FX134, FX1234, FX3030 Problem and Solutions

Similar documents
OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N

FAULT CODE TROUBLESHOOTING INDEX

COMPRESSOR REPLACEMENT PROCEDURE (R-134A)

R E D I C O N T R O L S

Running the LiCor 6400 Infra Red Gas Analyzer (IRGA) with 4 whole-plant cuvettes attached

COMPRESSOR MANUAL. (888)

Section 3- Repair and Calibration Procedures

CO 2. (R744) Service Station Presentation. Contents. Goals Basic functions Specification Recovery R477 Vacuum Charge Safety Other features Prototype

Instruction Manual Recovery Station

OPERATING INSTRUCTIONS

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3

KKT Training Series: ECO Series, Preventative Maintenance

Rejuvenation Instructions

KJ4000 Operating Instructions & Parts Manual NSN

REDI CONTROLS, INC. Model RS-503/13-C3. RECOVERY SYSTEM for Very High Pressure Refrigerants R-13, R-23, R-503, & SUVA-95

Mass Spec will not Autotune

Product Sheet Spraymist Unit

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

Installation Instructions

NGP-250/500 Nitrogen Generator Quick Start Guide

Installation Instructions

STREAMLINE SHOP SERIES MODEL 30040V OPERATION & PARTS MANUAL

Marschalk Model # 94000

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

Refrigerant Recovery, Recycling and Recharging Station

Installation Instructions

OPERATION MANUAL ID900

AUTOMATIC TIRE INFLATOR # MW-60, MW-60-4WAY & MW-64HP

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

RG6000. Refrigerant Recovery Machine. Operating Manual. 99 Washington Street Melrose, MA Phone Toll Free

Operating Manual. Model 25200B/25202B Refrigerant Recovery Unit. (Not for use in automotive R-134a applications)

with O 2 Controller Instruction Manual

Refrigerant Recovery System Model 3600 Part No

In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure

DRS4-RM Manual. Set Up Instructions for DRS4 Series Single Tank

Installation Instructions

Aquavar SOLO 2 Frequently Asked Questions

RecoverXLT2-AP Oil-Less Universal Refrigerant Recovery System Operation and Maintenance Manual

Diagnostic codes Introduction. 6.2 Reference Tables SECTION

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

GETZ EQUIPMENT INNOVATORS RECOVERY SYSTEM CLEAN AGENT FE-36 / HALOTRON 1 PART NO. 4G59751 OPERATIONS MANUAL

INSTALLATION & MAINTENANCE INSTRUCTIONS

D10S/D20S Wall/Post Mount Inflator Quick Start Manual

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER COMPRESSOR For your personal safety please read, understand and follow the information provided in

1 HP / 1.6 GALLON AIR COMPRESSOR OPERATING MANUAL

ProMaster Troubleshooting Guide

RAM 4021 Operation Manual

LENNOX SLP98UHV DIAGNOSTIC CODES

Code AWC20HP Air Compressor

RecoverXLT Oil-Less Universal Refrigerant Recovery System. (For serial numbers and higher)

Operation and Maintenance Manual

The Discussion of this exercise covers the following points:

2 HP / 4 GALLON AIR COMPRESSOR OPERATING MANUAL

RecoverXL and RecoverXLT Oil-Less Universal Refrigerant Recovery Systems Operation and Maintenance Manual

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

AMS SUPER SILENT COMPRESSOR USER & MAINTENANCE GUIDE

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Inert Air (N2) Systems Manual

QBS Electronic Pressure Regulator

Portable Oil Lube Air Compressors

AA-75CF Portable Air Compressor NSN:

Model 3600-R410A. Part No Instruction Operation & Maintenance

Concentrate Distribution System (Stand Mounted) A-CDS-70-X & A-CDS-TANK-X-ST Industrial Drive, Orlinda, TN 37141

Fieldpiece. Refrigerant Recovery Machine OPERATOR'S MANUAL. Model MR45

Fieldpiece. Refrigerant Recovery Machine OPERATOR'S MANUAL. Model MR45

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Operating Instructions Model and Hydrostatic Test Pump

Electro-hydraulic control valve - Calibrate - Remote valve calibration

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

Operating Instructions Part No

BUBBLER CONTROL SYSTEM

Columbus Instruments

STREAMLINE SHOP SERIES MODEL OPERATION & PARTS MANUAL

450P AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

SPECIFICATIONS APCEPH1

VACUUM REGULATORS CONTENTS

Instruction Manual VCG-6

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

Installation of Your SprayMaster System

DPC-30 DPC-100. Reference Manual

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

AC1810 / AC1810-A TECHNICAL SPECIFICATIONS. Operating Pressure psi ( kgs/cm²) [AC1810] Displacement. Net Weight

NTF-515. Operation Manual

24 Litre Air Compressor

CentriFlow Meter Integrated Air Entrainment System

PC1131 Electric Air Compressor

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

Universal Valve Company Inc

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION SPECIFICATIONS. CE (EMC) Compliant

200 PSI HIGH-FLOW AIR SOURCE KIT

RAM Operation Manual

SomnoSuite FAQ. Setup. Calibration 4. What are the calibration requirements for the SomnoSuite? Settings

High Performance Oilless Commercial Refrigerant Recovery Unit. User Manual Rev. 4 November 2010

444C DUAL PERFORMANCE VALUE PACK

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

JAVAC EVO-HS REFRIGERANT RECOVERY MACHINE

400C & 450C DUAL PERFORMANCE VALUE PACKS

Calcium Reactor. CalcFeeder PRO. User Manual 1.1a. Model. CalcFeeder AC1 PRO CalcFeeder AC2 PRO CalcFeeder AC3 PRO CalcFeeder AC4 PRO

Transcription:

FX134, FX1234, FX3030 Problem and Solutions Unit Will Not Power Up Turn the power switch on. The unit LCD will display revision program and filter life within 3 to 5 seconds after turning on unit. If this process does not happen then see the trouble shooting tips below. 1. Check power cord is firmly plugged into unit all the way. 2. Check Circuit breaker on unit. Check that it is not tripped. 3. Check power source to unit. Check with voltage meter. 4. Fan should run after turning on power switch. 5. Check for LED light on main PCB is powered up. Remove low side gauge and verify red LED lights on PCB. 6. Check power to the power supply PCB (120 volts AC in) and power from the (PCB 12 volts DC out). 7. Unit passes the above checklist. The LCD or Main PCB maybe bad. 8. Call technical support. 1800-277-3808 ext 313 1

Unit Stuck In PT Calibration Mode Turn the power switch on. The unit LCD will display revision program and filter life within 3 to 5 seconds after turning on unit. Then re zeroing Pressure Transducer will display. During the Pressure re zeroing mode the recovery compressor will run first until Pressure transducer is in a vacuum. (5 to 6 seconds) The pressure transducer will then zero out to zero on both PT1 and PT2. The vacuum pump will run for a short period of time and turn off. (5 seconds) The unit will then look to see if air purge is needed. If no air purge is needed then the compressor will turn on and clear out pressure sample and then displays Main Menu. If air purge is called out, then unit will show purge pressures. One as what tank pressure and what the purge target is. This process from turning unit on to main menu display is 60 seconds. Note: If the unit needs to purge then process will take longer than the 60 seconds. Additional 5 minutes is possible depending on pressure in recovery tank being purged. If the above process does not happen then see trouble shooting tips below. 1. If recovery compressor runs continually see the follow trouble shooting tips. a. Check service hose ends that there tight and couplers are tight. b. Check to see if calibration is off on pressure transducer (PT 1) Recalibrate if necessary. Rerun start up to see if problem is corrected.. (Run PT diagnostic test in service menu) 3. Check that vacuum pump is good. The vacuum pump should come on for a bout 5 seconds after the recovery compress shuts off. If the vacuum Pump runs continually. Please see trouble shooting tips below. a. Check oil level on vacuum pump. (Vacuum pump over filled won t pull vacuum.) b. Check service hose ends that there tight and couplers are tight. c. Check to see if calibration is off on pressure transducer (PT 1) Recalibrate if necessary. Rerun start up to see if problem is corrected.. (Run PT diagnostic test in service menu) d. Check vacuum hose on vacuum pump is tight. 5. Check tank pressure and purge tank if needed. Purge mode in maintenance menu. 2

Oil Drain Bottle Blew Oil Out 1. Check tank valves and tank hoses are open. 2. Check tank pressure and purge tank if needed. Air purge in maintenance menu. Compressor Kicking Breaker 1. Extension Cord heavy enough 14gage at least. 2. Manually purge Compressor on suction and discharge port in service menu. LV1, LV2, LV4, HV2, and HV3. The purge will drain thru oil drain bottle port. Empty oil from drain bottle before hand. Unit Will Not Recover Refrigerant 1. Check for pressure on gauges. 2. Checks the service couplers are open. 3. Check tank valve are open. 4. Check that the compressor is running. 5. Check tank pressure and purge tank if needed. Air purge in maintenance menu. 6. Close liquid ball valve on tank filter. If recovery then happens the charge solenoid valve has dirt in valve. Unit Will Not Refill Refrigerant 1. Check for pressure on Red gauge. 2. Checks the Red service coupler is open. 3. Check tank valve are open. 3

4. Check that the virgin tank bottle valve is open and refill adaptor not over tightened. 5. Check that the compressor is running. 6. Check tank pressure and purge tank if needed. Air purge in maintenance menu. 7. Close liquid ball valve on tank filter. If recovery then happens the charge solenoid valve has dirt in valve. Unit Will Not Pull Into Vacuum during Recovery 1. Check the service couplers are tight to service hoses. 2. Check that the compressor is running. 3. Check that gauges are calibrated. a. Remove couplers from service hoses. Gauges should read 0 PSI. If adjustment is needed, then remove plastic plug from plastic lenses and adjust to 0 psi. 4. Check that the o rings in service couplers are good. Remove couplers from car service ports and recover hoses. If gauge pull down into vacuum o rings need replaced. 5. Check tank pressure and purge tank if needed. Air purge in maintenance menu. 6. Close liquid ball valve on tank filter. If recovery then happens the charge solenoid valve has dirt in valve. 7. Remove service couplers from car and pull vacuum on service hose only. Unit Vacuum Pump Will Not Pull Deep Vacuum 1. Check the service couplers are tight to service hoses. 2. Check that vacuum pump is running. 3. Check that oil level in sight glass is not over filled. 4. Check that gauges are calibrated. 5. Remove service couplers from car and pull vacuum on service hose only. 4

a. Remove couplers from service hoses. Gauges should read 0 PSI. If adjustment is needed, then remove plastic plug from plastic lenses and adjust to 0 psi. 5. Check o rings in service couplers are good. Remove couplers from car service ports and recover hoses. If gauge pull down into vacuum o rings need replaced. Unit Will Not Charge 1. Display stated unit charging, but weight showed the unit did not put any refrigerant in (Hose holds 2 oz). Then the check connection message came up on display after two minutes. 2. Check that the gauges are reading pressure, if so then the Charge solenoid is working. If the gauges are still in vacuum need to continue to next step. 3. Check the valves on the recovery tank and tank hoses ball valves are open. 4. Check that the service couplers are open. 5. Check that there is refrigerant available for charging. (4 to 5 lbs in tank after charge selected). 6. Check service couplers for flow restriction. 7. Check that the solenoid Valve is clicking after starting charge mode. Unit Will Not Complete Charge 1. Display stated unit charging with pressure on gauges, but did not complete the full charge. Then the check connection message came up on display after two minutes. 2. Check that there is refrigerant available for charging. (4 to 5 lbs in tank after charge selected). 5

3. Vacuum pump ran for 15 minutes on closed system, and 45 minutes on opened system for deep vacuum. 4. Scale calibration need to be checked wit 1lb weight. E5 Ball Valve Error Message 1. E5 is motorized ball valve error. LV in the message indicates low side valve. HV in the message indicates hi side valve Number indicated which valve is having trouble. 2. Check connector on PCB for motorized ball valve location. High Pressure cut out 450psi 1. Check tank and hose valves are open. 2. Check tank pressure. 3. Check orange high pressure switch wire for connection. 4. LCD Display Is Dim or No Read out 1. PCB/LCD Assembly is bad. 6

Pulling Filter Down For Changing Filter Taking To Long 1. Remove filter from tank bracket and turn filter 90 degrees with red liquid hose pointed downwards. It will cut 30 minutes off recovering filter. 2. Close red tank valve off to prevent additional refrigerant into filter. Air Flow Switch E-15 Error 1. Check wire connection on main PCB two purple wires. (FX 134A has a jumper) 2. Check that the air flow switch assembly has two clear PVC tubes attached properly, and routed correctly. One inside and one outside the cabinet. (FX1234,FX3030 units only) 3. Jump out two pins on main PCB where flow switch purple wire connect to confirm wires or flow switch is bad. 4. Unit is out of packaging and on all four wheels. FX Error Codes "E1-BAD TXT EPROM"; "E2-SCALE ADC"; "E3-SCALE EPROM"; "E4-CANNOT CAL"; "E5-MBV FAULT: X"; A bad scale may cause this, also. Connection to the scale electronics lost. Scale not calibrated? Scale cannot be calibrated or bad calibration. Where X is a number from 1 to 5 indicating which MBV has failed. 7

"E6-AMB. THRM"; "E7-TNK THRM"; "E8-PT TRANS"; "E9-WEAK BATT"; "E10-BAD FILTERTIME"; "E11-DEFAULTS NOT SET"; "E12-BAD GRAPH MEM"; Ambient thermistor in the head is bad. Thermistor attached to the oil sep. is bad. Pressure transducer is bad. Should never appear. Filter code problems. What it says Problems with the graphics like Chinese and Russian. "E13-BAD PTR. TO INFO MEM"; Major software corruption, fatal error. E15 FLOW SWITCH ERROR Air flow switch is open. "UNKNOWN ERROR"; What it says Identifier Codes FX1234/FX3030 00001 Error #1: The air or gas readings were unstable. Solution: Move the unit away from sources of EMF or RFI such as radio transmitters and arc welders. 00002 Error #2: The air or gas readings were excessively high. Solution: Move the unit away from sources of EMF or RFI such as radio transmitters and arc welders. 00003 Error #3: The air calibration resulted in a low output. Solution: Prevent refrigerant from flowing into the unit through the sample inlet during air calibration. 8

Solution: Allow any refrigerant in the atmosphere to dissipate before performing air calibration. Solution: Verify that the air intake and the exhaust are not obstructed Solution: Verify that the white filter is correctly plugged into the rubber grommets. 00004 Error #4: The unit is beyond the operating temperature range Solution: Move the unit to an area where the ambient temperature is within the specified operating range. 00005 Error #5: The refrigerant sampled has an excessively large amount of air or there was little or no sample flow due to a closed valve or plugged sample filter. This is the code to prompt the user to change the brass filter. This should be considered more as a prompt than an actual error. Solution: Verify the coupler valve is open. Solution: Verify the sample filter is not plugged with debris or oil Solution: Replace brass sample filter Solution: Verify that the white filter is correctly plugged into the rubber grommets. 00006 Error #6: The air sensor has expired and must be replaced before the analyzer can be used. 00007 Error #7: The pressure read by the sensor has been determined to be too high. Solution: Verify that the exhaust is not obstructed. 9