opti-visor tm Ultra-efficient chiller plant automation Sequence of operation File No: Date: december 17, 2015 Supersedes: new Date: new

Similar documents
Design Envelope Booster. Sequence of operation

E.2 Series. High efficiency circulator. Technical overview

Multistack BACnet Solution: MS70/90 Standard Chiller Module

INNCOM SYSTEM MONITORING MARRIOT HOTEL DOWNTOWN PHILADELPHIA, PA. Report 9. July 2, CH2M HILL Project No

Air Eliminator Series

Hydronic Systems Balance

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

Let s examine the evolution and application of some of the more popular types. Cascading Pressure Type

Supersedes: RP1(495) Form RP1 (1102)

Revision 1 AIR & WATER COOLED LIQUID CHILLERS MICRO BASED CONTROL SYSTEM WITH IPUII

BUBBLER CONTROL SYSTEM

Custom-Engineered Solutions for the Nuclear Power Industry from SOR

DESIGN ENVELOPE 6800 G 1 DUTY PUMP

Expansion Tank Design (Chilled Water)

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL

Uniflair LE TDAR-TUAR

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly

LEAD FREE * Product Specification. Features n. Specifications n. Relay Specification n ! WARNING NOTICE

The Advancement of Pressure Independent Technology

1 STARTUP Overview Buttons Basics of Control Resetting Faults and Alarms OPERATION...

WMC Magnetic Bearing Compressor Chillers

SAUTER flexotron 800 heating. List of network variables for Modbus communication. Manual P A P

MODBUS. Index Variable/BACnet Name Description Type Access Format Default Minimum Maximum MultiStat Value Multistate Text Inactive Text Active Text

WEST ESSEX REGIONAL SCHOOL DISTRICT HIGH SCHOOL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO

Additel761 Series Firmware Updates

Using Modbus Protocol with the ALTUS Net Oil Computer. Instruction Manual

COMPRESSOR PACK SUCTION CONTROLLER TYPE: LP41x

CONTROL PANEL OPERATING MANUAL

CONTROL PANEL OPERATING MANUAL. AIR COOLED SCREW CHILLER GLOBAL DESIGN Software version ASDU01C and later D-EOMCP EN

Remotely-installed Hydraulic Module

High performance disc valves Series Type BA, BK, BW, BM, BN, BO, BE, BH Rev Safety Manual

COLD WATER STORAGE CONTROL AYLESBURY DELAYED ACTION FLOAT-ACTIVATED VALVES

Jamesbury Pneumatic Rack and Pinion Actuator

NOTE: Inserted Literature Supplement - YT Style "J" Chillers New Style Oil Filter/"O"-Ring

BUBBLER CONTROL SYSTEM

Screw Compressors 11-22kW

2017 Edition GUIDANCE NOTE GN 8 INVERTER DRIVES FOR FANS AND PUMPS GN 8 - INVERTER DRIVES FOR FANS AND PUMPS

DOMESTIC HOT WATER TEMPERATURE CONTROL with SAFEGUARD

The Next Generation for Level Control. By Ryan Spooner, Singer Valve

Burner Management System DEMO Operating instructions

Neles trunnion mounted ball valve Series D Rev. 2. Safety Manual

Spirax EasiHeat TM DHW Potable and Process Water Heating Compact Heat Transfer Solution

Liquid Level Controllers

TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES

Steam Turbine Performance Measurement. Pressure Measurement

KKT Training Series: ECO Series, Preventative Maintenance

Technical Bulletin, Communicating with Gas Chromatographs

RPLA. Heat Pumps. Parts List 19-July-2011

WHITE PAPER. SmartPlant P&ID Engineering Integrity 10 Example Rules

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

FAULT CODE TROUBLESHOOTING INDEX

Performa Cv Twin Alternating and High Flow Systems. Manual Supplement

Spirax EasiHeat TM HTG Heating System Compact Heat Transfer Solution Installation and Maintenance Instructions

Spirax EasiHeat TM HTG Steam Side Control Water Heating Compact Heat Transfer Solution Installation and Maintenance Instructions

Ventam 85 Installation & Commissioning Instructions

BIOME DESIGN TECHNICAL DATA

Neles ValvGuard VG9000H Rev 2.0. Safety Manual

Basic STPA Exercises. Dr. John Thomas

Oerlikon Sputtering Evaporator SOP

TANKTRONIC. STANDARD CONFIGURATION Single Tank. ADVANCED CONFIGURATION Multiple Tanks. Twin Tank (common valve) Twin Tank (separate valves) Vent box

Ingersoll Rand. X-Series System Automation

Built-in Purge Control Functions

Model 106 DPI "Micro-switch" Installation and Operating Instructions

AIR COOLED SCREW WATER CHILLERS

Specifications and information are subject to change without notice. Up-to-date address information is available on our website.

QuickHeat TM Packaged Heat Exchanger Solutions

LP Separator Level Control by Variable Speed and Multi Stage Brine Reinjection Pumps at Kawerau and Nga Awa Purua Geothermal Projects, New Zealand

Measuring range Δp (span = 100%) Pa

HART Communications Board

Industrial Compressor Controls Standard Custom

OPERATING PROCEDURES

COLD WATER STORAGE CONTROL AYLESBURY TM FLOAT VALVE RANGE

Product Sheet Pre-Fabricated Flushing Bypass Assembly for Terminal Applications Mini-Flush 40

This parts list is current as of the above revision date. See for the current revision.

Quick Installation Guide Doc nr.: C Date:

CONTROL and INSTRUMENTATION

ATEX VACUUM PUMPS AND GAUGES CHEMICALLY RESISTANT, OIL-FREE AND SAFE

DF-550E PROCESS ANALYSERS APPLICATIONS FEATURES

OPERATING INSTRUCTIONS Pressure Control System PCS-20 through PCS-100

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL OTHER FLUID POWER VALVES. This work covers part of outcome 2 of the Edexcel standard module:

CHAPTER 7: THE FEEDBACK LOOP

CMC Peer-to-Peer Control System Software. User s Manual Version 1.0

Is there any visible damage to the machine? If yes, describe damage:

WF STEUERUNGSTECHNIK GMBH. INFORMATION and TECNICAL DESCRIPTION

PressureGuard. Self-Contained Hydraulic Emergency Shutdown Systems For Rotary or Non API 6A Linear Valves

FUEL GAS FIRING CONTROL RJ (Dick) Perry Safety Systems Consultant 6 June 2016

Digital Vacuum Regulator

Gas Injection Systems

Lifespan Improvements Available in the Industry

Coriolis Mass Flow Meter

LPG, LEG, LNG tankers & Chemical and Product tankers

RPKA. Heat Pumps. Parts List 07-May-2014

Perpetua Power Puck Solutions

Types S100K and S102K Pressure Regulators

Solenoid Valves used in Safety Instrumented Systems

mcsg Ultra-compact Clean Steam Generation System Installation and Maintenance Instructions

Flow and Energy Measurement F-5400 THERMAL MASS FLOW METER

MOL LNG Transport (Europe) Ltd File: 02 Checklists 6 pages Rev. No. 1 Loading Plan Part Two (2) (Line UP) Loading Plan Part Two (2) (Line Up)

Is there any visible damage to the machine? If yes, describe damage:

Required Indoor Draft Hood. Optional Outdoor Vent Cap

Transcription:

Ultra-efficient chiller plant automation Sequence of operation File No: 90.897 Date: december 17, 2015 Supersedes: new Date: new

2 variable primary chilled water operation general requirements All Sequencing shall be by the bas. The bas will be responsible for calculating and adjusting speed of chilled water pumps in response to the building requirement and min/max flow of the chillers. The bas will manage the staging and rotation of equipment. At any time, the bas shall have the ability to override recommendations. The shall provide recommended operating points as outlined in the points list including chwst set point. The will provide a recommendation of the number of chillers and cooling towers to run including number of pumps to match chiller and tower requirements. The will provide a recommended speed for condenser water pumps and cooling tower fans. normal operation 1 The is always enabled. 2 The plant start-up and shutdown sequence is as per the bas internal and independent to the. 3 The will recommend a number of chillers/ cooling towers to run. 4 The bas will enable the required number of chillers/cooling towers. 5 The bas will start the primary chilled water pumps and condenser pumps associated with active chiller/tower. 6 The bas will confirm minimum-flow is met before starting the associated chiller/s. 7 The bas shall calculate the speed of the chilled water pumps. 8 The bas shall adjust the chilled water pump speed to: Maintain the active dp zone at set point. Maintain the minimum flow required by the active chillers Where; a A change in chwp speed in the down direction shall have a 60 second delay. b The up speed change shall occur only after the flow difference is 3% or more. 9 The bas shall maintain all primary chilled water pumps at the same speed. 10 The bas shall restrict primary chilled water pump speed to match chiller minimum flow and chiller maximum flow settings as determined during commissioning. 11 The bas shall modulate the chw bypass valve to maintain minimum flow through the active chillers. 12 The will recommend condenser pump speed, and cooling tower fan speed. 13 The bas will adjust the condenser pump and cooling tower fan speed based on recommendations; and can over-ride recommendations at any time. 14 The bas shall communicate operating data to the optivisor tm as per the attached points list.

3 general assembly drawing 16.00 10.75 20.00 system architecture Serial Communication to bas: BACnet ms/tp BACnet tcp/ip Modbus rtu Flow meter chw Temperature Transmitters Chiller Isolation Valves chw Bypass Valves dp Switches building automation system cw Temperature Transmitters Cooling Tower Isolation Valves cw Bypass Valves oat Sensor Chiller(s) Chilled Water Pump(s) Condenser Water Pump(s) Cooling Tower Fan(s)

4 data pointslist # variable name description 1 Primary Flow Gallons per Minute, 0 decimals 2 chwst Fahrenheit, 1 decimal 3 chwrt Fahrenheit, 1 decimal 4 lcwt Fahrenheit, 1 decimal 5 ecwt Fahrenheit, 1 decimal 6 Chiller 1 Status 0=n/a, 1=stop, 2=running, 3=alarm 7 Chiller 2 Status 0=n/a, 1=stop, 2=running, 3=alarm 8 Chiller 3 Status 0=n/a, 1=stop, 2=running, 3=alarm 9 Chiller 4 Status 0=n/a, 1=stop, 2=running, 3=alarm 10 Chiller 5 Status 0=n/a, 1=stop, 2=running, 3=alarm 11 chwp 1 Status 0=n/a, 1=stop, 2=running, 3=alarm 12 chwp 2 Status 0=n/a, 1=stop, 2=running, 3=alarm 13 chwp 3 Status 0=n/a, 1=stop, 2=running, 3=alarm 14 chwp 4 Status 0=n/a, 1=stop, 2=running, 3=alarm 15 chwp 5 Status 0=n/a, 1=stop, 2=running, 3=alarm 16 cwp 1 Status 0=n/a, 1=stop, 2=running, 3=alarm 17 cwp 2 Status 0=n/a, 1=stop, 2=running, 3=alarm 18 cwp 3 Status 0=n/a, 1=stop, 2=running, 3=alarm 19 cwp 4 Status 0=n/a, 1=stop, 2=running, 3=alarm 20 cwp 5 Status 0=n/a, 1=stop, 2=running, 3=alarm 21 ct 1 Status 0=n/a, 1=stop, 2=running, 3=alarm 22 ct 2 Status 0=n/a, 1=stop, 2=running, 3=alarm 23 ct 3 Status 0=n/a, 1=stop, 2=running, 3=alarm 24 ct 4 Status 0=n/a, 1=stop, 2=running, 3=alarm 25 ct 5 Status 0=n/a, 1=stop, 2=running, 3=alarm 26 Chiller 1 kw kilowatt, 1 decimal 27 Chiller 2 kw kilowatt, 1 decimal 28 Chiller 3 kw kilowatt, 1 decimal 29 Chiller 4 kw kilowatt, 1 decimal 30 Chiller 5 kw kilowatt, 1 decimal 31 chwp 1 kw kilowatt, 1 decimal 32 chwp 2 kw kilowatt, 1 decimal 33 chwp 3 kw kilowatt, 1 decimal 34 chwp 4 kw kilowatt, 1 decimal 35 chwp 5 kw kilowatt, 1 decimal 36 cwp 1 kw kilowatt, 1 decimal 37 cwp 2 kw kilowatt, 1 decimal 38 cwp 3 kw kilowatt, 1 decimal 39 cwp 4 kw kilowatt, 1 decimal

5 # variable name description 40 cwp 5 kw kilowatt, 1 decimal 41 ct 1 kw kilowatt, 1 decimal 42 ct 2 kw kilowatt, 1 decimal 43 ct 3 kw kilowatt, 1 decimal 44 ct 4 kw kilowatt, 1 decimal 45 ct 5 kw kilowatt, 1 decimal 46 chwp 1 Speed Percent, 1 decimal 47 chwp 2 Speed Percent, 1 decimal 48 chwp 3 Speed Percent, 1 decimal 49 chwp 4 Speed Percent, 1 decimal 50 chwp 5 Speed Percent, 1 decimal 51 cwp 1 Speed Percent, 1 decimal 52 cwp 2 Speed Percent, 1 decimal 53 cwp 3 Speed Percent, 1 decimal 54 cwp 4 Speed Percent, 1 decimal 55 cwp 5 Speed Percent, 1 decimal 56 ctf 1 Speed Percent, 1 decimal 57 ctf 2 Speed Percent, 1 decimal 58 ctf 3 Speed Percent, 1 decimal 59 ctf 4 Speed Percent, 1 decimal 60 ctf 5 Speed Percent, 1 decimal 61 (Optional) chw Bypass Valve Position Percent, 1 decimal 62 (Optional) cdw Bypass Valve Position Percent, 1 decimal 63 (Optional) Most Open Cooling Valve Position Percent, 1 decimal 64 (Optional) Dry Bulb Temperature Fahrenheit, 1 decimal 65 (Optional) Wet Bulb Temperature Fahrenheit, 1 decimal 66 Number of Chillers Demand Integer 67 Number of Condenser Water Pumps Demand Integer 68 Condenser Water Pumps Speed Percent, 1 decimal 69 Number of Cooling Towers Demand Integer 70 Cooling Tower Fan Speed Percent, 1 decimal 71 chws Temperature Setpoint (Optivisor) Fahrenheit, 1 decimal 72 Watchdog Integer, Increments by 1 every 5 seconds, rollsover at 100 73 bas Non-Compliance Alarm true = Non-Compliance, false = Compliance

toronto 23 bertrand avenue toronto, ontario canada m1l 2p3 +1 416 755 2291 buffalo 93 east avenue north tonawanda, new york u.s.a. 14120-6594 +1 716 693 8813 birmingham heywood wharf, mucklow hill halesowen, west midlands united kingdom b62 8dj +44 (0) 8444 145 145 manchester wolverton street manchester united kingdom m11 2et +44 (0) 8444 145 145 bangalore #59, first floor, 3rd main margosa road, malleswaram bangalore, india 560 003 +91 (0) 80 4906 3555 shanghai no. 1619 hu hang road, xi du township feng xian district, shanghai p.r.c. 201401 +86 21 3756 6696 são paulo rua josé semião rodrigues agostinho, 1370 galpão 6 embu das artes sao paulo, brazil +55 11 4781 5500 armstrong fluid technology established 1934 armstrongfluidtechnology.com tm