Liquid level glasses, type LLG REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Similar documents
Regulating valves Type REG 6-65 Type REG-SS REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Safety relief valves Type SFV 20-25

Regulating valves REG-SA and REG-SB

Overflow valves Type OFV REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Overflow valves Type OFV Type OFV-SS REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Safety relief valves SFV 20-25

Pressure regulating valves Types OFV, OFV-SS

Quick closing oil drain valve, type QDV 15 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Gas powered stop valves, type GPLX REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Solenoid valves, two-step on/off Type PMLX REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Safety relief valves, type BSV 8 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Modulating liquid level regulators, servo-controlled PMFL / PMFH and SV

Hand operated regulating valves Types REG-SA and REG-SB

Safety relief valves Type BSV-8

Hand-operated regulating valves in stainless steel Types REG-SA SS and REG-SB SS

Safety relief valves, type SFA 15 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Safety relief valves, type SFA 15

Safety relief valves Type SFA 15 and SFA 15-50

for for Industrial Refrigeration

MAKING MODERN LIVING POSSIBLE. Pilot operated internal safety valves type POV REFRIGERATION AND AIR CONDITIONING DIVISION.

Float valves Types SV 4, SV 5 and SV 6

Pilot valves for pilot operated servo valves

Liquid level regulating valves Types PMFL / PMFH and SV

Shut-off valve Type QDV

Float valves Types SV 1 and SV 3

Modulating liquid level regulators, direct-controlled, type SV 1 and 3 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Instructions. Control Solution ICF 20-4, ICF 25-4, ICF ICF 40-4, ICF 20-6, ICF 25-6, ICF 32-6, ICF 40-6, Direction and position.

Instructions. Control Solution ICF 20-4, ICF 25-4, ICF ICF 40-4, ICF 20-6, ICF 25-6, ICF 32-6, ICF 40-6, Direction and Position.

Selection of ICF made easy Save even more time with ICF

Solenoid Valves, one - or two step, on/off ICLX

Serie 06-M6. Swing wafer check valve. made in. Application fields. Check valves E U R O P E WATER CONDITIONING INDUSTRY

Si C132. Safety valves for pressure relief in accordance to PED, DIN/EN and ASME. Engineering GREAT Solutions

2-step solenoid valve Type ICLX

2-step solenoid valve Type ICLX

Shut-off Liquid level and regulating valves for for Industrial Refrigeration

Dual position solenoid valve Type ICSH 25-80

Horizontal Bladder Tanks

80% Less installation time with just two welds for fast and efficient installation.

Vertical Bladder Tanks

SCA Series Inverted Bucket Steam Traps

Ball Float Steam Trap UNA 43 PN 16/CL 125/JIS 10K UNA 46 PN 40/CL 150/CL 300/JIS 10K/JIS 20K DN 80, 100, 150, 3", 4", 6"

Water. VAG DUOJET Automatic Air Valve Single-chamber type PN 10/16/25/40 - DN KAT-A 1912

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

Model MTB-ASME Vertical Bladder Tanks

Ball valve HKSF-W100. Ball valve HKSF-W100. RMA Kehl GmbH & Co. KG Oststrasse 17 D Kehl / Germany

Model MTB-ASME Horizontal Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Pressure Reducing Valve DMV 750 set range: bar

Hydraulic Accumulators with Back-Up Nitrogen Bottles

Mounting and Operating Instructions EB 2172 EN. Series 43 Temperature Regulators. Type 43-5 and Type Type Type 43-6

Valve Station ICF 15, 20 and 25

Reliable System Performance PM valves

Pressure reducing valves Index

Leak-Free Load-Control Valve SAE ½ psi flange

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

GA24 Technical Datasheet

Expansion Thermometers Stainless Steel Series, Model 70

Gas Filters DN15 DN300. delta-elektrogas.com EE151 03/17

STAD-D. Balancing valves Balancing valve for domestic water systems, DN Balancing valves

Pressure and Flow Control Valves DBGM, German and European Patents

Steam Trap BK BK 212-ASME. Original Installation Instructions English

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

STA. Double regulating valves DN 15-50

UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions

Technical Data Sheet T 2025

Pressure Equalising Valves Model , for Differential Pressure Gauges

SV5 Safety Valve Installation and Maintenance Instructions

UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors

Pressure Measurement Single-range transmitters for general applications

Differential pressure controls, Type MP 54, 55 and 55A

Pneumatic switch module 3/2-way valve (On/Off) Types P Types FP Function tested for use of the float in Ex-zone 0

Crankcase pressure regulator, type KVL REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Slam Shut Valves SCN

Valves. Diaphragm shut-off valves, kidney-type

Universal Charging and Testing Unit FPU-1

STAD. Balancing valves DN (MD60, MD61, MD62)

Pressure transmitters EMP 2

Differential pressure controller (PN 16) AVPL - return mounting, adjustable setting

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

80% Less installation time with just two welds for fast and efficient installation.

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Water valve Type WVO. Data sheet MAKING MODERN LIVING POSSIBLE

vacon nx ac drives hxm120 cooling unit, ss-piping commissioning and maintenance manual

Diaphragm monitoring system with threaded connection For the chemical and petrochemical industries Model DMS34

Y-Pattern Strainer Valves Range

vacon nx ac drives hxl040 cooling unit, ss-piping commissioning and maintenance manual

Mechanical Pressure Measurement

Pressure relief valve DHV 712 DN 65-80: 0,5-10 bar, DN : 0,3-4 bar, DN 100: 0,5-6 bar

HM and HM34 Inverted Bucket Steam Traps Installation and Maintenance Instructions

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions

STAP. Differential pressure controllers DN , ANSI flanges

Shut-off ball valve Type GBC

Gas Filters DN15 DN300. elektrogas.com EE151 06/13

Data sheet Pressure switch type CS December 2001 DKACT.PD.P10.A B1119

Fuel Filters DN15 DN25. elektrogas.com DE

STAD. Balancing valves DN 15-50

Pressure relief valve DHV 716 set range: 0,5-10,0 bar

Materials : Stainless steel ASTM A351 CF8M

Steam Trap BK 15 (DN40, DN 50) Original Installation Instructions English

Transcription:

Liquid level glasses, type LLG 185-1550 REFRIGERATION AND AIR CONDITIONING Technical leaflet

Introduction LLG are liquid level glasses in ductile steel which meets the strictest requirements on industrial and marine refrigeration installations. The liquid level glasses are offered in 3 different versions: with welding nipples (LLG) with stop valves equipped with caps (LLG S) with stop valves and sight adapter in acrylic glass ready for insulation on site (LLG SF). The range of liquid level glasses is based on 3 basic liquid level glasses: LLG 185, LLG 335 and LLG 740. The other standard lengths are combined by using variations of basic glass lengths. LLG produce sufficient flow areas to secure the highest possible degree of synchronous operation, and have a specially hardened reflection glass for quick reading. The front and the base frame are mounted together from the front with countersunk allen screws. This ensures easy insulation on site as well as easy inspection and service, if any. All liquid level glasses are equipped as standard with a built-in safety system (non return device). If a glass is damaged, the pressure of the refrigerant will activate the safety system and refrigerant loss will be limited to an absolute minimum. Features Refrigerants Applicable to all coon non flaable refrigerants including R717 and non corrosive gases/liquids dependent on sealing material compatibility Temperature range 10/+100 C ( 14/+212 F) or 50/+30 C ( 58/+86 F) Maximum operating pressure: 25 bar g (363 psi g) Equipped with boron silicate glass, hardened by an accurately controlled heat treatment process Classification: To get an updated list of certification on the products please contact your local Danfoss Sales Company Design Glass LLG's are equipped with a boronsilicate glass, hardened by an accurately controlled heat treatment process. All glasses are according to DIN 7081. Gaskets The glasses are equipped with a special nonasbestos carbon compound gasket which provides superior mechanical characteristics and a long time guarantee against service leakage. Connectors LLG 590, LLG 995, LLG 1145 and LLG 1550 are joined together by 2 basic LLG s by means of a connector. The connector holds the two basic glasses together by means of screws and guiding pins, which ensures a rigid construction. Stop Valves/Nipples The glasses are connected to the refrigeration system by means of welding nipples or stop valves. Which ever system is used, the nipples or stop valves are screwed into a flange, which is located in the correct position and subsequently tightened with a seal gasket and 4 screws. Installation Install the glasses on a bracket using the 4 screws supplied with the glass. Use the threaded holes on the back of the frame to mount the glass on a bracket (not of Danfoss supply). Always connect the piping after mounting on the bracket. Please note the importance of a minimum of stress in the liquid level glasses from the connected pipes. Please also make sure that there is sufficient space behind the the liquid level glasses to ensure proper insulation, service and inspection, etc. For installations below 10 C (+14 F) it is recoended to add the sight adapter to enable reading after insulation has been applied. For installations below 10 C (+14 F) in R717 plants it is recoended to use an oil column as described in the following pages. There will be no formation of bubbles or ice build-up in oilfilled liquid level glasses, which may be the case in the refrigerant-filled glasses. The liquid sight glasses are designed to withstand high internal pressures. However, the piping system in general should be designed to avoid liquid traps and reduce the risk of hydraulic pressure caused by thermal expansion. Note: The LLG liquid level glass can only be placed in CE approved applications with the stop valves in front. 2 DKRCI.PD.GG0.A2.02 / 520H0855 Danfoss A/S (IR/MWA), 04-2010

Technical data Refrigerants The liquid level glasses are applicable to all coon non flaable refrigerants including R717 and non corrosive gases/ liquids dependent on sealing material compatibility. For further information please see installation instruction for LLG. Flaable hydrocarbons are not recoended. For further information please contact your local Danfoss Sales Company. Temperature range The liquid level glasses are applicable to the above mentioned refrigerants within the temperature range of: 10/+100 C (+14/+212 F) for the LLG types with safety system with welding nipples and the LLG S types with safety system with stop valves. 50/+30 C ( 58/+86 F) for the LLG SF types with safety system with stop valves and sight adapter (acrylic glass) and the LLG F types with safety system and sight adapter (acrylic glass). Pressure range All LLG types are designed for: Max. operating pressure 25 bar g (363 psi g) Strength test: 50 bar g (725 psi g) Leakage test: at 25 bar g (363 psi g). Frostproof liquid level glasses Example 1 Refrigerant: R717 (aonia). Temperature: Recoended for temperatures below 10 C (+14 F). The principle shown in fig. 1 can be used in connection with low temperature liquid separators or intermediate coolers when the refrigerant is R717 (aonia). As the liquid level in the R717 separator varies the oil level will change simultaneously. Oil Charging The system is charged with synthetic oil type SHC 226 with a specific weight, differing from that of R717, and (h) must be multiplied by approximately 1.35 (the ratio of density oil to density R717) to calculate H. Charge the oil vessel (volume approximate 10 litres) to a level just below the lower balancing pipe (A) through the oil charging valve. Close the oil charging valve. The oil will show in the liquid level glass at a level equal to the level in the oil vessel. When R717 is filled into the separator or intermediate cooler it will enter the oil vessel and press down the oil surface. The R717 will also rise into the upper balance pipe (B) to a level equal to the level in the separator or intermediate cooler. As the oil surface in the oil vessel is pressed down, the oil will rise into the liquid level glass. Note: It is important to use an oil which is not likely to mix with R717. The oil must have a high viscosity index to ensure easy flowing at low temperatures. Mobil SHC 226 of the synthetic polyalphaolefin type has proven suitable for this purpose. Separator/ Intermediate cooler Purge valve Oil charging valve Oil vessel Fig. 1 Danfoss A/S (IR/MWA), 04-2010 DKRCI.PD.GG0.A2.02 / 520H0855 3

Frostproof liquid level glasses Example 2 Refrigerant: R717 (aonia). Temperature: Recoended for temperatures below 10 C (+14 F). Fig. 2 shows a frostproof liquid level glass for an R717 liquid separator which is placed above ground level. The arrangement is called a Hampsonmeter. Due to the evaporation taking place in the uninsulated balance pipe (ND 80/3 ) the pressure in this pipe will be equal to P 1 = P 0 + H ρ g. P 0 Separator pressure... N/m 2 H R717 liquid level (see fig. 2)... m ρ R717 density...kg/m 3 g Acceleration due to gravity 9.81...m/s 2 Oil Charging The pressure will act on the oil surface in the oil vessel and cause the oil to rise in the liquid level glasses which are installed in a length of e.g. 2 pipe, the top of which is connected to the top of the separator which is at pressure P 0. The oil will rise to a level h and H can then be calculated by multiplying h by 1.35 (the ratio of density oil to density R717). Charge the oil vessel through the oil charging valve to a level of approximately ¾ of full level. The level will show in the lower liquid level glass. Take care that the volume of the oil vessel is sufficient to allow the oil to rise into the liquid level glasses. When the system is operating keep the bypass valve closed. Note: It is important to use an oil not likely to mix with R717, and having a high viscosity index to ensure easy oil movements at low temperatures. Mobil SHC 226 of the synthetic polyalphaolefin type has proven suitable for this purpose. Separator pressure P 0 Uninsulated Bypass Oil charging valve Purge valve Fig. 2 Oil vessel 4 DKRCI.PD.GG0.A2.02 / 520H0855 Danfoss A/S (IR/MWA), 04-2010

Material specification LLG LLG S and LLG SF No. Part Material DIN ISO ASTM 1 Front frame Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 2 Back frame Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 3 Sight glass Glass 4 Gasket Non-asbestos 5 Protective coating for sight glass Non-asbestos 6 Sight adapter PMMA-acrylic 8 Connecting piece Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 10 O ring Cloroprene (Neoprene) 14 Flange Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 15 Balls Stainless steel 18 Welding nipple Steel RSt. 37.2, 17 100 Fe 360 B, 630 Grade C, A 283 19 Stop valve (SNV-ST*) Steel * See technical data for SNV-ST valves. Danfoss A/S (IR/MWA), 04-2010 DKRCI.PD.GG0.A2.02 / 520H0855 5

Dimensions and weights LLG LLG S and LLG SF * Only for LLG SF with sight adapter. Type A B C D Weight LLG 185-1550 LLG 185 185 7¼ 255 10 69 2¾ 48 2 4.2 kg 1 ) 5.8 kg 2 ) LLG 335 335 13¼ 405 16 63 42 2 1 / 2 1¾ 7.5 kg 1 ) 9.2 kg 2 ) LLG 590 590 23¼ 660 26 69 + 63 2¾ + 2½ 48 + 42 2 + 1¾ 13.2 kg 1 ) 15.1 kg 2 ) LLG 740 740 29¼ 810 32 63 2½ 42 1¾ 16.5 kg 1 ) 18.5 kg 2 ) LLG 995 995 39¼ 1065 42 69 + 63 2¾ + 2½ 48 + 42 2 + 1¾ 22.5 kg 1 ) 24.7 kg 2 ) LLG 1145 1145 45 1215 47¾ 63 2½ 42 + 42 1¾ + 1¾ 25.7 kg 1 ) 28.0 kg 2 ) LLG 1550 1550 61 1620 63¾ 63 2½ 42 1¾ 33.5 kg 1 ) 36.1 kg 2 ) 1 ) Type LLG 2 ) Type LLG S and LLG SF Specified weights are approximate values only. * please note that LLG 740 consist of one back piece and 2 front sight glasses. 6 DKRCI.PD.GG0.A2.02 / 520H0855 Danfoss A/S (IR/MWA), 04-2010

Ordering How to order The table below is used to identify liquid level glasses required. Please note that the type codes only serve to identify the liquid level glasses, some of which may not form part of the standard product range. For further information please contact your local Danfoss Sales Company. Example for type codes Type codes LLG 740 SF Valve type LLG Liquid Level Glass Nominal size in 185 DN 185 335 DN 335 590 DN 590 LLG 185 + LLG 335 Combined by: 740 DN 740 LLG 740 consist of one back piece and 2 front sight glasses 995 DN 995 LLG 185 + LLG 740 1145 DN 1145 LLG 335 + LLG 740 1550 DN 1550 LLG 740 + LLG 740 Equipment - Safety system and welding nipples F S SF Safety system and sight adapter Safety system and stop valves (SNV-ST) Safety system, stop valves (SNV-ST) and sight adapter Liquid level glasses - LLG With safety system and welding nipples Length Type Code no. 185 7¼ LLG 185 2512+049 335 13¼ LLG 335 2512+050 590 23¼ LLG 590 2512+051 740 29¼ LLG 740 2512+052 995 39¼ LLG 995 2512+053 1145 45 LLG 1145 2512+054 1550 61 LLG 1550 2512+055 Liquid level glasses - LLG S With safety system and stop valves (SNV-ST) Length Type Code no. 185 7¼ LLG 185 S 2512+056 335 13¼ LLG 335 S 2512+057 590 23¼ LLG 590 S 2512+058 740 29¼ LLG 740 S 2512+059 995 39¼ LLG 995 S 2512+060 1145 45 LLG 1145 S 2512+061 1550 61 LLG 1550 S 2512+062 Liquid level glasses for insulating - LLG F With safety system and sight adapter Length Type Code no. 185 7¼ LLG 185 F 2512+078 335 13¼ LLG 335 F 2512+079 590 23¼ LLG 590 F 2512+080 740 29¼ LLG 740 F 2512+081 995 39¼ LLG 995 F 2512+082 1145 45 LLG 1145 F 2512+083 1550 61 LLG 1550 F 2512+084 Liquid level glasses for insulating - LLG SF With safety system, stop valves (SNV-ST) and sight adapter Length Type Code no. 185 7¼ LLG 185 SF 2512+066 335 13¼ LLG 335 SF 2512+067 590 23¼ LLG 590 SF 2512+068 740 29¼ LLG 740 SF 2512+069 995 39¼ LLG 995 SF 2512+070 1145 45 LLG 1145 SF 2512+071 1550 61 LLG 1550 SF 2512+072 Important! Where products need to be certified according to specific certification societies or where higher pressures are required, the relevant information should be included at the time of order. Danfoss A/S (IR/MWA), 04-2010 DKRCI.PD.GG0.A2.02 / 520H0855 7

www.danfoss.com/ir 8 DKRCI.PD.GG0.A2.02 / 520H0855 Danfoss A/S (IR/MWA), 04-2010