COOPER POWER SERIES. 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

Similar documents
COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

COOPER POWER SERIES. QD8 Quik-Drive tap-changer VR or VL reversing switch stationary contact assembly kit number A48 installation instructions

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv class PUSH-OP bushing adapter cap installation instructions. Deadbreak Apparatus Connectors MN650050EN

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

COOPER POWER SERIES. 600 Ampere Deadbreak Grounded Standoff Bushing 15 & 25 kv and 35 kv Class Installation Instructions. Bushings MN650045EN

COOPER POWER SERIES. UltraSIL Polymer-Housed Distribution-Class MOV Surge Arrester Installation Instructions. Surge Arresters MN235006EN

Effective March 2015 Supersedes S August 2002

COOPER POWER SERIES. Series winding ratio test procedure instructions. Voltage Regulators MN225060EN. 120 Vac VOLTMETER

COOPER POWER SERIES. 600 A 15, 25 and 35 kv class bushing adapter installation instructions. Deadbreak Apparatus Connectors MN650058EN

COOPER POWER SERIES. VariSTAR Storm Trapper high energy MOV arrester installation instructions. Surge Arresters MN235017EN

DT400/436 Tee Connector Installation Instructions

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

COOPER POWER SERIES. UltraSIL polymer-housed VariSTAR surge arrester IEC for MV systems to 36 kv installation instructions

COOPER POWER SERIES. 200 A 15/25 kv class deadbreak straight connector installation instructions. Deadbreak Apparatus Connectors MN650043EN

DAI630TB2669 Dead Front Arrester Installation Instruction

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. 200 A 15/25 kv class elbow installation instructions. Deadbreak Apparatus Connectors MN650042EN

COOPER POWER SERIES. 600 A, 15, 25, and 35 kv Class Cleer Grounding Elbow Installation Instructions. Loadbreak Apparatus Connectors MN650056EN

COOPER POWER. SERIES VariSTAR type AZE station class surge arresters installation and maintenance instructions. Surge Arresters MN235022EN 0.

COOPER POWER SERIES. Operation Counter Replacement Instructions. Reclosers MN280047EN. Effective May 2016 Supersedes S December 2003

Effective January 2017 Supersedes July 2011 (I ) VariSTAR Type AZG4 Surge Arresters Installation and Maintenance Instructions

Effective May 2017 Supersedes July 2009 (S ) 600 A 35 kv Class T-OP II connector assembly installation instructions 200 A PROTECTIVE CAP LRTP

S Surge Arresters

COOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN

COOPER POWER SERIES. 600 A 35 kv class PUSH-OP deadbreak connector installation instructions. Deadbreak Apparatus Connectors MN650052EN

COOPER POWER SERIES. 200 A 35 kv class LE series elbow installation instructions. Loadbreak Apparatus Connectors MN650010EN

600 A 35 kv class PUSH-OP deadbreak connector installation instructions

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with optional integral jacket seal installation instructions. Loadbreak Connectors MN650008EN

COOPER POWER SERIES. 200 A 15 and 25 kv class elbow with integral jacket seal* for use on tape and wire shielded cable installation instructions

Effective May 2017 Supersedes August 2005 (S )

Operation Manual Enabling Pole-Top Communication Via the TripSaver II Magnet Tool

Medium voltage standard-duty, heavyduty, and extreme-duty single-phase, unfused capacitor units and accessories

S Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection

2000 lb manual winch

Angled Sign Light with Shade

Permanent Roof Anchors

Foldable Magne c Exercise Bike

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

S Loadbreak Apparatus Connectors WARNING: WARNING:

Sunset Swings By Health in Motion, LLC

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

12 Inch Barn Light. Owner s Manual

This document to be used with Hurley traditional Davits

COMPACT METAL bender 99826

USER INSTRUCTION MANUAL CONCRETE BOLT ANCHORAGE CONNECTOR

Yoke Block Instruction Manual

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

FLANGED TWO-PIECE BALL VALVES

BS Series Basket Strainer

3M Liqui-Cel EXF-14x28 and 14x40 Series Membrane Contactor

DISASSEMBLING & REASSEMBLING CARTRIDGE INSTALLING SEATPOST ON BIKE

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

For ELECTRIC ANCHOR WINCH Models: T Pontoon 35 T sw Salt Water Series Coastal 35

Inspection Recommendations

FLANGED TWO-PIECE BALL VALVES

Booster Pump PB4-60 Replacement Kits

INSTALLATION AND OPERATING INSTRUCTIONS. T10219-AD Deckboat 40 with AutoDeploy and Wireless Remote Control

OPERATOR S MANUAL. Fabric Grass Catcher PART NO PRINTED 1/2011 PRINTED IN USA

Installation Instructions and valve Maintenance Rev. 0 of 21/09/15

OPERATOR'S MANUAL GRASS CATCHER GC-4D

DK ton, Double-acting, Die-type Crimping Tool

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

For ANCHOR WINCH Model: T Big Water 45 T sw Salt Water Series Big Water 45

Spectrum AquaLight (SAL ) Color Underwater Light Owner s Manual

S Vacuum Switches. Contents. Type VCS-1 Single-Phase Vacuum Capacitor Switch Installation and Operation Instructions

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

TITAN FLOW CONTROL, INC.

SPECIFICATIONS ATTENTION

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

OPERATOR'S MANUAL. MODEL GC-F4 Fabric Grass Catcher P/N 9055 GRASS CATCHER GC-F4. PART Rev.2 SC301G

Cocoa Patio Pond with Lit Spillway

OPERATION AND INSTRUCTION MANUAL

4-in-1 Professional Inflator Kit

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

35 TON HYDRAULIC PUNCH WARNING

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

FLANGED MULTI-PORT BALL VALVES

WALL-MOUNT GARDEN HOSE REEL OWNER S MANUAL

100C Air Compressor Kit

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Model ASSEMBLY and OPERATING INSTRUCTIONS

INTRODUCTION BILL OF MATERIALS SPECIFICATIONS & TOOLS PROCEDURES OPERATION OF SEATPOST GIANT LIMITED WARRANTY

INSTRUCTION MANUAL. Includes: OPERATION SETUP USE & CARE SERVICE. SPORTS ATTACK LLC

Backboard and Rim Owners Manual

UE- 90- X X X X X X O P E R AT I N G M A N UA L 0 TO 90 HYDRAULIC UPENDER

INSTRUCTION MANUAL Pressure Relief Device LPT

Yoke Block Instruction Manual

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

GRAVITY BIKE RACK ASSEMBLY & OPERATING INSTRUCTIONS

U S E R M A N U A L CAUTION. SAVE THESE INSTRUCTIONS Federal (USA) law restricts this device to sale by or on the order of a physician.

OWNERS MANUAL. Model Shown with optional Primary Mooring Cleats. Portable Mooring System SAFETY OPERATION MAINTENANCE PARTS

Transcription:

Voltage Regulators MN800013EN Effective February 2016 Supersedes S800-70-1 August 2012 COOPER POWER SERIES 50 A 2:1 series multiple (dual voltage) switch cap/wrench, lever or hotstick operable handles installation instructions

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016

Contents SAFETY INFORMATION Safety Information...iv PRODUCT INFORMATION Introduction...1 Acceptance and Initial Inspection....1 Handling and Storage...1 Standards...1 GENERAL MOUNTING DESCRIPTION Torque requirements...1 Clearance...1 Mechanical strength...1 Electrical ratings...1 OPERATION INSTRUCTIONS Warning labels....2 MOUNTING SEQUENCE AND DIMENSIONS.... 3 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iv 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016

Product information Introduction Eaton s Cooper Power series 50 A externally operated single phase dual voltage switches are designed for use in distribution transformers filled with transformer oil, Envirotemp FR3 fluid, or an approved equivalent. They are designed for use in pole- or pad-mounted transformers. The switches are used to connect primary windings in series for a higher winding ratio or parallel for a lower voltage winding ratio. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Acceptance and initial inspection Each tap changer switch is in good condition when accepted by the carrier for shipment. Upon receipt, inspect the shipping container for signs of damage. Unpack the tap changer switch and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the tap changer switch to minimize the possibility of damage. If the switch is to be stored for any length of time prior to installation, provide a clean, dry storage area. Standards ISO 9001 Certified Quality Management System General mounting description Torque requirements To Seal - 80-120 inch pounds. Clearance Table 1. Dielectric Clearance Dimensions Minimum mounting clearance under-oil to Gnd/ kv BIL between phases/and depth below top level 95 1.1 125 1.5 Mechanical - External handle clear of obstructions. When the lever handle with index plate is used, flattening for the gasket sealing surface must not exceed a depth of.25. Mechanical strength Designed to support leads sized per rating of switch. Standard dielectric dimensions for lead separation should be followed. Connection of leads can be made either to bolt tabs or crimped into connectors (if supplied). Special stationary contact with crimp barrels are available for #16-14, #12-10, and #8 copper wires. Bolt tab designed to accept 1/4-20 bolt and ring tongue terminals through #4. A larger terminal may be used if the terminal amperage rating corresponds with the switch rating. CAUTION Equipment Damage. Caution should be used in lead training [dressing] to avoid lead forces of over 60 pounds on the switch in any direction. Anticipate thermal expansion and contraction as well as mechanical stresses from transportation, which will vary by application. Misuse of lead training could result in equipment damage. Electrical ratings Impulse Withstand 125 kv BIL 60 Hz 1 Minute Withstand 40 kv Continuous Current 50 A rms Series Position 100 A rms Parallel Position 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016 1

Operation instructions Cap/wrench It is keyed for one way in/one way out when fully switching to ensure positive switch contact. The molded arrow on the switch shaft must line up with the molded arrow inside the wrench. The white molded arrow on the interior of the cap points to the switched position. Lever or hotstick handles Lever or point of rigid Hotstick Handle points to the switched position. To switch, back out lockscrew, rotate to desired position, turn in lockscrew to ensure positive switch contact. The decals included with the handle kit are to be located on the tank wall near the switch operating handle as a warning to service personnel (see Figure 1). Failure to do so will constitute a waiver of all warranty and indemnity obligations attributable to Eaton. Cap/Wrench Switches! Enclosed Warning decals (Cooper P/N 1139089A01 and P/N 1139090A01) must be displayed at or near operating handle of switch as a warning to service personnel. Failure to do so will constitute a waiver of all warranty and indemnity obligations which may be attributable to Eaton. The misapplication of the switch constitutes a potential hazard to life and property. Accordingly, the user must exercise due care in utilizing these instructions to assure that the switch is properly applied. DE-ENERGIZE TRANSFORMER BEFORE CHANGING VOLTAGE. REMOVE PROTECTIVE CAP AND USE KEY ON END TO OPERATE SWITCH, REPLACE CAP BEFORE ENERGIZING. 1139089A01 Lever or Hotstick Handle Switches! DE-ENERGIZE TRANSFORMER BEFORE CHANGING VOLTAGE. BEFORE OPERATING HANDLE, BACK OUT LOCKSCREW TO CLEAR INDEX PLATE. AFTER CHANGING SWITCH POSITION, TURN IN LOCKSCREW SECURELY BEFORE ENERGIZING AGAIN. Figure 1. Warning decals. 1139090A01 2 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016

Mounting sequence and dimensions Handle Screw Lock washer Nut Index Plate (Optional) Tank Wall Flat Washer Nut Handle Index Plate Gasket Tank Wall Gasket Switch Figure 2. Cap/wrench assembly. Switch Figure 5. Lever handle assembly. 2.07 (53 mm) 2.3 (59 mm) Ø 3.50 (89 mm) 1.54 (39 mm) Figure 3. One-phase cap wrench switch. * Dimension will decrease as tank wall thickness increases. Maximum dimension given with 14 gauge tank wall. B 2.4" (61) Figure 6. Lever handle switch. * Dimension will decrease as tank wall thickness increases. Maximum dimension given with 14 gauge tank wall. ( B Dimension - See Table 2) DUAL VOLTAGE SWITCH DEENERGIZED OPERATION ONLY 2 DUAL VOLTAGE SWITCH DEENERGIZED OPERATION ONLY 1 Ø 3.50" (89) Figure 4. Cap wrench-front view. NNote: Switch can be used on 14 gauge to.25 inch thick frontplate. Bolt tabs are bent up 90 and have a hole to accept.25 inch (6 mm) hardware. Figure 7. Lever handle-front view. * Dimension will decrease as tank wall thickness increases. Maximum dimension given with 14 gauge tank wall. MAX MAX 2.07" 1.54" 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016 (52.6) (39.1) 2 1 3 B

Screws 2.25 (57 mm) Flexible Hotstick Handle 3.3 (84 mm) Screw Lock Washer B Flat Washer Handle Figure 9. One-phase flexible hotstick switch. * Dimension will decrease as tank thickness increases. Maximum dimension given with 14 gauge tank wall. ( B Dimension - See Table 2) Nut Index Plate Tank Wall DUAL VOLTAGE SWITCH DEENERGIZED OPERATION ONLY 2 Gasket 1 Switch Figure 10. Flexible hotstick handle-front view. Figure 8. Flexible hotstick handle assembly. NNote: Switch can be used on 14 gauge to.25 inch thick frontplate. Bolt tabs are bent up 90 and have a hole to accept.25 inch (6 mm) hardware. 3.3" (84) B A 4 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016

Screw Lock Washer Flat Washer 3.44 (87 mm) Handle B Nut Figure 12. One-phase rigid one-piece hotstick. * Dimension will decrease as tank wall thickness increases. Maximum dimension given with 14 gauge tank wall. ( B Dimension - See Table 2) Index Plate Tank Wall DUAL VOL E SWITCH DEENERGIZED OPERATION ONLY 2 Gasket Figure 13. Rigid one-piece hotstick-front view. * Dimension will decrease as tank wall thickness increases. Maximum dimension given with 14 gauge tank wall. Switch Figure 11. 100 A tap-changer mounting with rigid onepiece hotstick handle. (One-phase switch view shown.) * Dimension will decrease as tank wall thickness increases. Maximum dimension given with 14 gauge tank wall. 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016 5

Table 2. Dual Voltage Switch Mounting Sequence (All configurations). Contact Type A Dia. B Dim. Bolt Tabs 90 Bend 2.91 (74.0 mm) 14-16 AWG Long Shank 10-12 AWG Long Shank 8 AWG Long Shank Three 14-16 AWG Long Shank and Two 90 Bolt Tab Three 10-12 AWG Long Shank and Two 90 Bolt Tab Three 18 AWG Long Shank and Two 90 Bolt Tab Three 14-16 AWG Long Shank and Two Straight Bolt Tab Three 10-12 AWG Long Shank and Two Straight Bolt Tab Three 8 AWG Long Shank and Two Straight Bolt Tab 4.20 (106.70 mm) 2.91 (73.9 mm) 4.47 (113.5 mm).25-20 Stud 90 4.07 (103.3 mm).25-20 Stud 45 4.52 (114.8 mm) 2.81 (71.4 mm) 2.18 (55.4 mm) 2.81 (71.4 mm) 2.18 (55.4 mm) 2.81 (71.4 mm) 2.18 (55.4 mm) 6.26 (159 mm) 5.50 (139.7 mm) 1.06 (26.9 mm) 3.75 (95.3 mm) 3.50 (88.9 mm) 1.12 (28.4 mm).56 (14.2 mm) A Figure 14. Switch with terminal posts. * When required, accepts.25 inch rounded short square neck bolt, carriage bolt. Hardware not included. 1.33 (33.7 mm) 0.14 in. rad. (3.6 mm) 0.66 in. (16.8 mm) Figure 15. Switch mounting hole. 6 50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016

50 A 2:1 SERIES MULTIPLE SWITCH CAP/WRENCH, LEVER OR HOTSTICK HANDLES INSTRUCTIONS MN800013EN February 2016 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN800013EN Rev 00 (Replaces S800701 Rev. 01 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.