Technical Instructions

Similar documents
TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

VB-7263 Series. Application. Features. Applicable Literature

VBS-9263 Series. Application. Features. Applicable Literature

VB-7211 Series. Application. Features. Applicable Literature. 1/2" to 1-1/4" Union End NPT Stem Up Open, Two-Way Valves General Instructions

VB-7213 Series. Application. Features. Applicable Literature. 1/2" to 2" Screwed NPT Stem Up Open, Two-Way Valves General Instructions

VB-7273 Series. Application. Features. Applicable Literature

A t. VB-7323 Series. Application. Features. Applicable Literature. l/2 to 2 Screwed NPT SIEBE

VB Series. Application. Features. Applicable Literature. 1/2 to l-1/4 Union End NPT Stem Up Open, Two-Way Valves General Ins tructions

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

Pressure Independent Control Series

TITAN FLOW CONTROL, INC.

Application Worksheet

Type 1098-EGR. Pilot-Operated Valve Link Regulators. Features. Fisher Controls

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Eaton Filtration, LLC

Simple Set Max. Pressure Independent Control Valves 2 Way 2-1/ /09/18

Model 4000 Pressure Controller

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

CSA Sample Draw Aspirator Adapter Operator s Manual

CVI Valve Line. Exceeds the industry s highest standards for reliability and performance

Float Operated Level Controllers

WW-720. Pressure Reducing Control Valve

TECHNICAL DATA. Page 1 of 12

Installation, Operation and Maintenance Manual for Back Pressure Regulator

AWWA C504 COMPLIANT VALVES FROM 3 THRU 108

The Hoffman Specialty Series 2000 consists of main

BACK PRESSURE / SUSTAINING

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

WW-720. Pressure Reducing Control Valve

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

2-Port Seat Valves with Flange, PN 16

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Engineering Data Sheet

Series 42 Self-operated Regulators Differential Pressure Regulators with Type 2424/Type 2428 Actuator (closing) Type Type 42-28

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

PRO-50 Instrument Supply Regulator

FLANGED TWO-PIECE BALL VALVES

INSTALLATION & MAINTENANCE INSTRUCTIONS

Manual Actuated Boiler Blowdown Valves

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Bermad Pressure Reducing. Model: 42T

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

2-port and 3-port valves PN 16

61R2 STANDARD REGULATOR COMPACT REGULATOR. Phone Fax

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

WW-730. Pressure Sustaining/Relief Control Valve

FLANGED TWO-PIECE BALL VALVES

BACK PRESSURE / SUSTAINING

2-Port Seat Valves with Flange, PN 16

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

T 2523 EN Type 2406 Excess Pressure Valve Self-operated Pressure Regulators ANSI version

1800C and 1800C-HC Service Regulators

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Pressure Regulator B-95

Wafer Check Valve. Contents. User s Manual. (1) Be sure to read the following description of our product warranty 1

Two-port valves, male threaded, PN25

829S1 Series Flexflo Pilot

Eaton Filtration, LLC

General. Rugged, Reliable with Value-added Features. Pipe Sizes. Temperature Limits. Spring Ranges. Buried Service. Increased Outlet Pipe Sizes

3-port seat valves with externally threaded connection, PN 16

Petrofac Client Doc. No JI-DTS-5002 Page 2 of 8 Rev. TABLE OF CONTENTS

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

1805 Series Relief Valves

BS Series Basket Strainer

HAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

V43 Pressure Actuated Water Regulating Valve

Noth American 7347 High Pressure Gas Regulators

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

CAST IRON VALVES FLOAT VALVE

2-port and 3-port seat valves, PN16

61 Series Pilots for Pilot-Operated Pressure Reducing Regulators

Model 141-A Regulators

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

TECHNICAL DATA CAUTION

1213B2 Service Regulators Maximum Inlet Pressure 125 PSIG

DS MZ, MZF, MJF THREE-PORT SEAT VALVES

Horizontal Bladder Tanks

SERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.

627 Series Pressure Reducing Regulators

SDS -Series 4C-D201/-D202 Supplemental Drying System User s Manual

Vertical Bladder Tanks

94270 Vapor Guard Tank Blanketing Valve Vapor Guard Tank Blanketing Valve What is Tank Blanketing? Features How does it work?

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

1200 Series Pressure Regulators

Design DSA Steam-Atomized Desuperheater

CV3000 Series Pressure Balanced High-Pressure Cage type Control Valves

Type 299 Pressure Reducing Regulators

TECHNICAL DATA Q= C. Table 1 - Specifications

V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

TITAN FLOW CONTROL, INC.

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION SPECIFICATIONS. CE (EMC) Compliant

CL31 Series Commercial Regulator. Advanced Metering and Regulation Technology at Work.

Transcription:

Technical Instructions IS-P-596MI Flowrite II Iron ody Series 596 MI Description n Powers Flowrite II Water Mix (MI) Valves combine hot and cold water proportionally to satisfy the demands of the controlling instrument. The valve's linear inherent characteristic produces equal changes in flow per unit of valve stroke regardless of plug position. The valve is air operated and can be used in a variety of mixing applications. Specifications n VALVE ody Sizes:... 2 1/2" 6" ody Material:... Cast Iron (per ASTM A126-93 Class ) End Connectors:... 125 # Flanged (per ASNI 16.1-1993) Trim:... ronze Packing:... Spring loaded TFE packing Seat Leakage:... ANSI Class III; <0.1% leakage Cv Range:... 74-390 Rangeability:... 100:1 Characteristics:... Linear/Mixing Maximum Pressure:... 200 psi @ Temp. <150 F Max. Differential Press.:... 50 psi Temperature Range:... 40 281 F ACTUATOR Housing Construction:... Die cast aluminum Diaphragm Construction:... Replaceable molded neoprene Diaphragm Area:... 46 in 2, 100 in 2 Maximum Press. and Temp:... 35 psi and 200 F Ambient Shipping Limits:... -40 to 220 F Ambient Operating Limits:... -20 to 220 F Air Connection:... 46 in 2 1/4" NPT 100 in 2 1/8" FNPT Position Indication:... 1/8" increments Mounting:... In any upright position with actuator head above 45 of the center line of the valve body. Actuator head may be swiveled to any convenient position. Table of Contents n Description... 1 Specifications... 1 Application Information... 2 Theory of Operation... 2 Valve Sizing and Selection... 3-4 Close Off Data... 5 Temperature/Pressure Ratings... 5 Dimensional Data... 6 Installation... 7 Maintenance... 7 Ordering Information... 8 596 MI with 46 in 2 actuator shown Sizes Actuators Available 2 1/2" 46 in 2 or 100 in 2 Diaphragm 3" 46 in 2 or 100 in 2 Diaphragm 4" 46 in 2 or 100 in 2 Diaphragm 5" 100 in 2 Diaphragm 6" 100 in 2 Diaphragm! WARNING FAILURE TO COMPLY WITH PROPER INSTALLATION AND MAINTENANCE INSTRUCTIONS COULD CONTRIUTE TO THE VALVE FAILURE. Watts Hot Water Master Tempering Valves cannot be used for tempering water temperature at fixtures. Severe bodily injury (i.e., scalding or chilling) and/or death may result depending upon system water pressure changes and/or supply water temperature changes. ASSE standard 1016, 1069 or 1070 listed devices should be used at fixtures to prevent possible injury. The Watts Hot Water Tempering Valves are designed to be installed at or near the boiler or water heater. They are not designed to compensate for system pressure fluctuations and should not be used where ASSE standard 1016, 1069 or 1070 devices are required. These Watts valves should never be used to provide anti-scald or anti-chill service. The components of the system must be of materials with a construction capable of withstanding the high limit output temperatures of the water heating source.! WARNING Need for Periodic Inspection: Periodic inspection by a licensed contractor is recommended. Corrosive water conditions, temperatures over 210 F, and or unauthorized adjustments or repair could render the valve ineffective for service intended. Regular checking and cleaning of the valve s internal components and check stops helps assure maximum life and proper product function. Frequency of cleaning and inspection depends upon local water conditions and water temperature.

Application Information n Flowrite II 596MI Valves are used for mixing hot and cold-water streams or bypassing flow with the valve in the return line. The controlling instrument positions the mixing valve to obtain the approximate mixture temperature. Figure 1 shows an example of a mixing application, a typical boiler hot water control system. The cold inlet supply is fed to the upper inlet port (A port) of the valve as well as through the boiler for production of hot water to be fed into the bottom port ( port). Figure 2 shows an example of a bypass application, piping for control of a heating or cooling coil, with the valve in the return line. The controlling instrument positions the valve so that the hot water will bypass the coil when the air is at the proper temperature. A pump is recommended in the coil loop to improve the heat transfer characteristics of the coil. Figure 1 Cold Water Supply Control Valve Return A oiler A Hot Water Inlet oiler Hot Water Control System Figure 2 Coil Valve ypass Valve ypass Return Coil Return Supply Stem down flow through coil. Stem up flow through coil bypass. Supply Stem up flow through coil. Stem down flow through coil bypass. ypass Piping for Control of a Heating or Cooling Coil Theory of Operation n Air pressure from the controlling instrument enters the pressure tight chamber of the actuator between the diaphragm and the upper housing. An increase in control air pressure causes the diaphragm to press down on the thrust plate, compressing the springs and moving the valve stem downward. In the valve, this reduces the flow through the "" port and increases the flow through the "A" port. Conversely, A decrease in control air pressure reduces the downward force on the actuator diaphragm, moving the thrust plate and stem upward. The flow through the "" port is increased, and the flow through the "A" port is decreased. Figure 3 A Three-way valve A 2 In temperature mixing applications the hot inlet is usually plumbed to the "A" side port, which will close on loss of signal. Otherwise, the "" lower port is used for hot, "A" upper side port for cold, and the "A" outlet for the mixed combination (see Figure 3). Three-way mixing valves are designed so that the flow from either of the inlet ports to the outlet is approximately linear, which means the total flow from the outlet is almost constant over the stroke of the valve stem. See Figure-4 for typical flow characteristics of 596 MI. Rated Flow 100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0% 0% "A" Port Stem In 20% Figure 4 40% Stroke 60% Rated Flow vs Stroke Diagram 80% "" Port Stem Out 100%

Valve Sizing and Selection n NOTE: Supply pressures (inlet) are affected by piping schedule, internal surface conditions, and vertical runs (back pressure) so the actual flowing pressure is best measured at the point of valve use. Proportional to Mix Supply Flows Proportional valves when used to blend two water flows control the output by varying the water temperature to the heat exchanger at constant flow. These valves require high pressure drops for good control results. They can be sized for a pressure drop of 20% of the flowing pressure or equal to 25% of the pressure drop through the heat exchanger at full flow. Table - 1 Water Capacity in Gallons Per Minute Valve Cv Size Rating Differential Pressure ( in psi) 5 10 15 20 25 30 35 40 45 50 2.5 74 165 234 287 331 370 405 438 468 496 523 3 101 226 319 391 452 505 553 598 638 678 714 4 170 380 538 658 760 850 931 1006 1075 1140 1202 5 290 648 917 1123 1297 1450 1588 1716 1834 1945 2051 6 390 872 1233 1510 1744 1950 2136 2307 2467 2616 2758 Proportional to ypass Flow Proportional mixing valves when used to bypass flow are piped on the outlet side of the hot water source to throttle the water flow and thereby control heat output. These valves are usually selected to take a pressure drop up to 50% of the flowing pressure through the valve. 3

Valve Sizing and Selection cont. n Cavitation, Flashing and Choked Flow: Limitations on Valve Pressure Drop A concern in high temperature water systems is the potential for cavitation, which is caused by the downstream pressure being lower than that of the vapor pressure of the fluid. This basically causes the water to "boil" and can result in reduced flow/capacity, excessive noise, vibration, wear and should be avoided if possible. If the pressure downstream of the area restriction rises rapidly above the vapor pressure, the vapor bubbles will collapse violently (implode). The bubble collapse is an affirmation of cavitation. Use the following equation below to estimate the maximum allowable pressure drop across the valve. Flashing is a phenomenon where the flowing high temperature water inlet experiences a significant pressure drop, with the outlet pressure below the vapor pressure of the water (as in cavitation) and is converted to a vapor within the control region of the valve. This can also produce a choked flow condition where the rapidly expanding vapor prohibits any increase in flow, even though P1 (inlet) pressure is increased. Pmax = 0.5 (P1 Pv) Where: Pmax = Maximum allowable pressure drop P1 = Absolute inlet pressure (psia) Pv = Absolute vapor pressure (refer to psia - Table 2) Absolute pressure = gage pressure + 14.7 Table-2 Vapor Pressure of Water Water Vapor Water Vapor Temp. Pressure Temp. Pressure ( F) (psia) ( F) (psia) 40 0.12 140 2.89 50 0.18 150 3.72 60 0.26 160 4.74 70 0.36 170 5.99 80 0.51 180 7.51 90 0.70 190 9.34 100 0.95 200 11.53 110 1.28 210 14.12 120 1.69 220 17.19 130 2.22 230 20.78 4

Close Off Data n Varying the preload is possible to adjust close offs between the upper and lower ports. Table 3 - Close Off Data Close Off ( P in psi) Signal-to-Actuator Valve Size Actuator (Positioner) (in) Size (in 2 ) 3-15 PSI 1-17 PSI 0-30 PSI Upper Port Lower Port Upper Port Lower Port Upper Port Lower Port 2.5 46 8 8 27 27 73 73 100 (1M) 13 98 55 125 55 125 3 46 3 3 16 16 48 48 100 (1M) 6 66 35 94 35 125 4 46 0 0 6 6 24 24 100 (1M) 1 34 17 50 17 125 5 100 (1M) 0 21 9 31 9 97 6 100 (1M) 0 13 5 20 5 66 Temperature/Pressure Ratings n Never exceed the temperature/pressure ratings of the valve (see figure 5). The shaded area shows the acceptable region. Figure 5 Temperature F 596MI Pressure psig Temperature and Pressure Ratings 5

Dimensional Data n Table-4 Dimensions for 596MI Series Valves Nominal Pipe Size 2-1/2" 3" 4" 5" 6" A 8.500 9.500 11.500 13.000 14.000 STROKE 0.875 0.875 0.875 1.750 1.750 5.375 6.375 8.500 8.750 9.750 C 3.500 3.750 4.500 5.000 5.875 D 10.375 10.375 10.375 N/A N/A E 10.000 10.000 10.000 N/A N/A F 16.625 16.625 16.625 19.000 19.000 G 10.313 10.313 10.313 10.313 10.313 Valve Weight (lbs) 62.00 82.00 115.00 180.00 264.00 Weight w/46" 75.00 95.00 128.00 N/A N/A Weight w/100" 87.00 107.00 140.00 205.00 289.00 Figure 6 G 100" Actuator F 46" Actuator E D C 2-1/2" to 6" Valve odies A Table - 5 Flange Detail for American Standard 125 lb. Cast Iron Pipe Flanges Flanges Drilling olting Length of Valve Flange Flange Diameter of Diameter of Number Diameter Machine Size Diameter Thickness olt Circle olt Holes of olts of olts olts A C D E 2-1/2" 7" 11/16" 5-1/2" 3/4" 4 5/8" 2-1/2" 3" 7-1/2" 3/4" 6" 3/4" 4 5/8" 2-1/2" 4" 9" 15/16" 7-1/2" 3/4" 8 5/8" 3" 5" 10" 15/16" 8-1/2" 7/8" 8 3/4" 3" 6" 11" 1" 9-1/2" 7/8" 8 3/4" 3-1/4" Figure 7 E D C A 6

Installation n Inspection Inspect the package and contents for damage. If damaged, notify the appropriate carrier immediately. If consultation is necessary, please contact Powers Customer Service for assistance. Requirements Pipe wrenches Flange gaskets, bolts / nuts Installer must be a qualified, experienced technician CAUTION! Install the valve with the flow in the direction of the flow arrows ("A" and "" ports are inlets and "A" port is the outlet). Do not exceed the ratings of the device. Avoid locations where excessive moisture, corrosive fumes, or vibration are present. Figure 8 - Installation of Flanged End Valves Valve ody Gasket: Supplied by Others Companion Flange Mounting / Orientation 1. The valve should be mounted in a location that is within the ambient limits of the actuator. When selecting a location, allow sufficient room for valve linkage, actuator, and other accessories and for service of the product. 2. The preferred mounting position for the valve is with the valve stem vertical above the valve body. Avoid mounting the valve so that the valve stem is below horizontal. 3. The valves must be piped with two inlets ("A" and "" ports) and one outlet ("A" port). Flanged Connection The 596 series flanged valve bodies conform to ANSI Standard 125 Lb. Cast Iron Pipe Flanges. The companion flanges (not provided) should be the same specification as the valve. The 125 Lb. Flanges have plain flat faces and should not be bolted to a raised faced flange. 1. All parts should be clean to assure the best results. 2. The pipe with the companion flanges installed should be properly supported and aligned. e sure the companion flange is flush with the face of the valve body flange and lined up squarely. 3. Use a gasket material (not provided) that is recommended for the medium being handled. CAUTION! Do not apply pipe dope to the valve flange, gasket, or companion flange. 4. See Figure-7 for flange and flange bolt details. Figure-8 shows the proper way a flanged valve should be mounted. Maintenance n Regular maintenance of the total system is recommended to assure sustained performance. See Table-6 for maintenance kit part numbers. Table - 6 Maintenance Kits for 596MI Valves Valve Description Replacement Replacement Valve Repair Kit* Pack Assembly Gaskets 2.5 596 Pack 596250G MIGOMTK 3 596300G MIHOMTK 4 596400G MIJOMTK 5 596500G MIKOMTK 6 596600G MILOMTK * Kit includes replacement packing and stem & plug assembly. Water System Maintenance All systems are susceptible to valve and system problems caused by improper water treatment and system storage procedures. These guidelines are provided to help avoid valve and water system problems resulting from improperly treated water or storage procedures and to obtain maximum life from the valves. To maintain non-damaging conditions, follow these guidelines: Clean the system prior to start up. Use filtration equipment where needed. Properly store off-line systems and monitor water treatment results. Follow the advice of a water treatment professional. Durability of valve stems and packings is dependent on maintaining non-damaging water conditions. Inadequate water treatment or filtration can result in corrosion, scale, and abrasive particle formation. Scale and particulates can result in stem and packing scratches and can adversely affect packing life and other parts of the hydronic system. 7

Ordering Information n 596- M I Size Order Code 2 1/2" 250 3" 300 4" 400 5" 500 6" 600 End Connections 125# Flange F Valve Trim ronze Action Mixing Packing Teflon M T Actuator Select Code (see below) Accessories Select Code (see below) Actuator Select Code n Code Pneumatic Diaphragm Actuators 46 46 Sq. in, 1" Max Valve Stroke with Stainless Steel Springs, adjustable start w/ 7 ~ 12 lb. Fixed span 4X 46 Sq. in, 1" Max Valve Stroke with Extended Springs (requires positioner), adjustable start w/22 lb. span. 1M 100 Sq. in, 5-10 psi Spring Range (Mixing Valves) Accessories Select Code n I/P Transducers n The "standard" 3-15 psi signal was originally designed as a transmission signal, not a valve actuation signal. The Fluid Controls Institute (in Standard 87-2) has recommended that a 1 17 psi air signal range be used when directly actuating a control valve without a positioner. Powers concurs with this recommendation, and therefore, offers a 1 17 psi I/P transducer and a 0 30 psi I/P transducer and the Accritem pneumatic controller for maximum close-off. 3-15 psi I/P transducers should be used in conjunction with positioners. Code IS TS US ES S PS RS SS OS Description ellofram 1000 I/P S 3 15 psi 1 17 psi 3 27 psi Control/Air Type 900X I/P 0 30 psi Utility Positioner and I/P 4 20 ma Utility Positioner 3 15 psi 3 9 psi 9 15 psi No Accessories No Accessories Positioners n Positioners are used for one or more of the following reasons: 1) To split range valves. 2) To eliminate unwanted valve movement caused by line pressure variations 3) To minimize the effects of "stick-slip" 4) To speed response time and/or 5) To increase close-off rating when I/Ps are used. Warranty n The Seller warrants that the equipment manufactured by it and covered by this order or contract is free from defects in material and workmanship and, without charge, equipment found to be defective in material or workmanship will be repaired, or at Seller s option replaced F.O.. original point of shipment, if written notice of failure is received by Seller within one (1) year after date of shipment (unless specifically noted elsewhere), provided said equipment has been properly installed, operated in accordance with the Seller s instructions, and provided such defects are not due to abuse or decomposition by chemical or galvanic action. This express warranty is in lieu of and excludes all other warranties, guarantees, or representations, express of implied. There are no implied warranties of merchantability or of fitness for a particular purpose. The Seller assumes no responsibility for repairs made on the Seller s equipment unless done by the Seller s authorized personnel, or by written authority from the Seller. The Seller makes no guarantee with respect to material not manufactured by it. A Watts Water Technologies Company IS-P-596MI 1043 EDP# 6512249 2010 Powers