Pressure regulators. Introduction. TR Head. 3 ways body Dival

Similar documents
Dival 600. Pressure Regulators

Norval Pressure Regulators

Pressure Regulators. Aperflux 101

Slam Shut Valves SBC 782

Aperval Pressure Regulators

Slam Shut Valves SCN

Norval Pressure regulator

Pressure Regulators. Aperflux 851

Pressure Regulators. Reval 182 ANSI 300

ASX 176 Axial Pressure regulator

Sizing Pressure Regulators & Control Valves

RB 4700 Commercial & Industrial Regulator

Dival 500 Pressure Regulators

Reflux 819/FO. Pressure Regulators

Deltaflux Control Valve

RR 16 Commercial & Industrial Regulator

RR 16 Commercial & Industrial Regulator

Safety Shut-off Valve SSV

PRESSURE REGULATORS. Type B/240. Process Management TM

PRESSURE REGULATORS. Type A/140. Process Management TM

RB 4000 Commercial & Industrial Regulator

RTG 311 pressure regulators are included within the direct acting and balanced valve regulator class.

Gas Pressure Regulator HON 300

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

PRESSURE REGULATOR LBM SERIES

Gas Pressure Regulator HON 270 MK2

RB 4700 Commercial & Industrial Regulator

RTG 25. Introduction

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

GAS PRESSURE REGULATORS AP

SLAM-SHUT VALVES. Type BM5. Process Management TM

T208VR Series Tank Blanketing Vacuum Regulator

I Connected Industrial. HON 5020 Gas Pressure. Enabling Dependable Gas Operations

299H Series Pressure Reducing Regulators

I Connected Industrial. HON 5020 GAS PRESSURE REGULATOR Enabling Dependable Gas Operations

Type EZH Relief or Backpressure Regulator

DN 50 REGULATOR SUTON 5000A1 REGULATOR SUTON 5000D1

Gas Pressure Regulator HON 502

Safety Shut-Off Valve HON 720

RELIEF VALVES. V Series. Process Management TM. Type V/20-2. Type V/50. Type V/60

Y692VB Series Vacuum Breaker

Type 310A-32A Pressure Reducing Regulator and Type 310A-32A-32A Working Monitor Regulator

PRESSURE REDUCING VALVE RP45 (EN)

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Series 100 Slam Shut Valve. Technical Bulletin

Gas Filters DN15 DN300. delta-elektrogas.com EE151 03/17

Model 1800 PFM Series Regulator. Technical Bulletin

safety Shut-Off Valve HON 721

MT-239-E ENGLISH PRESSURE REGULATOR STAFLUX MINI TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

RELIEF VALVES. Type VS- FL. Process Management TM

Dual Modular Safety Shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators

Pressure Regulator 133 / 233

SLAM-SHUT VALVES. Type BM6X. Process Management TM

Gas Pressure Regulator HON 200

Gas Appliance Pressure Regulators and. Line Pressure Regulator. FRS 7../6 Series FRS 5... Series

Type 1098-EGR. Pilot-Operated Valve Link Regulators. Features. Fisher Controls

SV - Safety Shutoff Valve with Proof of Closure 1/2" NPT - 2" NPT. SV/614 Series SV-DLE/614 Series

HON HSV086 Series Safety Shut-off Valves for Efficient, Sustainable and Safe Gas Distribution. Proven Technology. Superior Performance.

SPRING-LOADED GAS PRESSURE REGULATOR

MT-182-E ENGLISH PRESSURE REGULATOR. Aperval TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

627 Series Pressure Reducing Regulators

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

Aperflux TECHNICAL MANUAL PRESSURE REGULATOR ENGLISH MT-208-E INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

Dual Modular Safety Shutoff Valves with Proof of Closure. DMV-D/622 Series DMV-DLE/622 Series

Gas pressure regulator RS 254 / RS 255

MT-208-E ENGLISH PRESSURE REGULATOR. Aperflux TECHNICAL MANUAL INSTALLATION, COMMISSIONING AND MAINTENANCE INSTRUCTIONS

HON C210 Series Control Valves. High Pressure Control valves

Safety shut-off valve Control Control Lock-up Over pressure set point Under pressure set point pressure range accuracy class

e G) GOVERNOR t,5 ii:i! Line Pressure Regulators

Safety Cut-Off Valve HON 305

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

Type 299 Pressure Reducing Regulators

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

Cash Valve TYPE G-4 PILOT OPERATED PRESSURE REDUCING REGULATOR FOR STEAM, AIR AND GASES. ISSUED - MARCH 2001 CAVMC-0512-US-0208 ISO 9001 Certified

Paul Ladage 26 September 2017 MOVING THINGS AROUND - LATEST TRENDS IN HONEYWELL FLAGSHIP REGULATORS

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure. DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Gas Pressure Regulator R 51

Type EZL Pressure Reducing Regulator for Low Differential Pressure Applications

Dual Modular Safety shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

Two-port valves, male threaded, PN25

Gas pressure regulator RSP 254 / RSP 255. Product information. Regulator R / R / R Actuator AS 254 / AS 255

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

299H Series. 1% Accuracy for Fixed Factor Billing (PFM) I nlet Pressure up to 175 psig / 12.1 bar. Rugged Construction. Compact.

VG Series VGG and VGD Gas Valves for use with SKP Electro-hydraulic Actuators

Types 1098-EGR and 1098H-EGR Pressure Reducing Regulators

North American 7339 High Pressure Gas Regulators

EZH and EZHSO Series Pressure Reducing Regulators

VG Series VGG and VGD Gas Valves for use with SKP Electro-hydraulic Actuators

Pressure ranges and accuracy classes for outlet pressure and safety devices

RESIDENTIAL REGULATORS

Pressure reducing valves Index

PRESSURE REDUCING VALVE RP45 (ANSI)

1805 Series Relief Valves

Dual Modular Safety Shutoff Valves. DMV-D/602 Series DMV-DLE/602 Series

Pressure Regulators DIVAL TECHNICAL MANUAL

Dual Modular Safety Shutoff Valves with Two-stage operation and Proof of Closure DMV-ZRD/612 Series DMV-ZRDLE/612 Series

Gas Appliance Pressure Regulators with integrated gas filter. FRI/6 Series

Transcription:

Pressure Regulators

> Pressure regulators Introduction series pressure regulators are direct acting devices for low and medium pressure applications controlled by a diaphragm and counter spring. These regulators are suitable for use with previously filtered, non corrosive gases. TR Head 3 ways body Dival Fig.1

Main Features Modular design of pressure regulator series allows the installation of an incorporated slam shut or device for use as in line monitor on the same body without changing the face-to-face dimension. Furthermore the truly top entry design allows an easy periodical maintenance without removing body from the line. The features of series regulators make it a product suitable for any application. The fast response time makes it ideal for burner or industrial applications or whenever sudden changes of flowrate are part of the process. The high accuracy against any inlet pressure variation makes of series an optimum product also for gas district systems, an application generally where piloted operating regulators are preferred. An etremely easy maintenance and a reduced number of parts are the background of low cost operation. Accessories on request: - Incorporated slum shuh-valve - In line monitor function - Silencer; - Incorporated relief valve. Dival series 600 Dival series 600 + LA/... Designed With All Needs In Mind - Compact Design - High Turn Down Ratio - Easy Maintenance - High Accuracy - Top Entry - Low Operation Cost - Fast Response Time - Wide Range of Applications

Main Features -Design pressure PS: up to 20 bar (290 Psi) -Design temperature: -20 C to +60 C (-4 F to + 140 F) > -Ambient temperature: -20 C to +60 C (-4 F to + 140 F) -Ma inlet pressure Pu: 20 bar (290 Psi) -Outlet pressure range of Wd: from 12 to 4200 mbar (6"w.c. to 60,9 psig) -Accuracy class AC: up to 5 -Lock-up pressure class SG: up to 10 -Available size DN: 1 (25) -1 1/4 (32) - 1" 1/2 (40) - 2 (50) -Flanging: class PN 16/25 according to ISO 7005-1, ISO 7005-2; class ANSI 150RF according to ANSI B16.5, ASME B16.42 and class ANSI 125 FF according to ASME B16.1 -Threaded connections: DN 2" Rp ISO 7-1 or DN 2"NPTF ASME B1.20.1 (only ductile iron) Materials Body Head covers Diaphgram Valve seat Seals Cast steel ASTM A216 WCB Ductile cast iron GS 400-18 ISO 1083 Die cast alluminium EN AC-AISI 12 UNI EN 1706 Rubberized canvas Brass Nitril rubber The characteristics listed above are referred to standard products. Special characteristics and materials for specific applications may be supplied upon request.

( Choosing the pressure regulator Sizing of regulators is usually made on the basis of Cg valve and KG sizing coefficients (table 1). Flow rates at fully open position and various operating conditions are related by the following formulae where: Q = flow rate in Stm 3 /h Pu = inlet pressure in bar (abs) Pd = outlet pressure in bar (abs). A > When the Cg and KG values of the regulator are known, as well as Pu and Pd, the flow rate can be calculated as follows: A-1 in sub critical conditions: (Pu<2Pd) Q = KG Pd A-2 in critical conditions: (Pu 2Pd) Q KG = Pu 2 ( Pu - Pd) Q Q = 0.526 Cg Pu sen K1 = 0. 526 Cg Pu B > Vice versa, when the values of Pu, Pd and Q are known,the Cg or KG values, and hence the regulator size, may be calculated using: ( Pu - Pd Pu ( B-1 in sub-critical conditions: (Pu<2Pd) KG = Q Pd ( Pu - Pd) Cg = 0.526 Pu sen Q ( K1 Pu - Pd Pu B-2 in critical conditions (Pu 2Pd) Q KG = 2 Q Cg = Pu 0,526 Pu NOTE: The sin val is understood to be DEG. Table 1: Cg, KG and K1 valve coefficient Heads ø 280 ø280/tr Nominal diameter (mm) Size (inches) Cg coefficient KG coefficient K1 coefficient 25 1" 269 383 94 32 1" 1/4 300 315 95 40 1" 1/2 652 685 94 50 2" 781 821 86 25 1" 315 331 97 32 1" 1/4 334 351 97 40 1" 1/2 692 727 95 50 2" 770 809 97

> Pressure regulators The formulae are applicable to natural gas having a relative density of 0.61 w.r.t. air and a regulator inlet temperature of 15 C. For gases having a different relative density S and temperature t in C, the value of the flow rate, calculated as above, shall be multiplied by a correction factor, as follows: Fc = S 175.8 ( 273.16 + t ) Table 2 lists the correction factors Fc for a number of gases at 15 C. Table 2: Correction factors Fc Type of gas Air Propane Butane Nitrogen Oygen Carbon dioide Relative density 1.0 1.53 2.0 0.97 1.14 1.52 Fc Factor 0.78 0.63 0.55 0.79 0.73 0.63 Caution: In order to get optimal performance, to avoid premature erosion phenomena and to limit noise emissions, it is recommended to check gas speed at the outlet flange does not eceed 150 m/sec. The gas speed at the outlet flange may be calculated by means of the following formula: V Q = 345.92 2 DN 1-0.002 1 + Pd where: V = gas speed in m/sec Q = gas flow rate in Stm3/h DN = nominal size of regulator in mm Pd = outlet pressure in barg. Pd

Control Heads Outlet pressure range is determined by the control head installed. The control heads used are: - head Ø 280 from 12 to 340 mbar - head Ø 280/TR from 300 to 4200 mbar Slam-Shut Valve This is a device which stops immediately gas flow whenever downstream pressure eeeds given set-point. Device can be actuated also manually. Incorporated LA/... Slam-Shut LA Slam shut (see figure 2) can be incorporated in the standard regulator and in the in-line monitor. The regulator with the incorporated slam-shut has Cg and KG coefficients equal to those in table 3. A further advantage of the incorporated slam-shut valve is that it can be retro fitted at any time on a previously installed series without modifying the regulating unit (only with 4 ways body). Further the slam-shut can be positioned in four different positions (rotation on its ais) in such way to be fied in the most apropriated position versus the surrounding encumbrance if any. The main features of this slam-shut device are: - design pressure 20 bar for all the components; - accuracy (AG): ap to 5 for pressure increase, up to 15 for pressure decreasing; - internal by-pass; - intervention for over pressure and/or under pressure; - manual push-button control; - possibility of pneumatic or electromagnetic remote control; - compact overall dimensions; - easy maintenance; - possibility of application of devices for remote signal (contact or inductive microswitches). Fig.2 Table 3: Cg, KG and K1 coefficient with incorporated slam shut Heads Nominal diameter (mm) Size (Inches) Cg coefficient KG coefficient K1 coefficient ø 280 25 1" 267 280 94 32 1"1/4 298 313 95 40 1"1/2 698 733 94 ø280/tr 50 2" 818 859 86 25 1" 311 327 97 32 1"1/4 330 347 97 40 1"1/2 749 786 95 50 2" 811 852 97

> Pressure regulators Table 4 shows the available pressure switches Table: 4 Slam-Shut pressure switches Pressure switch Set point range for Overpressure Wdo Set point range for Underpressure Wdu Working pressure in bar LA/BP 0,030 0,180 0,006 0,060 LA/MP 0,140 0,450 0,010 0,240 LA/TR 0,25 5,5 0,1 3,5 series Functioning as Monitor The monitor is an emergency regulator which comes into operation in place of the main regulator if, in the event of failure, the latter allows the downstream pressure to reach the monitor set-point. Operation of the series functioning as Monitor series functioning as an in-line monitor is a regulator which, in addition to the standard version, has a further mobile assembly balancing device guaranteeing greater accuracy of regulated pressure and therefore an equally precise value for the intervention pressure without risk of interference with main regulator. Fig.3 Standard regulator Monitor regulator

Incorporated Relief Valve To avoid that small leak when there is no flow required or that sudden and of temporary overpressures such as deriving from rapid switching or overheating of the gas cause intervention of the slam shut, the DIVAL 600 it is possible to activate an incorporated relief valve (SBV). Incorporated silencer Whenever specific noise limits are required, the silencer allows you to considerably reduce the decibel (dba) noise emissions during the gas pressure regulators operation. The pressure regulator can be supplied with an incorporated silencer in either the standard version, with incorporated slam-shut or in line monitor version. With the built-in silencer the Cg and KG valve coefficients are not affected. Given the modular arrangement of the regulator, the silencer may be retrofitted to both standard version as well as those with incorporated slam-shut or monitor version, without any need to piping modification. Pressure reduction and control operate the same manner as in standard version. Installation To ensure proper operation and optimal performance, the following should be observed while installing series pressure regulator: a) filtering: the gas flowing in the piping shall be adequately filtered. It is also recommended that the piping upstream from the regulator is clean without impurities; b) sensing line: for correct operation, sensing line pick up must be appropriately positioned. Between the regulator and the downstream take-off there must be a lenght of pipe 4 times the diameter of the outlet pipe; beyond the take-off, there must be a further lenght of pipe 2 times the same diameter. Assembly positions Fig.4

> Pressure regulators Possible installation schemes DIVAL SERIES 600 + LA/.. + DIVAL SERIES 600 Fig.5 DILOCK 108 + DIVAL SERIES 600 + LA/... Fig.6 Inlet pressure Outlet pressure

D Dival Series 600 F TR Head only B1 B B M N E DN DN A N S Overal dimensions in mm Tipe DN 25 32 40 50 G 2" NPS 1" 1"1/4 1"1/2 2" 2" NPTF S 183 183 223 254 254 A 145 145 145 145 145 B 343 343 343 343 343 B1 433 433 433 433 433 D 280 280 280 280 280 E 215 215 215 215 215 Weights in Kgf Tipe DN 25 32 40 50 G 2" NPS 1" 1"1/4 1"1/2 2" 2" NPTF Dival 15 15 17 20 18 Face to face dimensions S according to IEC 534-3 and EN 334 Dival with slam shut LA/... 16 16 18 21 19 F 200 200 200 200 200 M Rp1/2" Rp1/2" Rp1/2" Rp1/2" Rp1/2" N Rp1/4" Rp1/4" Rp1/4" Rp1/4" Rp1/4"

Pietro Fiorentini S.p.A. via E.Fermi 8/10 I-36057 Arcugnano (VI) Italy Tel. +39 0444 968.511 Fa. +39 0444 960.468 via Rosellini 1 I-20124 Milano Italy Tel. +39 02 696.14.21 Fa. +39 02 688.04.57 www.fiorentini.com The data are not binding. We reserve the right to make eventual cheanges without prior notice. CT-s535-E July 2008