Gas Odorization System GOE 07

Similar documents
Gas Pressure Regulator RMG 505

RMG 790 water Safety Shut-Off Valve

Gas Pressure Regulator RMG 201

Safety Shut-Off Valve RMG 711

Safety Relief Valve RMG 835

Gas Pressure Regulator Series 277 Hi-Flo

Operation and Maintenance, Spare Parts Serving the Gas Industry - WORLDWIDE. edition 06/2005

Gas Pressure Regulator RMG 300

BUBBLER CONTROL SYSTEM

GAS PRESSURE REGULATOR RMG 512

MODEL 240 GAS PRESSURE REGULATOR

Electronic Turbine Meter TERZ 94

TRZ 03-K Volumeter. Proven Technology. Superior Performance. TRZ 03-K Volumeter is a Turbine Gas Flowmeter for Secondary Gas Metering.

MODEL 273PL GAS PRESSURE REGULATOR

MODEL 274 GAS PRESSURE REGULATOR

Pilot HON 625. Entwurf. Product information. serving the gas industry worldwide

Miniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 800

Actuator HON 670 / 671

BUBBLER CONTROL SYSTEM

Chlorinator MODEL MK-I

Valve Proving System VDK 200 A S06*

Valve Proving System VDK 200 A S02

Integral type Differential pressure flowmeter VNT Series

OPERATING INSTRUCTIONS MANUAL FOR QACV PNEUMATIC DOSING PUMP

Ultrasonic Flowmeter USZ 08

Gas Pressure Regulator HON 200

Expert Hydrostatic Level Transmitters

RMG Meßtechnik GmbH. Publication No E

safety Shut-Off Valve HON 721

HON 219 Pressure Reducer (D119a)

LPG DRIVER ATTENDED TRANSPORT LOADING

GRUNDFOS alldos product information. Vaccuperm 111 / 113. Vacuum gas dosing systems for chlorine gas, ammonia, sulphur dioxide and carbon dioxide

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

HON C210 Series Control Valves. High Pressure Control valves

Liquid Level Controllers

Hydrostatic Level and Pressure Measurement

INSTALLATION OPERATION MAINTENANCE

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL OTHER FLUID POWER VALVES. This work covers part of outcome 2 of the Edexcel standard module:

MOYNO FLUID DETECTION CONTROL SERVICE MANUAL. Section: ACCESSORIES. Page: 1 of 8 Date: May 1, 1998 GENERAL

Gas Pressure Regulator HON 300

Variable Area Flow Meters

FOAM TANK (1/2) DATA SHEET

Chemical Feed Equipment Floor-Mounted Gas Dispenser - Series CH4200

Installation, operating and maintenance Instructions for Seemag bypass level indicator

PK-2D Service Manual

ELADOS EDP L Diaphragm Metering Pump Type

Chlorinator. MODEL C-731 (Floor Mounted)

Air service units series K G1/8, G1/4

HON R100 Series High Pressure Regulator Ensuring Reliable Gas Operations

Introduction to Pumps

The Compact, Portable, Efficient and Economical Solution to boost Shop Compressed Air Pressure by 2 or 3 times

Pilot HON 630a, HON 640

LMU100/200 Series. Standard Specifications

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz

Safety Shut-Off Valve HON 720

Liquid level regulating valves Types PMFL / PMFH and SV

HERZ-Motorised flow controler

Measurement of Low GAS & Liquid Flows

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

HBLT-A1 LIQUID LEVEL SENSOR

Radar, Ultrasonic and RF Level Transmitters

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

SINGLE VALVE WITH LOW-FLOW BYPASS

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION

TECHNICAL DATA. Trimpac 257a. September 16, 2013

TECHNICAL DATA. than the water inlet pressure to the concentrate

SPECIFICATIONS ATTENTION

DataSheet. Series AA Electronic Metering Pumps. Configuration Data. Dimensions. Specifications. Model AA HI. ISO 9001 Certified

T EK-SUB 4800C 19 mm Submersible Level Transmitter

System Pressure Manager Standard & System Pressure Manager Plus

Series K Air service units G 1/8, G 1/4

TECHNICAL DATA. Trimpac 256a. October 31, 2013

Self-operated Pressure Regulators for special applications

Level transmitter LT 100

Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Reclaim Basic Set Up

Circulating Lubrication Systems (Oil)

OWNER S TECHNICAL MANUAL

Highest Quality. Gas Chlorination Systems

Multiple Pressure Booster Systems With Variable Speed Controller Type BL

Phuel Portable Control Units

FOAM TANK (1/2) DATA SHEET

Electropneumatic Positioner and Pneumatic Positioner Type 3760 JIS

Autocalibration Systems for In Situ Oxygen Analyzers

AIR DRIVEN. Gas Boosters & SYSTEMS. Accepting VISA, MasterCard and American Express

Pressure Automated Calibration Equipment

WhirlWind Multifunctional gas control Fully integrated gas-air system with control and safety function GB-WND 055 D01

Mechanical Pressure Measurement

GENO -Flushing Compressor Product Data Sheet F 02

Pressure Measurement Single-range transmitters for general applications

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

EC type-examination certificate UK/0126/0065 Revision 1

safety shut-off Valve HON 703 / HON 704

Dimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

Modulating liquid level regulators, servo-controlled PMFL / PMFH and SV

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI US Edition

Level MEASUREMENT 1/2016

The Discussion of this exercise covers the following points:

Transcription:

PRODUCT INFORMATION Serving the Gas Industry Worldwide

Features. Specifications. Features 1 Operates according to the suction method Safe and easy-to-operate stainless-steel design with clamping-ring connection (SWAGELOK) Diaphragm proportioning pump with solenoid actuator [EEx e] - Infinitely variable for volume-proportional odorization - High proportioning accuracy Permanently filled 5-litre reserve tank with level indicator Manual proportioning check Changing the odorant tank is possible without inter-rupting operation Integrated hand vacuum pump Easy start-up for filling the reserve tank for the first time Venting the pump head poses no problem even if the gas line is under pressure Convertible to sulfur-free odorant. Flushing device (option) Odorization measuring device (option) Specifications 1) Proportioning pump Pump type Displacement (mm 3 /stroke) (infinitely variable) Max. operating pressure (bar) Max. number of strokes per hour Solenoid actuator Design Parts in contact with fluids Injectable fluids Operating temperature range MH-6-47 10-80 40 7200 MH-6-65 20-150 20 7200 Single solenoid actuator, degree of protection EEx e G 4 196 V DC / 100% ED/0, 133 A Reciprocating diaphragm pump and ruby ball valves Stainless steel, ruby, PTFE Liquids, e.g. tetrahydrothiophene, mercaptans, S-free +5 C to +40 C 2) Performance data for odorization MH-6-47 MH-6-65 Odorization pump type Odorant concentration mg/nm 3 10 20 10 20 Pump strokes No. of strokes/h max. 7200 min. 60 max. 7200 min. 60 max. 7200 min. 60 max. 7200 min. 60 Odorizable gas flow Max. displacement Min. displacement Nm 3 /h Nm 3 /h 57600 480 28800 240 108000 900 54000 450 7200 60 3600 30 8640 72 4320 36

1. Mounting plate 2. Proportioning pump 3. Injection nozzle 4. Reserve tank 5. Interchangeable odorant tank 6. Hand vacuum pump 7. Sintered metal filter 8. Stroke setting unit 9. Measuring burette 10. Vacuum gauge 11. Flow monitor (option) 12. Connecting hoses 13. Activated carbon filter 14. Float switch, reserve tank 15. Stainless-steel collector 16. Stopcock, measuring burette 17. Stopcock, reserve tank 18. Stopcock, vacuum pump 19. Stopcock, starting circuit 20. Shut-off valve, injection pipe, with restrictor 21. Shut-off valve, injection nozzle 22. Non-return valve 23. Venting valve, reserve tank 24. Drain valve, reserve tank 25. Manual button 26. Connection box, proportioning pump 27. Intrinsically safe (EEx i) connection box for manual button, flow monitor and float switch 28. Hose clamp 29. Flushing device (option) 30. Shut-off valve flushing device 31. Measuring device for delivery rate ODM (option) 32. Solenoid valve for ODM 33. Shut-off valve ODM 2 Max. installation height from the lower edge of the odorant tank h1 = 1100 mm with THT h2 = 900 mm with mercaptans Suction height h3 = Filling level of the odorant tank (Value through vacuum gauge, item 10) Method of operation The odorization system operates in accordance with the injection method. The volume-proportional pulses received from a measuring device for volume at base conditions cause the electromagnetically operated diaphragm proportioning pump (2) to perform strokes through a control unit. With each stroke, the pump delivers the preset odorant quantity (mm 3 ) via the injection nozzle (3) into the gas flow. The odorization pump (2) replenishes its supply of odorant by drawing odorant from the odorant tank (5) through a permanently filled 5-litre reserve tank (4). The level of the reserve tank falls only when the odorant tank is empty. Start-up Using an integrated hand vacuum pump (6), a vacuum is built up in the pipes upstream of the odorization pump, which first fills the reserve tank. The vacuum persists and makes the system self-priming. Afterwards, only the odorization pump still needs to be vented for 1 minute and the system is ready for operation. Operation The odorant quantity in mm 3 per stroke has to be set at the stroke setting unit of the odorization pump depending on the required odorant concentration. A scaling factor for the frequency of the control pulses has to be programmed on the associated control unit. In this way, the pulse sequence of a measuring device for volume at base conditions is turned into a suitable stroke frequency of the pump and odorization is performed in proportion to the volume. Manual proportioning check It is possible to check the preset volume to be injected (mm 3 per stroke) at any time using the measuring burette (9) which is connected parallel to the reserve tank. At the same time, the measuring burette is used for checking the odorant level.

Control unit 3 The control unit (standard design) is supplied either in a wall-mounting enclosure (Type 7-IG 4) or installed in a 19" subrack (Typ 7-EU 4). It comprises the following modules: - MC 41-31R/S272-4 control card For pulse scaling and processing of faults or alarms. With various indicators and an internal pulse gene-rator for continuous odorization. - MC 82-SSI power supply card 24 V supply unit for the control system; power unit for controlling the odorization pump. - EEx i MC 13-241 ExO-T input card As 2-channel explosion-proof isolation of volume pulses from the area subject to explosion hazards (volume corrector, turbine meter, etc.). - EEx i MC 13-36 ExO-R input card For explosion-proof isolation of signals from the manual button. - EEx i MC 13-36 ExO-R/C16 input card (option) For explosion-proof isolation of signals from the flow monitor, float switch (reserve tank) and the level indicator of the odorant tank.

Control options Basically, there are three ways to control the odorization pump: - Through volume-proportional pulses outputted by a volume pulse transmitter. In this way, a constant level of odorant concentration can be achieved in the natural gas. - By means of an internal 10 Hz pulse generator enabling the odorization pump to be controlled independently of the volume pulse transmitter. - By operating the manual button, the odorization pump can be controlled independently of the volume pulse transmitter and the internal clock-pulse gene-rator. The pulse sequence of the signals from the volume pulse transmitter or the internal pulse generator can be converted through the control card to a pulse sequence which is appropriate for controlling the odorization pump (max. 2 Hz). Scaling ratios from 1:1 to 1:9999 can be set via four soft-touch coding switches. 4 If a number of input pulses has been detected which equal the preset scaling factor, the component outputs a control signal which causes the odorization pump to perform a stroke. At the same time, the output pulse indicator lights up. Manual control is independent of the pulse scaler. Each time the manual button is pressed, a control signal is outputted to the odorization pump. Control unit installed in a 19" subrack (Type 7-EU 4) Indicators All incoming and outgoing signals are indicated by LEDs: volume pulses from the area subject to explosion hazards (2 input channels) signals from the internal pulse generator pulses from the manual button output pulses to the odorization pump. Fault indicators The following faults are indicated on the control unit: Level warning for the reserve tank (option) Level warning for the interchangeable odorant tank (option) Delivery fault of the odorization pump (option) Centralized alarm (lights up when any malfunction occurs). Control unit installed in a wall-mounting enclosure (Type 7-IG 4) Every fault indication causes a relay to switch in the control unit. The switching contacts are connected to the terminals. In this way, fault indications can be transmitted to other devices. OSG 2000 odorization control unit Alternatively, the GOE 07 odorization system can be equipped with the OSG 2000 odorization control unit. This control system is based on a stored-program controller in conjunction with an operator and display panel. This enables the control unit to meet the individual requirements of each odorization system. Please refer to RMG Publication No. 4.351-E for a detailed description of the OSG 2000 odorization control unit.

Design diagram for odorization pumps For gas quantities up to 4,000 mn 3 /h, the figures for V0/h and q must be divided by 10, where-as they must be multiplied by 10 for gas quantities up to 400,000 mn 3 /h, and by 100 for gas quantities up to 4,000,000 mn 3 /h. If tetrahydrothiophene is used, 1 mg equals 1 mm. 5 Level indicator Continuous odorant level indication is provided by the vacuum gauge (10) which is installed as standard. It is also used for checking the functional performance of the system at the same time. In the case of malfunc-tions or an empty odorant tank, the system cannot build up a vacuum. Options - Odorant concentration monitoring The odorization measuring device ODM which is installed in unpressurized section upstream of the pump is used for calculation of concentration odorant. - Delivery monitoring The flow monitor of Type FS-01 (11) which is installed in the outlet pipe of the odorization pump monitors the delivery of the odorant into the piping with each pump stroke. - Level monitoring Float switch (14) in the reserve tank. - Stainless-steel cabinet For installation of the odorization system. - Floor stand For locating the odorization system. Accessories 2 flexible PTFE connecting hoses (12) with stainless-steel sheathing. Injection nozzle (3) with non-return valve (22) and shut-off valve (21). Stainless-steel safety collector (15) for odorant (50, 100 and 200 litres). Odorant tank for transportation and storage (5) of THT, approved by GGVE/GGVS and DVGW as per DIN 30 650 (25, 50 and 200 litres). Activated carbon filter as odor trap for installation in the venting pipe (13). Its location has already been provided. Insulating coupling for the injection pipe, dia. 6 mm, for the electrical isolation of the piping and the odorization system, with Swagelok fitting.

6

For More Information To learn more about RMG s advanced gas solutions, contact your RMG account manager or visit www.rmg.com GERMANY RMG Regel + Messtechnik GmbH Osterholzstrasse 45 34123 Kassel, Germany Phone: +49 (0)561 5007-0 Fax: +49 (0)561 5007-107 ENGLAND Bryan Donkin RMG Gas Controls Ltd. Enterprise Drive, Holmewood Chesterfield S42 5UZ, England Phone: +44 (0)1246 501-501 Fax: +44 (0)1246 501-500 RMG Messtechnik GmbH Otto-Hahn-Strasse 5 35510 Butzbach, Germany Phone: +49 (0)6033 897-0 Fax: +49 (0)6033 897-130 RMG Gaselan Regel + Messtechnik GmbH Julius-Pintsch-Ring 3 15517 Fürstenwalde, Germany Phone: +49 (0)3361 356-60 Fax: +49 (0)3361 356-836 WÄGA Wärme-Gastechnik GmbH Osterholzstrasse 45 34123 Kassel, Germany Phone: +49 (0)561 5007-0 Fax: +49 (0)561 5007-207 POLAND Gazomet Sp. z o.o. ul. Sarnowska 2 63-900 Rawicz, Poland Phone: +48 65 545 02 00 Fax: +48 65 546 24 08 CANADA Bryan Donkin RMG Canada Ltd. 50 Clarke Street South, Woodstock Ontario N4S 0A8, Canada Phone: +1 (0)519 53 98 531 Fax: +1 (0)519 53 73 339 USA Mercury Instruments LLC 3940 Virginia Avenue Cincinnati, Ohio 45227, USA Phone: +1 (0)513 272-1111 Fax: +1 (0)513 272-0211 TURKEY RMG GAZ KONT. SIS. ITH. IHR. LTD. STI. Birlik Sanayi Sitesi, 6. Cd. 62. Sokak No: 7-8-9-10 TR - Sasmaz / Ankara, Turkey Phone: +90 (0)312 27810-80 Fax: +90 (0)312 27828-23 Gas Odorization System GOE 07 2010-12 2010 Honeywell International Inc.