PT-500 Modbus Series User Manual APG

Similar documents
PT-400 User Manual APG

PT-400 User Manual APG

APG. Intrinsically Safe, Heavy Duty Pressure Transducer Series: PT-400

High-performance submersible pressure transmitter For level measurement Model LH-10

Deep Submersible Level Transducer Series 300DS

! Unique Cable Seal System! Fully Temperature Compensated! Datalogger Compatible

Modbus Submersible Level Transducer

High-performance submersible pressure transmitter For level measurement Model LH-10

SDX Submersible Depth Transmitter User Manual

T EK-SUB 4800C 19 mm Submersible Level Transmitter

ASIC-Based Small Bore Submersible Level Transducer

Type N-10, N-11 Hazardous Area Non-incendive Transmitters

EcoPRO-Series 4-20mA SUBMERSIBLE PRESSURE TRANSMITTER INSTRUCTIONS

FTS SUBMERSIBLE PRESSURE TRANSMITTER USER S MANUAL

TEK-SUB 4800B. Submersible Level Transmitter. Flow Level Temperature Pressure Valves Analyzers Accessories TekValSys LEVEL

SDX Submersible Depth Transmitter User Manual

Installation and Operation Manual

DeltaSpan Pressure Transmitters LD10 Series Owner s Manual

ETd 04. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. Type: ETd 04. class 0.05

86BSD Backside Digital Output

DM01. Please visit our website: Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

IDL01. Battery Powered Precision Digital Gauge for Leak Testing. Stainless Steel Sensor. class 0.05

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

DeltaSpan General Purpose Water Small Bore or Wastewater Pressure Level Transmitter LD34 and LD35 Series Manual

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

CSA Sample Draw Aspirator Adapter Operator s Manual

DM01. Battery Powered Precision Digital Gauge. Stainless Steel Sensor. class 0.05

For a similar sensor with o-ring mounting, refer to the 85BSD digital output pressure sensor.

PRESSURE COMPARATOR 10000PSI 700bar. Operator Instructions CRYSTAL. engineering corporation

HAYWARD FLOW CONTROL TFS SERIES FLOW METER INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

OPTIBAR P 1010 C Technical Datasheet

DPC-30 DPC-100. Reference Manual

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

AMS 2710 PCB pressure sensor module with V output

3.0 Pressure Transmitter Selection

AUTO PUMP STATUS CENTER

Flowline, Inc Humbolt Street Los Alamitos, CA Tel: (562) Fax: (562) Rev B MN of 16

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

ASDX Series Silicon Pressure Sensors

Gas Pressure Probe. Information Sheet. Total Dissolved Gas

L (up to 25 m) Electronic part. working temp.: Ñ IP 66 / IP67. Mounting bracket ÐÑ. Sensor type. working temp.:

Dynisco SPX Industrial (2280/2281) Series

GG-VL2-NH3 AMMONIA VENT LINE SENSOR. Installation and Operation Manual

DTG - LCD Digital Temperature Gauge USER MANUAL

P499 Heavy Duty Pressure Transducer

OPERATION AND INSTRUCTION MANUAL

EPRB-2 Pressure Transducer

GASGUARD VENT LINE3 Ammonia Sensor OPERATING & INSTALLATION MANUAL

P9000 DESCRIPTION. For parts requiring RoHS compliance, please contact factory. P February /6

Depth/Level. Druck Submersible Pressure Sensors Product Guide. GE Sensing. Applications. Features

NOVALYNX CORPORATION MODEL BAROMETRIC PRESSURE SENSOR PCB MODEL BAROMETRIC PRESSURE SENSOR IN NEMA ENCLOSURE INSTRUCTION MANUAL

Media-Isolated Mag Plus Probe Low Pressure-ISO Kit

HAYWARD FLOW CONTROL Series PBV Back Pressure Valve and Series RPV Pressure Relief Valve INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

2600T Series Pressure Transmitter Models 264DC Differential and 264HC Gage Level Transmitters. Kent-Taylor

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel:

210 Series Transmitter with External Electrochemical Sensor

KTE6000 / KTU6000 Series OEM pressure transmitters for industrial media

AMS 6916 Board mount pressure sensor with ratiometric analog output

Mini-Pro CO2 Sensor User s Manual - ANALOG MODEL -

Float Operated Level Controllers

AMS 6915 Board mount pressure sensor with digital output (I²C)

Advanced Test Equipment Rentals ATEC (2832)

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER FILTER DRYER

GasSense NDIR User Manual

RGC-IR Remote Gas Calibrator for IR400

PX3005. Rangeable Industrial Pressure Transmitter M-5721/1018

OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: SWY100N

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

GILMONT ACCUCAL FLOWMETERS

RK-IR Sample Draw Aspirator Adapter Operator s Manual

DFB FLOW METERS (DESIGNED FOR BLENDERS, DUAL TAPER)

INSTALLATION & MAINTENANCE INSTRUCTIONS

HAYWARD FLOW CONTROL FLV SERIES, PVC/CPVC FILTER VESSEL INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20

LJ1-25 LouieJRtm Tapping Machine

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

P900. P900, Datenblatt Seite 1 DESCRIPTION

OPERATION AND INSTRUCTION MANUAL Swivel Anchor Model: HD26248

RK LEL Sample Draw Aspirator Adapter Operator s Manual

SC HYDRAULIC ENGINEERING CORPORATION

PRESSURE SENSOR - ABSOLUTE (0 TO 700 kpa)

High-performance submersible pressure transmitter For level measurement Model LH-20

OPERATION AND INSTRUCTION MANUAL

HLM-2000-TX Gas Transmitter User Manual

High-performance submersible pressure transmitter For level measurement Model LH-20

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers

Sensoric 4-20 ma Transmitter Board Operation Manual

High-speed pressure sensor Model CPT6140

SDI mA Pressure Transducer (Submersible + Dry) Model WL2100 Operating Manual

60 farm jack. Distributed exclusively by Harbor Freight Tools Mission Oaks Blvd., Camarillo, CA 93011

TRANSDUCER KIT 2 INSTALLATION INSTRUCTIONS

WL16 WATER LEVEL LOGGERS Submersible pressure transducer and USB datalogger combination

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER

1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/22 Siemens FI

Compact Triple Cabinet Outlet Station Model Installation and Operating Instructions

Additel 761 Automated Pressure Calibrators Selection Guide

9700 Transmitter Submersible hydrostatic level transmitter

DEEPSEA. Power & Light. Micro SeaLaser. Operator s Manual Ruffin Road San Diego, CA USA T: (858) F: (858)

PURA. Pure Gas Dewpoint Transmitter. Users Guide

Transcription:

PT-500 Modbus Series User Manual APG R Doc #9003999 Rev A, 02/15

Table of Contents Introduction... iii Warranty and Warranty Restrictions... iv Chapter 1: Specifications and Options... 1 Dimensions...1 Specifications... 2 Model Number Configurator... 3 Electrical Pinout Table, Power Supply Table, and System Wiring Diagrams... 4 Chapter 2: Installation and Removal Procedures and Notes...5 Tools Needed... 5 Mounting Instructions... 5 Electrical Installation... 5 Removal Instructions... 6 Chapter 3: Programming...6 Modbus Programming... 6 Modbus Programming with RST-6001 and APG Modbus Software... 6 PT-500 Modbus Register Lists... 7-9 PT-500 Modbus Sensor Parameters - L5 pressure series... 10 PT-500 Modbus Sensor Parameters - L31 level series... 10 PT-500 Modbus Application Parameters - L31 level series... 11-15 Chapter 4: Maintenance...16 General Care... 16 Vent Tube Drying...16-17 Repair and Returns... 17 NOTE: Wiring information in this User Manual is specific to the Modbus Series of the PT-500. If you have a 0-5V, mv/v, or 4-20 ma Series sensor, please consult the factory at 1-888-525-7300, or our website at www.apgsensors.com/support, for the appropriate manual for your sensor. ii

Introduction Thank you for purchasing a PT-500 modbus series submersible pressure transmitter from APG. We appreciate your business! Please take a few minutes to familiarize yourself with your PT-500 and this manual. PT-500 submersible pressure transmitters offer reliability in harsh industrial conditions. The small size, integrated electronics, wide operating temperature range, and durability make the PT-500 the perfect instrument for static and dynamic pressure measurement. Reading your label Every APG instrument comes with a label that includes the instrument s model number, part number, serial number, and a wiring pinout table. Please ensure that the part number and pinout table on your label match your order. iii

Warranty and Warranty Restrictions APG warrants its products to be free from defects of material and workmanship and will, without charge, replace or repair any equipment found defective upon inspection at its factory, provided the equipment has been returned, transportation prepaid, within 24 months from date of shipment from factory. THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES NOT EXPRESSLY SET FORTH HEREIN, WHETHER EXPRESSED OR IMPLIED BY OPERATION OF LAW OR OTHERWISE INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. No representation or warranty, express or implied, made by any sales representative, distributor, or other agent or representative of APG which is not specifically set forth herein shall be binding upon APG. APG shall not be liable for any incidental or consequential damages, losses or expenses directly or indirectly arising from the sale, handling, improper application or use of the goods or from any other cause relating thereto and APG s liability hereunder, in any case, is expressly limited to the repair or replacement (at APG s option) of goods. Warranty is specifically at the factory. Any on site service will be provided at the sole expense of the Purchaser at standard field service rates. All associated equipment must be protected by properly rated electronic/electrical protection devices. APG shall not be liable for any damage due to improper engineering or installation by the Purchaser or third parties. Proper installation, operation and maintenance of the product becomes the responsibility of the user upon receipt of the product. Returns and allowances must be authorized by APG in advance. APG will assign a Return Material Authorization (RMA) number which must appear on all related papers and the outside of the shipping carton. All returns are subject to the final review by APG. Returns are subject to restocking charges as determined by APG s Credit Return Policy. iv

Chapter 1: Specifications and Options Dimensions 7.14" [181.3mm] 7.40 [187.9mm] REMOVABLE SENSOR CAGE ASSEMBLY NON-REMOVABLE SENSOR CAGE ASSEMBLY 2.00" [50.8] 2.24 [56.9mm] ø3.50" [88.9mm] ø3.50 [88.9mm] PT-500 with Reusable Cage PT-500 with Welded Anti-snag Cage 5.29" [134.4mm] 6.44" [163.5mm] 1 1/2" SANITARY FITTING ø.188 THRU PROTECTIVE CONE ø1.98" [50.3mm] ø1.00" [25.4mm] PT-500 with Tri-clover Sanitary Fitting PT-500 with Removable Plastic Nose Cone 1

Specifications Performance Pressure Ranges 0 to 300 PSIG Digital Output Modbus RTU, 4-wire RS-485 Over Pressure 2X FSO Burst Pressure 3.0X FSO 1 Year Stability 0.75% FSO Accuracy Linearity, Hystereses & Repeatability ±0.25% of Full Scale (BFSL) up to ±0.1% of Full Scale Thermal Zero Shift @ 70 F ±0.045% FSO/ C (±0.025% FSO/ F) Thermal Span Shift @ 70 F ±0.045% FSO/ C (±0.025% FSO/ F) Environmental Operating Temperature -40 to 85 C (-40 to 185 F) Compensated Temperature -17 to 54 C (0-130 F) Maximum Submersible Depth 462.2 ft / 140.88 m / 300 psig Electrical Supply Voltage (at sensor) 5-28 VDC Current Draw 2 ma max. Protection Reverse Polarity and Surge (per IEC 61000-4-5) Load Limitation R (max) = ((V s -12V)/0.02A)-(0.042Ω per ft. of cable) Startup Time 200 ms Materials of Construction Wetted Materials Anti-snag Cage Cable Protective Nose Cone Mechanical Pressure Connection Cable Tensile Strength 316L Stainless Steel 316L Stainless Steel Urethane, PVC, or Hytrel Delrin See model number configurator for complete list Up to 200 pounds Patents US Patent No. 7,787,330 2

Model Number Configurator Part Number: PT-500 - - - - - - - A B C D E F G H A. Cable Type - A B C D Urethane - Blue (with vent tube) PVC - Black (no vent tube - sealed unit) Hytrel.31 Ø - Black (with vent tube) PVC - Black (with vent tube) Hytrel.25 Ø - Black (with vent tube) B. Pressure Range Specify range in desired unit of measure Max Water Depth 462.2 ft. (140.9 m), 300 psig C. Standard Units of Measure PSI FTH2O INWC INH2O MMH2O FWC D. Output L1 4-20 ma, 2-wire L3 0-5V, 4-wire* L9 mv/v, 4-wire* L10 0-10V, 4-wire* E. Overmold E0 No overmold for 1/2 NPTM fitting for conduit E37 Pigtail with overmolded cable F. Process Connection P1 1/2 NPTM with removable plastic nose cone P5 1/4 NPTF P37 Welded Cage (anti-snag 1 piece fitting) P38 1-1/2 tri-clover with 3/4 diaphragm P39 Reusable Cage (includes P38 fitting) G. Cable Length (specify length of cable needed in feet) H. Accuracy N0 ±0.25% N1 ±0.25% with NIST certification N2 ±0.1% with NIST certification Note: Indicates this option is standard. Note: *Indicates this option does not yet have CSA Approvals. L5 Modbus RTU, 4-wire RS-485* Pressure reading only L31 Modbu RTU, 4-wire RS-485* Level calculations, tank volume 3

Electrical Pinout Table, Supply Power Table, and System Wiring Diagrams PT-500 Modbus Series Pinout Table PT-500 Modbus Series Supply Power Table Pigtail Red Black Green White Shield Modbus + Power - Power B (TX-) A (TX+) Case Gnd Power Supply Modbus 5-28 VDC Modbus System Wiring Power Supply +5-28 Vdc GND Use Shielded Cable Master Device RS-485 A (TX+) RS-485 B (TX-) 120 Ω terminating resistor Note: PT-500 modbus sensors use reversed TX+/TX- pins. When connecting to your system, ensure continuity of TX- to TX- and TX+ to TX+, rather than A to A and B to B. PT-500 modbus series sensor Sensor 1 V+ B (TX-) A (TX+) GND PT-500 modbus series sensor Sensor 2 V+ B (TX-) A (TX+) GND PT-500 modbus series sensor Sensor 3 V+ B (TX-) A (TX+) GND 120 Ω terminating resistor at last sensor Modbus System Wiring with RST-6001 Power Supply +5-28 Vdc GND Use Shielded Cable USB to computer with APG Modbus software RST-6001 Modbus Controller A B -5V +5V Equivalent 120 Ω terminating resistor internal to RST-6001 Note: An independent +5-28 Vdc power supply is required when using an RST-6001 Modbus Controller. The RST-6001 can only supply ±5 Vdc, not the +5-28 Vdc required by the modbus series PT-500. PT-500 modbus series sensor Sensor 1 V+ B A GND PT-500 modbus series sensor Sensor 2 V+ B A GND PT-500 modbus series sensor Sensor 3 V+ B A GND 120 Ω terminating resistor at last sensor 4

Chapter 2: Installation and Removal Procedures and Notes Tools Needed Wrench sized appropriately for your PT-500 s process or conduit connection. Thread tape or sealant compound for threaded connections. Mounting Instructions Your PT-500 can be mounted in three ways: via NPT process connection, free-hanging suspension, or conduit mounted. Mounting your pressure transducer is easy if you follow a few simple steps: Never over-tighten the sensor. In all cases, tighten the sensor as little as possible to create an adequate seal. Always use thread tape or sealant compound on tapered threads. Wrap thread tape in the opposite direction of the threads so it does not unravel as you screw the sensor into place. Unraveling can cause uneven distribution and seal failure. Always start screwing in your sensor by hand to avoid cross-threading. Thread failure can be a problem if you damage threads by over-tightening them or by crossing threads. For suspension mounting the PT-500, drill a 3/16 hole into the 1/2 NPTF to 1/2 NPTF hex coupler (P/N 511414) and secure it to the 1/2 NPTM coupler fitting of the PT-500. Attach a.060 diameter 316L SS cable of desired length to the hex coupler and secure the steel cable according to your application requirements. NOTE: If your PT-500 has a vent tube, do not seal, cover, or close the vent tube with anything other than an APG-provided venting cap or desiccant drying cartridge (See Figure 4.1 and 4.2). Unapproved seals or covers will prevent proper sensor operation. Electrical Installation Attach the wires of your PT-500 to your control system according to the pinout table above. IMPORTANT: APG modbus equipment uses reversed TX+/TX- pins. When making connections between APG equipment, ensure continuity of A to A and B to B pins. When connecting APG modbus equipment to other systems, ensure continuity of TX+ to TX+ and TX- to TX-. 5

Removal Instructions Removing your PT-500 from service must be done with care. It s easy to create an unsafe situation, or damage your sensor, if you are not careful to follow these guidelines: For sensors installed via NPT process connection, make sure the pressure is completely removed from the line or vessel. Follow any and all procedures for safely isolating any media contained inside the line or vessel. Remove the sensor with an appropriately sized wrench (per your process connection). For suspended sensors, retrieve the sensor from the vessel. Follow any and all procedures for safely isolating any media contained inside the line or vessel. Carefully clean the sensor s fitting and diaphragm of any debris (see General Care) and inspect for damage. Store your sensor in a dry place, at a temperature between -40 F and 180 F. DANGER: Removing your process connected PT-500 Pressure Transmitter while there is still pressure in the line could result in injury or death. IMPORTANT: Any contact with the diaphragm can permanently damage the sensor. Use extreme caution. Chapter 3: Programming Modbus Programming PT-500 L5/L31 modbus series sensors use standard Modbus RTU protocol (RS-485). The sensors can only operate as slave devices. Sensor default transmission settings are 9600 Baud, 8 Bits, 1 Stop Bit, No Parity, and require a minimum delay of 300 ms between transactions to return the contents of all registers. Commands returning fewer registers will require shorter delays. See PT-500 Modbus Register Lists on pages 7-9. NOTE: For more information about Modbus RTU, please visit www.modbus.org. 6

Modbus Programming with RST-6001 and APG Modbus Software APG RST-6001 Modbus Controller can be used in tandem with APG Modbus to program and control up to 20 PT-500 L5 or PT-500 L31 sensors. Through APG Modbus, you can monitor the raw readings from the sensor, including level or pressure, temperature and battery voltage, or configure the sensor. See PT-500 Modbus Register Lists on pages 7-9. NOTE: For APG Modbus programming instructions, or to download APG Modbus software, please visit www.apgsensors.com/support. PT-500 Modbus Register Lists Input Registers (0x04) Register Returned Data 30299 Model Type 30300 Pressure (L5 - PSI; L31 - mmh 2 O) 30301 N/A 30302 Temperature Reading (in 0 C, signed) 30303-30304 Calculated (raw) 30305-30306 N/A 30307 N/A 30308 Battery Voltage 30309 Trip 1 Status 30310 Trip 2 Status NOTE: The Calculated Readings will be returned without a decimal place. In order to obtain the true result, the Decimal Place setting must be taken into account. 7

Holding Registers (0x03) - PT-500 L5 pressure series 40401 Units 0-16 40402 Application Type 0 or 8 40403 N/A 40405 Max Pressure *0-32,000 PSI 40406 Full Pressure 0-32,000 PSI 40407 Zero Offset -15,000-30,000 PSI 40408 Pressure Decimal 0-3 40409 A/D Gain *1, 2, 4, 8, 16, 32, 64, 128 40410 N/A 40411 Parameter Default 0 = No; 1 = Restore Defaults 40412 Averaging 0-10 40413 Calibration Value *-32,767-32,767 40414 Calibration Flag *0-300 40415 Sample Rate 10 to 1000 milliseconds 40416 Scale *0-65,535 40417 Offset -20,000-20,000 40418 Voltage Offset -20-20 40419 Baud Rate 0-3 (2400, 9600, 19200) 40420 Parity 0-2 (none, even, odd) 40421 Stop Bit 0-1 (0 = 1 stop bit; 1 = 2 stop bits) 40422-40423 Pressure X^3 *N/A 40424-40425 Pressure X^2 *N/A 40426-40427 Pressure X^1 *N/A 40428-40429 Pressure X^0 *N/A 40430 Trip 1 Pressure -15,000-30,000 PSI 40431 Trip 1 Window 0-30,00 PSI 40432 Trip 1 Type 0-29 40433 Trip 2 Pressure -15,000-30,000 PSI 40434 Trip 2 Window 0-30,00 PSI 40435 Trip 2 Type 0-29 40436-40437 Multiplier 0.0010-99.9999 (float) 40438-40439 Description A - Z, 0-9, /.-,+* (16 char) 40446 Temperature Offset -20-20 40447-40448 Temperature X^3 *N/A 40449-40450 Temperature X^2 *N/A 40451-40452 Temperature X^1 *N/A 40453-40454 Temperature X^0 *N/A *Setting is factory calibrated. Do not adjust. 8

Holding Registers (0x03) - PT-500 L31 level series 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 0-11 40403 Volume Units 1-7 40405 Max Level *0-65,535 mm 40406 Full Level 0-65,535 mm 40407 Zero Offset 0-610 mm 40408 N/A 40409 A/D Gain *1, 2, 4, 8, 16, 32, 64, 128 40410 Specific Gravity 1-2,000 40411 Parameter Default 0 = No; 1 = Restore Defaults 40412 Averaging 0-10 40413 Calibration Value *0-65,535 40414 Calibration Flag *0-300 40415 Sample Rate 10 to 1000 milliseconds 40416 Scale *0-65,535 40417 Offset -20,000-20,000 40418 Voltage Offset -20-20 40419 Baud Rate 0-3 (2400, 9600, 19200) 40420 Parity 0-2 (none, even, odd) 40421 Stop Bit 0-1 (0 = 1 stop bit; 1 = 2 stop bits) 40422-40423 Pressure X^3 *N/A 40424-40425 Pressure X^2 *N/A 40426-40427 Pressure X^1 *N/A 40428-40429 Pressure X^0 *N/A 40430 Trip 1 Level 0-65,535 (mm) 40431 Trip 1 Window 0-65,535 (mm) 40432 Trip 1 Type 0-29 40433 Trip 2 Level 0-65,535 (mm) 40434 Trip 2 Window 0-65,535 (mm) 40435 Trip 2 Type 0-29 40436-40437 Parameter 1 0-1,000,000 (mm) 40438-40439 Parameter 2 0-1,000,000 (mm) 40440-40441 Parameter 3 0-1,000,000 (mm) 40442-40443 Parameter 4 0-1,000,000 (mm) 40444-40445 Parameter 5 0-1,000,000 (mm) 40446 Temperature Offset -20-20 40447-40448 Temperature X^3 *N/A 40449-40450 Temperature X^2 *N/A 40451-40452 Temperature X^1 *N/A 40453-40454 Temperature X^0 *N/A *Setting is factory calibrated. Do not adjust. 9

PT-500 Modbus Sensor Parameters - L5 pressure series 40401 - Units Determines the units of measure for the calculated reading. 0 = PSI 5 = mmh2o 10 = mmhg 14 = insw 1 = BAR 6 = cmh2o 11 = cmhg 15 = insw 2 = mbar 7 = mh2o 12 = inhg 16 = msw 3 = kpa 8 = inh2o 13 = kg/cm 2 4 = MPa 9 = fth2o All H2O pressure measurements @ 20 C. All HG pressure measurements @ 0 C. 40402 - Application Type Determines the units of measure for the calculated reading. 0 = Standard (units selected in 40401 are displayed) 8 = Custom (units selected in 40401 and multiplier in 40436-40437 are used to compute desired units; description in 40438-40439 is label for measurement) PT-500 Modbus Sensor Parameters - L31 level series 40401 - Units Determines the units of measure for the calculated reading when Application Type is set to 0, 1, or 7. 1 = Feet 2 = Inches 3 = Meters 40402 - Application Type Determines the type of calculated reading performed by the sensor. 0 = Distance 1 = Level 2 = Standing Cylindrical Tank with or without Hemispherical Bottom 3 = Standing Cylindrical Tank with or without Conical Bottom 4 = Standing Rectangular Tank with or without Chute Bottom 5 = Horizontal Cylindrical Tank with or without Spherical Ends 6 = Spherical Tank 7 = Pounds (Linear Scaling) 8 = N/A 9 = Vertical Oval Tank 10 = Horizontal Oval Tank 11 = Strapping Chart 10

40403 - Volume Units Determines the units of measure for the calculated reading when Application Type is set to 2-6 or 9-11. 1 = Feet 3 5 = Liters 2 = Million Feet 3 6 = Inches 3 3 = Gallons 7 = Barrels 4 = Meters 3 PT-500 Modbus Application Parameters - L31 level series Application 0 - Distance 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 0 40403 Volume Units -- Application 1 - Level 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 1 40403 Volume Units -- Application 2 - Volume of Standing Cylindrical Tank ± Hemispherical Bottom 40401 Units -- 40402 Application Type 2 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm Full Level Diameter 40436-40437 Tank Diameter 0-1,000,000 (mm) 40438-40439 Radius of Bottom Hemisphere 0-1,000,000 (mm) or Bottom Radius 11

Application 3 - Volume of Standing Cylindrical Tank ± Conical Bottom 40401 Units -- 40402 Application Type 3 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm Full Level Diameter 40436-40437 Tank Diameter 0-1,000,000 (mm) 40438-40439 Cone Diameter (at bottom of cone) 0-1,000,000 (mm) 40440-40441 Length (height) of Cone 0-1,000,000 (mm) Cone Length Cone Diameter Application 4 - Volume of Standing Rectangular Tank ± Chute Bottom 40401 Units -- 40402 Application Type 4 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm Full Level Tank X 40436-40437 Tank X Dimension 0-1,000,000 (mm) 40438-40439 Tank Y Dimension 0-1,000,000 (mm) 40440-40441 Chute X Dimension 0-1,000,000 (mm) 40442-40443 Chute Y Dimension 0-1,000,000 (mm) 40444-40445 Length (height) of Chute 0-1,000,000 (mm) or Chute Length Chute X Chute Y Tank Y 12

Application 5 - Volume of Horizontal Cylindrical Tank ± Hemispherical Ends 40401 Units -- 40402 Application Type 5 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm 40436-40437 Tank Length 0-1,000,000 (mm) 40438-40439 Tank Diameter 0-1,000,000 (mm) 40440-40441 Radius of End Hemispheres 0-1,000,000 (mm) End Radius Diameter Length Full Level Application 6 - Volume of Spherical Tank 40401 Units -- 40402 Application Type 6 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm Full Level Diameter 40436-40437 Tank Diameter 0-1,000,000 (mm) 13

Application 7 - Pounds (Linear Scaling) 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 7 40403 Volume Units -- 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm 40436-40437 Multiplier (linear scalar) 0-1,000,000 (1000 = 1.000) Application 9 - Volume of Vertical Oval Tank 40401 Units -- 40402 Application Type 9 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm 40436-40437 Tank Length 0-1,000,000 (mm) 40438-40439 Tank Depth 0-1,000,000 (mm) 40440-40441 Tank Width 0-1,000,000 (mm) Full Level Width Depth Length 14

Application 10 - Volume of Horizontal Oval Tank 40401 Units -- 40402 Application Type 10 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm 40436-40437 Tank Length 0-1,000,000 (mm) 40438-40439 Tank Depth 0-1,000,000 (mm) 40440-40441 Tank Width 0-1,000,000 (mm) Full Level Depth Length Width Application 11 - Strapping Chart (Polynomial Values) 40401 Units 1 = Feet, 2 = Inches, 3 = Meters 40402 Application Type 11 40403 Volume Units 1-7 40405 Max Level (factory set) 40406 Full Level 0-65,535 mm 40436-40437 X^3 Coefficient 0-1,000,000 40438-40439 X^2 Coefficient 0-1,000,000 40440-40441 X^1 Coefficient 0-1,000,000 40440-40441 X^0 Coefficient 0-1,000,000 15

Chapter 4: Maintenance General Care Your PT-500 series pressure transmitter is very low maintenance and will need little care as long as it is installed correctly. However, in general, you should: For process connected sensors, keep the transmitter and the area around it generally clean. Avoid applications for which the transmitter was not designed, such as extreme temperatures, contact with incompatible corrosive chemicals, or other damaging environments. Inspect the threads whenever you remove the transmitter from duty or change its location. Avoid touching the diaphragm. Contact with the diaphragm, especially with a tool, could permanently shift the output and ruin accuracy. Clean the diaphragm or the diaphragm bore with extreme care. If using a tool is required, make sure it does not touch the diaphragm. IMPORTANT: Any contact with the diaphragm can permanently damage the sensor. Use extreme caution. Vent Tube Drying Condensation in the vent tube can damage the electronics in your sensor, resulting in unreliable readings. APG offers two methods of preventing vent tube condensation: a venting cap, and a desiccant drying cartridge. The venting cap is a PVC tube with a hydrophobic patch that allows moisture to pass out of the tube without allowing water in (See Figure 4.1). The cap is sealed by an o-ring, and is easily installed in the field. The desiccant drying cartridge with vent tube adapter absorbs any moisture in the vent tube to keep vapor from condensing (See Figure 4.2). The installation of the desiccant drying cartridge is quick and easy. Common installation methods are cable tie, Velcro, and cable clamps. IMPORTANT: Do NOT use desiccant cartridge in the presence of vapors or liquids containing phosphate esters, synthetic lubricants, hydrocarbon solvents, methanol, acetone, lacquer solvents, or other organics. 16

Figure 4.1 Figure 4.2 NOTE: Desiccant crystals change from blue to pink as they become saturated. Cartridge must be replaced when all crystals have saturated. Repair and Returns Should your PT-500 series pressure transmitter require service, please contact the factory via phone, email, or online chat. We will issue you a Return Material Authorization (RMA) number with instructions. Phone: 888-525-7300 Email: sales@apgsensors.com Online chat at www.apgsensors.com Please have your PT-500 s part number and serial number available. See Warranty and Warranty Restrictions for more information. 17

APG R Automation Products Group, Inc.