Understanding Swimming Pool Ventilation. Presented by Tom Sands Mobile: CPD003/v03tcs2016

Similar documents
VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES

Crab and Lobster Live Holding System Part II (Water Pumps, Air Pumps and Pipework)

Increase in Evaporation Caused by Running Spa Jets swhim.com

Established since ZANE GULFSTREAM Get the most out of your swimming pool with Zane solar pool heating.

The routine maintenance and inspection of local exhaust ventilation (LEV)

Product Specification Spring Finger

Laser Spectrometers for Online Moisture Measurement in Natural Gas. Ken Soleyn GE M&C

Selecting the right pressure sensor for your application

LEV Issues. Local Exhaust Ventilation. A Salesman Approaches! Why is LEV important? What is it supposed to do? What comprises an LEV system?

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

INFORMATION NOTE No 353: MICROBIOLOGICAL TESTING

High Pressure Breathing Air Compressors

NZQA registered unit standard version 2 Page 1 of 5

Modular one-piece solar panels. Outstanding heat transfer properties. Exceptional durability and UV stabilised


01 18/11/2013 correction of the reference of the product 1 4 5

Commercial Pool Legislation

Effect of clothing ventilation on thermal insulation and vapor resistance

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction

- Introduction: a) Metallized Paper & Film :The market Outlook The following diagram shows the estimated usage of the main metallized materials

EXAM # 2. First Name Last Name CIRCLE YOUR LECTURE BELOW: INSTRUCTIONS

Commercial Pool Legislation (M39)

Solar Water Heaters for Swimming Pools

LEGIONELLA MANAGEMENT PROCEDURE

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

Kameleon Glazed Natural & Smoke Ventilator. Smoke Control

Chapter 3 Atmospheric Thermodynamics

Pre-filter for Brushless Blower Instruction Manual

Standard Pools LLC Swimming Pools Works

Water Balance Indexes Revised September 2017

We are manufacturer & supplier of FRP Products, Play Park Equipment, Swimming Pool Chemicals & Tiles. In addition to this, we also offers with

STA Level 3 Award in Pool Plant Operations

SAFETY DATA SHEET ARDEX WPC POWDER

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

Automatic extractor outlet

Culligan swimming-pools: don t settle for less.

CONSIDERATION OF DENSITY VARIATIONS IN THE DESIGN OF A VENTILATION SYSTEM FOR ROAD TUNNELS

Qualification Specification. Pool Water Treatment Y T. Version 17.1

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

Air Handling Unit (AHU) Air handling unit which serves to condition the air and provide the required air movement within a facility.

Alain PERSON, Anne-Marie LAURENT, Yvon LE MOULLEC Laboratoire d Hygiène de la Ville de Paris

Proficiency Module Syllabus. P601 - Thorough Examination and Testing of Local Exhaust Ventilation Systems

DP40 is a versatile 2K Epoxy Surfacer. It is light grey in colour, chromate-free and has good corrosion resistance over bare metal.

CLB 3 ATTRACTIVE JOINABLE LINEAR PROFILE EASILY ACCESIBLE VOLUME ADJUSTMENT INCLUDED FLEX CLAMP HEATING AND COOLING TERMINAL REHEAT AVAILABLE

CEILING DIFFUSERS technical CONTROL THE AIR YOU BREATHE. types -CD, CAB. Europair Africa a division of Performancair Products Africa (Pty) Ltd

Measuring range Δp (span = 100%) Pa

THE COMPACT LINE. Mobile power packs in convincing BAUER quality l/min 225 / 330 bar TOUGH RELIABLE WELL ESTABLISHED

Screw Compressors 11-22kW

Total Alkalinity TOO HIGH TOO LOW. Ideal. Difficulty Adjusting. Low ph Corrosion ph Fluctuation ppm. Cloudy Water High ph

Controlling Cabin and Envelope Air Flows & Pressure Differentials

Understanding Water Vapor

Abrasive Blasting Removal Systems

RH800 & 2000 BASIC OPERATIONS

Air Intake Placement and Design and Fresh Air to Improve Air Quality Donald Cyrus Baker & Randy Baxter

Module 1 - Situation: Body Ambient Bondgraph Model Using Heat Flux. Transducer

SAMPLE RH = P 1. where. P 1 = the partial pressure of the water vapor at the dew point temperature of the mixture of dry air and water vapor

Cleaning robots for swimming pools - fully automatic, persistent and powerful YOUR PARTNER FOR SWIMMING POOL HYGIENE

Vickers. Filters. Reservoir Vent Filters. Spin-on Air Filters & Adaptors. Rev. 3/98

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

Compressed Air - Food/Bev. Presented By: Adam Zimmerman

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

Product Data. CK5A, CK5B, CK5P Furnace N-Coils. Sizes A018 thru A060

TExT Thorough Examination & Test of LEV Local Exhaust Ventilation Systems

Gas Vapor Injection on Refrigerant Cycle Using Piston Technology

FloCon Commissioning Modules DESIGN GUIDE - JUNE Variable Flow Systems & Solutions brought to you by Hurlstones

ASPHALT PLANT LEVEL 1

SURF-AIR MOBILE ATTRACTION TECHNICAL SPECIFICATION

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

NZQA registered unit standard version 2 Page 1 of 5

TECHNICAL DESCRIPTION

CASED HORIZONTAL FURNACE COIL. Model CK3B. Form No. SS-CK3B-01 FEATURES

Application Block Library Fan Control Optimization

SKAC25 Operate plant to maintain the quality of pool water

MD61 Thermal Conductor Gas Sensor

Effect of airflow direction on human perception of draught

For Inground & Portable Spas

2017 Edition GUIDANCE NOTE GN 8 INVERTER DRIVES FOR FANS AND PUMPS GN 8 - INVERTER DRIVES FOR FANS AND PUMPS

Scott Denning CSU CMMAP 1

ENGINEERING FLUID MECHANICS

CLOSED LOOP SOLVENT EMISSIONS CONTROL. David C.H. Grant

KATEDRA MATERIÁLOVÉHO INŽENÝRSTVÍ A CHEMIE. 123MEAN water vapor transport

Product Data CAPMP, CARMP EVAPORATOR COIL A COIL - CASED MULTIPOISE CAPMP / CARMP CAPMP / CARMP (3619, 4823, 6025)

VENTILATION DURING TUNNEL CONSTRUCTION INDUSTRY CONSIDERATIONS

STINK OR SWIM DON T BLAME HVAC FOR BAD POOL CHEMISTRY!

Finishing Surfaces by Applying Treatments A/508/5116

Membrane modules for nitrogen and oxygen generator systems. Technology Overview ENGINEERING YOUR SUCCESS.

F13.11 PARALLEL HINGES F13 PROJECT-OUT WINDOWS AND TOP HUNG WINDOWS

THE IMPACT ON ENERGY CONSUMPTION CAUSED BY PRESSURE DROP IN A COMPRESSED AIR SYSTEM

VB-7273 Series. Application. Features. Applicable Literature

Above Ground Pool Care The Complete Guide to Fun Pool Water Maintenance

Atmospheric Stability/Skew-T Diagrams. Fall 2016

The Hoffman Specialty Series 2000 consists of main

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012

MET Lecture 8 Atmospheric Stability

LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM

Experiment 13: Make-Up Lab for 1408/1420

11. Aquasalt. Aquasalt Aquasalt 440. Salt electrolysis demonstration 442. Spare parts and Accessories 443. Chemical Products

Pools that stand up to anything!! The first chlorine-resistant reinforced membrane for swimming pools, even under extreme conditions.

EDUCTOR. principle of operation

Transcription:

Understanding Swimming Pool Ventilation Presented by Tom Sands Mobile: 07768 244555 Email: tom.sands@ves.co.uk CPD003/v03tcs2016 1

Learning Objectives At the end of the presentation you should have a broader understanding of Swimming Pool Ventilation including: 1. Issues Attributed to Swimming Pool Halls 2. Legislation and Design Guides 3. Studies into Humidity/Evaporation 4. How to Calculate a Ventilation Rate 5. Air Flow Calculation (Working Example) 6. Energy Efficiency and Running Costs 7. Energy Saving Potential 8. System Design Considerations 9. Summary 2

Issues Attributed to Swimming Pools 3

Issues associated with indoor Swimming Pool environments Both water & air must be heated resulting in high energy usage & operational costs Evaporation must be controlled to prevent aggressive condensation from pool causing severe damage to building fabric Pool water must be continuously disinfected with chlorine, which leads to potentially harmful disinfectant by-products (DBPs) DBP s in both the water & air cause poor experience for swimmers & potential health effects to both swimmers & pool staff alike High maintenance, particularly on the water side Storage & handling of hazardous chlorine on site 4

Issues Attributed to Swimming Pools Corrosion & building fabric damage - All three elements are present for accelerated corrosion in a pool hall. Moisture Warmth Chlorine Water containing DBP s is constantly evaporating from the warm pool water & is aggressive to the building fabric if allowed to condense on the fabric. 5

Issues Attributed to Swimming Pools The Environmental Cost Leisure Centres are one of the most energy intensive buildings to operate. According to the Office of National Statistics, in 2012 the UK sports sector spent ~ 700m on energy Approximately 70% of these energy costs can be directly attributed to the swimming pool hall and adjoining changing areas. 6

Issues Attributed to Swimming Pools Two thirds of energy is accounted for by Space heating and fans & pumps. 470m a year 7

Increasing pool hall temperatures Pool types & usage has changed over recent years with; An increase in leisure style pools Increase in the use of chlorine based disinfection Higher pool water temperatures. Typically these have increased by 1 C over the past 10 years: Competition Pools 27 C now 28 C Conventional Pools 28 C now 29 C Leisure Pools 29 C now 30 C Learner Pools 29 C now 31 C Hydrotherapy Pools 35 C now 36 C 8

What does a swimming pool ventilation system need to do? A swimming pool ventilation system needs to be designed to: Heat the air to maintain the pool hall temperature Provide sufficient fresh air for swimmers & staff Control the relative humidity to prevent aggressive condensate getting on & into the building fabric where it will cause damage Extract, treat or dilute DBP s 9

Legislation and Design Guides 10

Legislation and Design Guides There are numerous methods around to design pool ventilation systems. But other than the building regulations, there is no specific legislation. There are however numerous different design guides for pools available 11

Legislation and Design Guides Sport England Swimming Pools Updated Guidance for 2013 HSE Managing Health & Safety in Swimming Pools. Published 2003 (Revised 2013) Pool Water Treatment Advisory Group Treatment and Quality Standard for Pools and Spas Building Regulations Approved Document F Table 6.3 refers to CIBSE Guide B2005 CIBSE Guide B2005 Section 2.3.21 (Table 2.27) - Sports Centre Ventilation Guide 12

Varying Design information These offer a wide variety of somewhat differing advice; Ventilation rate of 4 to 10 air changes per hour a large difference 10 l/s per the total floor area (m²) somewhat nonsensical? 12 l/s of fresh air per person Correct, but likely to be a secondary factor Minimum 30% fresh air if recirculation is used an arbitrary figure Provide a slight negative pressure in the pool hall to prevent moisture ingress and permeation -correct Control over humidity and temperature - correct Air temperature to be ~1 C above pool water temperature generally correct Pool ventilation system should be operational 24/7 - correct Air temperatures should generally not exceed 31 o C with a relative humidity of between 55% and 65% - correct 13

Humidity and Evaporation & how to Calculate a Ventilation Rate 14

Humidity and Evaporation How can we control humidity in a pool hall? One method is to regulate the difference in absolute moisture content between outside air (fresh air) and the warm humid conditions found in a pool environment (pool air). To do this we can use fresh air as it will always be drier than pool air. These properties can be illustrated on a Psychrometric chart 15

Winter Condition: -4 C @ 100% RH Summer Condition: 28 C @ 50% RH Pool Hall Condition: 30 C @ 60% RH Pool Hall Summer 16.3 g/kg 12.1 g/kg Winter 2.6 g/kg -4 C 28 C 30 C 16

How to Calculate Ventilation Rate As mentioned, there are various methods. But the most reliable in our experience is the Biasin & Krumme formula. Firstly we have to calculate the evaporation rate in kg/hr; Evaporation Rate (m2) =0.118 + (0.01995 x (40 - (42.40 x 0.6))) Where; 0.118 is an empirical factor applied for the random shape of water 0.01995 is a factor applied relating to heat convection 40.0 is the vapour pressure of pool water at 29 C 42.4 is the vapour pressure of saturated air at 29 C 0.6 = 60%RH So the above equation can be broken down as follows; 42.4 x 0.6 = 25.44 40-25.44 = 14.56 0.01995 x 14.56 = 0.2905 0.118 + 0.2905 = 0.4085 kg/hr/m² continued/2 17

How to Calculate Ventilation Rate Next calculate the Total Swimming Pool Evaporation Rate = E x U x A Where: E = Evaporation Rate U = Activity Factor (detailed on the following page) A = Area of swimming pool in m² (in this case we will use a pool with an area of 300m²) So; E 0.4085 kg/hr/m² x U 0.4823 activity factor x A 300m2 = 59.1 kg/hr 18

How to Calculate Ventilation Rate Activity factors are applied to the formula as increased disturbance of the water surface due to activity increases the rate of evaporation. Typical factors are; 0.7947 Activated water such as a Jacuzzi, Flume, Wave Pool etc. 0.4823 Large public swimming pool 0.4329 School/Private swimming pools 0.2673 Unoccupied 19

How to Calculate Ventilation Rate Having established the evaporation rate we can now calculate air volume: V = W x 1000 (Xi Xo) x 1.175 x 3600 V = Ventilation rate (m³/s) W = Evaporation rate from pool (kg/hr) Xi = Moisture content at design condition (g/kg of air at 30/60%RH) Xo = Moisture content of ambient air (g/kg of air at 28/50%RH) 1.175 is a constant for air density (kg/m³) 3600 to convert m³/hr to m³/s 20

Unusual Factors Careful consideration should be given to unusual or additional factors such as: If very large numbers of spectators are present Very large water attractions in leisure pools such as flumes, slides & wave pools found in Center Parcs, Butlins, etc Large or unusual builiding s such as this old Victorian swimming baths 21

Calculating Air Flow (Working Example) 22

Calculating Airflow (Working Example) The following example has been based on a typical modern swimming pool: Internal pool hall volume of 2500 m³ Pool is 25m long with 8 lanes Pool water temperature is 29ᴼC Winter temperature: -4ᴼC @ 100% RH Summer design condition: 28ᴼC @ 50% RH No pool cover No additional activated water attractions 23

Calculating Airflow (Working Example) First calculate the maximum evaporation rate (kg/hr) when the pool is occupied. Evaporation Rate (W/m2) =0.118 + (0.01995 x (40 - (42.40 x 0.6))) So; 0.4085 kg/hr/m² x 0.4823 activity factor x 300m2 = 59.1 kg/hr (maximum evaporation rate) 40.0 is the vapour pressure of pool water at 29 C 42.4 is the vapour pressure of saturated air at 29 C 300 is the surface area of the pool 24

Calculating Airflow (Working Example) Then calculate the minimum evaporation rate (kg/hr) when the pool is unoccupied. W = (0.059 + 0.0105 x 0.2673 (40.0 42.4 x 0.6)) x 300 So the above equation can be broken down as follows; 42.4 x 0.6 = 25.44 40-25.44 = 14.56 0.0105 x 14.56 = 0.15288 0.059 + 0.15288 = 0.21188 kg/hr/m² x 300m2 = 63.56 x 0.2673 calm activity factor = 17kg/hr W =17 kg/hr (minimum evaporation rate) Pool water is assumed to be calm therefore activity factor is 0.2673 Vapour pressure and relative humidity of pool water & air at 29 C is as when the pool is occupied. 0.059 and 0.0105 are reduced constants to take into account undisturbed water. 25

Calculating Airflow (Working Example) Then you can calculate the maximum and minimum air volume flow rates (m³/s) for when the pool is occupied and unoccupied. 59.1 x 1000 V = (16.2 12.0) x 1.175 x 3600 V = V = V = 3.33 m³/s (maximum or occupied) 17 x 1000 (16.2 12.0) x 1.175 x 3600 0.96 m³/s (minimum or unoccupied) 26

Calculating Airflow (Working Example) Compare this calculation to other rule of thumb methods: Biasin & Krumme 3.33 m³/s 4 AC/Hr 2.77 m³/s 10 l/s of total pool hall area 4.64 m³/s 10 AC/Hr 6.94 m³/s 15l/s/m2 of wetted area 4.5m3/s 27

Calculating Airflow (Working Example) Cross-referencing this against a minimum fresh air requirement based on 12 l/s per person: If you assume an occupancy of 50 people in the pool hall this would equate to 600 l/s or 0.6 m³/s. If the maximum calculated air volume is 3.33 m³/s, 0.6 m³/s would equate less than 20% of fresh air. 28

Energy Efficiency & Running Costs 29

Energy Efficiency and Running Costs What is the optimum heat recovery solution for a swimming pool hall? Run Around Coil - Too Low Thermal Wheel 45% Efficient 75% Efficient Plate Heat Exchanger 70% Efficient - This we have found the optimum practical solution, particularly when combined with the ability to mix/return air from the pool hall 30

Optimum heat recovery Using a plate heat exchanger combined with a mixing facility & accurately modulating the amount of fresh air, efficiencies well in excess of 80% can be attained If a pool cover is used this can be increased to over 90% during unoccupied periods using more recirculated air & the dwell time increases on the plate heat exchanger with a lower air volume 31

Energy Saving Potential 32

Energy Saving Potential Using data from the previous examples and typical annual energy costs and usage: Occupied Air Volume Unoccupied Air Volume Gas Energy Tariff* Electrical Energy Tariff* 3.33 m³/s 0.96 m³/s 3.5 pence per kw/hour 10 pence per kw/hour *Gas & Electric Tariffs based on a generic industry national averages Average Daily Temperature** Pool in use 11 C (across the year) 12 hours a day **Average daily temperature based on Met Office data for London (2014) 33

Energy Saving Potential Total annual saving of over 600,000 kw/h 34

Energy Saving Potential 35

Importance of high energy efficiency Why is PHX efficiency and correct air flow so important? Every 1% decrease in PHX efficiency will have the effect of increasing running costs by over * 500 per year Similarly, for every 0.1 m³/s above the required design air flow it will approximately cost an additional * 240 per year to run * Based on data taken from previous example 36

System Design Considerations 37

System Design Considerations Consideration should also be given to the maximum specific fan power (SFP) for an air handling unit serving a pool: Source: Part L2 of the Building Regulations Existing New Build Mechanical Ventilation 1.8 W l/s 1.5 W l/s PHX Heat Recovery 0.3 W l/s 0.3 W l/s Return Air Filter 0.1 W l/s 0.1 W l/s Maximum SFP 2.2 W l/s 1.9 W l/s Because a pool is considered a process, it does not necessarily need to adhere to ErP 2016 regulations. But well designed systems would generally do so because of their high efficiencies 38

System Design Considerations What to look for when designing a pool ventilation system: Selection of durable well protected equipment Control options that can accurately maintain an optimum environment High energy recovery particularly important during winter months Systems that offer low energy use and a low maintenance regime Effective air distribution 39

System Design Considerations The use of a high grade paint finish inside and out will protect the AHU from aggressive chlorinated air. Whereas the use of low grade materials will not. 40

System Design Considerations Epoxy powder coated dampers. IP66 damper actuator motors protect against moisture ingress. 41

System Design Considerations Corrosion resistant plate heat exchanger that offer high transfer of energy (Anodised Aluminium or Virgin Plastic). 42

System Design Considerations Controls are an important integral part of any pool ventilation system. A sophisticated control package that enables full control over temperature and humidity will dramatically improve energy efficiency. 43

System Design Considerations To ensure the pool ventilation system runs at its optimum it is highly recommended to have the manufacturer undertake commissioning of the AHU and control systems. 44

System Design Considerations Air distribution is very important & warm dry air should be distributed over cold surfaces to prevent condensation. Also distribution should be designed as best as possible to allow & even low velocity (as possible) distribution of air across the pool hall & back to the extract point Manchester Grammar school is a recent project where sock, fabric ductwork was retro-fitted to great effect. The extract points in the ceiling had to be re-used 45

Summary Air volume should be no more than absolutely necessary as this will be detrimental to running costs. Pool halls should be maintained under a slight negative pressure to prevent pool air permeating other areas of the building and ingressing into the building fabric. A minimum of 20% fresh air should be introduced to the pool hall to maintain satisfactory air quality. Air temperature should be maintained approximately 1 C above pool water temperature to prevent unnecessary evaporation. 46

Summary Air temperatures should generally not exceed 31 C. Higher air temperatures can become uncomfortable for pool operators to work. Consideration for air distribution is very important & arm dry air should be distributed over cold surfaces to prevent condensation. 47

Thank you for your time 48

Energy Efficient Zero Maintenance Demand Responsive Robust Case Construction High Thermal & Acoustic Properties Blue Sense Controls Specific Pool Control Responds to Demand VOC Option (New) Over 80% Heat Recovery Durable Materials Integrated Mixing