Design a grit chamber for population with water consumption of 135 LPCD.

Similar documents
Module 15 : Grit Chamber. Lecture 20 : Grit Chamber

Grit chambers are basin to remove the inorganic particles to prevent damage to the pumps, and to prevent their accumulation in sludge digestors.

Bioreactor System ERT 314. Sidang /2011

Lecture 10 : Sewer Appurtenances

ROTAMAT Rotary Drum Fine Screen Ro 2 / RPPS

HUBER Rotary Drum Fine Screen ROTAMAT Ro2 / RPPS / STAR

The activated sludge process

Applied Fluid Mechanics

(Refer Slide Time: 2:16)

Free Surface Flow Simulation with ACUSIM in the Water Industry

6. Positioning. 6.1 General description

To plot the following performance characteristics; A pump is a device, which lifts water from a lower level to a higher

VORTEX REGULATOR Type WAB (UCY / CY-F / CE/V)

ASSIGNMENT-1 HYDROPOWER PLANT

Course Teacher: Prof. Dr. M. R. Kabir SPILLWAY & IRRIGATION PUMPS. Spillway:

CHAPTER-2 IMPACT OF JET

Factors that determine water movement. Morphometry Structure of stratification Wind patterns

PETROLEUM & GAS PROCESSING TECHNOLOGY (PTT 365) SEPARATION OF PRODUCED FLUID

Lesson 27: Real-World Volume Problems

Sediment Basin 7E-12. Design Manual Chapter 7 - Erosion and Sediment Control 7E - Design Information for ESC Measures BENEFITS.

6. EXPERIMENTAL METHOD. A primary result of the current research effort is the design of an experimental

DUAL-VORTEX SEPARATOR. Inspection and Maintenance Guide

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

ASSIGNMENT-1 HYDROPOWER PLANT

Energy Specialties International

Digester Processes. 1. Raw Sludge Pumping System

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

Structure of Mechanically Agitated Gas-Liquid Contactors

400V 50Hz. Tsurumi TRN. Submersible aerator. Auto-suction submersible aerator for communal and industrial waste water clearance and treatment.

Ocean Structures and Material Prof. Dr. Srinivasan Chandrasekaran Department of Ocean Engineering Indian Institute of Technology, Madras

Red Valve Coarse and Fine Bubble Air Diffuser Systems

The water supply for a hydroelectric plant is a reservoir with a large surface area. An outlet pipe takes the water to a turbine.

Effect of Fluid Density and Temperature on Discharge Coefficient of Ogee Spillways Using Physical Models

International Journal of Technical Research and Applications e-issn: , Volume 4, Issue 3 (May-June, 2016), PP.

Seated valves VRB 3, VRG 3

A. M. Dalavi, Mahesh Jadhav, Yasin Shaikh, Avinash Patil (Department of Mechanical Engineering, Symbiosis Institute of Technology, India)

Experiment (13): Flow channel

22. Specialty Valves.

CSO/STORMWATER MANAGEMENT. HYDROVEX VHV / SVHV Vertical Vortex Flow Regulator

Motion in 1 Dimension

Hours / 100 Marks Seat No.

IMPROVING PLANT AERATION USING GAS INFUSION TECHNOLOGY

Exercise (4): Open Channel Flow - Gradually Varied Flow

GROUTEC SCOTT VICKERS. Grouting Equipment

PHYS 101 Previous Exam Problems

Write important assumptions used in derivation of Bernoulli s equation. Apart from an airplane wing, give an example based on Bernoulli s principle

E 441 E 451 E 461 E 641 E 700 Tank mounting Nominal flow rate up to 800 l/min

Outlet Structures T-12

CHAPTER 3 : AIR COMPRESSOR

pumping gases JET PUMP TECHNICAL DATA

Experiment 8: Minor Losses

DARSHAN INSTITUTE OF ENGINEERING AND TECHNOLOGY

AIR FOAM CHAMBER DATA SHEET

E 084 Tank top mounting Connection up to G1 / -16 SAE Nominal flow rate up to 80 l/min / 21.1 gpm

Presented by. Mr.Danish.D.R. M.Tech Coastal Management Institute for Ocean Management Anna University, Chennai Tamil Nadu, India.

E 158 E 198 E 248. Tank top mounting Connection up to G11 / 4 Nominal flow rate up to 250 l/min e d

Flow in a shock tube

PSD 250 Minimum Lubrication System. For lubricants in the 1000 mm²/sec viscosity range

Fixed Displacement Motor A4FM

By Syed Ahmed Amin Shah 4 th semester Class No 8 Submitted To Engr. Saeed Ahmed

Tutorial 5 Relative equilibrium

Combination Air Valve

EPP pneumatic pumping stations PRODUCT CATALOG

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

FLUID DYNAMICS Ch.E-204 Umair Aslam Lecturer Department of Chemical Engineering

INTRODUCTION 1.0 GENERAL

The Mechanism Study of Vortex Tools Drainage Gas Recovery of Gas Well

Irrigation &Hydraulics Department lb / ft to kg/lit.

STANDARD OPERATING PROCEDURES

Crab and Lobster Live Holding System Part II (Water Pumps, Air Pumps and Pipework)

aeration and mixing systems

VISIMIX LAMINAR. BLENDING OF NON-NEWTONIAN LIQUID. POWER. CIRCULATION. MIXING TIME.

Displacement 12, , Maximum flow rate (at 1450 rpm) bar.

Vacutrans Instructions

Classic wine storage tanks model EXX

Fixed Displacement Pump KFA for commercial vehicles in open circuits

Installation and commissioning instructions 255 series and 256 series

Seated valves (PN 16) VF 2 2-way valve, flange VF 3 3-way valve, flange

E 328 E 498 Tank top mounting Connection up to G1½ / -24 SAE and SAE 2 Nominal flow rate up to 600 l/min / gpm

. In an elevator accelerating upward (A) both the elevator accelerating upward (B) the first is equations are valid

Wastewater combination air valve in stainless steel AISI 316 Mod. SCS

Student name: + is valid for C =. The vorticity

E 328 E 498 Tank top mounting Connection up to G1½ and SAE 2 Nominal flow rate up to 600 l/min

ZIN Technologies PHi Engineering Support. PHi-RPT CFD Analysis of Large Bubble Mixing. June 26, 2006

Pre AP Physics: Unit 7 Vibrations, Waves, and Sound. Clear Creek High School

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

Foam Chamber Model-FC

MITIGATING PIPE AND RISER HYDRAULIC PIPELINE ISSUES WITH THE I-RISER PLUS

Kinematics of Vorticity

Calculus 12: Evaluation 3 Outline and Review

9408 Series Dissolved Oxygen Systems. Dissolved oxygen systems designed for reliable operation with minimal operating costs

Hours / 100 Marks Seat No.

COURSE NUMBER: ME 321 Fluid Mechanics I Fluid statics. Course teacher Dr. M. Mahbubur Razzaque Professor Department of Mechanical Engineering BUET

COMPRESSED AIR DISTRIBUTION SYSTEMS

Seated valve for steam (PN 25) VFS 2 2-way valve, flange

E 094 E 103 E 143 Tank top mounting Connection up to G1 / -16 SAE Nominal flow rate up to 135 l/min / 35.7 gpm

Seated valve for steam (PN 25)

CVEN 311 Fluid Dynamics Fall Semester 2011 Dr. Kelly Brumbelow, Texas A&M University. Final Exam

Supratec AERATION TECHNOLOGY. von-drais-straße 7 D Simmern / Hunsrück. tel.: / fax: /

Fixed Displacement Motor A4FM

Transcription:

1 Example:1 Design a grit chamber for population 50000 with water consumption of 135 LPCD. Solution Average quantity of sewage, considering sewage generation 80% of water supply, is = 135 x 50000 x 0.8 = 5400 m 3 /day = 0.0625 m 3 /sec Maximum flow = 2.5 x average flow = 0.0625 x 2.5 = 0.156 m 3 /sec Keeping the horizontal velocity as 0.2 m/sec (<0.228 m/sec) and detention time period as one minute. Length of the grit chamber = velocity x detention time = 0.2 x 60 = 12.0 m Volume of the grit chamber = Discharge x detention time = 0.156 x 60 = 9.36 m 3 Cross section area of flow A = Volume / Length = 9.32/12 = 0.777 m 2 Provide width of the chamber = 1.0 m, hence depth = 0.777 m Provide 25% additional length to accommodate inlet and outlet zones. Hence, the length of the grit chamber = 12 x 1.25 = 15.0 m Provide 0.3 m free board and 0.25 m grit accumulation zone depth, hence total depth = 0.777 + 0.3 + 0.25 = 1.33 m and width = 1.0 m Example :2 Design a horizontal flow grit chamber with rectangular cross section for treating maximum sewage flow of 10 MLD at maximum temperature of 34 o C during summer and minimum temperature of 15 o C in winter. Solution The settling velocity of the grit particle will be minimum at minimum temperature, i.e., 15 o C. At this temperature kinematic viscosity = 1.14 x 10-2 cm 2 /sec In first trial assume Reynolds number R less than or equal to 0.5. g S 1 Vs = D 18 ν 2 Vs 981 2.65 1 0. 02 2 18 1.14x10 = 2

2 = 3.15 cm/sec Reynolds Number R = v.d/ν = 3.15 x 0.02 / 1.14 x 10-2 = 5.53 > 0.5 Therefore, Vs is not equal to 3.15 cm/sec because the equation for Vs is valid only for R < 0.5. Using Vs = 3.15 cm/sec, calculate R and C D and then again Vs till it converges. Subsequent Trial Vs = 2.4 cm/sec R = 2.4 x 0.02 /(1.14 x 10-2 ) = 4.21 C D = 24 3 + + 0.34 4.21 4.21 = 7.50 From equation 4 981 Vs = (2.65 1)0. 02 3 7.50 Vs = 2.4 cm/sec Hence, O.K. Now for β = 0.06, f = 0.03, and D = 0.02 cm 8β Vc = g( S 1) D f 8x0.06 Vc = 981(2.65 1)0. 02 0.03 = 22.76 cm/sec Now Q = 10 MLD = 0.116 m 3 /sec Therefore, C/S Area A = Q/V = 0.116/0.227 = 0.51 m 2 If width of 1 m is provided, the depth required = 0.51 m Provide total depth = 0.51 + 0.3 (free board) + 0.25 (space for grit accumulation) = 1.06 Say 1.1 m Now Vo/Vc = H/L = 2.4/22.7 Therefore theoretical length L = 22.7 x 0.51 / 2.4 = 4.824 m Provide 2 m extra length for inlet and outlet Therefore total length = 2 + 4.824 = 6.824 m say 6.9 m Total working volume = 0.51 x 6.9 x 1 = 3.52 m 3 Hence, Overall detention time = 3.52 / 0. 116 = 30.34 sec (within 30 to 60 seconds)

3 15.6 Square Grit Chamber The horizontal flow rectangular grit chamber faces the problem of sedimentation of organic matter along with grit particles, requiring external washing of the grit before disposal. This problem can be minimized by providing square shape of the grit chamber rather than long rectangular channel. Also, this shape will facilitate compact design of sewage treatment plant. Hence these days square grit chambers are used. In square grit chamber, the flow distribution may not be uniform due to non-ideal plug flow conditions, and hence continuous removal of grit is generally considered essential. These are designed based on overflow rates that are dependent on the particle size and temperature of wastewater. Minimum two number of grit chambers should be used to facilitate maintenance of the raking mechanism, whenever required. The grit deposited at the bottom is raked by rotating mechanism to a sump at the side of the tank, from which it is moved up by an inclined reciprocating rake or screw pump mechanism (Figure 15.5). While passing up the incline conveyer, organic solids are separated from grit and flow back into the basin. Thus, cleaner washed grit is obtained, compared to washed grit from separate grit washers. Figure 15.5 Square grit chamber 15.7 Aerated Grit Chamber Excessive wear of grit handling equipment and necessity of separate grit washer can be eliminated by using aerated grit chamber. It is designed for typical detention time of 3 minutes at maximum flow. Grit hopper about 0.9 m deep with steeply slopping sides is located along one side of tank under air diffusers (Figure 15.6). The diffusers are located at about 0.45 to 0.6 m from the bottom. The size of particles removed will depend upon velocity

4 of roll or agitation. The air flow rate can be easily adjusted to control efficiency and 100% removal of grit can be achieved. Wastewater moves in the tank in helical path and makes two or three passes across the bottom of the tank at maximum flow (and more at less flow). Wastewater is introduced in the direction of roll in the grit chamber. The expansion in volume due to introduction of air must be considered in design. The aerated grit chambers are equipped with grit removal grab buckets, traveling on monorails over the grit collection and storage trough. Chain and bucket conveyers can also be used. Two grit chambers in parallel are used to facilitate maintenance. Typical design details for aerated grit chamber are provided below (Metcalf and Eddy, 2003): Depth : 2 to 5 m Length : 7.5 to 20 m Width : 2.5 to 7.0 m Width to depth ratio: 1:1 to 5:1 Detention time at peak flow: 2 to 5 min (3 minutes typical) Air supply m 3 /m.min of length : 0.15 to 0.45 (0.3 typical) Figure 15.6 Aerated grit chamber (first figure showing the helical flow pattern of the wastewater in grit chamber and second showing cross section of grit chamber) Example : 3 Design aerated grit chamber for treatment of sewage with average flow of 60 MLD. Consider the peak factor of 2. Solution: 1. Average flow = 60 MLD = 0.694 m 3 /sec, and Peak flow = 0.694 x 2.0 = 1.389 m 3 /sec 2. Volume of grit chamber Provide two chambers to facilitate periodic cleaning and maintenance

5 Provide detention time = 3.0 m Volume of each tank = 1.389 x 3 x 60 /2 = 125.01 m 3 3. Dimensions of aeration basin: Provide depth to width ratio of 1: 1.2 Provide depth = 3.0 m, hence width = 1.2 x 3.0 = 3.6 m Length = 125.01 / (3 x 3.6) = 11.575 m Increase length by 20% to account for inlet and outlet conditions. Total length = 11.575 x 1.2 = 13.89 m. 4. Determine the air-supply requirement Consider 0.3 m 3 /min.m of length air supply Air Requirement = 13.89 x 0.3 = 4.17 m 3 /min Provide air swing arrangement at 0.5 m from floor 5. Quantity of grit : Consider grit collection 0.015 m 3 /10 3 m 3 Volume of grit = 1.389 x 60 x 60 x 24 x 0.015 x 10-3 = 1.8 m 3 /d 6. Check for surface overflow rate (SOR) The settling velocity of the smallest particle = 2.4 cm/sec, the actual SOR in the grit chamber = 1.389 / (2 x 3.6 x 11.575) = 0.0167 m/s = 1.67 cm/sec, which is less than the settling velocity of the smallest particle hence design is safe. 15.8 Vortex-Type Grit Chamber These types of grit chambers are used in small plants and these require lesser area as compared to earlier types. In this grit is removed with vortex flow pattern. The wastewater enters tangentially and exit in the perpendicular direction of motion either from top or from side. Due to inertia the grit particle will remain in the chamber and liquid free from grit will only escape. The rotating turbine maintains constant velocity and helps in separating organic matter and grit. The centrifugal force on the grit particle can also be maintained without turbine by properly introducing wastewater in the tangential direction in the chamber. Toroidal flow path is followed by the grit particles due to action of propeller (Metcalf and Eddy, 2003). Grit particle settles by the action of gravity into hopper from where it is removed by a grit pump or air lift pump. Washed grit, free from the organic matter, can be obtained from this device.

6 Questions 1. Why separate grit chamber is provided in sewage treatment plant? 2. Describe different types of grit chambers. 3. Describe square grit chamber. Design a rectangular grit chamber and square grit chamber for treatment of sewage with average flow of 8.5 MLD and peak flow factor of 2.25. 4. Prepare notes on vortex type grit chamber.