Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Similar documents
Type Operating Instructions. 2/2-way solenoid valve 2/2-Wege Magnetventil Electrovanne 2/2 voies.

Type 0404 / /2-way solenoid valve 2/2-Wege-Magnetventil Électrovanne 2/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Rocker valve. Type Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type 2000 INOX. Quickstart. English Deutsch Français. 2/2-way angle seat valve 2/2-Wege Schrägsitzventil Vanne à siège incliné 2/2 voies

Type 2080 FALTENBALGVENTIL BELLOWS VALVE VANNE A SOUFFLET. Operating Instructions. Bedienungsanleitung Manuel d utilisation

Type /2-Way Globe Valve 3/2-Wege-Geradsitzventil Vanne à siège droit 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

Type BBS-03, BBS-05, BBS-06, BBS-25

Type C-CUT. Quickstart. English Deutsch Français

* * Data Sheet and Operating Manual. Digital manometer ME01 ## # 87 # HL S#### Dust explosion protection Zone 22.

Operation Manual Air Saver Unit ASV5000 Series

Type 2030, 2031, 2031 K, 2032, 2033, 2037

Safety. Operating instructions Solenoid valve for gas VG 6 VG 15/10 DANGER. Contents WARNING CAUTION. Changes to edition 09.14

2/2- and 3/2-way Rocker Solenoid Valve - bistable (impulse) version

Mounting and Operating Instructions EB 2558 EN. Self-operated Pressure Regulators. Type Pressure Build-up Regulator

SPCH/ Blowing block

Instruction Manual Differential Pressure Transmitter

4/2 way Pneumatic Solenoid Valve

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

Pressure maintenance valve SDV-P / SDV-P-E

Instruction Manual Contact Pressure Vacuum Gauge

Installation & Maintenance Instructions TEC-11N TIMER. Analogue electronic timer 02/09

Electro-Pneumatic Converter YT-940 SERIES

MANUAL DIRECT PURGE OPTION. UNION Instruments GmbH CWD2005 PLUS. General information, safety standards and regulations for direct purge option

Operating Instructions

Mounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity

444C DUAL PERFORMANCE VALUE PACK

Instruction Manual Differential Pressure Transmitter

Type 3709 Pneumatic Lock-up Valve. Translation of original instructions. Mounting and Operating Instructions EB 8391 EN

Pneumatic proportional controller Types M Types FM Function tested for use of the float in Ex-zone 0

3G Operating instructions. Digital Purge Gas Valve 3G Type: Document no.: D0001 Version: 01. July 2011/Rev.

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

Inverse Proportional Pressure-Relief Cart., Size 2 4

Instruction Manual Contact Pressure Gauge

Type Pressure Regulator. for increased air capacity. Fig. 1: Type Pressure Regulator. Mounting and Operating Instructions EB EN

Proportional Pressure-Relief Cartridge Valve, Size 2...4

Inverse Proportional Pressure-Relief Cart., Size 2 4

2/2-Way Solenoid Control Valve

Pressure booster combination DPA-CRVZS. Operating instructions a [ ]

Pneumatic pressure switch 20DD

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

OPTIBAR P 1010 C Technical Datasheet

Safety. Operating instructions Solenoid valve for gas VG 10/15 VG 65 DANGER. Contents WARNING CAUTION. Changes to edition 11.14

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

Operating and maintenance manual Filter and reducing station Series / 1.0

Proportional Pressure-Relief Cartridge Valve, Size 2...4

Prop. 3-Way Pressure-Reducing Cart., Size 5 / SAE 08

Mounting and Operating Instructions EB 8546 EN. Type 4708 Supply Pressure Regulators. Translation of original instructions. Type Type

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

Inverse Prop. Pressure-Relief Cart., Size 2 4

No.IL02-OM00011-A PRODUCT NAME LOCK UP VALVE. MODEL/ Series IL201 IL211

These operating instructions apply to: PKL 190 PKL 2100 PKL 450 PKL 5000 PKL 740 PKL 10000

200 PSI COMPRESSORS - MODEL NUMBERS

Compact pressure switches for gas and air

100C Air Compressor Kit

VS18/26 with PROFINET and EtherNet/IP Interface. ATEX Installation Instructions

Proportional Throttle Cartridges, Size 16

400C & 450C DUAL PERFORMANCE VALUE PACKS

Declaration of Conformity as per Directive 97/23/EC

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

OPERATION MANUAL PNEUMATIC VALVES

Single and double acting, magnetic, self-centering Bores: ø 16, 20, 25, 32, 40 mm

Instruction manual. for. high purity gas pigtails 200 bar / 300 bar

Operating Manual * * Pressure Transmitter. Table of Content. 1 Safety Guidelines. 1.3 Risks due to Non-Observance of Safety Instructions

Operating Instructions

RTD Temperature sensor TH11

2-finger parallel gripper KTG 50

OPERATING MANUAL CHEMTRAC 840M MANUAL RETRACTABLE PROCESS HOLDER

Measurement accessories METPOINT OCV for the measurement in systems up to 40 bar

Safety instructions and operating manual

DK46 - DK800 Supplementary instructions

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

IMPORTANT SAFETY INSTRUCTIONS

Operating Instructions

compact ejector, Series ECM with Adjustable release pulse with silencer With filter vacuum switch: electronic 2 x PNP

Inverted Bucket Steam Trap IB 16A-7

FMMP. FluidMonitoring Module Pressure. Operating and Maintenance Instructions. English (Translation of original manual) Documentation no.

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

Air Purge Unit. Series: LSP-compact Type: EJG 2-2. (Controlled with DigiFlow 515) Installation & Operation Manual 11/2014

Siphon vessel / Priming aid

Type 4708 Supply Pressure Regulator

Inverse Proportional Pressure-Relief Cartridge, Size 10

INSTRUCTION MANUAL Pressure Relief Device LPT

LRS(H)4 Pressure-Reducing Regulator User Manual

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

Mounting instructions. Strain transducer SLB-700A. B 26.SLB700A.10 e

3-Way Safety Block DSV

SPECIFICATIONS ATTENTION

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

Mounting and Operating Instructions EB 8546 EN. Supply Pressure Regulator Type Fig. 1 Supply pressure regulators

Pressure reducing valve, pilot operated

MODELS (2 foot Version) (4 foot Version)

Pull-rope emergency stop switch Type HENEX and SEGEX OPERATING INSTRUCTIONS

2/2-Way Proportional Valve (motor-driven)

PRAHER PLC-MP AQUASTAR MANAUL 2009

Flow and check valves Logic valves series 551. Brochure

Type C-CUT. Operating Instructions. Bedienungsanleitung Manuel d utilisation

GAS FUEL VALVE FORM AGV5 OM 8-03

Pilot Check Valve: Metal Body Type

Transcription:

2/2- and 3/2-way cartridge solenoid valve 2/2- und 3/2-Wege-Cartridge-Magnetventil Électrovanne cartridge à 2/2 ou 3/2 voies Operating Instructions Bedienungsanleitung Manuel d utilisation

We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous réserve de modifications techniques. Bürkert Werke GmbH & Co. KG, 20-2017 Operating Instructions 1706/ _ _00 / Original DE

Contents 1 Operating instructions...4 1.1 Definition of term... 4 1.2 Symbols... 4 2 Authorized use...5 8 Shutdown...14 8.1 Safety instructions...14 8.2 Disassembly...14 9 Transport, storage, disposal...15 3 Basic safety instructions...5 4 General information...6 4.1 Contact address... 6 4.2 Warranty... 6 4.3 Information on the Internet... 6 5 Technical data...7 5.1 Operating conditions... 7 5.2 Fluidic data... 8 5.3 Designation... 9 6 Installation...9 6.1 Safety instructions... 9 6.2 Installation space of the cartridge solenoid valve...10 6.3 Installation of Type 6164...11 6.4 Electrical connection...12 6.5 Electrical installation...13 7 Maintenance, troubleshooting...14 7.1 Maintenance...14 7.2 Troubleshooting...14 3

Operating instructions 1 Operating instructions The operating instructions describe the entire life cycle of the device. Keep these instructions in a location which is easily accessible to every user, and make these instructions available to every new owner of the device. Important safety information. Read the operating instructions carefully and thoroughly. Study in particular the chapters entitled Basic safety instructions and Authorized use. The operating instructions must be read and understood. 1.1 Definition of term The term device used in these instructions always stands for the cartridge solenoid valve Type 6164. 1.2 Symbols The following means of representation are used in these instructions. Danger! Warns of an immediate danger! Failure to observe the warning may result in a fatal or serious injury. Warning! Warns of a potentially dangerous situation! Failure to observe the warning may result in serious injuries or death. Caution! Warns of a possible danger! Failure to observe this warning may result in a moderate or minor injury. Note! Warns of damage to property! Indicates important tips and recommendations. Refers to information in these operating instructions or in other documentation. designates instructions for risk prevention. designates a procedure which you must carry out. 4

Authorized use 2 Authorized use Non-conforming use of the cartridge solenoid valve Type 6164 may be a hazard to people, nearby equipment and the environment. The cartridge solenoid valve has been designed for application as a pneumatic valve. It controls neutral gases. Do not use the Type 6164 outdoors. In the potentially explosive area use Type 6164 only according to the specification on the separate Ex identification. To use the device, observe the additional information with safety instructions for the Ex area enclosed with the device. Do not use devices without a separate Ex identification in the potentially explosive area. Only use the device in combination with installation dimensions recommended by Bürkert. The device must be used in compliance with the characteristics and commissioning and use conditions specified in the contractual documents and in the user manual. Correct transportation, correct storage and installation and careful use and maintenance are essential for reliable and faultless operation. Use the device only as intended. 3 Basic safety instructions These safety instructions do not make allowance for any contingencies and events which may arise during the assembly, operation, and maintenance. local safety regulations the operator is responsible for observing these regulations, also in relation to the installation personnel. Risk of injury from high pressure in the system or device. Before working on the system or device, cut off the pressure and deaerate or drain lines. Risk of injury due to electrical shock. Before working on the system or device, switch off and isolate the power supply to prevent reactivation of the device. Observe applicable accident prevention and safety regulations for electrical equipment! Risk of burns or risk of fire if used for a prolonged duty cycle through hot device surface. Keep the device away from highly flammable substances and medium and do not touch with bare hands. 5

General information General hazardous situations. To prevent injury, ensure: Secure the device from unintentional actuation. Only trained technicians may perform installation and maintenance work. Install the valves in accordance with the valid regulations of the respective country. After an interruption in the power supply, ensure that the process is restarted in a defined or controlled manner. Observe the general rules of technology. To prevent damage to property of the device, ensure: Do not use the cartridge solenoid valve for fluids. Do not feed aggressive or combustible media into the media connections of the system. Do not carry out any external modifications to the devices. 4 General information 4.1 Contact address Germany Bürkert Fluid Control Systems Sales Center Christian-Bürkert-Str. 13-17 D-74653 Ingelfingen Tel. + 49 (0)7940 10-91 111 Fax + 49 (0)7940 10-91 448 E-mail: info@burkert.com International Contact addresses are found on the Internet under: www.burkert.com 4.2 Warranty The warranty is only valid if the device Type 6164 is used as authorized in accordance with the specified application conditions. 4.3 Information on the Internet The operating instructions and data sheets for Type 6164 can be found on the Internet at: www.burkert.com 6

Technical data 5 Technical data 5.1 Operating conditions Warning! Risk of injury due to malfunction if device used outdoors. Do not use the device outdoors and avoid heat sources which may cause the permitted temperature range to be exceeded. Permitted temperature 1) Design Ambient temperature Medium temperature Standard -10...+55 C -10...+55 C Special design (variable code NF22 in the device key) -20...+55 C -20...+55 C 1) Deviating temperature ranges will be approved after technical clarification. Note! The specifications with respect to the ambient temperature apply in general to a single valve installation and to a row of valves installed in a brass block (voltage tolerance ±10 %; duty cycle 100 %). If installation materials or installation situations differ, the specified ambient temperature can be reached by reducing the voltage tolerance to ±5 %. Medium: Life time: If parts of the compressed air network are subject to lower temperatures than the ambient temperature, select the humidity class so that the pressure dew point is 10 K below the minimum expected temperature to prevent the risk of icing over. To do this, observe DIN ISO 8573-1. Degree of protection: compressed air, neutral and gaseous media (filtering 10 µm), technical vacuum if devices have device key NL07 (installation without lubrication), the life time will be reduced accordingly in the installed state depending on the electrical connection: Pins: IP00 Special plug: IP40 Wires: IP54 Protection class: 3 according to IEC 61140 7

Technical data 5.2 Fluidic data Circuit function 2 C 1 3 3/2-way valve, direct-acting, deenergized output 2 depressurized Circuit function C Circuit function D Circuit function T (can also be used as circuit (can also be used as circuit function A by blind connection to 3) function B by blind connection 3) D 2 1 3 3/2-way valve, direct-acting, deenergized output 2 pressurized 3 1 3/1 T 2 1 3 3/2-way valve, universally applicable Fig. 1: 2 1 Fluidic connections 3 2 1/3 2 Fluidic connections 1 P Pressure port 2 A Working port 3 R Exhaust air port 8

Installation 5.3 Designation Fig. 2: Circuit function Type Voltage Designation on the device (example) Nominal diameter Seal material Identification number Approval information 6 Installation 6.1 Safety instructions Danger! Risk of injury from high pressure in the system or device. Before working on the system or device, cut off the pressure and deaerate/drain lines. Observe applicable accident prevention and safety regulations for electrical equipment. Warning! Risk of injury from improper installation. Installation may be carried out only by trained technicians and with the appropriate tools. Warning: Sharp solder pins. Risk of injury due to inadvertent switching on of the system and uncontrolled restart. Secure system against unintentional activation. Following installation, ensure a controlled or defined restart. 9

Installation 6.2 Installation space of the cartridge solenoid valve Cartridge solenoid valve, fully recessed Cartridge solenoid valve, semi-recessed * * E Ø9.1±0.05 E Ø 8.77±0.05 Ø1.4±0.05 Ra1.6 Ø4.2 Connection assignment according to circuit function 19.55±0.03 14.5±0.05 11.2±0.05 9 6.5 0.3 Ø1.3±0.03 13.75±0.03 0.1 x 30 19.85±0.03 M2.5 3±0.10-0.2 +0.1 3±0.10 0.2±0.10x45 30 Ø9.2±0.05 Groove recommended for disassembly (Ø 8.77) Location of the M2.5 thred anywhere on ø 13.2 Ø13.2 Ra0.8 Rmax10 R0.2±0.10 Rmax16 Ra0.8 30 30 7.5±0.05 M1.6 x 5 M1.6 x 5 (Ø 9.1) Ra 0.8 Rmax10 13.2±0.05 (11.2) fully recessed 3.8 (0) semi-recessed (14.5) fully recessed (8.65) semi-recessed * E Ø8.77±0.05 Ø1.4±0.05 Ø 4.2 Connection assignment according to circuit function 8.85±0.03 3.8±0.05 0.3±0.05 0.1 x 30 9.15±0.03 E * Diameter tolerated acc. to ISO 14405 E 30 * Ø 9.1±0.05 Ø1.3±0.03 3.05±0.03 Fig. 3: Installation space for fully recessed and semi-recessed cartridge solenoid valve 10

Installation 6.3 Installation of Type 6164 Check the O-rings at the valve and the installation space for cleanliness. Outer O-rings are provided with an anti-friction coating at the factory. If required, use a suitable lubricant (e.g. water) during installation. Define the alignment of the electrical contacting, use the front bore for this purpose (see Fig. 4 right). Note! Damage to device caused by transverse forces on encapsulation or pin. Do not touch the socketing or pin. F Socketing and pin 2.5 X 1-0.4 deep Fig. 5: in relation to the screw axis only in the areas highlighted in gray (see Fig. 5 ). Alignment of the pins for the semi-recessed valve Secure the valve using the supplied fasteners (screw, bracket). To ensure that the valve functions perfectly, screw the screw head as far as the block support and ensure that the bracket is correctly positioned. Fig. 4: Alignment of the electrical contacting Install the valve (it can no longer be moved when installed). In the case of the semi-recessed model, the pins can be aligned Fig. 6: Correct position of the bracket 11

Installation Observe tightening torques: - fully recessed valves max. 0.65 Nm, - semi-recessed valves depending on material of the mounting block (e.g. brass max. 0.12 Nm). Cartridge solenoid valve, fully recessed Cartridge solenoid valve, semi-recessed 6.4 Electrical connection 8.3 0.5 5.08 Observe polarity for Ex device 2.8 PFA Wire AWG 24 Width: 11 Width: 11 3.3 3.8 10 6.3 Do not use the socketing and pin for the alignment Do not use the socketing and pin for the alignment Fig. 7: Installation of the cartridge solenoid valve Contact the valve electrically. 4.3 2.65 1.4 Fig. 8: R1.6 4.3 2.65 1.4 3.2 7.6 7.6 Electrical connection R1 2.5 When directly soldering pins, do not exceed maximum soldering temperature of 350 C short term. 12

Installation 6.5 Electrical installation Voltage supply: DC, Tolerance ±10 % UL recognized (Code PU01): only for connection to a NEC Class 2 supply Power consumption: 0.7 W (standard) see data sheet for further versions Nominal operating mode: Continuous operation, on time 100 % All devices of Type 6164 with the LT feature in the device key must be operated with an external power reduction. Note! Malfunction due to overheating. If devices with the LT feature in the device key are operated without a power reduction, overheating may occur. If a power reduction is applied, the following parameters must be used: PWM-Signal f = 20 khz U Duty cycle = 30 % Switch-off point 100 % 0 20 ms Switch-on pulse t Characteristic values for intermittent operation according to DIN VDE 0580: t SD - Cycle time t ED - Duty cycle t SP - De-energized pause ED - Relative duty cycle SH - Switching frequency t ED t SD t SP 60 t SD [s] = SH 1 min t ED [s] = ED [%] 100 t SP [s] = t SD [s] - t ED [s] Permitted operating conditions during intermittent operation: rel ED [%] 100 90 80 70 60 50 40 30 20 10 Fig. 9: 10 20 30 40 50 60 70 Ambient temperature [ C] Relative duty cycle (ED) t SD [s] max. admissible: 75 5 Hz 10 Hz 12.5 Hz 16.7 Hz 13

Maintenance, troubleshooting 7 Maintenance, troubleshooting Warning! Risk of injury from improper maintenance work. Maintenance may be carried out only by trained technicians and with the appropriate tools. Secure system against unintentional activation. Following maintenance, ensure a controlled restart. 7.1 Maintenance The device is maintenance-free under normal conditions. 7.2 Troubleshooting In case of a fault, check: Port connections in accordance with circuit function. Operating pressure. Voltage supply and valve control. If the valve still fails to respond, please contact the Bürkert Service dept. 8 Shutdown 8.1 Safety instructions Danger! Risk of injury from high pressure in the system or device. Before working on the system or device, cut off the pressure and deaerate or drain lines. Warning! Risk of injury from improper disassembly. Disassembly may be carried out only by trained technicians and with the appropriate tools. Warning: Sharp solder pins. 8.2 Disassembly Disassembly of type 6164 is not intended. If disassembly is still necessary, proceed as follows: Switch off the pressure and drain the lines. Remove the electrical contacts. Loosen the fasteners (screw, bracket). Use suitable pliers to take hold of the valve in the provided groove and extract it out. 14

Transport, storage, disposal Note! Damage to device caused by transverse forces on encapsulation or pin. Do not touch the socketing or pin. X Groove provided for disassembly 9 Transport, storage, disposal Note! Transport damage. Inadequately protected devices may be damaged during transportation. Protect the device against moisture and dirt in shock-resistant packaging during transportation. Prevent the temperature from exceeding or dropping below the permitted storage temperature. Incorrect storage may damage the device. Store the device in a dry and dust-free location! Storage temperature: -10 +55 C. Damage to the environment caused by parts contaminated with medium. Dispose of the device and packaging in an environmentally friendly manner. Observe applicable disposal and environmental regulations. Fig. 10: Extracting a cartridge solenoid valve Prior to installation of a new valve, thoroughly clean the installation space. 15

Transport, storage, disposal 16

www.burkert.com