SUBSTATION EXPLOSION BARRY GASS HIGH VOLTAGE TRAINING. Barry Gass Training Manager High Voltage Training South Africa

Similar documents
Power Unit 075. Maintain Substation Circuit Breakers

Innovative Techniques for Mitigating Arc Flash Exposure

PSSI 3 High Voltage Metal-Enclosed Switchgear

MANAGING ARC FLASH: A Risk Management Approach. Steve Williams Engineers Australia - Electrical College 14 June 2017, Brisbane

MANAGING ARC FLASH RISKS: A Strategic Approach. Steve Williams Rockwell Automation TechED March 2016, Auckland

Removing Yourself from Hazards During Equipment Operation

Electrical Safety. Hazard Awareness

ELECTRICAL FLASHOVER HAZARDS AND SAFETY MEASURES REFERENCE TO DESIGN AND MAINTENANCE. Intrduction: B.MAHARANA, AGM(EM)/HOD NTPC,RAMAGUNDAM

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager

Why do I need to do an Arc-Flash Analysis?

Selection of Electrical PPE Tables

This presentation provides an overview of modern methods for minimizing the arc-flash hazard.

To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC

Electrical Safety in the Food Industry

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

2012 NFPA 70E: Electrical Safety In The Workplace

General Lockout Training Briefing

HIGH-IMPACT SAFETY TRAINING FOR QUALIFIED ELECTRICAL WORKERS

Electrical Safety Program

Field Instruction. 2.6 Worksite Clothing - Personal Protective Equipment (PPE) Requirements

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

Field Instruction. 2.6 Worksite Clothing - Personal Protective Equipment (PPE) Requirements

KMU SUBSTATION WORKSHOP

Power System Safety Rules. Revision

Gas Network Craftsperson

Appendix A: Energized Work Permit

POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH

This Procedure details the procedures to be followed in order to achieve Safety from the System when:

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

GAS INSULATED SWITCHGEAR

Field Instruction. The purpose of this instruction is to inform all Horizon Power workers of the safety requirements when working from a EWP.

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

Leader s Guide ERI Safety Videos

PSSI 1 High Voltage Switching

MaxSB - Low Voltage Switchboard

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

NORTHERN POWERGRID. Distribution Safety Rules 2015 Edition

PSSI 10 Plant and Apparatus Containing Dielectric Gas

COOPER POWER SERIES. VFI SF6-insulated vacuum fault interrupter installation, operation and maintenance instructions. Switchgear MN285004EN

Arc Flash. Safety 21

Insulating Gas Management Program

PURE H2O FORUM. Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program

Progressive Safety Services LLC - All Rights Reserved

Standard. Extra High Voltage (EHV) Indoor Gas Insulated Switchgear Standard R Version 1.0, June 2018

NFPA 70E Policies and Best Practices

You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services

SM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems

NFPA 70E What Changed? Keeping People Safe from Electrical Hazards for over 50 Years

Isolation of power supplies

Dealing with Electrical Hazards in the Workplace

ARC:Gear from Unipart Rail

Original Date of Issue: 04/09

Session Seven: Arc Flash Hazard (AFH) Rio Tinto Bell Bay Site

GATOR Battery-powered Pistol Grip Cable Cutters

HEALTH TECHNICAL MEMORANDUM Authorised persons logbook STATUS IN WALES APPLIES

SAFE-WORK PRACTICES Working On Or Near Energized Electrical Equipment CAT A-1 SOP #4

Arc Flash 101. presented by Arc Flash Blaster LLC

Status Date Prepared Reviewed Endorsed Approved

Electrical Safety Program

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

Maintaining electrical equipment/systems

The invisible killer - electrical safety in the food and drink industry

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

2. The purpose of this program is to achieve the following objectives:

MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC

Management Plan for Electrical Safety ISD #535

Baseline Risk Assessment and Hazard Identification

CIRCUIT BREAKER TESTING - JOB SAFETY ANALYSIS

Hazard Sheet 8. Electricity. Electricity

Big 5 Site Training Support Information

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks

OPERATING CODE NO. 8 APPENDIX 2

Isolating plant. Guidance Note. June 2011

Risk Assessment Procedure

ARC:Gear from Unipart Rail

D Square Construction LLC

Working Safely on Overhead Lines

List all key terms and acronyms used in the procedure, and their definitions.

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE

Safety Meeting Topic #6 Working Around /On Energized Equipment

LOCKOUT/TAGOUT PROGRAM

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

Gas Network Craftsperson

Advanced Pump Control for Irrigation Applications

Electrical Safety Program

Major Changes. Standard. TECH TOPIC standards and. By Peter Walsh, PE

NESC WORKSHOP Revisions to Part 4 (Work Rules) Sam Stonerock. October 18, 2016

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

Leader s Guide ERI Safety Videos

100 Questions on Electrical Safety Study Guide

Operating Instructions

CSA Z462 2 nd TO 3 rd EDITION DIFFERENCES CHANGES & UPDATES

Gas density monitor With integrated transmitter Model GDM-100-TI

Inspection Recommendations

Transcription:

High Voltage Training Barry Gass Training Manager High Voltage Training South Africa BARRY GASS HIGH VOLTAGE TRAINING INTRODUCTION An authorised person closed an 11kV Oil Circuit Breaker (OCB) onto a fault at a substation. INTRODUCTION The OCB exploded and the force of the blast blew off the substation doors, seriously damaging the building.

INTRODUCTION The authorised person broke his right arm, when the door behind which he was standing was blown open. The fire that followed destroyed all the equipment within the substation. SEQUENCE OF EVENTS The electromechanical relay protecting the cable did not flag. One of the cables feeding a Mini Substation (MSS) developed a fault and the OCB tripped. FLAG

SEQUENCE OF EVENTS No cause was found for the OCB to trip, so it was decided to close the breaker. REMOTE SWITCHING CLOSING TRIPPING NO ELECTRICAL CLOSING LOCK OFF HOLE FOR LANYARD

FLASH SUIT LANYARD APPLIED SEQUENCE OF EVENTS As an added precaution, the authorised person decided to wear a flash suit. ELECTRICIAN * * AUTHORISED PERSON SUBSTATION LAYOUT INCOMER OUTGOING CABLE FEEDERS FAULTED OCB OCB OCB OCB OCB OCB OCB OCB LANYARD Another electrician, who was present, stood further away, as he was not wearing a flash suit. MAIN DOORS SEQUENCE OF EVENTS The explosion blew off the main central doors of the substation, through a metal link fence, ending up about 20 metres away.

SEQUENCE OF EVENTS The authorised person broke his right arm, when the door behind which he was standing was blown open. SEQUENCE OF EVENTS The fire that followed destroyed all the equipment within the substation. DOOR UNBOLTED ROOT CAUSE The OCB was closed onto a fault and did not trip, due to mechanical failure. The oil vapourised and the OCB exploded.

CONTRIBUTING FACTORS The age of the OCB. Lack of maintenance. SPLIT TANK The electromechanical relay did not flag, indicating the original cause of the fault. CONTRIBUTING FACTORS The risk assessment only took into account the danger of arc flash and not the power released by the OCB exploding.

CONCLUSIONS The OCB was closed onto a fault. The electromechanical relay sent a trip signal to the circuit breaker, but it failed to trip, probably due to lack of maintenance. All existing circuit breakers to be fitted with remote operating devices, to allow operation outside the substation. As the breaker was an OCB, it was more susceptible to fire and explosion. All general risk assessments must be reviewed, especially where OCBs are presently used, to include strategies to mitigate the risk of explosions.

Controls must be put in place and applied. Procedures to be revised accordingly and all operating staff (authorised persons) trained on them. Regular maintenance to be carried out on all switchgear. A maintenance schedule to be compiled and complied with. Old OCBs to be replaced with new Vacuum Circuit Breakers (VCBs) or Sulphur Hexafluoride (SF6) breakers. A replacement schedule to be compiled and monitored. VCBs All circuit breakers to be trip tested once a year. Relays to be secondary injected and calibrated every two years. A mini-risk assessment (Take 5) must be carried out at the work site, over and above the existing general risk assessment. The risk changes at each work site, although the task remains the same.

Medium/High Voltage (MV/HV) operating training must be conducted and reviewed every two years (refresher courses conducted). OHSAct 8(e) Employer shall provide: Information Instruction Training Supervision

Full flash suits must be worn when racking in or out a circuit breaker, spring charging and any other local operations, including tests for zero potential and live electrical phasing. H

Personnel to stand away from any open door and in such a position that they cannot be injured by the blast from an explosion or from doors being blown open. Batteries and battery chargers to be maintained and calibrated.

Batteries to be load tested on entry into substation, if load test facilities exist. The question is - how many times can you close a circuit breaker after a fault? There is no definitive answer to this question, as there are so many variables: How old is the breaker? When was the breaker last maintained? How many times has the breaker tripped on fault since the last maintenance was carried out? What protection scheme is installed on the circuit breaker? When was it last tested?

What is the insulating medium? If it is an OCB, what is the condition of the oil? The insulating properties of the oil and its flash point are reduced after a fault current passes through it. It is a misconception, that, if the circuit breaker or MSS is vacuum or SF6, an explosion will not occur during operation. 140*C AFTMD-93 In fact, if the integrity of the SF6 or vacuum is lost, the operator is opening/closing the circuit breaker/mss in air and a flashover could ensue.

When operating with SF6 filled equipment, the authorised person must always check the SF6 gas level on the gas pressure gauge (if one exists). The flash suit provides protection for arc flash and will give the operator little physical protection against the force of a blast; therefore, remote tripping must always be the first option, before resorting to PPE. When looking at flash suits, it is important that the correct type and cal rating is selected (a low voltage flash suit, for example, is not suitable for use on Medium or High Voltage). All other staff in, or working in the vicinity, should move away to a reasonable distance whilst operating is being carried out. It is also important to call the relevant Control Centre when entering substations, so that they do not operate switchgear remotely, via Supervisory Control And Data Acquisitions (SCADA), whilst the operator is in the substation.

Nowadays, circuit breakers can be designed to have arc spaces in the switchgear, so that the breaker must be opened, closed, racked in or out with the door closed and any explosion contained in the chamber. Protection systems have also become more sophisticated and faster. REMEMBER However, the clearance time is still dependent on the actual circuit breaker tripping time. If the fault is not cleared quick enough then. NO OPERATING CONDITION OR LOSS OF SUPPLY CAN EVER JUSTIFY ENDANGERING THE LIFE OF ANYONE

BARRY GASS HIGH VOLTAGE TRAINING Email:bgass@vodamail.co.za Cell: 083 459 8298 Tel: 033 239 5572