IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring

Similar documents
COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

CTG Certification Protocol -- Version 3.0 SUMMARY

4/17/2013. The Implementation of WHO Guidelines on Construction/ Engineering Aspect of TB Infection Control

Validation of a Neutral Pressure Isolation Room

1. The laboratory supervisor must enforce the institutional policies that control access to the laboratory.

ASSESSMENT OF BIOAEROSOL REDUCTION METHODS IN STEM CELL TRANSPLANT UNITS AT A UNIVERSITY HOSPITAL

Airtightness Testing in Large Buildings: NESEA 2016

Regulatory Basics for Facility Design (WHO GMP): Current GMP Requirements

Air Handling Unit (AHU) Air handling unit which serves to condition the air and provide the required air movement within a facility.

FABI Ventilation and Thermal Details Coral Springs, FL. Joseph Lstiburek, Ph.D, P.Eng, ASHRAE Fellow. Adventures In Building Science

PI: Comments 1 12/18/14

Verification Of Calibration for Direct-Reading Portable Gas Monitors

THE UNIVERSITY OF WESTERN ONTARIO DIVISION OF HUMAN RESOURCES OCCUPATIONAL HEATH & SAFETY

Airborne Activity Sampling and Monitoring at Hinkley Point A Site. David Williams, Hinkley Point A Site

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN

THE UNIVERSITY OF WESTERN ONTARIO OCCUPATIONAL HEATH & SAFETY

Proficiency Module Syllabus. P601 - Thorough Examination and Testing of Local Exhaust Ventilation Systems

RPS900W Redundant Power Supply. Installation Guide.

Draft. Equipment/Instrument

Field Evaluation of ASTM E in Relation to Control Room Habitability Testing and Boundary Maintenance in Nuclear Power Plants.

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

LABORATORY SAFETY SERIES: Laboratory Hoods

Calibration and Bump Test Requirements for Direct Reading Portable Gas Monitors

Zonal Pressurization Diagnostics (ZPD)

"LABORATORY SAFETY SERIES"

Calibration Requirements for Direct Reading Confined Space Gas Detectors

GSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS)

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

Highlights of Respirable Crystalline Silica. Jim Shelton, CAS Houston North Area Office

CEMP-ET DEPARTMENT OF THE ARMY ETL U.S. ARMY CORPS OF ENGINEERS Washington. DC Technical-Letter No February 1999

Title: Standard Operating Procedure for Elemental and Organic Carbon (EC and OC) using Non-Dispersive Infrared Detection (NDIR)

MANAGEMENT PROCEDURE FOR LABORATORY VENTILATION

Demand Control Ventilation Using CO 2

The primary purpose of laboratory fume hoods is to keep toxic or irritating vapors out of the general laboratory working area.

The routine maintenance and inspection of local exhaust ventilation (LEV)

Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

Annex 8. Guidelines on heating, ventilation and air-conditioning systems for non-sterile pharmaceutical products. Background. Summary of main changes

Respirable Crystalline Silica

Best Practices Pneumatics Machine & Design. Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016

Ventam 85 Installation & Commissioning Instructions

4 Testing Agency Guide. 4.1 U.S. Army Corps of Engineers (USACE) Standard for Air Leakage

Guideline to the Inspection of Hormone Product Manufacturing Facilities QAS/08.256, February 2008

PENETRATION OF N95 FILTERING- FACEPIECE RESPIRATORS BY CHARGED AND CHARGE- NEUTRALIZED NANOPARTICLES

University of Dayton Respiratory Protection Program 29 CFR

Exposure Control Plan for Drilling/Grinding Concrete

Presented by ARAMSCO

PERFORM Operating Document

SECTION LEAD-BASED PAINT REMOVAL AND DISPOSAL

3M TM Versaflo TM AP-600 Series Air Filtration Panels For use with 3M TM Versaflo TM Supplied Air Respirator Systems. Work. in a World of.

Presented by: Laura Cullom Phillips 66 Rodeo Jay Prescott Shell Martinez Refinery

Are you really doing your job if you fail to measure static pressure every time you service a unit? The answer is no.

An enterprise of United McGill Corporation Family owned and operated since System Pressure Testing for Leaks McGill AirFlow LLC

NZQA unit standard New US 1Non-coal of 7145 version 1 Page 1 of 5

Series SFD. Clean Air Filter. Variations. Made to Order. Type. Cartridge (replaceable element) Disposable (non-replaceable element) Up to 100

Building Official's Guide to Duct Testing based on 2009 IECC

Presented By: Kary S. Amin Nova Environmental, Inc. Nova Environmental, Inc.

Laboratory Ventilation. Environmental, Health, and Safety

Controlling Cabin and Envelope Air Flows & Pressure Differentials

PERFORM Operating Document

(iii) The controlling contractor must apprise the host employer of the information exchanged with the entry entities pursuant to this subparagraph.

Wildfire Smoke and Your Health

B. Diagnostic Equipment Information 01 Number of Manometers Used to Measure Home Pressurization Manometer Make. Manometer Serial Number

Technical Information

SERVICE MANUAL MODEL BA200AMST-S1 BREATHING AIR PANEL

GOOD MANUFACTURING PRACTICES FOR HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS FOR NON-STERILE PHARMACEUTICAL DOSAGE FORMS: PART 2


Cross Infection in Hospital Wards with Downward Ventilation - Different Locations of Return Openings without and with Partitions between Beds

Guidance on room integrity testing and its interpretation

A. Evaluation of the written program

Air Leakage Detailing & Awareness Services

B. Diagnostic Equipment Information 01 Number of Manometers Used to Measure Home Pressurization Manometer Make. Manometer Serial Number

WhisperValue DC. The ideal Multi-Family Solution High Performance Built for the Long Run

Kansas State University Fume Hood Operation

Protean Instrument Corporation 231 Sam Rayburn Parkway, Lenoir City, TN TEL/FAX:

TEST BENCH SAFETY VALVES ¼ - 5 DN10 DN125

Respiratory Protection

Chemical and. Respiratory. Protective Suits. Purpose-designed, integrated PPE solutions protecting you in the harshest environments

Inspection Checklist for BSL4 Laboratories (7CFR 331; 9 CFR 121; 42 CFR 73; BMBL 5th Edition)

VALITEQ DMS v2.o Document Management Software Tutorial

SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL

HVAC Air Duct Leakage. Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA

What is Pressure? Residential Pressure Measurement

SECTION LEAD-PAINT REMOVAL

Recommendations - USA

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

THE IMPACT ON ENERGY CONSUMPTION CAUSED BY PRESSURE DROP IN A COMPRESSED AIR SYSTEM

Using Vaporized Hydrogen Peroxide

SERVICE MANUAL MODEL BA020AMST BREATHING AIR PANEL

Laboratory Safety Training. Environmental Health and Safety

SERVICE MANUAL MODEL BA100BMST 100 SCFM PORTABLE AIR PANEL

NZQA unit standard 7145 version 9 Page 1 of 5. Design and maintain effective ventilation systems for an underground coal mine

County of Santa Clara Emergency Medical Services System

CONTROL OF SUBSTANCES HAZARDOUS TO HEALTH PROCEDURE

SOUTHBANK PLACE Asbestos Removal (Brief Guide)

IDEAL FOR SHORT- TO MEDIUM- TERM ANAESTHESIA OR VENTILATION. Anaesthesia Tracheal Tubes

Automatic Isokinetic Sampler. ST5 Evo

TECHNICAL INFORMATION

Minimum Ventilation. Bernard Green Ventilation Technical Service Manager - Asia

Simplified Automated Ventilator Training Slides

Transcription:

IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring IC Sentinel is a real-time environmental quality monitoring solution, comprised of facilitywide, low-cost, compact, multi-sensor modules. IC Sentinel sensors can be placed just about anywhere in the facility to allow immediate realtime and 24/7 monitoring and long-term profiling. The sensors can also be conveniently moved around the facility as needed to respond to construction or problematic areas. There is no limit to the number of IC Sentinel units that can be deployed within a facility to ensure adequate coverage. INFECTION CONTROL Monitor airborne particulate count facility-wide Monitor differential room pressure of key areas Verify Performance Protective Environment rooms Verify Performance of Airborne Infection Isolation rooms Test for elevated humidity levels FACILITIES MANAGEMENT Monitor construction and renovation areas for particulates Verify barrier and air filtration, effectiveness Monitor indoor air quality (IAQ), verify performance of HVAC Generate real-time alerts OBJECTIVE This article provides guidance in installation and application of the IC Sentinel product to achieve the following objectives Monitor an Airborne Infection Isolation room (AII) Monitor an Airborne Infection Isolation room with an antechamber Monitor a Protective Environment (PE) Monitor a Protective Environment with Antechamber Monitor a construction area

The CDC has provided the following chart for Engineered specifications for positive and negative pressure rooms (CDC EIC MMWR June 6 2003) Pressure Differentials Air Changes per Hour (ACH) Filtration Efficiency Protective Environment(PE) Positive Pressure > + 2.5 Pa (Pascal) (0.01 Positive water gauge) > 12 Supply: 99.97%@ 0.3um DOP1 Return: none required2 Airborne Infection Isolation (AII) Negative pressure > - 2.5 Pa (Pascal) (0.01 Negative water gauge) > 12 (for renovation or new construction) Supply: 90% dust spot test Return: 99.97%@0.3um DOP1,3 Room Air Flow Direction Out to the adjacent area In to the room Clean to Dirty air flow in room Away from high risk /immunosuppressed patient Towards the patient (Airborne disease patient ) Ideal Pressure Differential > +8 Pa > -2.5Pa 1 DOP is abbreviation for dioctylphthaltate particles of 0.3um 2 If the patient requires both PE and AII, return air shall be HEPA filtered or otherwise exhausted to the outside 3 HEPA filtration of exhaust air from AII rooms should not be required providing that the exhaust is properly located to prevent re-entry into the building The 2010 Guidelines for Design and Construction of Healthcare Facilities specifies the following for Operating Rooms (ORs) Air pressure relative to adjacent areas Positive Minimum Air exchanges of outside air per hour 4 Minimum total air exchanges per hour 20 Air re-circulated by means of room units? Relative Humidity NO 20-60 percent

Design Temperature 68-75 Degrees F In addition, the FGI and ASHRAE Design Guidelines recommend the following: Sealed room with about 0.1cfm/ft2 Greater than 125 cfm airflow differential Supply vs. Exhaust Clean to dirty airflow Monitoring of PEs, AIIs, Construction and renovation areas, other critical areas > 12 air changes / hour (ACH) in new construction and 6 air changes / hour in renovation areas Anteroom airflow patterns suitably designed for the application APPLICATIONS GUIDE Use this guide to assist in determining where to place IC Sentinel monitor units. OUTDOOR BASELINE IC Sentinel can be used to create a baseline for outdoor air quality conditions. Outdoor air quality can be adversely affected by dust storms, pollen, outdoor construction, pollution, forest fires and other factors. Before reacting to degraded indoor air quality, it is best to know if such degradation is caused by degraded outdoor air quality and particle count. For this application, the IC Sentinel monitor unit should be located indoors, ideally in the proximity of the outdoor location to be sampled. If it is desired to get differential air pressure, then the unit should be located in a nominal air pressure indoor location. Tubing is conducted from the IC Sentinel monitor s particle detector inlet (using the inlet adapter from the Zero Count Filter P/N 80846-1) to the outdoor location. The outdoor location should be located in the proximity of the air intake, to best sample air being brought into the building. Of course, an important factor is that the indoor air quality (particle count) is better than the outdoor air quality (particle count) but this is not always the case. Typically, it is desired that the indoor air pressure is positive relative to outdoor air pressure.

Monitoring outside particle count for baseline Air Quality Create air quality baseline Verify indoor air is cleaner than outdoor air Monitor for poor outside air conditions Verify differential air pressure AIRBORNE INFECTION ISOLATION (AII) ROOMS AIIs are designed to protect healthcare workers, other patients, and the public in the hospital environment from potential infection by airborne agents carried by infected, or potentially infected, patients or groups. The AII will have a negative pressure relative to adjacent spaces, and the (potentially infectious) air inside the AII must be suitably exhausted. With the AII, the IC Sentinel is mounted outside of the AII room so that it can be visually checked without entering the AII (in general, the IC Sentinel monitor unit is placed in the positive pressure location). Static Sensor Pressure Tips (P/Ns242901-0X) are used to sample the air pressure in the AII, so that it can be compared to the air pressure in the adjacent corridor.

Thresholds can be set to alert personnel when the differential air pressure drops below desired levels. An AII anteroom may be used in certain circumstances to provide additional AII capacity in a hospital. In this case, the IC Sentinel Monitor unit can be placed in the anteroom, on the wall outside of the AII room. Static Sensor Pressure Tips (P/Ns242901-0X) are used to sample the air pressure in the AII room, so that it can be compared to the air pressure in the ante room. The AII room should remain at a negative pressure relative to the anteroom. Thresholds can be set to alert personnel when the differential air pressure drops below desired levels. Negative Pressure Room for Airborne Infection Isolation Procedure/treatment Emergency rooms Bronchoscopy room Autopsy rooms

Negative Pressure Room for Airborne Infection Isolation with Positive Pressure Ante Room Procedure/treatment Emergency rooms Surge capacity Pandemic isolation PROTECTIVE ENVIRONMENTS (PE) PEs are designed to protect patients who are most susceptible to airborne infectious agents. The PE will have a positive pressure relative to adjacent spaces, to keep airborne particles from leaking into the PE. With the PE, the IC Sentinel monitor unit is mounted inside the PE room so that it can be visually checked periodically by those within the PE. Static Sensor Pressure Tips (P/Ns242901-0X) are used to sample the air pressure in the adjacent space,

so that it can be compared to the air pressure in the PE. Thresholds can be set to alert personnel when the differential air pressure drops below desired levels. In general, the IC Sentinel monitor unit is placed in the positive pressure location. A PE anteroom may be used in certain circumstances to provide additional PE capacity in a hospital. In this case, the IC Sentinel Monitor unit is placed in the PE room adjacent to the anteroom. Static Sensor Pressure Tips (P/Ns242901-0X) are used to sample the air pressure in the ante room, so that it can be compared to the air pressure in the PE room. The PE room should remain at a positive pressure relative to the anteroom. Thresholds can be set to alert personnel when the differential air pressure drops below desired levels. Importantly, the IC Sentinel will also measure particle counts in PE rooms (and other rooms where it is desired to monitor presence or generation of particles). Ideally the IC Sentinel monitor unit is located close to the diffuser or source of air, high on a wall or ceiling, so that the particle count is representative of the air coming into the room. This will enable the IC Sentinel system to detect degradations of incoming air quality, and help to minimize "false alarms" due to normal activities within the room which can create spikes in particle counts. In general, the IC Sentinel monitor unit is placed in the positive pressure location. IC Sentinel will also monitor room humidity, which is a requirement in ORs. Sound and light levels can also be monitored which is important factors for overall patient satisfaction.

Positive Pressure Room for Protective Environments Immune compromised patient Operating rooms

Positive Pressure Room for Airborne Infection Isolation and Protective Environments with Negative Pressure Ante Room Immune compromised patient Operating rooms CONSTRUCTION AND RENOVATION Construction and renovation activities create special requirements for monitoring differential pressure and particle counts. Work areas within the hospital must be maintained at a negative pressure so that particles generated within the work area do not spread through the facility. The air within the work area is circulated through a HEPA filter and is exhausted suitably. The IC Sentinel Monitor unit should be located outside of the work area. Static Sensor Pressure Tips (P/Ns242901-0X) are used to sample the air pressure in the work

area, so that it can be compared to the air pressure in the adjacent corridor or patient area. Thresholds can be set to alert personnel when the differential air pressure drops below desired levels, which may indicate that the barrier has been incorrectly constructed, breached or damaged. For soft barriers, the IC Sentinel Monitor unit can be mounted on a ceiling adjacent to the barrier, and the sampling tube is conducted and attached to the barrier. It is important to monitor particle count in areas adjacent to work areas to detect large increase in particle count caused by construction or renovation, which can signal a degradation in the barrier, malfunction of HEPA filter or fan, or ICRA procedure violations. Mount the IC Sentinel Monitor unit on the ceiling or on a high wall to avoid spurious false alarms due to normal activities, which can create spikes in particle count. Monitoring Negative Air Pressure in construction area Barrier verification Temporary monitoring ICRA Compliance Hazard Control

REFERENCES ASHE/FGI Guidelines for Design and Construction of Healthcare Facilities, 2010 Edition ASHRAE 170-2008: Ventilation of Health Care Facilities Centers for Medicare and Medicaid services (CMMS), Paragraph 482.41 Physical Environment 2012 Joint Commission Standards CDC- Guidelines for Environmental Infection Control in Health Care Facilities www.cdc.gov/mmwr/preview/mmwrhtml/rr5210a1.htm Solution Infographic HAIs and Airborne Infectious Disease IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring 1999-2013 Oberon, Inc.