gas quality For verification of several parameters in one operation 3-038-R... Multi-Analyser without return system 3-038R-R... Multi-Analyser with return system This multi-functional
More informationUsing Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands
21, rue d Artois, F-75008 PARIS CIGRE US National Committee 2012 Grid of the Future Symposium http : //www.cigre.org Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems
More informationAdvanced Test Equipment Rentals ATEC (2832) OMS 600
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OMS 600 Continuous partial discharge monitoring system for power generators and electrical motors Condition monitoring
More informationC I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005
RELIABILITY AND LONG TIME BEHAVIOUR OF MV-DISTRIBUTION SWITCHGEAR IN SEVERE ENVIRONMENTAL CONDITIONS - EXAMINATION OF SF 6 -INSULATED RING MAIN UNITS (RMU) UP TO 20 YEARS IN SERVICE. B. I. Oftedal, Siemens
More informationSF 6. Gas Handling. DILO. Sustainably tight. Made in Germany
Gas Handling DILO. Sustainably tight. Made in Germany 1 Table of contents information / General 04 08 gas refilling and evacuating devices 09 26 gas service carts 27 84 Micro Series 31 34 Mini Series
More informationAnalysis of Pressure Rise During Internal Arc Faults in Switchgear
Analysis of Pressure Rise During Internal Arc Faults in Switchgear ASANUMA, Gaku ONCHI, Toshiyuki TOYAMA, Kentaro ABSTRACT Switchgear include devices that play an important role in operations such as electric
More informationMODELING&SIMULATION EXTRAPOLATED INTERNAL ARC TEST RESULTS: A COUPLED FLUID-STRUCTURAL TRANSIENT METHODOLOGY
MODELING&SIMULATION EXTRAPOLATED INTERNAL ARC TEST RESULTS: A COUPLED FLUID-STRUCTURAL TRANSIENT METHODOLOGY Jérôme DOUCHIN Schneider Electric France Jerome.douchin@schneider-electric.com Ezequiel Salas
More information23.1 Functions, Basic Configuration, and Interfaces
23 (6.6.D) SF 6 and Other Special Gases 23.1 Functions, Basic Configuration, and Interfaces 23.1.1 Functions The primary function performed by the SF 6 and other special gases system is to provide SF 6
More informationBreakdown Performance of Vacuum Circuit Breakers Using Alternative CF 3 I-CO 2 Insulation Gas Mixture
14 P. Widger et al.: Breakdown Performance of Vacuum Circuit Breakers Using Alternative CF 3 I-CO 2 Insulation Gas Mixture Breakdown Performance of Vacuum Circuit Breakers Using Alternative CF 3 I-CO 2
More informationTECHNICAL SPECIFICATION. SPC-1 Stirling Process Cryogenerator
TECHNICAL SPECIFICATION SPC-1 Stirling Process Cryogenerator Reference 80 8013 00 Issue Date August 1, 2015 1. INTRODUCTION This document contains detailed technical information and specifications for
More information6-way characterised control valves DN15 / DN 20 / DN 25
6-way characterised control valves DN15 / DN 20 / DN 25 Table of contents Introduction 2 Project planning 2 Structure of the 6-way characterised control valves 2 Range of use 2 Characteristic curve 3 Flow
More informationTECHNICAL SPECIFICATION. SPC-4 Stirling Process Cryogenerator
TECHNICAL SPECIFICATION SPC-4 Stirling Process Cryogenerator Reference 80 8043 00 Issue Date August 1, 2015 1. INTRODUCTION This document contains detailed technical information and specifications for
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More informationPower Unit 075. Maintain Substation Circuit Breakers
Power Unit 075 Maintain Substation Circuit Breakers The specification details the required skills, knowledge and behaviours to establish competence to carry out the maintenance of high voltage power circuit
More informationRecent development of SF6 alternative gases for switching applications
Recent development of SF6 alternative gases for switching applications Authors: M. Seeger, R. Smeets, J. Yan, H. Ito, M. Claessens, E. Dullni, L. Falkingham, C. M. Franck, F. Gentils, W. Hartmann, Y. Kieffel,
More informationProcedure of Xenon Transfer
Procedure of Xenon Transfer Feng Zhou,MIT CC: Martina Green February 28, 2005 In this write up, we discuss the procedure on how to transfer xenon to a designed gas storage vessel that supplies xenon to
More informationPower Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers
Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling
More informationStandard. Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R Version 1.0, June 2018
Standard Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R565990 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared
More informationSafety Manual VEGAVIB series 60
Safety Manual VEGAVIB series 60 NAMUR Document ID: 32005 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions... 6 1.4 Setup... 6 1.5 Reaction
More informationThis test shall be carried out on all vehicles equipped with open type traction batteries.
5.4. Determination of hydrogen emissions page 1 RESS-6-15 5.4.1. This test shall be carried out on all vehicles equipped with open type traction batteries. 5.4.2. The test shall be conducted following
More informationOnline DGA-monitoring of power transformers
Online DGA-monitoring of power transformers Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 Vaisala Webinar content 1. Dissolved gases why and which gases 2. Fault
More information1. Functional description. Application program usage. 1.1 General. 1.2 Behavior on bus voltage loss and bus voltage. 1.
Application program usage product family: Product type: Manufacturer: Name: Order-No.: Valve actuators Constant valve actuator Siemens Valve actuator AP 562/02 5WG1 562-7AB02 Commissioning For commissioning
More informationTesting Distribution Switchgear for Partial Discharge
Testing Distribution Switchgear for Partial Discharge Mr. Neil Davies Affiliation: EA Technology Ltd, UK; neil.davies@eatechnology.com ABSTRACT Over the past 30 years handheld instrumentation has been
More informationTest pumps. Pressure sources. Good reasons for proper and reliable calibration
Test pumps Pressure is one of the most commonly measured quantities in engineering, which is why exact and reliable pressure measurement is especially important. However, the characteristics of the even
More informationSafety Manual. Process pressure transmitter IPT-1* 4 20 ma/hart. Process pressure transmitter IPT-1*
Safety Manual Process pressure transmitter IPT-1* 4 20 ma/hart Process pressure transmitter IPT-1* Contents Contents 1 Functional safety 1.1 General information... 3 1.2 Planning... 4 1.3 Instrument parameter
More informationh2000 plus HyDROGEN LEAk DETECTOR
H2000 plus hydrogen leak detector hydrogen leak detector h2000 plus Fast, easy to use, and durable. Leak testing with Hydrogen tracer gas The Hydrogen Method Detecting leaks using Hydrogen, called the
More informationMarc McMullen. Physics Detector Support Group
Marc McMullen Physics Detector Support Group Hall B Gaseous Detectors 1. Drift Chamber (DC) 2. Low Threshold Cherenkov Counter (LTCC) 3. High Threshold Cherenkov Counter (HTCC) 4. Silicon Vertex Tracker
More informationLubricating Oils Hydraulic Oils Turbine Oils Cutting and Cooling Mineral Oils Compressor Oils Synthetic Fluids Insulating Oils Quenching Oils
HIGH VACUUM DEGASFICATION Model E865A & EHV Enervac's High Vacuum Process is used for the dehydration and degasification of electrical insulating liquids including transformer oils, polybutene and silicone
More information973-SF 6 Analyzer. Precise and Stable SF 6 Gas Analyzer REFLECTING YOUR STANDARDS
Precise and Stable SF 6 Gas Analyzer Simultaneous measurement of humidity, SF 6 purity and SO 2 concentration Integrated gas recovery system with automatic pump back Fully automated SF 6 gas testing Fundamental
More informationGAS INSULATED SWITCHGEAR
GV3N 36kV 630A...2500A 25/31.5kA GAS INSULATED SWITCHGEAR Safe Reliable Compact Answer For Reliable and Efficient Network The switchgear specialist www.tamco.com.my Introducing TAMCO GV3N up to 36kV 25/31.5kA
More informationMass Flow Controller (MFC) for Gases
Mass Flow Controller (MFC) for Gases Type 8713 can be combined with... Direct flow measurement by MEMS- Technology for nominal flow rates from 1 ml N /min to 8 l N /min (N 2 ) High accuracy and repeatability
More informationH 2. Sensor Series Take no risk! Install a Hydrogen Sensor in your Gaschromatograph
Sensor Series 9000 Take no risk! Install a Hydrogen Sensor in your Gaschromatograph Carrier Gases for GC Probably more than 90% of the present GC instruments run with helium as carrier gas. Some people
More informationField Instruction Storage, Handling, Transport and Disposal of Sulphur Hexafluoride (SF6) Gas
6.14 Storage, Handling, Transport and Disposal of Sulphur Hexafluoride (SF6) Gas Purpose Describe the minimum requirements for safe handling, storage, maintenance, repair, transport and disposal of equipment
More information" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>
" High Voltage Switch Yards & How Safe are these really" High Voltage Forum Brisbane 2013 Duty of Care As part of an asset owner Duty of care
More informationSafety Manual VEGAVIB series 60
Safety Manual VEGAVIB series 60 Contactless electronic switch Document ID: 32002 Contents Contents 1 Functional safety... 3 1.1 General information... 3 1.2 Planning... 4 1.3 Adjustment instructions...
More information6-way characterised control valves DN15 and DN 20
6-way characterised control valves DN15 and DN 20 Table of contents Introduction 2 Project planning 2 Structure of the 6-way characterised control valves 2 Range of use 2 Characteristic curve 3 Flow direction
More informationIEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)
IEC 62271-200 April 2004 Authorized Sole Agent : PT. Wisma Niagatama Perkasa Phone : (031) 5041242 Fax. : (031) 5044580 IEC 62271-200 Introduction Scope This standard specifies requirements for factory-assembled
More informationCMC Series Moulded Case Circuit Breaker Cielo Electric
Model name CMC: Series 225: mpere frame size Line side terminal In: Rated current Ue: Rated operational voltage Icu: Rated ultimate short-circuit breaking capacity Ta: mbient temperature In: 225 Icu: 55k@415V
More informationThe RCM Analyst - Beyond RCM
The RCM Analyst - Beyond RCM darylm@strategic-advantages.com About the Author: Daryl Mather was originally trained in RCM in 1991, after which he was involved in the application of the method through a
More informationdeltaflowc deltaflowc Venturi or Probe
deltaflowc Mass Flowmeter for Gases - Multivariable with ultra fast dp, p and T-sensors - Compact, accurate and user-friendly - Ideal for OEMs deltaflowc Venturi or Probe Precise mass flow metering deltaflowc
More information2/2-Way Solenoid Control Valve
2/2-Way Solenoid Control Valve Excellent range (1:200) Very good response Compact valve design Orifice sizes 0.05... 2.0 mm Port connection 1/8 or sub-base Type 2871 can be combined with Type 8605 Digital
More informationASX 176 Axial Pressure regulator
ASX 176 Axial Pressure regulator ASX 176 Classification and Area of Application ASX 176 is a downstream pressure regulator, pilot controlled, for medium and high pressure applications. It is particularly
More informationSM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service
SM6 Anglais MV distribution factory built assemblies at your service instructions for use connection with compartment for incoming cable from the top foreword... 3 symbols and conventions... 3 as per iso
More informationIt is essential that the maintenance staff is qualified for electrical works and follows safety procedures.
MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained
More informationOn-Stream Tightness Testing of Vacuum Process Installations
ECNDT 2006 - Tu.2.6.3 On-Stream Tightness Testing of Vacuum Process Installations André de JONGE, Leak Detection Group, DCI Meettechniek B.V., Kapelle, The Netherlands DCI Meettechniek. -DCI was founded
More informationTank Blanketing Pressure Regulators RHPS Series
www.swagelok.com Tank Blanketing Pressure Regulators RHPS Series Types: pressure reducing and vapor recovery 16L stainless steel construction 1/2, 1, and 2 in. end connections Working pressures up to 22
More informationEXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS
The 9 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 25 EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS
More informationGuidelines to the standard IEC60601
EUROPEAN POWER SUPPLY MANUFACTURERS ASSOCIATION (Visit the EPSMA website at www.epsma.org) Medical Approvals for Power Supplies Guidelines to the standard IEC60601 Revision Date: 2009-09-12 This document
More information2/2-Way Proportional Valve (motor-driven)
2/2-Way Proportional Valve (motor-driven) Type 3280 can be combined with Seat valve with stepper motor - actuator isolated from flow path Excellent range (1:100) Low power consumption Fast response Orifice
More informationEFFECTIVE CONDITION ASSESSMENT OF MV SWITCHGEAR
EFFECTIVE CONDITION ASSESSMENT OF MV SWITCHGEAR Author & Presenter: Chris Lowsley BEng Technical Services Director, EA Technology Co-author: Neil Davies BEng MSc Products Director, EA Technology Co-author:
More informationLINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER
LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER Michael T Tang, Ph.D. Grace Feng Greg Merideth Rui Huang Matheson Gas Applied Lab
More informationThe New PHD 4 Portable Helium Detector
The New PHD 4 Portable Helium Detector SPECIAL FEATURES: High Sensitivity to Helium Easy to Use Truly Portable Versatile Dependable The system is designed to allow easy replacement of sampling line components
More informationSUBSTATION MAINTENANCE ELECTRICAL OPERATING PROCEDURE
Page 1 of 6 A. PURPOSE AND SCOPE This procedure establishes safe working practices for handling sulfur hexafluoride (SF 6 ) gas and release minimization practices. This document also specifies methods
More informationGas Network Craftsperson
Gas Network Craftsperson Unit EIAU016 Carrying out Fault Diagnosis on Electrical Equipment and Circuits This assessment specification has been developed as part of the network maintenance craftsperson
More information628 Differential Pressure Decay Leak Tester
628 Differential Pressure Decay Leak Tester The 628 puts Uson s industry leading differential pressure decay sensitivity in your hands and in your budget with no compromise in quality, reliability, and
More information2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications
Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity
More informationPSSI 10 Plant and Apparatus Containing Dielectric Gas
1. SCOPE This Safety Instruction applies the principles established by the ScottishPower Safety Rules (Electrical and Mechanical) and the Company Safety Instructions to achieve Safety from the System for
More informationPRC CO ² -LASER PRESENTATION
Page 1 of 7 PRC CO ² -LASER PRESENTATION GENERAL CHARACTERISTICS - Embedded PC104 Electronics with exchangeable software allowing very easy integration of customer specified functions: such as eg. specific
More informationPoint level switches for safety systems
Point level switches for safety systems By: Bill Sholette Level Products Business Manager Northeast US - Endress+Hauser Point level switches are often used in applications designed to prevent accidents.
More informationAUTOMATIC HOSE TEST UNIT, TYPE SPU
VALVES AND FITTINGS UP TO 14,000 BAR TEST AND CONTROL EQUIPMENT H IGH PRESSURE TECHNOLOGY AUTOMATIC HOSE TEST UNIT, TYPE SPU Pressure range from 1 up to 10,000 bar User-friendly touch panel operation HIGH-PRESSURE
More informationMass Flow Controller (MFC) for Gases
Mass Flow Controller (MFC) for Gases Bypass MFC with capillary technology for nominal flow rates from 5 ml N /min to 15 l N /min Applicable for aggressive gases Compact design and digital communication
More informationMETHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the
1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method
More informationWhat I have learned about SF 6 gas testing.a Practical explanation
What I have learned about SF 6 gas testing.a Practical explanation Over the past few years, testing of SF6 gas quality has become increasingly important and with the EPA in USA, setting guidelines for
More informationOIL AND GAS INDUSTRY
This case study discusses the sizing of a coalescer filter and demonstrates its fouling life cycle analysis using a Flownex model which implements two new pressure loss components: - A rated pressure loss
More informationRMG 5020 Gas Pressure Regulator Enabling Dependable Gas Operations
RMG 5020 Gas Pressure Regulator Enabling Dependable Gas Operations Proven Technology. Superior Performance. Today s natural gas industry has a growing demand for operational excellence. Pilot-operated
More informationHigh Pressure Compressed Air and Gas Solutions
High Pressure Compressed Air and Gas Solutions Intelligent Air Technology World leaders in the manufacture and commissioning of high pressure compressors for industry It is not by accident that CompAir
More informationEXPERIENCE WITH A PRE-SERIES SUPERFLUID HELIUM TEST BENCH FOR LHC MAGNETS
EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH European Laboratory for Particle Physics Large Hadron Collider Project LHC Project Report 388 EXPERIENCE WITH A PRE-SERIES SUPERFLUID HELIUM TEST BENCH FOR LHC
More informationTIGHTNESS. Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements.
TIGHTNESS Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements. ODU has the necessary expertise for developing and manufacturing connectors
More informationDistributed Control Systems
Unit 41: Unit code Distributed Control Systems M/615/1509 Unit level 5 Credit value 15 Introduction With increased complexity and greater emphasis on cost control and environmental issues, the efficient
More informationHYDROGEN - METHANE MIXTURES : DISPERSION AND STRATIFICATION STUDIES
HYDROGEN - METHANE MIXTURES : DISPERSION AND STRATIFICATION STUDIES A. Marangon, M.N. Carcassi Department of Mechanical, Nuclear and Production Engineering, University of Pisa, Via Largo Lucio Lazzarino,
More informationMathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption
Mathieu Guertin Director Europe, Russia and Africa Morgan Schaffer Inc. Canada A cost effective strategy for smart grid technology adoption Why protecting assets? Cost of fault: $52 MILLIONS!!! Easy ROI
More informationMathematics of Planet Earth Managing Traffic Flow On Urban Road Networks
Mathematics of Planet Earth Managing Traffic Flow On Urban Road Networks Adrian George Manager Network Improvements Anthony Fitts Manager Signal Design Melbourne s transport demands are growing 5m people
More informationPressure on Demand. Air Pressure Amplifiers
Pressure on Demand Air Pressure Amplifiers Introduction Haskel air pressure amplifiers offer the most comprehensive range in the industry combining simple principles of operation with rugged construction
More informationProportional valves with piezo technology in medical technology
Proportional valves with piezo technology in medical technology You develop high-end medical technology. You expect solutions that meet your specific needs. We deliver customised and value-adding solutions.
More informationCompiled by: B Beard. Approved by: SH Carstens. Description of requirements and procedures for compact provers to be used as verification standards.
1. Scope Description of requirements and procedures for compact provers to be used as verification standards. 2. Reference documents Trade Metrology Act SANS1698 3. Policy A. BASIC REQUIREMENTS Compact
More informationPro-V Multivariable Flowmeter Model M22 In-line Vortex
Pro-V Multivariable Flowmeter Model M22 In-line Vortex Pro-V TM Advantage: Volumetric or mass flow monitoring of most liquids, gases, and steam Multivariable meter delivers mass flow, temperature, pressure,
More informationPHOENIX L300i Best-in-class Helium Leak Detectors
180.85.02 Best-in-class Helium Leak Detectors The perfect Helium leak detector matching your demands The helium leak detector opens up new dimensions of productivity and reliability for your applications.
More informationTechnical Data Sheet MF010-O-LC
Technical Data Sheet MF010-O-LC - 1 - 1. Properties The oxygen measuring system MF010-O-LC determines the oxygen content in gas mixtures up to a temperature of 250 C. It is particularly suitable for the
More informationInternal Arc Simulation in MV/LV Substations. Charles BESNARD 8 11 June 2009
Internal Arc Simulation in MV/LV Substations Charles BESNARD 8 11 June 2009 The Internal Arc Fault The fault A highly energetic and destructive arc (10, 20, 40 MJ!) The effects and the human risks Overpressures
More information11 Air ends 12 Motor 13 Belt driven. 1. ELECTRONIC REGULATION The ES4000 is a control system, designed for medium and high power compressors.
Infinity CSC & CSD Rotary Screw Compressor Range Infinity CSC/CSD compressors are a compact, easy to install range, offering belt or gear driven, fixed or variable speed models. Requiring minimal maintenance,
More informationMedium Voltage Switchgear. Installation Manual for Pressure Relief Ducts
Uniswitch Medium Voltage Switchgear Installation Manual for Pressure Relief Ducts TABLE OF CONTENTS 1 Summary... 1 2 Transportation and storage... 2 2.1 Condition on delivery... 2 2.2 Unpacking at installation
More informationBPZM-MRD Nitrogen Injection System
BPZM-MRD Nitrogen Injection System (Transformer protector) Overview BPZM-MRD Nitrogen Injection Explosion Prevention & Fire Protection System became more advanced fire protection and explosion prevention
More informationGas Vapor Injection on Refrigerant Cycle Using Piston Technology
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Gas Vapor Injection on Refrigerant Cycle Using Piston Technology Sophie
More informationOfficial Journal of the European Union L 92/3
3.4.2008 Official Journal of the European Union L 92/3 COMMISSION REGULATION (EC) No 303/2008 of 2 April 2008 establishing, pursuant to Regulation (EC) No 842/2006 of the European Parliament and of the
More informationDISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS
DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University
More information