Sizing Enclosures for SCR Power Controllers

Similar documents
General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

Lighting Contactors. 4.1 UL Rated AC Contactors

1

Thermal design of APFC Panels

Cooling NI Single-Board RIO Systems Appendix: Reference Examples NI sbrio-9605/6

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus

Environmental Protection of HMI Components

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof

Evaporator (DX) Freon Applications 1 12 Tons MHF

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TechNote FM APPROVAL: HAZARDOUS LOCATION EQUIPMENT CLASSIFICATION

Technical Data Bulletin #221

CUSTOM ENCLOSURE CUTOUTS

Sprockets. Section Contents ROLLER CHAIN DRIVES

IP DEFINITIONS. Technical Notes. Definitions. IPXX Code

Industrial Components Preventive Maintenance, Enclosures, and Contact Ratings Specifications

Liquid Level Measurement

Fuel Filters DN15 DN25. elektrogas.com DE

Niltox Breathing Air Purifier Range

SR500 PAPR Copyright 2015 by The S.E.A. Group 1

Vickers. Filters. Reservoir Vent Filters. Spin-on Air Filters & Adaptors. Rev. 3/98

GLAUNACH THE SILENCER HANDBOOK INSTALLATION GLAUNACH GMBH ALL RIGHTS RESERVED -

TotalPac X Single interlock Preaction system Electric release

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

Hot Tub Pre-Delivery Guide

MODEL NUMBER: P PORTABLE COMPRESSOR

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

V43 Pressure Actuated Water Regulating Valve

Valve Proving System VDK 200 A S02

MAINLINE MLA14 AIR CONDITIONERS

Valve Proving System VDK 200 A S06*

MODEL NUMBER: P PORTABLE COMPRESSOR

G92 Series BASOTROL Automatic Pilot Gas Valve

Oxygen Concentrator. Installation and Operation Manual. ClearWater Tech, LLC. Integrated Ozone Systems

Kansas State University Fume Hood Operation

INGRESS PROTECTION RATIO IP

400C & 450C DUAL PERFORMANCE VALUE PACKS

Right-Angle Tube Roller Model

Model 26.5 WEAU242AA WEAU244BA 29.0 WEAU242BA 29.0 WEAU304AA 33.0 WEAU302AA WEAU304BA 33.0 WEAU302BA 33.

Gas Filters DN15 DN300. delta-elektrogas.com EE151 03/17

C 10 Pressure Reducing Valve

GENERAL APPLICATION NOTES

Standard Operating and Maintenance Instructions for Pumping System Model PS-90

Workhorse-15 Oxygen Generator

CLASS TLP Pressure Reducing Valve

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

INSTRUCTION MANUAL MST AFTERCOOLER SYSTEM MODEL

GEN-1e CO2 Generator OVERVIEW INSTALLATION PROPANE GENERATORS ONLY NATURAL GAS GENERATORS ONLY

) for different types of systems Test of contact function The correct pressure control for your system

LENNOX SLP98UHV DIAGNOSTIC CODES

TECHNICAL DATA. Q = C v P S

AIR CONDITIONERS WA14**W SERIES

PRESSURE DIFFERENTIAL PRODUCTS 2008 TRICO CORPORATION. ALL RIGHTS RESERVED.

CTK Co., Ltd. (Ho-dong) 113, Yejik-ro, Cheoin-gu, Yongin-shi Gyeonggi-do KOREA, REPUBLIC OF Tel: Fax:

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS

F13.11 PARALLEL HINGES F13 PROJECT-OUT WINDOWS AND TOP HUNG WINDOWS

Workhorse 8 Oxygen System Model No 5665, 5673, 5679

COATINGS SPRAY GUIDE Urethane 520

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

Dual Safety Shutoff Valves with Proof of Closure and NEMA 4x Enclosure. DMV-D/624L Series DMV-DLE/624L Series

444C DUAL PERFORMANCE VALUE PACK

Dual Modular Safety shutoff Valves with Proof of Closure and NEMA Type 4x Enclosure DMV-D 704/624 DMV-D 704/634 DMV-DLE 704/624 DMV-DLE 704/634

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Services. Fire Sleeve. by Carol and Brian Carpenter

200 PSI HIGH-FLOW AIR SOURCE KIT

This test shall be carried out on all vehicles equipped with open type traction batteries.

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

COATINGS SPRAY GUIDE Acrylics (210, 211, 211HT, and 212)

CATALOGUE

Summary of Substantive Changes between the 2004 e1 and 2017 editions of ASSE 1011, Hose Connection Vacuum Breakers

100C Air Compressor Kit

AIR CONDITIONERS WA14 SERIES

FIK In-Tank Filters FIK. Max Flow: 170 gpm (643 lpm) Working Pressures to: Rated Static Burst to: Flow Range to:

Residential Swimming pools

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

COATINGS SPRAY GUIDE Fast Set Urethane 530

200 PSI FAST-FILL AIR SOURCE KIT

TFE-LINED VAREA-METER PVC-TUBE VAREA-METER

VMR VMR-OTN VMR 6 bar

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Flow Measurement Equipment Armored Purge Meters

AIR CONDITIONERS. Features. Manufactured for Fujitsu General America, Inc. Fairfield, NJ. FORM NO. AFJ-220 Supersedes Form No.

Dual Modular Safety Shutoff Valves with Two-stage operation. DMV-ZRD/602 Series DMV-ZRDLE/602 Series

CTK Co., Ltd. (Ho-dong) 113, Yejik-ro, Cheoin-gu, Yongin-shi Gyeonggi-do KOREA, REPUBLIC OF Tel: Fax:

Dual Modular Safety Shutoff Valves DMV-D 525/11 DMV-DLE 525/11

GWINNETT COUNTY SWIMMING POOL PLAN REVIEW CHECKLIST

Are you really doing your job if you fail to measure static pressure every time you service a unit? The answer is no.

PPE: RESPIRATORY PROTECTION EQUIPMENT

Inert Air (N2) Systems Manual

Barcol-Air BRM Radiant Module

BGA244 Binary Gas Analyzer

TECHNICAL DATA. Q= Cv S

Pre-filter for Brushless Blower Instruction Manual

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the. IGF Code

MODEL NUMBER: P-A AUTOMATIC PORTABLE COMPRESSOR

Best Practice Guide, Servomex 2700

Models EXN and OLG. General Description. Features and Benefits. Pressurizer for Vertical Air Conditioners Increased Safety for Hazardous Locations

Section 3000 CONVEYOR CHAIN LUBRICATION SCHEMATIC...39 AIR OPERATED SPRAY DISPENSERS - CENTRAL ACRYLIC RESERVOIR Section 3000 Index

Transcription:

INTRODUCTION Application Note 1002 Sizing Enclosures for SCR Power Controllers Author - George A. Sites, AMETEK HDR Power Systems Most applications for SCR Power Controllers require some type of enclosure. This application note is intended to assist you in properly selecting an enclosure, taking into consideration 1. The environment and 2. The type of SCR Power Control. SELECTION CRITERIA The first step in selecting an enclosure is to evaluate the environment. Answers to the following eight questions are essential before a selection can be made properly. 1. What is the maximum ambient temperature where the enclosure will be mounted? 2. Will the enclosure see any reflected heat from any nearby sources? 3. Is there dust, water, oil or other contaminants that may affect the overall operation of the equipment? 4. Is the user installing any additional equipment in the enclosure? 5. Will both sides, top, bottom, front and back be exposed to the air for heat sinking purposes? 6. Are there any objections to forced-air cooling? 7. Is cooling water available if a sealed enclosure is required? 8. Are there any size restrictions? TYPES OF ENCLOSURES Once the above questions are answered, you can select an enclosure type from the following list. NEMA 1 General Purpose used indoors as a safeguard for personal safety, normally where special conditions do not exist. NEMA 1 enclosures may be ventilated. NEMA 2 Drip Proof used indoors where falling, non- corrosive liquids and falling dirt may damage electrical/electronic components. NEMA 3 Dust Tight for outdoor use where protection from wind-blown dust and water is required. NEMA 3R Rain Tight same as NEMA 3, except NEMA 3R enclosures provide equipment protection from rain. They are not dust tight or sleet-resistant. NEMA 4 Watertight and Dust Tight for indoor or outdoor use where splashing or seeping water, falling or hose-directed water and severe external condensation are threats to the electrical/electronic components. NEMA 12 Industrial Use, Dust Tight and Drip Tight used indoors for protection from fibers, dust and dirt, light splashing, seepage, dripping and external condensation of non-corrosive liquids. Note: There are many other types of NEMA enclosures for very special applications but beyond the scope of this paper. Copyright 2003, Republished Dec 2012 1

SIZING THE ENCLOSURE Sizing Enclosures 1 for SCR Power Controllers After selecting the enclosure, you can size it. This requires knowing: 1) the ambient temperature at the installation site; 2) the SCR Power Control dimensions; 3) whether additional equipment will be installed and 4) the maximum allowable equipment operating temperature. Space is always at a premium, so initially select the smallest enclosure that will hold the equipment while allowing proper clearance for mechanical, electrical and thermal considerations. Calculating Power Loss The next step is to calculate the power losses into the enclosure for each piece of equipment mounted. If there is more than one of the same type, multiply the losses by the quantity. When calculating power losses for any HDR power controller, a conservative estimate is given by this formula: Power Loss = Maximum Current x 1.5 x Number of Controlled Legs Enclosure Heat Sinking Capabilities After calculating the power losses, determine the heat sinking capability of the enclosure. Find the square inches of surface area required for the maximum temperature rise allowed in Table 1. Subtract the maximum ambient temperature from the equipment maximum allowable temperature rating to find the maximum temperature rise allowed. The surface area required is the product of the total losses in watts multiplied by the surface area required per watt from Table 1. Now you know the type of enclosure, the estimated size and the surface area. Next, you need to verify the thermal size. In the following example, assumptions are: 1. Only one Power Controller will be mounted in the enclosure (an HDR ZF1-480-120) 2. The external ambient conditions will be 30 C or less 3. There are no restrictions on enclosure size 4. The enclosure will be mounted on a wall, which allows the top, bottom, two sides and the front for heat dissipation 5. A dust-tight and drip-tight enclosure is desired and 6. The actual full load current is 110 amperes. Example #1 Based on the above assumptions, the procedure for selecting the appropriate enclosure is as follows. 1. Select the enclosure type from the list. The correct enclosure is NEMA 12. 2. Select the physical dimensions of the enclosure. The AMETEK HDR Power Control has dimensions of 15"H x 11"W x 10"D. Based on experience, the first pick for an enclosure size will be 30"H x 24"W x 12"D. This allows 7.5" clearance top and bottom, and 6.5" clearance on each side. This is ample room for the power controller to fit and leaves plenty of room for wiring. Copyright 2003, Republished Dec 2012 2

Sizing Enclosures 1 for SCR Power Controllers 3. Calculate the power losses. Loss = 110 x 1.5 x 1 Loss = 165 watts 4. Calculate the required surface area. The maximum ambient temperature is 30 C and the power controller s maximum operating temperature is 50 C; therefore, you can allow for a 20 C temperature rise. From Table 1, 9.2 sq. in of surface area are needed to dissipate each watt of power. Required Surface Area = 9.2 x 165 Required Surface Area = 1518 square inches MAXIMUM ALLOWABLE TEMPERATURE RISE SURFACE AREA REQUIRED SQ. IN. / WATT MAXIMUM WATTS SQ. IN. 10 C 0.054 18.4 20 C 0.108 9.2 30 C 0.103 6.1 40 C 0.218 4.6 50 C 0.260 3.8 TABLE 1 ENCLOSURE HEAT SINK VARIABLES 5. Calculate the available enclosure surface area using the top, bottom, both sides and the front for heat dissipation Front: 30 x 24 = 720 Top: 24 x 12 = 288 Bottom: 24 x 12 = 288 Two Sides: 30 x 12 x 2 = 720 Total = 2016 square inches available Since 2016 sq. in. are available and 1518 sq. inches are required, the calculations show that the available surface area is greater than the required surface area. This situation indicates a good thermal design and the power controller will operate at 100% duty cycle at full current. Fan Cooling If the enclosure had not been large enough, the next size enclosure would be selected and the calculations reworked. If the application had required a smaller enclosure and allowed forced-air cooling, you would perform all of the previous calculations plus determine the air flow (CFM) requirements using chart 1. If a fan is required, and the enclosure size is already determined, calculate the heat dissipation of the enclosure based on Table 1 using the Maximum Watts/Sq. In. column. Simply determine the surface area of the enclosure and multiply by the watts/sq. in. number based on the maximum allowable temperature rise. Copyright 2003, Republished Dec 2012 3

Sizing Enclosures 1 for SCR Power Controllers Next calculate the maximum power generated by the power controller and subtract the enclosure power dissipation from the power controller dissipation. This is the total watts that must be removed by the fan. Refer to chart 1 to determine the fan size. Sample calculations for this procedure are shown in example #2. Example #2 In this second example, the assumptions are: 1) One power controller will be mounted in the enclosure (an HDR ZF2-480-225), 2) All other conditions are the same as the previous example except the actual full load is 215A. Under these conditions, selecting the proper enclosure is as follows. 1. Select the type of enclosure. Once again the proper choice is a NEMA 12. 2. Determine enclosure dimensions. The power controls dimensions are 15"H x 14"W x 10"D. Using the previous NEMA 12 sized 30"H x 24"W x 12"D allows about 7.5" clearance top and bottom and 5" on the sides for mechanical and electrical considerations. 3. Calculate the power losses. Loss = 215 x 1.5 x 2 Loss = 645 watts 4. Calculate the required surface area. Required Surface Area = 9.2 x 645 Required Surface Area = 5934 square inches 5. Calculate the enclosure s surface area. The calculations are the same as the previous example - 2016 square inches. Since 2016 square inches are available but 5934 square inches are required, a fan is required! 6. Determine the watts the enclosure will dissipate (use table 1). Enclosure Dissipation = 2016 x.108 Enclosure Dissipation = 218 watts 7. Calculate the watts the fan must remove. Remaining Watts = 645-218 Remaining Watts = 427 watts 8. Select the fan. Copyright 2003, Republished Dec 2012 4

Watts Sizing Enclosures 1 for SCR Power Controllers Using the fan requirement chart, note that removing 427 watts requires a 40 cfm fan. To extend the applicability of this chart if the power dissipation is higher than the range shown, multiply both the vertical and horizontal numbers by the same factor. 5000 4500 4000 3500 3000 2500 2000 1500 1000 500 0 0 TR = 25 C TR = 20 C TR = 15 C TR = 10 C TR = 5 C 50 100 150 200 250 300 350 400 450 500 Air Flow (cfm) CHART 1 Fan Requirements There are many other ways to cool electrical equipment enclosures. Included are air-to-air heat exchangers, direct water cooling, air-to-water heat exchangers and venturi tubes just to name a few. These are usually used on equipment installed in dirty installations where it is extremely important to keep the enclosure sealed such as in a steel foundry. Note: this application note originally appeared in the May 1991 issue of Industrial Heating magazine Copyright 2003, Republished Dec 2012 5