L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

Similar documents
Bubble Tube Installations

DPC-30 DPC-100. Reference Manual

Electropneumatic Transducer (I/P) Installation, Operation and

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION SPECIFICATIONS. CE (EMC) Compliant

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

The Ins and Outs of I/P Transducers

I/P Transducer Positioner Module

KING-GAGE. Calibration Instruction Manual. D/P LiquiSeal Purge Control and D/P Purge Control

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

Model 130M Pneumatic Controller

P-5215 Differential Pressure Transmitter

How to specify a product. Process Sensors and Mechanical Instruments

256 Pneumatic Pressure Indicator

Design Features. General Description

Model 106 DPI "Micro-switch" Installation and Operating Instructions

Installation and Operation Manual

Torque Tube TB300 Digital Transmitters

ISQB1 INTRINSICALLY SAFE ELECTRO-PNEUMATIC CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS HAZARDOUS AREA CLASSIFICATION

INSTALLATION & MAINTENANCE INSTRUCTIONS

P9000 DESCRIPTION. For parts requiring RoHS compliance, please contact factory. P February /6

OPERATING AND MAINTENANCE MANUAL

IPH 2 & IPX 2. Features Type 4X & Explosion-Proof Current-to-Pressure (I/P) Transmitters. Approved for Use with Natural Gas.

SDX Submersible Depth Transmitter User Manual

Air Bubbler Depth Gauge DG2200 Installation and Reference Manual

SDX Submersible Depth Transmitter User Manual

Inert Air (N2) Systems Manual

ACV-10 Automatic Control Valve

The Discussion of this exercise covers the following points:

BAPI Pressure Line of Products - FAQs

Title: Standard Operating Procedure for R&R Environmental Devices Model MFC201 Gas Dilution Calibrator

Model Series 62 Constant Differential Relay

Float Operated Level Controllers

QBS Electronic Pressure Regulator

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels

TANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel

Types 749B and R130 Changeover Manifolds

Liquid Level Measurement

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

FTS SUBMERSIBLE PRESSURE TRANSMITTER USER S MANUAL

The Discussion of this exercise covers the following points:

CSA Sample Draw Aspirator Adapter Operator s Manual

The M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions

Installation, Operation & Maintenance Manual

DeltaSpan Pressure Transmitters LD10 Series Owner s Manual

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

Cover Page for Lab Report Group Portion. Pump Performance

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

SINGLE VALVE WITH LOW-FLOW BYPASS

Over 20,000 Strain Gage Target flowmeters installed since 1952.

CDS-2000 CO 2 Sensor Verification, Calibration, and Troubleshooting Bulletin

analytical bulk flow distance FLOW level pressure temperature industrial communication

GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL

P900. P900, Datenblatt Seite 1 DESCRIPTION

RK-IR Sample Draw Aspirator Adapter Operator s Manual

TEK-SUB 4800B. Submersible Level Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL

INSTRUCTIONS FOR MODEL SG6500 GAS HEATERS

Liquid level measurement using hydrostatic pressure and buoyancy

INSTRUCTIONS FOR FM4460N SERIES HIGH PRESSURE, METAL TUBE FLOWMETERS

Auto-Zero Calibration Technique for Pressure Sensors

Two-Wire In Situ Oxygen Analyzer (550 to 1400 C)

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

ONSITE PROVING OF GAS TURBINE METERS Daniel J. Rudroff Invensys Metering Systems

INSTRUCTION MANUAL STATION CONTROLLER SC100 MOTOR PROTECTION ELECTRONICS, INC.

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

780S Ultra High Purity Series

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel:

RCD - Ultra-Rugged Differential Pressure Flowmeter

ACCURATE PRESSURE MEASUREMENT FOR STEAM TURBINE PERFORMANCE TESTING

T EK-SUB 4800C 19 mm Submersible Level Transmitter

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

Instruction Bulletin Addendum For Pressure-Balanced In Situ Oxygen Probes

Quick Installation Guide Doc nr.: C Date:

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW

Level MEASUREMENT 1/2016

EASIDEW TRANSMITTER with Current Source Output

RC 195 Receiver-Controller

Model PDT Dewpoint Transmitter

Air Eliminators and Combination Air Eliminators Strainers

Basic Nitriding Sampling System Hydrogen Analyzer with Calculated % DA, % NH 3, and K N Values. Operations Manual

DTG - LCD Digital Temperature Gauge USER MANUAL

RAM 4021 Operation Manual

Flow meter. bellow vaporizer. APL valve. Scavenging system

SCOPE OF THIS GUIDE STARTING-UP. 1 Check mini CORI-FLOW functional properties

Technical Manual. Liquid Level Transmitter CT801-LB/S

Improving distillation tower operation

GG-VL2-NH3 AMMONIA VENT LINE SENSOR. Installation and Operation Manual

XMO2. Panametrics Smart Oxygen Analyzer. Applications. Features. bhge.com. An oxygen transmitter for use in:

Precision Liquid Settlement Array Manual

NOVALYNX CORPORATION MODEL ANALOG OUTPUT EVAPORATION GAUGE INSTRUCTION MANUAL

RAM 4021-DPX Operation Manual

RAM Operation Manual

Instrumentation & Data Acquisition Systems

Transcription:

L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6 8 Columbia Drive, Amherst, New Hampshire 03031 USA Phone: (603) 886-9400 Fax: (603) 889-1844 sales@controlair.com www.controlair.com 741-622-064 rev. 11/09/10 L100 Bubble-Tube Level System Page 1

DANGER 1.0 INTRODUCTION 1.1 Scope The L100 Bubble-Tube Level System is comprised of fully self-contained instruments requiring only connections to air or gas supply, dip tube and electrical power source to provide precise level indication. Because only the stationary dip tube and the purged gas come in contact with the liquid, these systems are ideal for applications involving hazardous locations or strict liquid in an open tank including those which are highly corrosive, viscous, hot (molten metal), explosive, slurry type or foodstuff. In addition, the electronic output from the L100 is compatible with almost all analog instrumentation, including local and remotelylocated indicators, computers, data loggers, recorders and controllers. 1.2 Functional Description In the L100 Bubble-Tube Liquid Level System, the level is measured in a vented vessel by measuring the pressure required to force a gas into the liquid at a point beneath the surface. This method allows for level measurement without liquid entering the piping or the instrument. A pressure regulator and constant-flow regulator combine to establish a consistent flow of clean air or gas to a bubble pipe immersed a fixed distance in the tank. The flow is regulated to a very low level, building up pressure in the end of the bubble pipe. Thereafter, pressure is kept at this value by the escape of air bubbles through the liquid. Changes in the measured level cause the gas pressure to build or drop. An integral P200 is then used at this point to measure the back pressure and transmit an electrical signal proportional to the level or volume of liquid. The presence of the high-quality, industry-leading P/I Transmitter in the L100 Bubble-Tube Level System provides the user with an established and recognized electronic interface. Since the totally solid-state P200 transmitter is typically capable of accuracies of 0.10% of span, the entire L100 System may be expected to maintain a 0.25% accuracy. Additionally the L100 may be used in indoor or outdoor hazardous areas due to the NEMA 4 design and the FM & CSA explosion-proof and FM & CSA intrinsically safe certifications of the P200. The L100 provides for a variety of features which simplify the application of bubble-tube techniques to liquid level. Over-pressure relief and back-flow check valves are used to protect the P200 and are supplied as standard equipment in every system along with a flowmeter to read purge flow. Provision for manual blowdown of the bubble pipe by high pressure air is included to allow the user to clear any obstructions form the bubble pipe. Figure 1 shows a labeled drawing of the L100 System, and Figures 2 through 4 give functional representations of the technique. Note in Figure 5 the small V-notch in the bottom of the pipe which allows the air to exit in a steady stream rather than in intermittent large bubbles. The L100 System provides two possible means of accurate measurement. Although a very well-regulated constant air flow is provided by the L100, the following formula and table show that a significant pressure drop may occur in long lengths of tubing between the bubble system and the tank: P D = (K x A x L) 1000 Where: P D = Pressure drop in inches of water. K = Coefficient which is a function of the tubing. See table. A = Air flow in standard cubic feet per hour. L = Length of tubing in feet. TABLE 1 Values of K in Formula Size Pipe K Size Tubing K 1/8 (0.269 ID) 3.0 1/8 ID 70.0 1/4" (0.364 ID) 0.9 3/16 ID 12.5 3/8 (0.493 ID) 0.27 1/4 ID 4.0 1/2 (0.622 ID) 0.105 1/2" ID 0.245 1/4" (0.824 ID) 0.035 3/4" ID 0.050 741-622-064 rev. 11/09/10 L100 Bubble-Tube Level System Page 2

If the pressure instrument (P200) is connected to the purge tubing near the flow regulator, a pressure drop in the tubing can introduce appreciable error in the instrument reading, see Figure 2. If the purge flow is precisely constant for all level, environmental and operating conditions; the fixed inaccuracy due to the pressure drop in the tubing may be calibrated out by an appropriate zero readjustment. However, in high accuracy situations a large pressure drop, subject to even small operational variations eliminate this error, the air purge can be decreased, the tubing size increased, or a separate sense/return tube can be run back to the P200 from the open tank. See Figure 3. This latter solution provides a zero pressure drop as sensed by the P200 because the P200 does not consume air. Upon request the L100 can provide the proper connections for this remote sensing. Aside from the many standard features of the L100 Bubble-Tube Level System, there are numerous standard options which are listed in the Specifications section. The factory can be contacted at any time to handle specific requests. 2.0 SPECIFICATIONS Range Gas Input Electrical Input Electrical Output Accuracy Sensitivity Repeatability Operating Temperature Thermal Sensitivity RFI/EMI Effect Environmental Available Options 0-30 psi or 0-69 feet water column or equivalent, full scale. 1.0 to 7.0 SCFH, regulated on-board to a pressure between 120% or 3 psi, whichever is greater, and 200% of full scale liquid head. Maximum blow-down pressure is 150 psi. Maximum onboard regulated pressure is 60 psi. Using P200: 10-42 VDC. Autoblow-down and digital readout options also require 120 VDC. P200: 2-wire, 4-20 ma into 700 Ohms at 24 VDC or 2-wire, 10-50 ma into 280 Ohms at 24 VDC 0.25% of span; 0.2% of span typical. Includes linearity, hysteresis and repeatability errors. 0.02% of span 0.1% of span; 0.05% of span typical. 30 0 F to 161 0 F 0.007% of span per 0 F for zero and span. Meets or exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1% of span at 10 volts/meter P/I is NEMA 4X and explosion-proof, standard. Entire plate assembly fits in an optional NEMA 4 enclosure for further protection. NEMA 4X enclosure with or without digital readout, remote analog readout, auto purge. 3.0 INSTALLATION 3.1 Dip Tube Considerations A poorly constructed or mounted Dip Tube will impair the accuracy and reliability of the Bubble-Tube Liquid Level System. Some problems and causes are on the following page. 741-622-064 rev. 11/09/10 L100 Bubble-Tube Level System Page 3

Problem Fluctuating Transducer Output Signal Transmitter Zero Shift Cause 1. Poorly supported Dip Tube, (tube allowed to move). 2. V-notch omitted from tube opening, See Figure 5 3. Turbulence within tank, (not related to dip tube design). 1. Changes in pressure drop due to long length of tube before dip tube or other restriction. 2. Narrowing of dip tube air passage, due to corrosion. 3.2 Calibration The L100 Bubble-Tube Liquid Level System has been calibrated at the factory for the service and column height specified on the customers purchase order. Calibration can be affected by restrictions in the piping system due to the length of piping before the bubble-tube or the size of the piping as well as volume of gas being forced down the bubble-tube. It is important to keep the size of the piping as large as economically feasible and the length as short as possible while reducing the gas flow to that which will still provide accurate readings; approx. 1.5 SCFH. 3.2 Checking for Leaks Before the Bubble-Tube Liquid Level System can operate properly, all leaks must be eliminated. The test pressure must be conservatively selected to prevent damaging the P/I Transducer by over pressurizing the sensor. We suggest that the test pressure be no more than one and a half (1½) times the full scale operating pressure. The full scale operating pressure can be determined by showing the following equation: PRESSURE (PSIG) = COLUMN HEIGHT IN INCHES X (.036PSIG 1 IN. COLUMN) X SG. SG. = SPECIFIC GRAVITY; WATER = 1 Example: What is the full scale operating pressure if a 75 water column is being measured? FULL SCALE OPERATING PRESSURE = 75 IN. H 2 0 X (.036PSIG IN. H 2 0) = 2.7PSIG Apply (1½ ) one and a half times the full scale operating pressure to the bubble-tube system (1½ X 2.7 PSIG = 4.1 PSIG). A pressure increase can be accomplished by turning the knob of the pressure regulator clockwise. The pressure gauge mounted on the same pressure regulator will indicate regulator output. Should the tank be dry and the dip tube accessible, seal the end of the dip tube while checking the Air Rate Indicator for signs of air flow. A leak in the system will cause the black ball to float within the tube. To inspect for leaks where the dip tube is not accessible or the tank partially full, a water-soap solution must be applied to all joints. All leaks must be eliminated before the system will operate correctly. 3.3 Correcting for Output Shifts Unpredictable pressure drops caused by the configuration of the piping will cause both the zero and full scale readings to be higher than expected. To determine if an output shift has occurred, the tank will have to be empty or full, or the pipe carrying the pneumatic signal to the dip tube will have to be disconnected from the dip tube. With the tank empty or the supply pipe disconnected from the dip tube. With the tank empty or the supply pipe disconnected from the dip tube, the output of the P/I Transducer should be zero based or 4 ma on a 4-20 ma scale. If the zero or full scale reading is higher than 4 or 20 ma respectively, an output shift has occurred. An output shift due to piping affects the zero and span calibration equally. For example, a system with a zero scale output of 4.23 ma will have a full scale output of 20.23 ma. Making an adjustment to the zero potentiometer of the P/I Transducer will cause both the zero and full scale readings to change simultaneously and equally. Do not adjust span potentiometer. 741-622-064 rev. 11/09/10 L100 Bubble-Tube Level System Page 4

3.4 Blow-Down / Purging Options A build up of contaminates at the end of a dip tube could cause a restriction that would create a false level signal. To overcome this problem, blow-down systems offered with bubble-type system. See Figures 2 through 4 inclusive. Figure 2 shows our basic bubble-tube system, L100, which has dip tube blow-down feature. A counterclockwise turn of the 2-way Valve will bypass the control portion of the circuit and blow full available air pressure through the dip tube. Figure 3 illustrates a remote sensing system which also offers a dip tube blow-down feature. When the control system bypass valve is opened, the maximum available system air pressure will force out any buildup of contaminates that may have accumulated in the dip tube. This system is equipped with a pressure relief valve that will limit the pressure to the P/I Transducer to under two (2) times full scale of the device (3 psig min.). If the transducer is exposed to (3) three times full scale pressure, recalibration of the transducer will become necessary. A shut-off valve shown in Figure 3 above the tee in the remote sensing line should be closed when air purging the dip tube. Closing this valve will ensure that the P/I Transducer will not be accidentally exposed to damaging pressures. Figure 4 illustrates a bubble-tube liquid level system with an automatic dip-tube blow down feature. Figure 4 and Figure 2 are similar systems with the exception that Figure 4 utilizes a timer and 2-way electrically operated valve to automatically air purge the system. 741-622-064 rev. 11/09/10 L100 Bubble-Tube Level System Page 5

FIG. 5 4.0 WARRANTY & DISCLAIMER ControlAir, Inc. products are warranted to be free from defects in materials and workmanship for a period of eighteen months from the date of sale, provided said products are used according to ControlAir, Inc. recommended usages. ControlAir, Inc. s liability is limited to the repair, purchase price refund, or replacement in kind, at ControlAir, Inc. s sole option, of any products proved defective. ControlAir, Inc. reserves the right to discontinue manufacture of any products or change products materials, designs or specifications without notice. Note: ControlAir does not assume responsibility for the selection, use, or maintenance of any product. Responsibility for the proper selection, use, and maintenance of any ControlAir product remains solely with the purchaser and end user. WARNING These products are intended for use in industrial compressed-air systems only. Do not use these products where pressures and temperatures can exceed those listed under Specification 741-622-064 rev. 11/09/10 L100 Bubble-Tube Level System Page 6