COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

Similar documents
COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

DT400/436 Tee Connector Installation Instructions

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

S Surge Arresters

Effective May 2017 Supersedes August 2005 (S )

S Loadbreak Apparatus Connectors WARNING: WARNING:

Norrsken Family Booklet

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

Inspection Recommendations

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

3M Liqui-Cel EXF-4x13 and 4x28 Series Membrane Contactors

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

USER MANUAL SAVE THESE INSTRUCTIONS. For the most current manual revision, please visit our Website:

RGC-IR Remote Gas Calibrator for IR400

Accu-Tab Systems 1000 Series by Axiall Corporation

Accu-Tab PowerBase 3012AT by Axiall Corporation

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Accu-Tab Systems 2000 P Series by Axiall Corporation

Acid- Rite ph Adjustment System 2500 by Axiall, a Westlake Company

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

USER MANUAL FLOW SELECTOR PM1000 SAVE THESE INSTRUCTIONS. Federal (USA) law restricts this device to sale by or on the order of a physician.

Installation Instructions Air Compressor Part # 2780, 2781

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

TL-12 FLUSH TANK. Manual Ref. # MN-??? Polyurethane Machinery Corp. REVISION 1.0

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges

URC Voltage Sensor SEN-VOLT for use with MRX units containing sensor ports

Accu-Tab PowerBase 3070AT by Axiall Corporation

2000 lb manual winch

APPENDIX D HYDRO-VAC

D Square Construction LLC

6 digital caliper with case

453 Series Steam Heated Vaporizing Regulator

CP-D/CP-M Circular Polarizer for Phoroptor. User s Guide

Remington 700. Disclaimer Limited Warranty Satisfaction Guarantee Installation Instructions

SERVICE LETTER WARRANTY CONDITIONS FOR ROTAX

INSTALLATION & MAINTENANCE INSTRUCTIONS

to Jack Frost National Golf Club Now is the time to make your plans for a great golf season at Jack Frost National Golf Club!

E2K-L. Liquid Level Sensor That Is Unaffected by the Color of the Pipe or Liquid. Liquid Level Sensor. Ordering Information

JMR FARMS 7441 Smith Blvd RR#1 Pefferlaw, Ontario L0E 1N0 Tel(905) Fax(905)

PPS PORTABLE POWER SUPPLY

U S E R M A N U A L CAUTION. SAVE THESE INSTRUCTIONS Federal (USA) law restricts this device to sale by or on the order of a physician.

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

New AQF Filter Polymer Filtration System

COMPACT METAL bender 99826

This is (Enter Company Name Here) Arc Flash Prevention policy. (Enter Name Here) will be responsible for overall direction of the Safety Program.

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

Operation Manual. O2 Quickstick. Oxygen Analyzer 08.17

Nuclear Associates

The Churchill. Chest Clip Guard

Instruction Manual No. 742, 8/98

Operation Manual. O2 Quickstick. Oxygen Analyzer

2018 SILENT DIVING, LLC REBREATHER AGREEMENT

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

Saline C 6.0 Junction Box

User s Guide Temperature Sensor Converter TSC-599

Modular skylight warranty

Pressure Relief Valve Instruction Manual

4-in-1 Professional Inflator Kit

Rev. 1. Cryogenics Thermoflasks. 2122, 2123, 2124, 2129, and 2130

Safety Powder Spray Systems

User Instruction Manual. Trauma Relief Pack. Part Number: RL-TRP. ISO 9001: 2008 Registered Manual

XXIV Commercial / Industrial Companies Energized Electrical / Hot Work Program

210 Series Transmitter with External Electrochemical Sensor

SMART Oxygen Analyzer. User Manual

FLANGED TWO-PIECE BALL VALVES

Victoreen B. Operators Manual. Image Intensifier Ion Chamber

Transcription:

Voltage Regulators MN225060EN Effective February 2017 Supersedes January 2012 (S225-60-2) Series winding ratio test procedure instructions COOPER POWER SERIES 120 Vac VOLTMETER S L SL

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... i Safety for life... iii Safety information... iii Safety Instructions... iii Product information.... 1 Introduction...1 Standards...1 Procedure instructions... 1 iii

SAFETY FOR LIFE Safety for life SAFETY FOR LIFE Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a sub stitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. iv

Ratio test procedure instructions Product information Introduction Service Information MN225060EN provides procedures for performing a ratio test on the series winding of a voltage regulator. The ratio test determines: If incorrect series winding tap changer connections have been made. If an open or short-circuit exists in the series or shunt winding. Refer to MN225003EN, CL-7 voltage regulator control installation, operation, and maintenance instructions and MN225008EN VR-32 voltage regulator with Quik-Drive TM tap changer installation, operation, and maintenance instructions or the literature applicable to your equipment for detailed service information on Eaton s Cooper Power series voltage regulators and controls. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or processes described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Standards ISO 9001 Certified Quality Management System S 120 Vac VOLTMETER L SL Procedure instructions 1. Ensure that the regulator operates correctly. Perform the steps in the Operational check section of the document MN225008EN. 2. Connect a voltmeter between the Load (L) and Source Load (SL) bushing terminals. 3. Use a variac to apply 120 Vac between the source (S) and SL bushing terminals, as shown in Figure 1. Caution Electrical Shock Hazard. Connecting an energized variac to the bushings will expose the tester to 120 Vac. Contact with the bushings will result in an electrical shock. 4. Connect a separate 120 Vac supply to the external source terminals on the control front panel. Consult the document MN225003EN and the section Connecting Power to External Source Terminals for instructions. 5. Move the control power switch to the external position to power up the control. WARNING Electrical Shock Hazard. The V1 and V6 (if present) knifeblade switches must be open when connecting external power to the control. If 120 Vac is incorrectly applied to the voltmeter terminals and the V1 and V6 switches remain closed, rated voltage may be created on the bushings. Contact with the bushings in such a case could result in death or serious injury. Caution Incorrect connection of an external power source to the control or supply of an over-voltage will result in damage to the control panel. 6. Increase the voltage on the variac connected between the S and SL bushings to 120 Vac. This will provide 12 volts on the series winding. 120 Vac x 10% regulation = 12 volts 7. Calculate the change in volts per tap change as follows: NNote: series winding volts = 12 = 0.75 volts per step 16 steps 16 If 160 Vac is applied between the S and SL bushings, and the calculations in item 5 and 6 are computed, you will see that a 1.0 volt difference between steps will result. Doing this will simplify the ratio check. Figure 1. Ratio test connections. 1

Ratio test procedure instructions Table 1. Typical meter readings with 120 Vac connected between the S and SL bushings Lower Raise 16L 108.0 16R 132.0 15L 108.75 15R 131.25 14L 109.5 14R 130.5 13L 110.25 13R 129.75 12L 111.0 12R 129.0 11L 111.75 11R 128.25 10L 112.50 10R 127.5 9L 113.25 9R 126.75 8L 114.0 8R 126.0 7L 114.75 7R 125.25 6L 115.5 6R 124.50 5L 116.25 5R 123.75 4L 117.0 4R 123.0 3L 117.75 3R 122.25 2L 118.5 2R 121.5 1L 119.25 1R 120.75 Neutral 120 8. Operate the tap changer with the control switch through all 32-steps from 16R to 16L. Record the voltmeter reading at each tap position. The change in voltage should be almost the same between each step (± 0.10 volts). If a substantial difference in any reading exists, then there is a problem with the windings or their connection. Readings will be the same with or without the equalizer winding. NNote: On a type B regulator, the difference between the taps will be slightly less than calculated as the regulator is tapped toward 16 lower. This is normal and inherent in the design of the type B regulator. Questions about the described procedure may be directed to your Eaton Representative. 2

Ratio test procedure instructions This page is intentionally left blank. 3

SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN225060EN / Rev. 0 February 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.