ENERGY BLADE 3K4. Energy Blade Installation Instructions

Similar documents
Installation and commissioning instructions 255 series and 256 series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

System Pressure Manager Standard & System Pressure Manager Plus

Float Operated Level Controllers

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

POP Safety Valve. POP Safety Valve INTRODUCTION DEFINITIONS

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

Installation, Operation and Maintenance Instructions Buffer Vessel OM006

Mainsboost Installation, Operation & Maintenance Instructions

Pressure Independent Control Series

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

776 Cryogenic Safety Valve

30T A/Manual Hydraulic Shop Press

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

Mounting and Operating Instructions EB 3007 EN. Self-operated Pressure Regulators. Differential Pressure Regulators (opening) Type Type 42-25

BS Series Basket Strainer

Manual Actuated Boiler Blowdown Valves

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

DS MB, MBF THREE PORT VALVES

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

Summary of the MRA LPG Codes of Practice

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

DC5A. Cyclone Separator Trap for Air. Copyright 2015 by TLV Co., Ltd. All rights reserved ISO 9001/ ISO MA-03 (DC5A) 19 June 2015

TITAN FLOW CONTROL, INC.

Two-port valves, male threaded, PN25

Regulator for 2 MPa ARX 20. How to Order. Bracket. Pressure gauge. Port size 1/8 1/4. Panel nut

OPERATING INSTRUCTIONS AND PARTS LIST FOR ELECTRIC VAPOURISERS TYPES ADCENG 200E/250E

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES

New AQF Filter Polymer Filtration System

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

553 Series.

HANDBOOK SAFETY DEVICES. Ed SAFETY DEVICES DS-ED 01/ ENG 1

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

Automatic Non-freeze Valve NF6

THE BP-690 SERIES. Operating and Service Manual. Series includes all variants of BP-LF/MF-690/691

BLADDER TANK PROPORTIONING SYSTEM PRE-PIPED

Tri-Tech Medical Inc.

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

ambiente Installation Guide AmbiScreedboard system more than underfloor Customer: Project: Project Reference: Date:

DS MZ, MZF, MJF THREE-PORT SEAT VALVES

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

PO Box 370 Phone: Swansea NSW 2281 Fax: AUSTRALIA Mobile: Web:

M03 WUNDATRADE. Heat Pump Manifold. Before you start: Check the contents. Optional. ...a division of WUNDA GROUP PLC

BIMBAR INFLATABLE PACKERS AND ACCESSORIES

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

Unit 24: Applications of Pneumatics and Hydraulics

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

PCS 340 Core Saturator : 115 Volt : 230 Volt. Instruction Manual

GI Series Diaphragm Pressure Gauge Guard

Instruction Manual Updated 7/26/2011 Ver. 2.2

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

2-port seat valves PN25 with externally threaded connections

CHEMICAL INDUCTION KIT (Pt.No Issue 6, October 2015)

PRESSURE TEST PUMP OPERATING & MAINTENANCE INSTRUCTIONS. Model No: PTP100. Part No: GC01/09

WHEATLEY Series 500 Swing Check Valve

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

1. Preface Important Safety Notes Brief Product Information Product Working Principle Installation Guidelines...

MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection

Horizontal Bladder Tanks

HYDROVEX TTT Membrane Flow Regulator

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

WHEATLEY Series 822/820 Swing Check Valve

TP1 and TP2 Temporary Cone Shaped Strainers

Instruction Manual LIMITED 1 YEAR WARRANTY. Hydraulic Punch Driver Read this material before using this product.

Vertical Bladder Tanks

Model MTB-ASME Vertical Bladder Tanks

Installation, commissioning and servicing instructions

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats

Tentec. Instruction Document. Mini Air Driven Pump Unit Model: HTT.627X Series. Part Identifier

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

Model MTB-ASME Vertical Bladder Tanks

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

G96 Series BASOTROL Dual Operator Valve

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

WATER MADE EASY MARINE ENERGY MUNICIPAL INDUSTRIAL

INSTALLATION INSTRUCTIONS Non-Pressurized Tank. Non-Pressurized Tank Part Number: AFCG1PT

Spiratec ST14, ST16 and ST17 Sensor Chambers and sensors

Vacuum Saving Valve Series ZP2V How to Order ZP2V A5 03 Connection thread symbol for the pad Male thread connection Symbol Thread Applicable fixed ori

AYLESBURY 'KB' TYPE FLOAT VALVES

Inflatable Packer Single & Double. Single & Double Packer Dimension. Wireline Packer. Water Testing Packer (WTP) Packer

Model C Pipe Line Strainer 6, 8 & 10 Inch (DN150, DN200 & DN250) 250 psi (17,2) General Description. Technical Data. Page of 6 MAY, 2006 TFP1644

PV4 and PV6 Piston Valves

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Models: C62/63/64-A/D

SSFU SUPER SPRAYFAST UNIVERSAL ADHESIVE APPLICATOR

LV LOADER DIRECTIONAL CONTROL VALVES INSTALLATION & USER GUIDE

Related Products: Auto Drain Valve. Model/Specifications. Model

Engineering Data Sheet

3" UC Ultra-Chuck Durable Lightweight Air Inflated Bladder Chuck Operation/Repair Manual. (76.2 mm) DOUBLE E COMPANY, INC.

Permanent Roof Anchors

75 Ton SD Shop Press Operating Instructions

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Transcription:

ENERGY BLADE 3K4 Energy Blade Installation Instructions 1

Contents General information 2 Scope of these instructions 2 Product information 2 Designated use 3 Warranty 3 Safety instructions 4 Assembly and installation 5 Positioning 5 Connections 6 Connecting multiple Energy Blade units 7 Filling and flushing 8 Design and Commissioning 8 Design conditions 8 Commissioning 9 Pressure loss vs Flow rate 10 Technical Data 12 General information Carefully read these instructions before installation and commissioning. Save these instructions for future reference. Scope of these instructions These instructions describe the function, installation and filling of Energy Blades for use in a closed loop, water collector, ground source heat pump installation and commissioning. Other components of a heat pump system such as the circulation pumps, pipe, fittings and valves, heat pumps, operating heat transfer fluids, and buffer tanks are required to make the complete system. They are not described in this manual and the instructions for these other components should be observed. Due skill and care is required to design the complete system of which an Energy Blade is just a part. These instructions are intended for specialist system installers. Product information The Energy Blade is a stainless steel, water-immersible heat exchanger specifically intended for use in closed-loop ground-source heat pumps systems. It is used for transferring energy from rivers, streams, lakes or ponds to the heat transfer fluid (glycol, anti-freeze) used by ground source heat pumps. 2

Designated use The Energy Blade may only be used as specified in this manual. Improper use invalidates warranty claims. Do not over-tighten the connections to the Energy Blade. When tightening fittings and connections always use two wrenches, one on the fitting and the other to counteract the torque applied to the fitting. Energy Blades must be installed submerged in a body of water with the individual plates vertical and the manifold at the top. Energy Blades may stand on the floor of the river or lake. In this case they must be supported above the silt or mud on skids, a frame structure, or on legs or by other means. Energy Blades may also be hung from a mounting frame or other structure such as a pier or jetty as described in this manual. They must be secured and protected suitably for the conditions. The body of water must be large enough to supply the energy loads required. Energy Blades are made from 304 stainless steel and are only suitable for fresh water applications. The glycol used should be non-toxic. We recommend propylene glycols such as Sentinel R500. Warranty Energy Blades are thoroughly tested as part of the manufacturing process. Any defect discovered on delivery must be reported immediately to your supplier to arrange replacement. Once installed Energy Blades are warranted against manufacturing defects for 1 year from invoice date provided the Energy Blades have been installed by professional installers in accordance with guidance and installation manuals, and the original purchase cost has been paid in full. Claims under this warranty must be made within 7 days of discovery of the defect or failure. The warranty does not cover: Damage in transit, storage or installation Damage in use by objects in the water Fair wear-and-tear, wilful damage, negligence, or abnormal working conditions Alterations or repairs without the supplier s prior written permission Failure to install and use according to these instructions The warranty does not cover the cost of shipping, dismantling or reconstruction in the place of installation. Statutory rights of a buyer acting as a consumer are not affected. 3

Safety instructions The design, installation and commissioning of heat pump systems incorporating Energy Blades requires a range of skills and competencies. In the UK the Microgeneration Certification Scheme (MCS) provides a certification framework that certifies organisations competent to install these systems. The following must be observed during installation and commissioning: Relevant local and national regulations Accident prevention and health and safety of employees and the public Instructions and safety precautions in this manual WARNING: Energy Blades weigh about 85kg when empty. Suitable equipment and qualified staff should be used to handle and install them. WARNING: Personal injury and damage may be caused by over pressure. Energy blades are pressure tested to pressures greater than 10 bar. They should not be pressurised by fluids to levels greater than the maximum working pressure specified in this manual. The system should be protected by suitable pressure relief valves. Energy Blades should never be pressurised by air. NOTICE: Care should be taken to store and carry Energy Blades keeping the blades vertical. Failure to observe this and the application of excessive loads and twisting forces should be avoided when handling the device and will invalidate the warranty. NOTICE: Energy Blades should only be filled with aqueous solutions of glycol as specified in this manual. Filling with other substances will invalidate the warranty. Use of glycols of a lower percentage may lead to freezing in some circumstances and prejudice the system performance and damage components. Use of glycols of a higher percentage than recommended will increase the pressure loss at a given flow rate and may adversely affect the system performance or require redesign of the circulation pump. 4

Assembly and installation Positioning The plates can be stood horizontally on the floor of the lake, pond or river with the blades vertical and the manifold at the top. The unit should rest on a suitable skid made of stainless steel or wood to lift the plates off the surface of the lake/river and to stop them from sinking into the silt. The unit may also be hung from a supporting structure made of steel, wood or another material that will not cause corrosion of the plates. Hangers from the support structure may be bolted to the 8mm holes on the edge of the plates. The load should be shared between at least 8 supporting holes. The Energy Blades are not designed to support additional loads other than their own weight and the fluid content. Additional weight loads should not be imposed. Care should be taken to avoid twisting or wrenching the manifold connections during installation. In fast flowing water care should be taken to ensure that the Energy Blades are anchored so that they will not be displaced. It may also be necessary to protect Energy Blades from debris being washed downstream. Energy Blades are suitable for use in fresh water. They should not be used in brackish water, sea water or other corrosive environments. Energy Blades are intended to be used and will perform best when fully submerged in water. Accumulation of silt, weed or debris will adversely affect the performance. We recommend Energy Blades should be inspected periodically so that silt and debris can be cleared. We recommend an annual check and clearance wherever possible. 5

Connection diragram Circulation pump Heating circuit Heat pump A B Energy Blades Connections The flow connection from the heat pump must be connected to the manifold side A (see diagram). This connects to the lower fluid path on the plates. The return connection to the heat pump must be connected to the manifold side B (see diagram). This connects to the upper fluid path on the plates. The flow connection and the return connection must come from opposite ends of the manifold (See diagram). Unused tails of the manifold should be sealed with end-stops. Two flow connections and two return connections are provided to give flexibility in connection and to enable cascading multiple units. The limit on the number of units that can be cascaded is the pressure drop. Two units may be a suitable limit. Fittings for connections should be in brass or stainless steel. We recommend steel or brass to plastic adaptors before continuing the flow and return pipe work in MDPE plastic pipe of a diameter suitable to support the flow rate. Air-vents should be connected in the threaded holes. If the manifold will be submerged these should not be automatic air-vents. 6

Connecting multiple Energy Blade units Diagrams below show some options for connecting multiple Energy Blades. Preferred method for connecting two Energy Blades Connecting four or more Energy Blades with reverse return Alternate method for connecting two Energy Blades 7

Filling and flushing The system can be filled and flushed either before or after positioning. Where the manifold will be submerged, it is preferable to flush the system before it is submerged so that air vents can be used to clear accumulated air. Provided the connections have been made as described above and the Energy Blades are installed horizontally, flushing the system of air is normally a straightforward process of circulating the operating fluid until the air is purged. The system should be filled to a static pressure of 1 to 1.5 bar. In any case the maximum design pressure of the system should not exceed the maximum rated pressure of the Energy Blade. As with any pressurised hydraulic system suitable expansion vessels and pressure relief valves according to applicable regulations should be included in the design. Design and Commissioning Design conditions A single Energy Blade (set of four) has been designed to run with a flow rate of 1.2 l/s to give a design flow-return temperature spread of around 3 o C and an acceptable pressure loss when using 25% by volume propylene glycol. The actual temperature spread at this flow rate will depend on the capacity of the heat pump that is attached. If a lower or higher flow rate is achieved in practice, the flow-return spread will vary. The performance of the system will not be substantially affected provided the range of flow rates does not fall much below 0.9 l/s. If it exceeds the design value the main effect will be to increase the pressure drop in the system, possibly requiring a larger circulation pump. For two Energy Blades connected in series the flow rates should be doubled. Energy Blades can be combined with other types of heat collector such as boreholes or horizontal ground loops. Designing the hydraulic system to ensure a balanced flow through each collector requires suitable design and techniques for measurement and commissioning. 8

Commissioning Commissioning an Energy Blade system consists of ensuring that: Air is flushed from the system The system holds pressure Pressure relief valves are installed and function Suitable expansion vessels are installed and have been set to the correct pressure When the system is switched on the flow rate in the Energy Blades can be measured. If that is not possible the flow and return temperature spread should be checked to make sure it is in the expected design range. If the spread is lower than required the pump speed should be increased or the pressure losses in the system are too high. The temperature of the heat transfer fluid flowing from the heat pump to the Energy Blade should exceed 0 o C at all times even when the water temperature is at its minimum. This is a requirement of current MCS installation standards. If the return temperature is too low, the system is extracting too much energy given the water flow conditions. Remedial action is to reduce the energy demand or to increase the number of Energy Blades or other heat collectors in the system. 9

Pressure loss vs Flow rate Propylene Glycol R500, 25% aqueous solution by volume at 20 o C 10

Notes 11

Technical Data Dimensions Length 3000 mm Width 785 mm Blade spacing 200 mm Blade height 492 mm Assembly height 603 mm Pipe connections 1 ½ BSP (male) Air vent fittings 3/8 BSP (female) Approximate liquid volume 35 l Heat exchange surface area (approx) 11.8 m 2 Heat transfer coefficient 200-400 W/m 2 /K Heat transfer to glycol based on water flow conditions Standing 8kW Typical 15kW Fast flowing 20kW Operating data Maximum permissible pressure 6 bar Maximum temperature 95 o C Minimum temperature -10 o C Maximum glycol concentration 50% Minimum glycol concentration Recommended flow rate Pressure drop at recommended flow rate (25% propylene glycol at 1.2 l/s) To avoid freezing 1.2 l/s < 25kPa Equipment Mounting holes Φ 8mm Materials Stainless steel 3042B 18 gauge Empty weight (approx) Propylene glycol: 25% recommended Ethylene glycols at similar concentration are also useable 85 kg Sentinel R500C or other equivalent Depends on water flow conditions 12