Installation & Operating Instructions for Genesys Series Manifolds

Similar documents
Installation & Operating Instructions for Genesys Analog Series Manifolds

Installation & Operating Instructions for Genesys Analog Series Manifolds

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Tri-Tech Medical Inc.

Installation Operating Instructions for Duplex Manual Manifolds PX-TMD Series

Installation & Operating Instructions for Genesys Analog Series Manifolds

Installation & Operating Instructions for Genesys Series Manifolds

Installation & Operating Instructions for Genesys Analog Series Manifolds

Installation and Operating Instructions For MANUAL MANIFOLDS SD and SDHP SERIES

Installation & Maintenance Manual. Economy Manifold

Pressure Differential Automatic Manifold For LPG. PDH1000 Series. LPG Installation & Operations Instructions

MEDICAL EQUIPMENT CATALOG

Fully Automatic Gas Manifold. Patent US 7,013,906. Installation & Operation Manual

Inert Air (N2) Systems Manual

Installation & Maintenance Manual. C2 & C3 Manifolds

Economy Manifold Alert -2. Installation and Maintenance Manual V1.6

AUTOMATIC GAS MANIFOLDS

SERVICE MANUAL AUTOMATIC CHANGEOVER MANIFOLD AGM2, AGM2HL, & AGM2HP SERIES AGM2 HEALTH CARE GAS MANIFOLD B20454 REL-0000 (0503)

Protocol Switchover Station

571 Series Medical TM. IntelliSwitch Electronic Switchover

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

Types 749B and R130 Changeover Manifolds

SPECIFICATIONS ATTENTION

Unimatic II Manifolds for Oxygen, Nitrous Oxide & Nitrogen Service Manual

G96 Series BASOTROL Dual Operator Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

High Pressure Inlet Kits for CONCOA BlendMites and BlendMasters

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50 Systems Outfitted with ABM-725 Monitor C O M P A N Y

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

Installation Instructions for NP100 Series Nitrogen Control Panels

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

Installation and Maintenance Manual. Microprocessor Based Digital Manifold NFPA

APPS-160 Gen 2 User Manual

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Rejuvenation Instructions

Operator: Save these instructions for future use!

Dual Solenoid Gas Valve Installation

36H SERIES Combination Gas Valve

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

Instruction Manual Updated 7/26/2011 Ver. 2.2

623 Series Dome Load Regulators

DPC-30 DPC-100. Reference Manual

MANUAL GAS MANIFOLDS

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

The 527 Series Automatic Switchover System

AUTOMATIC GAS MANIFOLD

INSTRUCTIONS FOR HIGH PURITY, CHANGEOVER REGULATOR SYSTEMS (PCS, CRS SERIES)

BGC258 Series BASOTROL Gas Valve

GM Series Dual-Block Multi-Function Gas Control Valves

Manifolds & pressure reducing sets

Operation Manual Piston Sensed Gas Pressure Regulators

INSTALLATION & MAINTENANCE INSTRUCTIONS

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

G92 Series BASOTROL Automatic Pilot Gas Valve

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

The 527 Series Automatic Switchover System with Inlet Pressure Transducers

BGA158 Series CE Approved Class A Shutoff Gas Valve

OPERATING AND MAINTENANCE MANUAL

Medical Gas Control Panel

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

453 Series Steam Heated Vaporizing Regulator

IntelliSwitch II Electronic Switchover

RD(H)20/25 Pressure-Reducing Regulator User Manual

TECHNICAL DATA. Trimpac 244a. September 16, 2013

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

I. Subject: Compressed gas cylinders, regulators, and portable liquid systems.

Tri-Safem Model I1 Regulator. INSTRUCTIONS and PARTS

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

Welcome to the Specialized Medical Services Respiratory training webinar series!

SINGLE STAGE ULTRA-HIGH PRESSURE REDUCING REGULATOR INSTALLATION AND OPERATION INSTRUCTIONS. Certified ISO 9001

BGA158 Series CE Approved Class B Shutoff Gas Valve

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel:

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

GM-7000 Series CE Approved Gas Control Valve

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

U S E R M A N U A L CAUTION. SAVE THESE INSTRUCTIONS Federal (USA) law restricts this device to sale by or on the order of a physician.

QBS Electronic Pressure Regulator

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Operator: Save these instructions for future use!

632 Series Gas Distribution System

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

1 Exam Prep NFPA 99 Health Care Facilities Questions and Answers (Plumbing Contractor)

620 Series Switchover System

Model PSI Compressor with 3-Gallon Air Tank 12VDC

MEGR-1627 Instruction Manual

INSTALLATION. and INSTRUCTION MANUAL. for QUALITY AIR BREATHING SYSTEMS. Model 50-P-Mini Portable Systems Outfitted with ABM-725 Monitor

Bermad Pressure Reducing. Model: 42T

IPG IGNITION GAS PILOTS BACK-LOADED GAS

TECHNICAL DATA. Q= Cv S

Your safety and the safety of others are very important.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

Model 130M Pneumatic Controller

INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May

Transcription:

Manufacturer of Medical Gas Pipeline Equipment Installation & Operating Instructions for Genesys Series Manifolds Model LLU Model CCU - 1 -

Features & Benefits Features & Benefits Fully automatic changeover no valves or levers to reset after each changeover Field upgradeable design kits allow unit to be changed from i.e. cylinders to portable bulk or from lower delivery pressure to higher delivery pressure Circuit board triggers all required NFPA 99 alarms simplifying wiring and reducing cost Unit includes hi/low line pressure transducer eliminating need to purchase hi/low pressure switch Easy to service layout/design Microprocessor based control panel incorporates LED s and illuminated digital LED displays readable even in poor lighting conditions Electronic monitoring of circuits with error messages displayed for ease of maintenance Accurate, long life pressure transducers for monitoring of line pressure and bank pressures Analog gauges also provided for use in event of power failure Pressures may be displayed in PSIG / kpa / BAR Built in DISS gas specific emergency feed ports Built in emergency reserve bank ports Input power 110 VAC, 50 to 60 Hz Dual line pressure regulators on NFPA 99 models Gas specific header bar with integral check valves and cylinder pigtail assemblies Variety of header configurations available to meet the available space requirements of your installation Available in weatherproof cabinet for outdoor installation 2

Contents Tri-Tech General Instructions ----------------- 4 Introduction---------------------------- 4 Features & Benefits ---------------------- 2 Installation - Control Cabinet ------ 5 Mounting----------------------------------- 5 Wiring -------------------------------------- 8 Plumbing ----------------------------------- 6 Installation Pigtails & Cylinders ---- 10 Remote Alarm Wiring ------------------- 9 Alarm Pressure Settings------------------- 9 Start Up and Testing Procedures----- 12 Model LLU Emergency Reserve------- 13 Alarm and Regulator Set Points---------- 13 Cylinder Replacement & Handling --- 14 Line Delivery Pressure Adjustment--- 14 Replacement Parts-------------------- 16 General Maintenance ---------------- 15 Trouble Shooting Guide ------------- 17 Table of Error Codes ---------------------- 15 Table of Contents Appendix A Glossary of Terms -------------------- 19 Appendix B Technical Specifications ------------- 20 Appendix C Model CC Piping Schematic -------- 21 Appendix D Model LL Piping Schematic -------- 22 Appendix E Model CC Wiring Schematic ------- 23 Appendix F Model LL Wiring Schematic ------- 24 Appendix G Heater Wiring Schematic------------ 25 Appendix H Field Adjustments--------------------- 26 Technical Assistance---- Phone 800-253-8692 or 440-937-6244 Fax 440-937-5060 E-mail sales@tri-techmedical.com - 3 -

Introduction & General Instructions Introduction Tri-Tech Medical manifolds are cleaned for use with oxygen. Each system is tested for changeover, triggering of alarms, leakage and flow. Each unit is designed and prepared for the indicated gas service. Tri-Tech Medical manifolds are built in accordance with the National Fire Protection Association and Compressed Gas Association guidelines. Warranty All Tri-Tech Medical manifolds are warranted against defects in material and workmanship for the period of one year from date of purchase. All circuit boards are warranted against defects in material and workmanship for the period of three years from date of purchase. General Instructions/Location & Shelter Manifolds should be installed in accordance with guidelines stated by the National Fire Protection Association, the Compressed Gas Association, OSHA, and all applicable local codes. Carbon Dioxide and Nitrous Oxide manifolds and cylinders should not be placed in a location where the temperature will exceed 120 F (49 C) or fall below 20 F (-7 C). The manifolds for all other gas services should not be placed in a location where the temperature will exceed 120 F (49 C) or fall below 0 F (-18 C). A manifold placed in an open location should be protected against weather conditions. During winter, protect the manifold from ice and snow. In summer, shade the manifold and cylinders from continuous exposure to direct sunlight. Leave all protective covers in place until their removal is required for installation. This precaution will keep moisture and debris from the piping interior. Caution Failure to follow the following instructions can result in personal injury or property damage: Never permit oil, grease, or other combustible materials to come in contact with cylinders, manifold, and connections. Oil and grease may react with explosive force when ignited while in contact with some gases particularly oxygen and nitrous oxide. Cylinder and master valves should always be opened very slowly. Heat of recompression may ignite combustible materials creating an explosive force. Pigtails should never be kinked, twisted, or bent into a radius smaller than 3 inches. Mistreatment may cause the pigtail to burst. Do not apply heat. Oil and grease may react with explosive force when ignited while in contact with some gases particularly oxygen and nitrous oxide. Cylinders should always be secured with racks, chains, or straps. Unrestrained cylinders may fall over and damage or break off the cylinder valve which may propel the cylinder from its current position. Oxygen manifolds and cylinders should be grounded. Static discharges and lightning may ignite materials in an oxygen atmosphere, creating a fire or explosive force. Welding should not be performed near nitrous oxide piping. Excessive heat may cause the gas to dissociate, creating an explosive force. Remove all protective caps prior to assembly. The protective cap may ignite due to heat of recompression in an oxygen system. 4

Installation Instructions Control Cabinet Installation 1. Determine and mark the vertical center line for installation of the manifold control cabinet. 2. Measure from the floor to a point 60 in height* above the finished floor of this vertical line. Using a level, mark a horizontal line at this point extending approximately 10 to the left and 10 to the right of center. This line indicates the location for the bottom two mounting bolts of the manifold control cabinet. (* - suggested manifold height. Wall mounting heights may vary depending on available space, cylinder height, etc.) 60 6.25 3. Draw another horizontal line 12.5 above and parallel to the lower horizontal line. This line should also extend 7 to the left and 7 to the right of center. This line indicates the location for the upper two mounting bolts of the manifold control cabinet. 4. Measuring from the vertical center line, along the two horizontal lines, make a mark at 6 ¼ to the left and another at 6 ¼ to the right of the vertical center line. These four locations are the mounting hole locations for the manifold control cabinet. Install the manifold control cabinet using fasteners suitable for the type of wall construction. 12.5 Center Line 12.5 Header Installation 1. Attach the headers to the union on each side of the manifold control cabinet. Using a level, mark the placement of mounting brackets while keeping the header on a horizontal plane. 2. Remove the U bolt assemblies from the header mounting brackets. Position the brackets so that the top of the bracket is aligned with the bottom of the headers and is centered between the cylinder connections. The end bracket should be placed as close to the last cylinder as possible to provide the most support and stability. 5

Installation Instructions 1. Mark the mounting hole and install fasteners suitable for type of wall construction. 2. Fit the U bolt over the header piping and tighten the two mounting nuts. Plumbing 1. The outlet of the manifold is located at the top center of the unit as shown here. The outlet connection is ½ NPT female. A ½ NPT male union should be installed between the outlet of the manifold cabinet and the pipeline system. This union is available as an accessory from Tri-Tech Medical (part # 17-0169). Outlet ½ F npt Line relief valve ½ F npt 2. Unions (part # 17-0169) should also be installed between all relief valves and the relief (vent) pipeline system(s). There are two ½ NPT female relief valve connections on the model CCU manifold. 3. The intermediate relief valve extension pipe nipple must be installed. It is bagged and taped to the inside of the cabinet for protection during shipment. Intermediate relief connection Line relief connection 6

Installation Instructions Plumbing 1. In addition to connecting the left & right primary and secondary portable bulk vessel supply banks, the LLU models must also have a high pressure reserve bank of cylinders connected to the cabinet to be in compliance with NFPA 99 guidelines. Emergency reserve in use pressure transducer High pressure reserve manifold Emergency reserve low pressure transducer 2. Knock outs have been provided on both the left and right sides of the control cabinet to allow for the high pressure reserve piping. 3. A check valve (part number CV-050F) must be installed between the emergency reserve in use pressure transducer and the high pressure reserve regulator. Emergency reserve in use pressure transducer with DISS demand check union Intermediate relief valve Check valve 4. The model LLU has one ½ NPT female line pressure relief valve connection and two ¼ NPT female intermediate pressure relief valve connections. Line pressure relief valve 7

Installation Instructions Electrical 1. Use one of the two ½ conduit knock-outs provided located nearest to the top left corner of the cabinet to route conduit to supply either 110 VAC to the power supply. Note: Separate conduit should be used for low voltage wires (use knock outs provided on the left side of the box). Conduit knockouts for 110 VAC Conduit knockouts for low voltage alarm signals 2. Remove the power supply cover by loosening the two screws located at the top and bottom of the cover and then sliding the power supply cover to the right until the screws are in the center of the tear-drop shaped cut out. Next, lift the cover until it clears the screw heads and the fuse. Allow the cover to rest on the dual line regulator assembly plumbing just below the power supply. 3. Route wires of proper gauge (per local building code requirement) through the power supply conduit, thru the grommet on the power supply bracket and into the terminal strip. Neutral Load Field Ground 4. Connect the 110 VAC facility emergency power source electrical wiring to the terminal strip provided on the front of the power supply mounting bracket (per photos right). (N = neutral, L = load, FG = field ground) 8

Installation Instructions Wiring remote alarms 1. Wires for remote alarms should be brought into the cabinet thru conduit or shielded cables (check local code requirements) thru the knockouts on the left side of the cabinet shown here.. Note: Separate conduit should be used for high voltage wires never run low voltage wires in the same conduit as high voltage wires. 2. If you are installing a model CCU (cylinder x cylinder) cabinet there are three alarm signals recommended per NFPA 99, High Line Pressure, Low Line Pressure and Reserve in Use. The CCU circuit board will trigger all three of these alarms (no hi/low pressure switch is required). The line pressure transducer has been equipped with a 10 cable and may be installed outside of the cabinet downstream of the source or main line valve with the cable being wired to the manifold circuit board. 3. As an option, the line pressure transducer may be mounted inside the cabinet (as shown here). In this arrangement, a hi/low pressure switch will be required to meet the NFPA 99 recommendations. Note: the hi/low pressure switch would be wired directly to the master alarm panels not to the manifold circuit board. Knock outs for low voltage remote alarm wiring Line pressure transducer 4. Remote alarm wires are connected to the circuit board at the terminal gate labeled P2. Signal wires and Common wires for Low Line Pressure, High Line Pressure and Secondary in Use should be connected to the terminals as indicated. 5. Note: all remote alarm terminals are normally closed when the gas pressure is in the normal range. The hi/low set points pre-programmed into the manifold circuit board logic chip are as per the following charts: Alarm Pressure Settings for CCU Models (all pressures in psig) Normal Delivery Press Line Relief Setting High Line Press Set Point Low Line Press Set Point Secondary In Use Set Point 50 75 60 40 200 left bank / 150 right bank 80 150 96 64 300 left bank / 250 right bank 190 250 228 152 300 left bank / 250 right bank Alarm Pressure Settings for LLU Models (all pressures in psig) Normal Delivery Press Line Relief Setting High Line Press Set Point Low Line Press Set Point Secondary In Use Set Point 50 75 60 40 95 both banks 80 150 96 64 95 both banks 190 250 228 152 190 both banks 9

Installation Instructions Installing pigtails & attaching cylinders CCU models 1. A fitting on one end of each pigtail is stamped with a flow direction arrow. Verify that the pigtail is oriented properly before connecting it to the manifold header. 2. Connect the pigtails to the valve outlets on the manifold header with the direction of flow from the Flow direction arrow cylinder to the header end of the pigtail. (Note if the pigtail is installed backwards, gas will not flow from the cylinder to the header). Master valve 3. Check the master valves to be certain they are open (turn counterclockwise to open). (Note: the master valve should always be left open. It is to be used only in the event of an emergency). Attach pigtails to header check valve outlets using 1 1 /8 open end wrench 4. SLOWLY open all cylinder valves (turn counter-clockwise to open). Check all cylinder and pigtail connections for leaks using an oxygen safe leak test solution (any bubbles forming around connections indicate leakage). 10

Installation Instructions Installing pigtails & attaching cylinders LLU models 1. A fitting on one end of each pigtail is stamped with a flow direction arrow. Verify that the pigtail is oriented properly before connecting it to the manifold header. 2. Connect the pigtails to the valve outlets on the manifold header with the direction of flow from the cylinder to the header end of the pigtail. (Note if the pigtail is installed backwards, gas will not flow from the cylinder to the header). 3. Connect the end of the pigtail with the CGA fitting to the Use valve mating fitting on the portable bulk vessel. Open the use valve (turn counter-clockwise to open). The pressure building valve or regulator should be turned on or opened for all vessels connected to the manifold (both service and reserve banks). Allow approximately 1 hour for the portable bulk vessel(s) to build pressure. Flow direction arrow Port for 2 nd pigtail Intermediate pressure relief valve x ¼ F npt 4. Check all cylinder and pigtail connections for leaks using an oxygen safe leak test solution (any bubbles forming around connections indicate leakage). 5. Verify that the pressure being supplied to the manifold cabinet exceeds the minimum inlet pressure requirements in the table below. Minimum inlet pressure requirements for LLU Manifold Manifold delivery pressure Minimum inlet pressure Relief valve setting on vessel 50 psig 135 psig 235 psig 80 psig 135 psig 235 psig 190 psig 250 psig 350 psig 11

Start Up & Checking Procedures Start up & checking procedures 1. Turn on the 110 VAC to the unit. The digital display should illuminate showing all zeros for the Line Pressure, Left Bank Pressure and Right Bank Pressure (model CCU). Both the left & right bank Red (Depleted) LED s should be illuminated and all digital displays should read zero. Both the left and right bank Green (In Use) and Yellow LED s (Ready) should be extinguished. 2. SLOWLY open one cylinder valve on the left bank. The left bank pressure gauge (inside the cabinet) and the digital display (on the outside of the cabinet) should show the full pressure of the cylinder. The Red (Depleted) LED for the left bank should have extinguished leaving only the Green (In Use) LED illuminated. 3. SLOWLY open one cylinder valve on the right bank. The right bank pressure gauge (inside the cabinet) and the digital display (on the outside of the cabinet) should show the full pressure of the cylinder. The Red (Depleted) and the Green (In Use) LED s for the right bank should have both extinguished and the Yellow (Ready) LED should have illuminated. 4. Turn off all open left bank cylinder valves. Create a slight flow of gas in the delivery pipeline system. DISS demand valves have been provided on the line regulators. Mating DISS fittings may be used to create a flow of gas within the manifold cabinet. The left bank pressure digital display and pressure gauge should fall and the control automatically switches over to the right bank. Delivery pressure remains constant. The left bank Red (Empty) LED will illuminate. The reserve in use alarm should activate on the master alarm(s). SLOWLY reopen the cylinders on the left bank. The left bank pressure gauge and digital display should return to full pressure. The left bank yellow (Ready) LED will illuminate simultaneously the left bank red (Empty) will extinguish. All remote reserve in use alarms will be canceled. Repeat step 4 to simulate an empty right bank. 12

Emergency Reserve Model LLU Model LLU Emergency Reserve Pressure Settings & Alarm Set Points 1. The model LLU includes digital displays for the emergency reserve bank pressure the intermediate area pressure. Remote master alarms will be triggered by the model LLU for the five required NFPA 99 alarms; high line pressure, low line pressure, secondary in use, emergency reserve in use and emergency reserve low. Refer to the chart below for information on setting the delivery (outlet) pressure of the emergency reserve regulator and pre-programmed emergency reserve in use and emergency reserve low alarm set points. 2. The emergency reserve low bank pressure transducer (part # 14-3001) should be installed on the extra port on the RWP series manifold. This port is located prior (upstream) to the master valve and the regulator. Emergency reserve low bank pressure transducer Emergency reserve in use pressure transducer 3. The emergency reserve in use pressure transducer (part # 14-3002) should be installed on copper tubing (provided by plumbing contractor) after (downstream) the check valve (part # CV-050F). Note: a DISS demand check union assembly should also be installed in case this transducer would ever need to be replaced. DISS demand check union assembly (part # PS-24 oxy) Check valve (part # CV-050F) 4. Both the emergency reserve bank pressure transducer and the emergency reserve in use transducer must be wired to the manifold circuit board as indicated by the labeling instruction. Remote master alarm signal and common wires must also be connected to the manifold circuit board as indicated by the labeling instruction. Manifold Delivery Pressure Recommended Emergency Reserve Regulator Delivery Pressure Setting Pre-programmed Emergency Reserve in Use alarm set point Pre-programmed Emergency Reserve Low alarm set point 50 psig 65 psig 75 psig 1200 psig 80 psig 70 psig 80 psig 1200 psig 200 psig 170 psig 180 psig 1200 psig 13

Cylinder Replacement & Line Pressure Adjustment Cylinder replacement & handling 1. Close all cylinder valves on the depleted bank. 2. SLOWLY loosen and remove the pigtail connection from the depleted cylinders. 3. Remove depleted cylinders and replace protective caps. 4. Place and secure full cylinders into position using chains, belts or cylinder stands. 5. Remove protective cylinder caps from full replacement cylinders. With the valve outlet pointed away from all people in the area, slowly open each cylinder valve slightly to blow out any dirt or contaminants that may have become lodged into the cylinder valve. 6. Connect pigtails to cylinder valves and tighten with wrench. 7. SLOWLY turn each cylinder valve until each cylinder is fully on. 8. Observe the following conditions: The red (Empty) LED is extinguished and the yellow (Ready) LED is illuminated and the remote reserve in use alarm is cancelled. 9. The manifold supply bank is now replenished and automatically placed in reserve. Line delivery pressure adjustment 1. Leave the manifold in full operational status. 2. Create a flow condition in the delivery piping system. DISS demand valves have been provided on the line regulators. Mating DISS fittings may be used to create a flow of gas within the manifold cabinet. DISS demand valves Ball valves 3. Open the manifold cabinet door and locate the line pressure regulators. Ball valves on the inlet and outlet sides of each regulator determine which regulator is on line and which is off line. Note: when the ball valve handle is perpendicular to the pipeline, the ball valve is closed. 4. Using a 3/4 open-end wrench, loosen the locknut on the adjusting screw (on high flow models only). Turn the T bar handle clockwise to increase pressure or counterclockwise to decrease pressure. T Bar Handle 5. After adjustment, retighten the locknut on the adjusting screw and close the cabinet door. 14

General Maintenance & Error Codes General Maintenance Control Cabinet Daily Record line and bank pressures Monthly Check regulators, compression fittings and valves for external leakage. Check valves for closure ability. Annually Check relief valve pressures Check regulator seats. Manifold Headers & Pigtails Daily Observe nitrous oxide and carbon dioxide systems for cylinder frosting or surface condensation. Should excessive condensation or frosting occur it may be necessary to increase manifold capacity. Monthly Inspect valves for proper closure. Check pigtails for cleanliness, flexibility, wear, leakage, and thread damage. Replace damaged pigtails immediately. Inspect pigtail check valves for closure ability. Every 4 years Replace all pigtails Error Codes This manifold is designed and equipped with some self-diagnostic software. A flashing error code will be displayed on the left bank and right bank pressure displays when an error occurs. An error indicates: a loose or disconnected or broken wire, a miss-connected wire, a bad transducer or an overpressure situation. ERR 001- Line pressure sensor Error codes correspond from left to right with the sensor input wire terminal connections on the P3, P4 and P5 circuit board positions. ERR 002 Emergency reserve in use pressure sensor ERR 003 Left portable bulk bank pressure sensor ERR 004 Right portable bulk bank pressure sensor ERR 005 Left cylinder bank pressure sensor or high pressure emergency reserve pressure sensor. ERR 006 Right cylinder bank pressure sensor. 15

Replacement Parts Item Part Number Description Primary Regulator & Repair Kits 68-0003 0 300 psig delivery, 3,000 psig inlet, 6 port 68-0003RK Rebuild kit for primary regulator 68-0003 Line Regulators & Repair Kits 68-0004 5 125 psig standard flow line regulator 68-0004RK Rebuild kit for 5-125 standard flow line regulator 68-0004 68-0002 5 125 psig high flow line regulator 68-0002RK Rebuild kit for 5-125 high flow line regulator 68-0002 68-0001 10 200 psig high flow line regulator 68-0001RK Rebuild kit for 0 200 high flow line regulator 68-0001 Circuit Board 35-1001 Universal Manifold PLC Board 35-1002 CCU Manifold PLC Board Transducers/Sensors 14-3001 0 2,500 psig x ¼ M npt 14-3002 0 500 psig x ¼ M npt 14-3003 0 250 psig x DISS N2 14-3004 0 100 psig x DISS Oxygen 14-3005 0 100 psig x DISS Medical Air 14-3006 0 100 psig x DISS N2O 14-3007 0 100 psig x DISS CO2 DISS Demand Check Union Assemblies PS-04 Nitrous Oxide ¼ M npt demand valve x 1/8 M npt nipple PS-08 CO2 ¼ M npt demand valve x 1/8 M npt nipple PS-12 N2 ¼ M npt demand valve x 1/8 M npt nipple PS-16 Medical Air ¼ M npt demand valve x 1/8 M npt nipple PS-24 Oxygen ¼ M npt demand valve x 1/8 M npt nipple Solenoid Valves 48-1001 Used on CC all gas services except N2, N2O & CO2 Viton Seals 48-1002 Used on CC N2O & CO2 only EPDM Seals 48-1003 Used on CC for N2 & LL for OXY & N2 Vtion Seals, left side 48-1004 Used on CC for N2 & LL for OXY & N2 Vtion Seals, right side 48-1005 Used on LL for CO2 & N2O EPDM Seals, left side 48-1006 Used on LL for CO2 & N2O EPDM Seals, right side Power Supply AA400-C 110 VAC / 24 & 5 VDC Gauges 14-1018 0 4,000 psig 1 ½ x 1/8 M npt center back 14-1016 0 400 psig 2 x ¼ M npt bottom port 14-1017 0 400 psig 1 ½ x 1/8 M npt center back 14-1009 0 300 psig 1 ½ x 1/8 M npt center back 14-1008 0 100 psig 1 ½ x 1/8 M npt center back Relief Valves RV-22-075 75 psig x ½ M npt inlet RV-22-150 150 psig x ½ M npt inlet RV-22-250 250 psig x ½ M npt inlet RV-11-235 235 psig x ¼ M npt inlet RV-11-350 350 psig x ¼ M npt inlet RV-11-400 400 psig x ¼ M npt inlet Check Valve 17-4003 ½ M npt x ½ OD tube compression Pigtails with check valves 20-1001 24 single loop rigid copper O2 CGA 540 20-0001 24 Flexible stainless braided O2 - CGA 540 20-1002 24 single loop rigid copper N2O CGA 326 20-0002 24 Flexible stainless braided N2O - CGA 326 20-0003 24 Flexible stainless braided CO2 CGA 320 20-0004 24 Flexible stainless braided AIR CGA 346 20-0005 24 Flexible stainless braided N2 CGA 580 Pigtails for portable bulk 20-2001 72 Flexible with check valve O2 CGA 540 20-2002 72 Flexible with check valve N2 or Ar or He CGA 580 20-2003 72 Flexible with check valve CO2 CGA 320 20-2004 72 Flexible with check valve N2O CGA 326 Union 17-0169 ½ M npt x ½ M npt 3 piece union 1 11 ½ NPS 16

Trouble-Shooting Guide Note: trouble-shooting and repairs should be done by qualified personnel only. Symptom Cabinet Indicator Lights No indicator lights on front panel illuminate when power is connected. Red indicator lights are on but both banks are full Left & right bank pressure LED s flashing/blinking ERR 000# Loss of Cylinder Contents Audible or inaudible gas leakage (origin unknown) Venting at relief valve Probable Cause Power input Internal wiring disconnected Circuit board defective Master valve or cylinder valves on bank are closed Pigtails are installed with check valves in wrong direction Bank pressure is not sufficient for logic board to place it in In Use or Ready status Loose or disconnected or broken wire, mis-connected wire, a bad transducer, a calibration problem or an over-pressure situation. Leakage at manifold piping connections Leakage thru manifold solenoid vent / relief Regulator with bad seat Leaking gauge Regulator set too high Overpressure due to failed regulator seat Regulator freeze-up (N2O or CO2) / heater failure Remedy or Check Check electrical power supply Check all wiring connections Replace circuit board Open valves SLOWLY Close cylinders and re-install pigtails in proper flow direction Replace cylinders with full cylinders. Or, if using portable bulk vessels, open pressure building valve on vessel or replace portable bulk vessel with higher delivery pressure portable bulk vessel Check wires for good and correct location connection to circuit board (See ERROR CODES pg 15) If all wires are connected properly and located properly it may be necessary to replace a transducer. Contact Tri-Tech if pressure exceeds transducer rating + 5%. (2,600 psi or 525 psi). Tighten, reseal or replace Replace solenoid valve Rebuild or replace regulator Replace gauge Set delivery pressure per specifications Rebuild or replace regulator Repair heater or add heater and consider adding additional cylinders 17

Trouble-Shooting Guide Note: trouble-shooting and repairs should be done by qualified personnel only. Symptom Loss of Cylinder Contents Both banks feeding Changeover occurs, reserve in use alarm is triggered and then clears Probable Cause Leaking header/pigtail connection Leaking intermediate check valve Leaking solenoid valve Model CCU primary regulator(s) out of adjustment Model LLU inlet pressure to control cabinet is too low Model LLU portable bulk venting Model LLU gas flowing thru economizer circuit Manifold is unable to support required flow Model LLU portable bulk vessel(s) are unable to support required flow Remedy or Check Tighten fitting or re-tape with Oxygen safe Teflon tape (if npt fitting) and tighten. Replace check valve Replace solenoid valve Set delivery pressure to specifications per chart on page 20 Verify that minimum inlet pressure requirements are met Gas usage not high enough to justify portable bulk reserve This is normal when reserve bank pressure is 50 psig greater than service bank pressure no correction needed to manifold control cabinet. May consider reducing size of banks if reserve bank is more than 35% depleted at time it is placed in service In Use If gas is flowing thru economizer when the reserve bank pressure is not 50 psig greater than service bank pressure the economizer check valve needs to be replaced. Increase manifold flow capacity (call factory for assistance) Increase bank size. If using two or more portable bulk vessels per bank currently, connect pigtail(s) (no check valve) from vent to vent of all vessels on the same bank and open the vent valves. This will equalize the head pressure of the vessels and utilize the combined vaporization capacity not just the capacity of the vessel with the highest delivery pressure set point. 18

Appendix A Appendix A Glossary of Terms AC BAR Alternating Current An electric current that reverses direction or polarity at regular intervals. Bar A measurement of the force in a compressed gas system. 1 BAR = 14.7 psig (1 atmosphere) Check Valve A valve which operates mechanically and automatically to stop a reverse flow of gas DC Direct Current An electric current that flows in one direction. The current can be steady or pulse. Economizer Circuit A mechanical piping circuit which allows built up reserve gas to be used in low volume rather than allowing the gas to vent to atmosphere. KPa LED NFPA Kilopascals A measurement of the force in a compressed gas system. 1 kpa =.14 PSI Light Emitting Diode A semiconductor diode that converts applied voltage to light. National Fire Protection Association The National Fire Protection Association is an association engaged in standards development. NC PSI Normally Closed An electrical circuit in which the switch is normally closed. Current flows through the circuit in normal operation. Only when the switch is opened is the flow of current stopped. Pounds per Square Inch A measurement of the force in a compressed gas system. 1 PSI = 6.9 kpa Solenoid Valve A valve that is opened or closed electromagnetically. Transducer A device that converts pressure into an electrical signal. Transient Signal An intermittent and brief signal that quickly corrects and returns the alarm to a normal operating mode before monitoring personnel can silence the alarm V Voltage Voltage is electrical pressure or force. One volt is equal to the difference of electrical potential between two points on a conducting wire carrying a constant current of one ampere when the power dissipated between the points is one watt. NO Normally Open An electrical circuit in which the switch is normally open. No current flows through the circuit in normal operation. Only when the switch is closed is the flow of current started. A normally open solenoid valve is one designed so that it is open when there is no power to the solenoid and closed when it is energized. 19

Appendix B - Specifications Appendix B Manifold Specifications Maximum Inlet Pressure: Model CCU: 2,500 psig Model LLU: 400 psig Operating Ambient Temperature range: Model CCU: 0 F (-18 C) to 120 F (49 C) all gases except N20 & CO2 20 F (-7 C) to 120 F (49 C) N2O & CO2 Model LLU -20 F ( -29 C) to 120 F (49 C) Storage Temperature: -20C(-4F) to +85C(185F) AC Input: Input Fuse: 120 volts AC - 50-60 Hz 5 amp input AC line fuse protects the input wiring to power supply Power Consumption: 45W (0.4 amps using 120 VAC) maximum without heaters 245W (2.1 amps using 120 VAC) maximum with heaters Pressure Measurement Accuracy: 0-100 PSIG transducer +/-1% - Line Pressure Oxygen, Nitrous Oxide, Medical Air, Carbon Dioxide 0-250PSIG transducer +/-1% - Line Pressure-Nitrogen 0 500 PSIG transducer +/-2% Bank & Intermediate Pressures model LLU only 0 2,500 PSIG transducer +/-2% Bank Pressures model CCU, Emergency Reserve Bank Pressure model LLU Solenoid Valve: 24VDC Normally Open (Valve opens when de-energized) Dimensions Control Cabinet: Dimensions excluding inlet & outlet fittings 15 ¾ W x 24 ¾ H x 9 ¼ D Dimensions including inlet & outlet fittings 17 ¼ W x 27 H x 9 ¼ D Line Pressure Transducers: Housing dimensions: 1.990W x 1.990H x 3.625 Length including inlet fittings Primary Regulator Settings (CCU Models) Note: All settings done with full cylinder pressure and with slight gas flow thru the manifold. Primary regulator outlet pressure will vary with varying inlet pressures. (The outlet pressure will rise as the cylinder pressure decreases). All pressures shown in psig. Normal Delivery Pressure (factory delivery pressure) Left Primary Regulator Set Point Right Primary Regulator Set Point 50 160 120 80 260 220 190 260 220 20

Genesys Manifold System Appendix C Piping Schematic Model CCU Ball valves Line pressure gauge Outlet ½ F npt Line pressure relief valve ½ F npt DISS demand valves may be used to bleed line pressure during service and as emergency feed ports for the facility Line pressure transducer may be installed downstream of manifold source valve to eliminate separate hi/low pressure switch. Manifold PCB will trigger master alarm hi/low line pressure alarms Line pressure regulator Line pressure regulator Intermediate pressure gauge Check valve Check valve Inlet pressure gauge Inlet pressure gauge Inlet pressure transducer Inlet pressure transducer Left bank primary regulator outlet pressure gauge Right bank primary regulator outlet pressure gauge Left bank primary regulator Right bank primary regulator Solenoid valve Intermediate pressure relief valves Intermediate relief outlet ½ M npt 21

Appendix D Piping Schematic Model LLU Ball valves Line pressure gauge Outlet ½ F npt Line pressure relief valve ½ F npt DISS demand valves may be used to bleed line pressure during service and as emergency feed ports for the facility Line pressure transducer may be installed downstream of manifold source valve to eliminate separate hi/low pressure switch. Manifold PCB will trigger master alarm hi/low line pressure alarms Line pressure regulator Line pressure regulator Intermediate pressure gauge Economizer circuit Economizer circuit Check valve Check valve Inlet pressure transducer Inlet pressure transducer Inlet pressure gauge Inlet pressure gauge Solenoid valves 22

Wiring Schematic Model CCU 23

Wiring Schematic Model LLU 24

Wiring Schematic CCU with Heater 25

Appendix H Field Adjustments Appendix H Pressure Display Units of Measure The digital pressure displays may be PSIG, kpa or BAR. If a selection is made at the time of order, your manifold will be set up to display the appropriate units. If no selection is made at the time of order, the unit will be set up to display in PSIG when shipped from Tri-Tech Medical. 1. To change the units of measure a jumper has been provided (see photo part # AA400-92) which must be installed on the circuit board. Before proceeding, remove the power from the manifold. 2. Remove the circuit board cover by loosening the four screws, sliding the cover so the screws are centered in the large part of the tear-drop shaped opening, then lift the cover off of the mounting posts. 3. Locate the set of jumper pins labeled JA1 on the lower left corner of the circuit board. 4. To change the display to kpa, install the jumper onto the top left & right pins of JA1. To change the display to BAR, install the jumper onto the next lower (from the top) left & right pins. 5. Replace the circuit board cover and restore power. The display will now reflect the units of measure selected (kpa or BAR). (Notes: all kpa units are x 10. Bar units are displayed with a one position decimal and decimal point.) JA1 pin block JA1 pin block with jumper installed to display BAR 26