Powers Controls D Day-Night Thermostats

Similar documents
RC 195 Receiver-Controller

Powers Controls RC 195 Single Input Receiver-Controller

Powers Controls RC 195 Multiple Input Receiver- Controller

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

P-5215 Differential Pressure Transmitter

DS06D,G Dial Set Pressure Regulating Valve

Model: 43T. Bermad Pressure Relief Valve

Float Operated Level Controllers

Reset Volume Controller 2 Reversing Relay 3 Air Valve Actuator 4 Lower-of-Two-Pressures Relay 4 Diverting Relay 5 Higher-of-Two-Pressures Relay 5

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Model 130M Pneumatic Controller

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING

EXH. Specifications. Descriptions. Min. working pressure MPa

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING

SINORIX Valve Reconditioning

DS05C,D,G Dial Set Pressure Regulating Valves

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

3/8" Dr. Air Butterfly Impact Wrench

PNEUMATIC PRESSURE CONTROLLERS

TEST SPECIFICATION NYT-909-C

D05 Pressure Regulating Valves

RG1200 Service and Repair Manual

V43 Pressure Actuated Water Regulating Valve

2 in. 18 Gauge Brad Nailer. User manual

CTC 1000 Series One-Pipe, Pneumatic Room Thermostat, Single Temperature

SERVICE MANUAL No. I-0043

Bermad Pressure Reducing. Model: 42T

Pressure Independent Control Series

Pressure Dump Valve Service Kit for Series 3000 Units

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

Series K Air service units G 1/8, G 1/4

Instruction Manual Updated 7/26/2011 Ver. 2.2

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

accidents which arise due to non-observance of these instructions and the safety information herein. SPECIFICATIONS

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

CUT OFF TOOL MODEL: CAT113

Model Series 62 Constant Differential Relay

Budget Range Operators Handbook

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Maximum 0.85 MPa pressure setting Long-life, high flow perfect for balancer applications

Pressure Dump Valve Service Kit for Series 2300 Units

Air service units series K G1/8, G1/4

1650EXLT, ,

4150K and 4160K Series Wizard II Pressure Controllers and Transmitters

TWO POST RAM PACKAGE 5 GALLON READ THIS MANUAL CAREFULLY BEFORE INSTALLING, OPERATING OR SERVICING THIS EQUIPMENT.

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

64 Series Pressure Reducing Regulators

Installation and User Manual

Vibration isolation system 1VIS10W. User manual

P14 Series Pressure Actuated Mechanical Sequencer

D05T Compact Design Pressure Regulating Valves

TECHNICAL INSTRUCTIONS

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

GX200 QX2 ENGINE, JPN, VIN# GCAE Page 1 of 34 AIR CLEANER (DUAL)

CRYOGENIC TANK SERVICES - CHART RECORDER MANUAL

Installation, Operation, and Maintenance Manual

Model 4000 Pressure Controller

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

ATV 90 Y-12 YOUTH 2-STROKE RED (A2004ATB2BUSR) Page 1 of 52 A-ARM, FLOOR PANEL, AND BUMPER ASSEMBLY

Replaces Lesco 300 & 500 Parts

Techcon Systems TS1254 Pressure Pot

ALE-32. Miniature General Purpose Regulators R07, R46 (non-repairable) Air line equipment. Technical data

TECHNICAL DATA. Page 1 of 12

4 ANGLE GRINDER MODEL NO: CAT 52 PART

200 PSI FAST-FILL AIR SOURCE KIT

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

AIR COMPRESSOR OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: CHAMP 3 PART NO: LS0115

MEGR-1912 Instruction Manual

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

Index Table. Model 794. Installation, Operating and Maintenance Instructions

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

accidents which arise due to non-observance of these instructions and the safety information herein. SPECIFICATIONS

GT20 String Trimmer UT Page 1 of 16 Accessories

VACUUM REGULATORS CONTENTS

450P- RV AUTOMATIC PORTABLE COMPRESSOR EXTREME SERIES

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

RARS5000 AIR BODY SAW OWNER S OPERATING MANUAL

Part No (Low Changeover) Part No (High Changeover) Part No (High Changeover)

Air Operated Hydraulic Pumping Systems to 50,000 psi

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

TECHNICAL DATA. Q = C v P S

TWO POST RAM PACKAGE 55 GALLON

7130 Lancer Rear Drive Magnetic Commercial Indoor Cycling Bike

Operating Instructions Model and Hydrostatic Test Pump

55DEHD 07 (63S5) 1F63S-561E1

OPERATING AND MAINTENANCE MANUAL

Beamex PG PRESSURE GENERATORS. Beamex PGM PGV PGC PGHH PGPH PGL

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Suggested Installation & Operating Instructions for Sidewinder Pumps

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

2.5 & 5.0 GALLON PRESSURE TANKS

accidents which arise due to non-observance of these instructions and the safety information herein.

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

WW-730. Pressure Sustaining/Relief Control Valve

REPAIR PART NUMBER NUMBER DESCRIPTION 0137 ELE 0136 ELE 12 VOLT SOLENOID

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

200 PSI HIGH-FLOW AIR SOURCE KIT

Transcription:

Powers Controls D Day-Night Thermostats Technical Instructions Document No. 155-073P25 TH 832-2 Description The D Day-Night or Two Temperature Thermostat is available as a room-type instrument. It is essentially two thermostats incorporated into one unit: The day setting controls when the supply pressure is 18 psi (124 kpa) and the night setting controls when the supply pressure is 25 psi (172 kpa). This thermostat is available with remote changeover of the supply air pressure. A manual reset lever is provided to allow any individual thermostat to control at its normal day setting while the balance of the system is operating on night control. Also, this manual reset lever can be moved to permit this particular thermostat to be reset to return it to night operation. When the system is changed back to day operation, all thermostats revert to automatic changeover. Application The D day-night Thermostat with remote changeover is recommended for temperature control of radiation, mixing dampers or unit ventilators in schools, residences, offices and hospitals. It is particularly applicable where all rooms or offices in a zone are vacated at approximately the same time and a lower control temperature is desired at night. Changeover from day to night and vice versa (see Operation) can be obtained by means of a zone "day-night" selector switch or by use of a program clock. The program clock will automatically set all thermostats for day operation at a selected hour in the morning and automatically change the system to night operation at some predetermined hour in the evening. Product Numbers Table 1. Product Number Description 832-1120 Key Set Point Adjustment with Thermometer 832-1140 Concealed Set Point Adjustment with Thermometer

Technical Instructions Document Number 155-073P25 D Day-Night Thermostats Specifications Typical Specifications Control Action Direct Acting Operating Range Day 60 to 80 F (15 to 26 C) Night 50 to 70 F (10 to 21 C) Operating Pressure 30 psi (206.8 kpa) Max. Sensitivity Fixed 2.5 psi per F (31.0 kpa per C) Temperature Response 0.5 F (0.3 C) Maximum Ambient Temperature 125 F (51.5 C) Dial Graduations (Day & Night) 2 F (1.1 c) Normal Air Supply Pressure Day 18 psi (124.1 kpa) Night 25 psi (172.4 kpa) Dimensions 2-7/8" x 5-5/8" x 2-3/16" deep (73 mm x 143 mm x 56 mm) Weight 5 lbs. (2.3 kg) Cover Style Key or Concealed Set Point Adjustment Cover Finish Silver is standard (other finishes on special order). All day-night thermostats shall be equipped with a volatile liquid type sensing element, shall be capable of operating on a change of plus or minus 1/2 F, (0.3 C) and shall be of the gradual type capable of positioning valves or dampers in intermediate positions. Day-night thermostats shall be of the non-bleed type so that no air shall be used except when positioning a valve or damper motor. Day-night thermostats shall be provided with two dials: on the day cycle the range shall be adjustable from 60 to 80 F (15 to 26 C); on the night cycle from 50 to 70 F (10 to 21 C). Changeover from day temperature to night temperature shall be accomplished pneumatically by remote change of the supply pressure. A manual reset lever shall be provided to allow any individual thermostat to control at its normal day setting while the balance of the system is operating on the night setting. This reset lever must also be capable of being manually returned to night setting. Operation (See Figure 1) By use of the special key furnished, the thermostat can be adjusted for desired day operation and for desired night operation. A day setting of from 60 to 80 F (15 to 26 C) or a night adjustment of 50 to 70 F (10 to 21 C) can be obtained. A thermostatic disc is attached to an adjustment lever which pivots on a pin. The action of the disc is controlled by either adjustment post or, depending on whether thermostat is operating on "day" pressure or "night" pressure. With the adjustment lever against the adjustment post, a decrease in temperature causes the thermostatic disc to contract. This moves the control lever and the adjusting screw away from the exhaust valve assembly. The exhaust valve opens and gradually decreases the branch return pressure from the thermostat. This decrease of control pressure opens the valve on the heating supply, or the hot blade of a mixing damper, to satisfy room temperatures. NOTE: When the exhaust valve is open, the supply valve is held closed by the supply valve spring, so that there is no constant waste of air. Page 2

D Day-Night Thermostats Operation, Continued Technical Instructions Document Number 155-073P25 With a rise in room temperature, the thermostatic disc expands forcing the control lever to close the exhaust valve assembly and open the supply valve. Branch return pressure then increases to throttle the heat supply. The air supply port also connects the supply valve chamber to the piston plate diaphragm chamber which acts on the piston plate. When the supply pressure is raised from the day setting of 18 psi (124 kpa) to the night setting of 25 psi, (172 kpa), the piston plate forces the piston plate extension against the adjustment lever. The adjustment lever then pivots and operates from the night adjustment post. Operation on the night setting and day setting is the same except for a different control point. Field Calibration Day setting - System supply pressure 18 psi (124 kpa) 1. Check the day air pressure reducing valve to be sure it is maintaining an 18 psi day pressure. 2. With actual room temperature within 5 F (2.7 C) plus or minus of set point of thermostat, the cover should be removed using the special key enclosed in the thermostat kit. 3. Loosen test screw one complete turn and immediately slip on the rubber tubing of the test gauge assembly. 4. Adjust the day dial to the actual room temperature. The test gauge should then read 7-1/2 psi (51.7 kpa) plus or minus 1-1/2 psi (10.3 kpa). If this is not the case, turn the adjusting post in either direction until it does read approximately 7-1/2 psi (51.7 kpa). Loosen the day dial retaining screw and reset the day temperature dial to the correct room temperature. Retighten dial retainer screw being careful not to change the setting of adjustment post. Be careful not to come in contact with thermostatic disc. Wait several minutes after installing test gauge hose before actually making recalibration. 5. Breathe onto the thermostatic disc and note whether branch pressure increases. If there is no rise in branch pressure, the thermostat is not functioning and should be returned to the factory for replacement. Night Setting - System Pressure 25 psi (172 kpa) 6. Check night air pressure reducing valve to be sure system has 25 psi (172 kpa) air pressure. Room temperature should be within 5 F (2.7 C) plus or minus of the normal night temperature setting of the thermostat. 7. Check adjustment as outlined in Step 4 and reset dial if necessary. Manual Reset - System on 25 psi (172 kpa) Night Operation 8. Set manual reset lever to the right until a "click" is felt. The thermostat is now controlling at the day dial setting. 9. Return system supply pressure to day 18 psi (124 kpa). The manual reset lever should automatically return to the left hand side of day cycle. 10. If the manual reset lever does not return to the left hand side when the supply pressure is 18 psi (124 kpa), the tension of spring will have to be increased by turning the adjustment spring retainer clockwise. About one complete turn of the adjustment spring retainer clockwise will increase the pressure change about 1 psi (7 kpa). For example: If the manual reset lever is returned to the day setting at 17-1/2 psi (120.6 kpa) system pressure, then the spring tension should be increased so that it would switch over at about 18-1/4 psi (125.7 kpa). This would be approximately three-fourths of a complete turn of the adjustment spring retainer. Page 3

Technical Instructions Document Number 155-073P25 D Day-Night Thermostats Manual Reset - System on 25 psi (172 kpa) Night Operation, Continued 11. Apply 25 psi (172 kpa) night supply pressure. Move reset lever to right. Thermostat will now control at day dial setting. Check calibration. 12. Move reset lever back to left. Thermostat will now control at night dial setting. Check calibration. 13. Instrument can now be considered in calibration. Test hose should be removed and test plug screwed in tightly. Replace cover with two cover screws. Bench Calibration General Figure 1. Test Equipment. Figure 2. All references are to the above figures or to Figure 3. Pressure gauges should be accurate to the nearest 1/2 psi (3.4 kpa); the thermometer to the nearest 1/2 F (0.3 C). These instructions to be used only when adequate testing facilities exist. Procedure See Figure 3 1. Obtain and set up test equipment shown in Figure 1. 2. Check thermostat for looseness or binding of parts. 3. See that friction spring (53) is in position. 4. Connect the thermostat to a terminal head. Do not use base plate or cover. 5. Remove both day (47) and night (51) temperature dials. 6. Turn day (high temperature) (48) adjusting post until the distance from the top of the lever bearing plate to the bottom of the dial pinion is 29/64" (11.5 mm) as shown in Figure.2 7. Completely immerse thermostat in 70 F (21 C) water with supply pressure 18 psi (124 kpa). Carefully turn valve adjusting screw (35) until return pressure is 7-1/2 psi (51.7 kpa). Allow several minutes to ensure that entire thermostat has reached this temperature. 8. Place thermostat in 60 F (15 C) water with supply pressure 25 psi (172 kpa). Turn the night (low temperature) adjusting post until return pressure is 7-1/2 psi (51.7 kpa). Page 4

D Day-Night Thermostats Procedure, Continued Technical Instructions Document Number 155-073P25 9. Recheck back at 70 F (12 C) supply pressure 18 psi (124 kpa). Return pressure should be 7-1/2 psi (51.7 kpa) or ± 1-1/2 psi (10.3 kpa). 10. Recheck back at 60 F (15 C) supply pressure 25 psi (172 kpa). Return pressure should be 7-1/2 psi (51.7 kpa) ± 1-1/2 psi (10.3 kpa). 11. If return pressure is not within these limits, check for a faulty disc or rubbing and binding of moving parts. 12. Carefully replace the day and night temperature dials so that the day dial reads 70 F (21 C) and the night dial reads 60 F (15 C). 13. Check changeover pressure as mentioned in item 9, Field Calibration. Page 5

Construction Figure 3. Page 6

Parts Lists (See Figure 3) Item Description Part No. Kit No.* 1 Cover & Grad Plate Assy. For: 832-1120 832-1140 2 Base & Finish Plate Assembly 3 Gasket 838-007 A, B 4 Terminal Head 5 Filter Disc 6 Screw 030-045 A 7 Screw 8 Frame 9 Filter (Screen) 833-078 B 10 Diaphragm 833-025 B 11 Supply Valve Gasket 12 Supply Valve Body 13 Supply Valve Cap 14 Supply Valve Cap Gasket 833-026 B 15 Spring Spacer 16 Supply Valve Spring 837-009 B 17 Exhaust Valve Stem 18 Supply Valve Stem 19 Spring 833-072 B 20 Screw 21 Diaphragm 22 Diaphragm Plate Screw 23 Diaphragm Plate 24 Diaphragm Ring 25 Spring Retainer Support 26 Spring 27 Spring Retainer 28 Screw Item Description Part No. 29 Spring 30 Dial Support 31 Diaphragm Plate Extension 32 Lever Bearing Plate 33 Diaphragm Ring 34 Screw 35 Valve Adjusting Screw 36 Exhaust Valve Body 37 Control Lever 38 Adjustment Lever Assy. 39 Nut 40 Lockwasher 41 Control Lever Pivot Pin 42 Thermal Assembly 43 Seal Screw 44 Test Valve Body 45 Retainer Ring 46 Spring Retainer Support 47 Dial (Day) 48 Adj. Screw & Pinion (Day) 49 Adj. Screw & Pinion (Night) 50 Dial Retainer Screw 51 Dial (Night) 52 Lever Pivot Pin 53 Friction Spr. (0.031 dia) Music Wire 54 Cover Screw (Supplied with Cover) Not Shown Miscellaneous Parts Kit (For mounting to Powerstar Wall Box) 832-180 NOTE: Replacement Kit No. 182-041 consists of thermostat less cover and base. * Included in Kit: A 182-041 B 832-164 Accessories Part Number Service Parts Part Number D Base for Exposed Tubing 832-034 Replacement Unit (Chassis only) 182-041 Adjustment Key 856-055 Exhaust & Supply Valve Repair Kit 832-164 Gym Guard 814-018 Cover Assembly Friction Knob (not in catalog) 833-033 Concealed Adjust Key Adjust 181-054 181-189 Siemens Building Technologies, Inc. Page 7

Dimensions Figure 4. Dimensions. Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Powers is a registered trademark of Product or company names mentioned herein may be the trademarks of their respective owners. 2005 Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com Document No. 155-073P25 Printed in the USA Page 8