ambiente Installation Guide AmbiPlate more than underfloor Customer: Project: Project Reference: Date:

Similar documents
ambiente Installation Guide AmbiScreedboard system more than underfloor Customer: Project: Project Reference: Date:

ambiente Installation Guide AmbiClip Systems more than underfloor Customer: Project: Project Reference: Date:

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

ENERGY BLADE 3K4. Energy Blade Installation Instructions

1. ABOUT THE PRODUCT:

SIMPLAIR PIPING TOOL. JXT Company

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

System Pressure Manager Standard & System Pressure Manager Plus

TOOL BOX 033- HOSEREEL SERVICE / FAULT FINDING

Budget Range Operators Handbook

Installation and commissioning instructions 255 series and 256 series

KTM 50 (DN ) Installation, maintenance and operating instructions

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150,

OWNER S TECHNICAL MANUAL

Engineering Data Sheet

IMPORTANT PLEASE READ BEFORE COMMENCING INSTALLATION

Flamco Flamco-Fill STA Flamco-Fill STM

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

Booster Pump PB4-60 Replacement Kits

AREA VALVE SERVICE UNITS

Installation, operating and maintenance Instructions for Seemag bypass level indicator

LNVx Gas Conversion Kit Instructions

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS

UltRo Dual Flow Reverse Osmosis Water System

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels

OPERATING AND MAINTENANCE MANUAL

Jacuzzi. J-CQ420 Cartridge Filter Installation and Operating Instructions

Electronic Single and Twin Pump System Pressure Managers

Thanks for choosing EJAI SOLAR product

Hydraulic Piston Accumulators

HYDRAULIC CYLINDER TEST

Assembly-, installation- and maintenance instruction manual for bladder accumulators IBV / EBV , top reparable

OPERATING INSTRUCTIONS

ThermaSkirt A N E C O R E V O L U T I O N I N R O O M H E A T I N G

Index Table. Model 794. Installation, Operating and Maintenance Instructions

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

1805 Series Relief Valves

book : t95575.fm Seite 1 Mittwoch, September 20, :10 AM. Avensys. Exposed Single Lever Mixer

bathrooms.com Concentric Thermostatic Shower Mixers Cleaning and Care Installation Manual Contents

OPERATION MANUAL NTF-15

B. Assemble the Method-25 sample train with a heated probe/filter.

Assembling and testing fluid power systems

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

SEries 29 Hydrant valves installation, operation & maintenance manual

TECHNICAL DATA. Q = C v P S

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats

Document How to Set Single Stage Press Pressures

Operation and Maintenance Instructions

Gas Conversion Kit Pilot Ignition Heaters

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

TECHNICAL DATA. Q= Cv S

OPERATION & MAINTENANCE INSTRUCTIONS

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

Installation and operation Manual. Bermad Surge Anticipation Valve. Model No 435

OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N

HORNE 20 THERMOSTATIC MIXING VALVE TYPE H-2003

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

INSTALLATION AND OPERATION INSTRUCTIONS

BS ml Bottle Sampling Unit

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

FILTER REGULATORS MODEL NO: CAT155 & CAT156 FITTING & MAINTENANCE INSTRUCTIONS PART NO: & ORIGINAL INSTRUCTIONS

k valve 2 (50)HF 2½ (65)SF installation guide aylesbury For valve sizes (DN): tel fax

Rapidmain Installation Guide

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

JET Mini Mechanical Pressurisation Equipment

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

BASIN AND WALL MIXER INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS Non-Pressurized Tank. Non-Pressurized Tank Part Number: AFCG1PT

AYLESBURY 'KB' TYPE FLOAT VALVES

Pure-Flo Handwheel Operated Valves (903, 913, 963) Instruction Manual

PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH

TB132. Gas Conversion Kits for NV & NVS Heaters. Issue 1.0 May Applies to models: NV & NVS

OPERATION MANUAL NTF-60 Plus

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

INSTALLATION AND OPERATION INSTRUCTIONS

SCA Series Inverted Bucket Steam Traps

Operation Manual Air Saver Unit ASV5000 Series

OWNER S GUIDE DUAL CONTROL THERMOSTATIC SHOWER VALVE. Shower Control. may differ depending on choice of Model. Concealing Plate. Handles and ISSUE 01

Fiber Optic Lighted Bubbler Spillway Pot (DLP-45) Installation Manual

MUELLER. Mega-Lite Drilling Machine. Reliable Connections. table of contents PAGE. Equipment 2. Operating Instructions 3-4. Parts Information 5

ATV 90 Y-12 YOUTH 2-STROKE RED (A2004ATB2BUSR) Page 1 of 52 A-ARM, FLOOR PANEL, AND BUMPER ASSEMBLY

1.0 - OPENING AND CLOSING THE DOOR

Manual Actuated Boiler Blowdown Valves

)RU FHUWLILHG FRPSDQLHV ROTEX 509 +HDWLQJ FLUFXLW GLVWULEXWRU 2SHUDWLQJ LQVWUXFWLRQV

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

SMV-001 Thermostatic Shower Mixer Valve Installation Instructions & Adjustment Settings

SIGNATURE DEF REELS Models: Bare Reel Reel Reel Reel

Model 106 DPI "Micro-switch" Installation and Operating Instructions

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Operating Instructions Model and Hydrostatic Test Pump

THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER

FPD175 Compact orifice carrier assembly

Direct Operated Precision Regulator Modular Style. Standard Specifications

Operating Instructions Models 36200, , 46200, Hydrostatic Test Pumps

Transcription:

ambiente more than underfloor Customer: Project: Project Reference: Installation Guide AmbiPlate 0 0 Date:

Ambiplate installation guide AmbiPlate Series Contents Designed for joisted/battened floors Maximum heat transfer Even heat diffusion highly conductive No impact on floor buildup Quick response time AmbiPlate systems are suitable for joisted and most timber floors with either joists or battens. The pre-grooved plates are fixed to either battens or joists and the UFH pipe is run through the grooves and mineral wool insulation is placed underneath the plates to ensure that the heat is deflected upwards to the floor. AmbiPlate system introduction Technical data Installation method Manifold positioning Commissioning the system step by step guide Record and report Almost any type of floor covering can be used with AmbiPlate, see floor coverings section of this guide for more details. This installation guide is suitable for the following AmbiPlate systems. Data sheets can be downloaded directly from our website. www.ambienteufh.co.uk AmbiPlate 0 (battened) AmbiPlate 0 (JOISTED) Ambiente Installation Guide t 0 1 1 e info@ambienteufh.co.uk

Technical data Technical Pipe Plate 1mm x mm PE-RT pipe 00mm x 0mm x 0.mm Diffuser Plate Heat Output Table - AmbiPlate systems Floor Finish Flow and Return Water Temperatures O C 0/0 / 0/0 Ceramic Tile (0.m K/W) 0 w/m w/m w/m Wood (0.1m K/W) 0 w/m w/m w/m Carpet and Underlay (0.0m K/W) w/m w/m w/m 1mm chipboard has been used as a sub floor layer in formulating the heat emissions shown above. Ambiente goes beyond just simply the supply of underfloor heating systems. At every stage in the project, we offer advice to all parties, in order to assist in the swift, safe and supportive implementation of your project. From project initiation to final commissioning, ambiente have every stage of underfloor heating covered. For more help and advice, contact our team of highly trained experts today. Visit us online at ambienteufh.co.uk for case studies, product resources and more information. For any installation questions speak to our installation team today on 0 1 1 or email info@ambienteufh.co.uk. For any information regarding our products and support call our highly trained sales team today on 0 1 1. www.ambienteufh.co.uk

INSTALLATION METHOD 1 Refer to the design plan drawings and prepare to lay the floor in accordance with the layout described. 1 Lay the insulation between battens/joists followed by the grooved diffuser plate. Check the system plans for the number and length of each loop required. Note: Ambiente pipe is marked every metre to help you calculate loop lengths. Starting on the left side of the manifold, connect to the manifold flow bar. Make a note of which zone the loop serves on the manifold tag supplied. Lay the pipe out, navigating the most efficient route between the manifold and the zone. Pipes will need to be notched into the batten/joist when they loop from one joist void to another. Secure aluminium diffuser plate to the batten/joist. Lay pipe into the pre-grooved aluminium diffuser plates, as per the system designs. Use pipe clips to secure the tail pipework as it crosses the batten/joist. On completion of the loop, follow the same route back to the manifold and connect to the return bar (bottom bar with blue caps), making a clear note of the actual loop length installed on the manifold tag. Follow the same procedure for all loops until the area is evenly covered with pipe, following your pipe layout design. Once all loops are installed and connected to the manifold, pressure test the system. 11 Lay final floor finish after the system has been successfully pressure tested. Ambiente Installation Guide t 0 1 1 e info@ambienteufh.co.uk

Manifold Positioning 0mm 0mm min. Note that the two manifold bars are offset so that the pipes can pass behind the lower bar for connection to the top bar we recommend using the top bar as the flow and the bottom bar as the return. The manifold comes left-handed as standard, but can be changed, see opposite for how to change the handing of Ambiente manifolds. 0mm 0mm mm Ambiente manifolds are supplied ready assembled and simply need mounting on brackets prior to installation. < Flow Local Fused Spur (on heating RCD) 0mm > Return 0vt Relay Box (if required) Wiring Centre Manifolds should be positioned where they are easily accessible to allow for future servicing and commissioning. We recommend allowing at least 00mm between the finished floor level and the bottom of the manifold, with mm clearance above and at least 0mm at either side. 0mm > Flow 00mm min. (00mm pref.) < Return Isolation points to be installed on primary pipework prior to the manifold for servicing purposes. Final Floor Level (FFL) 0mm min. 0mm min. for supply pipework 1mm 0mm As per table below 0mm min. 1 Manifold flow bar Manifold return bar Isolating ball valves CircoMax circulating pump Blending valve 1 Flow meter Actuator head (shown with pre-install caps) Pressure gauge Air vent Filling taps mm 0mm See manifold table below Four port manifold shown for example purposes Number of ports 11 1 Manifold Length (mm) 1 www.ambienteufh.co.uk

Commissioning the system Step By Step Checklist Filling and flushing the system Sequence Checklist Completed 1 Close the isolating ball valves that are connected to the manifold on both bars. Isolate all zones by screwing down the blue caps on the bottom (return) bar and the flow meters on the top (flow) bar. Open the first flow meter (start furthest away from the filling valve) on the top (flow) bar (use the red collar to turn the black section fully anti-clockwise, do not use grips hand tight only). Ensure that all other flow meters are closed, except the loop that you are flushing. Remove the black plastic blanking cap from the filling valve on the top (flow) bar and fit the hose connection/hose which should be connected to the mains water supply. Open the filling valve using the key on the reverse of the drain valve cap. Fix a suitable hose to the drain valve on the bottom bar. Fully loosen the blue protection cap on the bottom bar on the first zone to be filled. Open the tap on the mains water supply and open the drain valve on the bottom bar using the key on the reverse of the blanking cap. Run water through the loop until air is removed from the system, closing down the blue caps on each loop as it is purged. This can now be repeated for each zone by opening the next zone, closing the flushed zone and repeating steps -. At this point the system can be pressure tested if required by closing the drain valve and unscrewing all the blue protection caps the pressure should rise slowly allow it to rise to bar and then close the filling valve and close off the mains water. This should be left for hours to check for any significant drops in pressure. Pressure testing using an air compressor Sequence Checklist Completed 1 Close the isolating ball valves that are connected to the manifold on both bars. Open all zones by unscrewing the blue caps on the bottom (return) bar. Open all flow meters on the top (flow) bar use the red collar to turn the black section fully anti-clockwise. Open the filling valve using the key on the front of the blanking cap and connect the compressor hose up to it. Make sure the drain valve is closed. Turn on the air compressor and allow the pressure to rise to bar. Once the desired level has been reached, close the filling valve using the key on the blanking cap. This should be left for hrs to check for any significant drops in pressure. Change the handing of Ambiente manifolds Sequence Checklist Completed 1 Reverse the handing of the two manifold bars on their brackets. Remove the mixing valve from the base of the pumpset by undoing the nut that connects the two together. Unscrew the blanking cap from the base of the mixing valve. Note: this has a left-handed thread. Then unscrew the pump connection from the top of the mixing valve. Again, this has a left-handed thread. Rotate the mixing valve through degrees and swap the blanking cap and pump connection around. Remount the mixing valve onto the pumpset, making sure you use the rubber washers provided. Ambiente Installation Guide t 0 1 1 e info@ambienteufh.co.uk

Record and Report Site details Site name Address Date Reference Technician Floor level Pipe reference Manifold reference Please tick the appropriate boxes Installation Re-pressurise Repair Test method Hydraulic (Water) Period of test Min 0 mins Test method Co (air) Test pressure Min bar Sufficient room to attach pumpset (minimum 0mm required) Yes N/A Has the manifold label been fitted? Description Yes No Comments System left drained System left full of water System left under pressure Signature of tester Print name Date Signature of witness Print name Date Ambiente Systems UK cannot accept liability for water freezing within the pipes. This form must be completed and a copy returned to Ambiente Systems UK within 0 days of installation or 1 weeks of delivery, in order to activate the warranty. Please return to: Ambiente Systems UK, 1 Woodside Lane, Bell Bar, Hertfordshire AL DE Or mail a scanned form to: info@ambienteufh.co.uk www.ambienteufh.co.uk

ambiente more than underfloor Need more information or advice? Contact our team of highly trained experts today. 0 1 1 info@ambienteufh.co.uk www.ambienteufh.co.uk Ambiente Heritage House, 1 Woodside Lane, Bell Bar, Hertfordshire AL DE t 0 1 1 e info@ambienteufh.co.uk www.ambienteufh.co.uk