Instruction Manual Differential Pressure Transmitter

Similar documents
Instruction Manual Contact Pressure Vacuum Gauge

Instruction Manual Differential Pressure Transmitter

Instruction Manual Contact Pressure Gauge

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

Instruction Manual Differential Pressure Gauge

Operating Manual * * Pressure Transmitter. Table of Content. 1 Safety Guidelines. 1.3 Risks due to Non-Observance of Safety Instructions

Installation and Operation Manual

Pressure transmitter PASCAL Ci4

Precision pressure sensor Basic version Model CPT6020

Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

SITRANS P measuring instruments for pressure

Pressure Switches Application Guideline

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

Gas density monitor With integrated transmitter Model GDM-100-TI

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

Installation and Maintenance Instruction Manual

Transmitter CS 21 Operation Manual

High-performance submersible pressure transmitter For level measurement Model LH-10

High-performance submersible pressure transmitter For level measurement Model LH-10

Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor

QPL... Pressure Switches. Siemens Building Technologies HVAC Products

High-performance submersible pressure transmitter For level measurement Model LH-20

* * Operating manual ME12... R/S. Remotely configurable digital pressure transducer for use in explosive areas

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

Magnetic level switch type MR783 Instruction Manual

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation and Maintenance Instruction Manual

SITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.

Transmitter CS 21 Operation Manual

OPTIBAR P 1010 C Technical Datasheet

Instruction Manual EMA 84 Digital Pressure Gauge

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

High-performance submersible pressure transmitter For level measurement Model LH-20

Pressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

LMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0.

Pneumatic high-pressure controller Model CPC7000

Instruction Manual BA90 Precision Barometer

Pressure Transmitters 36 F-27839

Certified according to DIN EN ISO 9001 Technical Datasheet TRICOR Series Mass Flow Meters

Installation and Maintenance Instruction Manual

x act i Precision- Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor

User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

How to specify a product. Process Sensors and Mechanical Instruments

Bourdon tube pressure gauge for diaphragm seals

AMS 2710 PCB pressure sensor module with V output

SPD310/SPD360 Air Differential

Installation and Maintenance Instructions for F5509/F6509 Differential Pressure Gauges

Mounting instructions. Strain transducer SLB-700A. B 26.SLB700A.10 e

DMK 458. Pressure Transmitter for Marine and Offshore. Ceramic Sensor. accuracy according to IEC 60770: standard: 0.25 % FSO option: 0.

MANUAL KPS Pressure Control Valve

Expert Hydrostatic Level Transmitters

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

Pressure transmitters EMP 2

DPC-30 DPC-100. Reference Manual

WIKA INSTRUMENT CORPORATION

ATM.ECO - Analog Pressure Transmitter

Operating Instructions for Intrinsically Safe Pressure Transmitters Series DMG/******** for Hazardous Application in Coal Mining Industry

AMS 6916 Board mount pressure sensor with ratiometric analog output

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers

1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure

x act i Precision Pressure Transmitter for Food Industry, Pharmacy and Biotechnology Stainless Steel Sensor accuracy according to IEC 60770: 0.

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

OXY 3690 MP. Measuring transducer for air oxygen

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. Type: ETd 04. class 0.05

Differential pressure gauge For the process industry Model , all-metal media chamber

Electro-Pneumatic Converter YT-940 SERIES

Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC

T EK-SUB 4800C 19 mm Submersible Level Transmitter

Sensoric 4-20 ma Transmitter Board Operation Manual

deltaflowc deltaflowc Venturi or Probe

P900. P900, Datenblatt Seite 1 DESCRIPTION

DM01. Please visit our website: Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

Programmable Submersible Level Transmitters

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

DK48 - DK800. Quick Start. Variable area flowmeter

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Proportional pressure regulators VPPE

Pneumatic high-pressure controller Model CPC7000

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition

Safety Please read and keep in a safe place Operating instructions Linear flow control VFC Linear flow control with actuator IFC

better measurement Simply a question of SCHMIDT Flow Sensor SS The cost-effective alternative in pressurised systems up to 10 bars.

Model range*1) Switching pressure difference

Air Purge Unit. Series: LSP-compact Type: EJG 2-2. (Controlled with DigiFlow 515) Installation & Operation Manual 11/2014

Level transmitter LT 100

Product Catalogue MINICOMB. Switches for Pressure and Vacuum

Differenz-Drucktransmitter Differential pressure transmitter Transmetteur de pression différentielle bar

Tightness controls TC 1 3 and TC 4

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

INSTALLATION & MAINTENANCE INSTRUCTIONS

GEMS SENSORS & CONTROLS

High-performance submersible pressure transmitter For level measurement Model LH-20

Installation and Maintenance Instruction Manual Process gauge with integrated transmitter, model T5500E

Operating Manual VSA100A. tina29e1 ( )

Flowmeter. Original operating manual DFM

Pressure Measurement Single-range transmitters for general applications

Transcription:

DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance 7. Transport 8. Service 9. Accessories 10. Disposal 11. Specifications 12. Dimensions 13. Ordering Code 14. CE-Certificate 16.10.07 BA_GB_DE61.fm 1. Safety Instructions 1.1. General This manual contains detailed information about the product, and instructions for its installation, operation and maintenance. Operators and other technical personnel responsible for the equipment must read this thoroughly before attempting to install or operate this equipment. A copy of this manual must always be kept accessible at the place of work for reference by concerned personnel. Chapter 1 (sections 1.2 through 1.7) contains general as well as specific safety instructions. Chapters 2 through 10, covering topics ranging from intended purpose of the equipment to its final disposal, also include important points relating to safety. Overlooking or ignoring any of these safety points can endanger humans and animals, and possibly cause damage to other equipment. 1.2. Personnel Qualification Personnel responsible for installation, operation, maintenance and inspection of this product must have the qualifications, training and experience necessary to carry out such work on this type of equipment. 1.3. Risks of Disregarding Safety Instructions Disregarding safety instructions, use of this product for purposes for which it is not intended, and/ or operation of this product outside the limits specified for any of its technical parameters, can result in harm to persons, the environment, or the plant on which it is installed. Fischer Mess- und Regeltechnik GmbH will not be responsible for consequences in such circumstances. 1.4. Safety Instructions for Operators Safety instructions for the proper use of this product must be followed. This information must be available at all times to by personnel responsible for installation, operation, maintenance and inspection of this product. Adequate steps must be taken to prevent the occurrence of hazardous conditions that can be caused by electric energy and the convertible energy of the process media. Such conditions can, for example, be the result of improper electrical or process connections. Detailed information is available in relevant published norms (DIN EN, UVW in Germany; and equivalents in other countries), industrial standards such as DVWG, Ex-, GL-, VDE guidelines, as well as regulations of the local authorities (e.g., EVUs in Germany).

1.5. Modifications Forbidden Modification or other technical alteration of the product is not permissible. This also applies to the use of unauthorized spare parts for repair / maintenance of the product. Any modifications to this product, if and as necessary, should be done only by Fischer Mess- und Regeltechnik GmbH. 1.6. Operational Restrictions The operational reliability of the product is guaranteed only when used for intended purposes. The product must be selected and configured for use specifically with defined process media. The limiting values of operating parameters, as given in the product specification sheet, must never be crossed. 1.7. Safety Considerations during Installation and Maintenance The safety instructions given in this manual, existing national regulations relating to accident prevention, and the internal safety rules and procedures of the user organization regarding safety during installation, operation and servicing must all be followed meticulously. It is the responsibility of the users to ensure that only suitably qualified and experienced technical personnel are used for installation, operation and servicing of this equipment. 2. Intended Applications Measuring transmitter with limit switching functions for acquisition and transmission of lowest pressure and differential pressure. The product must be used only for applications and under conditions specified by the manufacturer. Please confer with Fischer Mess- und Regeltechnik GmbH prior to using this transmitter along with polluted or aggressive media. For use with this media it needs to be adjusted in every part with direct contact to the media. 3. Product Description and Functions 3.1. Block Schematic Diagram 1 2 3 4 3.2. Principles of Operation The function of this transmitter is based on a capacitive sensor element. Due to modern micromechanical manufacturing process this sensor is highly overpressure safe, shock and vibration resistant and long-time stable. The differential pressure acts on the sensor element and effects a measuring signal. The electronic amplifier then generates an electrical output signal of 0 / 4-20 ma. This output signal is used for external data processing and is shown on the LC-display e.g. in mbar. The LC-display can also be used for indication and precise adjustment of the differential pressure dependent switching functions. Both change-over contacts can be adjusted to any value within the measuring range. 4. Installation 4.1. Process connections Only qualified technicians authorized for this type of work should undertake installation. Only for intended mechanical process connection (for model information see Type Plate of instrument). Ensure that process equipment and pressure lines are at atmospheric pressure before making pressure connections. The instrument should be provided with suitable protection against pressure surges (e.g., snubber or pulsation damper). Ensure that the mechanical configuration and materials of construction of the instrument are compatible with the process media. Ensure that process pressure is always less than the specified safe pressure rating. 4.2. Electrical Connections Only qualified technicians authorized for this type of work should undertake installation. Electrical connections must comply with relevant international, national and local regulations and norms relating to electrical and instrumentation installations. Switch off electrical power to the plant before attempting electrical installation work of any kind. Make electrical connections to the transmitter through a suitable energy-limiting safety device (isolation or zener barrier). Sensor element 1. Signal output 2. Option square rooted 3. 2 change-over contacts 4. LC-display 5. Commissioning Power supply and signal cabling to the transmitter must be correctly selected to meet operational requirements, and installed in a way that does not cause physical stress to the instrument. Carefully check tightness of all pressure connections before start-up. 2

5.1. Pressure Connections The instruments pressure ports are marked by + and symbols. The pressure applications need to be installed according to the label. Differential pressure + = higher pressure measurement: = lower pressure. Pressure measurement + = pressure port Gauge measurement = negative pressure port 5.2. Shock Pressure Moderation During pulsating pressure on the plant mechanical wear and disturbances in functional capability may occur. To avoid this we recommend installing absorbers into the pressure lines. For Gaseous Media Adjustable attenuator valve MZ41 During operating condition adjust needle valve that way, that the indicator follows changements of pressure delayed. MZ41 Connect and switch on power supply. Measuring system depressurized: Output signal = 0 resp. (4) ma. Correct offset using zero point potentiometer N. Mount housing cover. 5.4. Switching Point Adjustment The instrument s main board has two calibration potentiometers and a coding switch to set switching points. After removing housing cover they are freely acessible. Adjustment sequence Switch on supply voltage. Open housing cover. Selector setting 1: Display indicates actual value. Selector setting 2: Display indicates switching point I. Selector setting 3: Display indicates switching point II. The respective setpoint values for contact 1 and contact 2 can be set in display using potentiometers K1 and K2. After adjustment is done turn selector to setting 1: actual value. Setpoint values can be displayed any time by turning selector to position 2 or 3. 5.3. Zero Point Adjustment Usually adjustment of the instrument is not necessary for it is factory calibrated. The output signal can be adjusted with inbuilt zero point potentiometer. Location of zero point potentiometer Selector and Set-up Potentiometer Mounting holes Selector Selector Switching point potentiometer 5.5. Electrical Connection 3-wire connection 24 V DC Range adjustment: N = Zero point 2-wire connection 24 V DC Adjustment sequence Open housing cover. Connect current indicator (0-20 ma) to output signal between terminals 11 and 12. 3

6. Maintenance The instrument is inherently maintenance-free. However, to ensure reliable operation and maximize the operating life of the instrument, it is recommended that the instrument, its external electrical and process connections, and external connected devices be regularly inspected, e.g.: Check the display. Check the switching function in connection with secondary components. Check all pressure connections for leak-tightness. Check the integrity of all electrical connections of the instruments. Inspection and test schedules depend on operating and site conditions. The operating manuals of other equipment to which the differential pressure transmitter is connected must be read thoroughly to ensure that all of them work correctly when connected together. 7. Transport The product must be protected against shock and vibration during transport. It must therefore be properly pakked, preferably in the original factory packaging, whenever it is to be transported. 8. Service Any defective devices or devices with missing parts should be retourned to Fischer Mess- und Regeltechnik GmbH. For quick service contact our service department. Remaining medium in and on dismantled measuring instruments may cause danger to persons, environment and equipment. Take reasonable precautions! Clean the instrument thoroughly if necessary. 9. Accessories 10. Disposal Protect your environment! Use the product in accordance with relevant regulations. Please be aware of environmental consequences of disposal at the end of the product's life, and take care accordingly. 4

11. Specifications General Measuring ranges 0...0.25 to 0...4.0 mbar (see 13. Ordering Code) Nominal pressure 0.6 bar Max. static pressure overpressure safe up to permitted nominal pressure Linearity 1% FS Hysteresis 0.1% FS Temperature drift 0.5% FS / 10K Perm. ambient temperature -10...60 C Perm. medium temperature -20...70 C Protection class IP 54 per DIN EN 60529 Electrical Electrical connections 3-wire 3-wire 2-wire Operating voltages 24 V DC 24 V DC 24 V DC Power consumption approx. 3 VA approx. 3 VA approx. 3 VA Output signal 0-20 ma 4-20 ma 4-20 ma Apparent ohmic resistance 700 Ω 700 Ω max. 450 Ω Current limit approx. 30 ma approx. 30 ma approx. 30 ma Square-rooted output ± 0.5% with suppression of leak flow volume 2% set up Span adjustment approx. 10% FS Zero point adjustment approx. 10% FS Measuring Indication / Switching Sections Measuring indication 3½ digit LC-Display Switching point adjustment The digital display can be switched over between the differential pressure actual value and the switch point adjustments via selector. The display then indicates the related setpoint value. Setpoint values are adjustable within full scale range. Switching point hysteresis approx. 2% Contact output 1 or 2 potential-free change-over contacts Load data of contacts U~ max. = 250 V AC, I~ max. = 2 A, P~ max. = 250 VA ohmic resistance U= max. = 30 V, I= max. = 2 A, P= max. = 60 W ohmic resistance Connection Electrical Connections Pressure Connections Materials Housing Housing cover Measuring element Installation wallmounting any other orientation internal connector bloc, M16x1.5 connection M12 plug connection female thread G¼, threaded hose coupling (al) for 6/8 mm flexible tube, cutting ring connection (brass) for 6/8/10 mm tube diecasted aluminium, varnished ABS, self-extinguishing silicium, glass, aluminium vertical, pressure ports downward correction of zero point recommended 5

12. Dimensions (all units in mm unless stated otherwise) Cable gland M16 x 1.5 Mounting holes 4.5 mm 6

13. Ordering Code Differential Pressure Transmitter DE61 9 Measuring Range 0...0.25 mbar... > 9 4 0...0.4 mbar... > 9 5 0...0.6 mbar... > 9 6 0...1.0 mbar... > 5 1 0...1.6 mbar... > 9 7 0...2.5 mbar... > 9 8 0...4.0 mbar... > 5 2 other measuring ranges (please indicate in plain text)... > 9 9 Pressure Connection Female thread G ¼...> 0 1 Cutting ring connection brass for 6 mm tube...> 2 8 Cutting ring connection brass for 8 mm tube...> 2 9 Cutting ring connection brass for 10 mm tube...> 3 0 Screw connection AI for 6 mm flexible tube...> 4 0 Screw connection AI for 8 mm flexible tube...> 4 1 Electrical Output Signal 0 20 ma linear, 3-wire...> A 4 20 ma linear, 2-wire, only 24 V DC, without contacts and square-root extraction...> B 0 20 ma square-rooted, 3-wire...> E 4 20 ma square-rooted, 3-wire...> F 4 20 ma linear, 3-wire...> P Supply Voltage 24 V DC...> 9 Indication / Switching Sections Without indication / without contacts...> 0 3½ digit LC-display / without contacts...> 1 3½ digit LC-display / with 1 potential-free contact...> 2 3½ digit LC-display / with 2 potential-free contacts...> 5 Electrical Connection Internal connector bloc...> M12 plug connection...> E M 7

14. CE-Certificate Technische Änderungen vorbehalten Subject to change without notice Changements techniques sous réserve Fischer Mess- und Regeltechnik GmbH Bielefelder Str. 37a D-32107 Bad Salzuflen Tel. +49 5222 9740 Fax +49 5222 7170 email: info@fischermesstechnik.de www.fischermesstechnik.de 8