CABLE PULLING GUIDELINES

Similar documents
INSTALLATION INFORMATION

Installation Guideline for Placing Fiber Optic Cable into an Underground Duct

TECHNICAL BULLETIN PINPOINT CONDUIT COUPLING AND SPLICING RECOMMENDATIONS

Appendix 4 Don t Get Hurt Pulling Cable

MV-105 MEDIUM VOLTAGE CABLE. 5kV, 8kV, 15kV, 25kV & 35kV

Ninth Edition, September Cable Installation Manual for Power and Control Cables. Foreword

SOUTHWIRE company SUbSTaTIOn cable InSTallaTIOn guide

I. Purpose... 1 II. Introduction... 2 III. General and Safety Precautions... 2 IV. Reference Documents... 3 V. Installation Overview...

Work Standard CABLE PULLING OPERATIONS

Type MMV Medium Power Cable

Other Si min/max. Cr min/max. 0.4/ / / / Bal.

Amphenol. PowerLink Solar Cables. Amphenol 97 Series Connectors are UL recognized and CSA recognized.

GENERAL APPLICATION NOTES

Bore-Gard Installation - 1,000 ft. Perry, Oklahoma

A hose layline contains important information for specifying the replacement assembly: manufacturer, hose trade name, working pressure and hose ID.

Electrical Tapes Selection Guide. 3Innovation

FIBERGLASS MULTI-GARD MULTI-CELL RACEWAY

Rules for the Installation, Inspection and Testing of Air Reservoirs (Other than on Locomotives)

woodlander B y w i r e r o p e i n d u s t r i e s

Installation and Operating Instructions for Automotive Winch Synthetic Rope

Donaghys Winch Ropes. Handling & Installation Guide

PSH (inch version) Application example. Pneumatic 2-Finger Parallel Grippers Long-stroke Grippers. Stroke per finger 14 mm.. 64 mm. Sizes 22..

Typical Strength of Glued Connection. Typical Strength of Screwed Connection


will not support combustion

Wire Rope Ordering Information

Made in the USA. For Fall Protection Only. SafeLok Part Description

AMTEC SUPPORT GRIPS STANDARD, HEAVY DUTY & CONDUIT GRIPS

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and

Related Elevator Products

MECHANICAL ASPECTS OF SUBMARINE CABLE ARMOUR

S Surge Arresters

Chapter 5 Site Considerations and Set-ups Table of Contents

Introduction GUIDELINES FOR INSTALLATION PREINSULATED TUBE UNITHERM... Principal of Operation

AUSTRALIAN LIFTING CENTRE PTY LTD

FOR MORE INFORMATION CONTACT OUR NEAREST BRANCH OFFICE

BRAKE WINCH RUP 503-[T/BT] EQUIPMENT FOR LIFTING LOADS. AT 053-[T/BT] xx

drilltech land drilling pipelining B y W i r e r o p e i n d u s t r i e s

Galvanized Rigid Conduit

Exam 3 Phys Fall 2002 Version A. Name ID Section

General Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association

ESA Elbow Sealing Adapter Kit

C-Line Electrical Connectors

INSTALLATION PROCEDURE FOR OPGW FIBER OPTIC CABLES

Pneumatic Grippers Swivel Modules

OPERATING and MAINTENANCE INSTRUCTIONS MAXIS Grips

Irrigation &Hydraulics Department lb / ft to kg/lit.

Hydrostatic Pressure Testing

Canadian Electrical Code, Part I Full Impact Assessment

MUELLER. Mega-Lite Drilling Machine. Reliable Connections. table of contents PAGE. Equipment 2. Operating Instructions 3-4. Parts Information 5

pvc well casing & drop pipe

Ph:

CP10K. 10,000 lb. Cable Puller Instruction Sheet. SAFETY ISSUES

PFC Lightweight Composite Push Up Mast. Operating Manual

APPENDIX D HYDRO-VAC

Presented to the International Technical Rescue Symposium, November Abstract

Typical application of rope access methods in accordance with SOP 43

All work on this packet is my own. I have not done anything to give myself or anyone else an unfair advantage on this assignment.

Level 3 Cambridge Technical in Engineering 05822/05823/05824/05825/05873 Unit 3: Principles of mechanical engineering

These products are available only in packs of 100 pieces

Sandvik Jaw Crushers

Life Cycle Testing of 3x19 Wire Rope

Installation and Operation Instruction Manual

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

VB-7212 Series. Application. Features. Applicable Literature. 5/8" O.D., 45 SAE Flared Stem Up Open, Two-Way Valves General Instructions

Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines

U.S. TSUBAKI BS/DIN ROLLER CHAIN

Installation and Initial Start-Up Guide for PSG Ex² Analyser Lines English Version

USER S MANUAL V3.0. MULTI-PURPOSE DEVICE Pulley Descent Control Belay

Job Sheet 12. Feeding Conductors into Conduit OBJECTIVE PROCEDURE

PSH. Application example. Pneumatic 2-Finger Parallel Gripper Long-stroke Gripper. Stroke per finger 14 mm.. 64 mm. Sizes

LGZ. Application example. Pneumatic 3-Finger Centric Gripper Universal Gripper. Sizes. Gripping force 120 N 1470 N. Weight 0.1 kg 0.

SQWUREL Testing, Certifications and Quality Control

and its weight (in newtons) when located on a planet with an acceleration of gravity equal to 4.0 ft/s 2.

4-63 T UBE FITTINGS TUBING P OLYURETHANE TUBING SERIES TU P RODUCTS FOR A LIST OF STOCKED PRODUCTS, PLEASE SEE THE CURRENT SMC PRICE LIST S TOCKED

MULETAPE, ROPE, GRIPS, AND LINES

Experiment 13: Make-Up Lab for 1408/1420

Live Line Tool Techniques

Outside Plant Single Armor Double Jacket

WINCH USER GUIDE WARN 3700 Utility Winch Part Number: 93700

PWG-S. Application example. Pneumatic 2-Finger Angular Gripper Universal Gripper. Sizes. Gripping moment 5.98 Nm Nm. Weight 0.21 kg 1.

BC Shackle. Made in the China. Alloy Steel Anchor Shackle. Instructions for handling and use - Please read in full before using this device

The Mechanics of Friction in Rope Rescue

Roughneck TM Mesh Slings

MoBiLe CrAnes. surelift. B y W i r e r o p e i n d u s t r i e s. tower CrAnes. port CrAnes

Operating Instructions

DT400/436 Tee Connector Installation Instructions

PRE-PURCHASE DECISIONS...1 BEFORE DELIVERY...1

High-performance submersible pressure transmitter For level measurement Model LH-10

The Outer Seal is highly abrasion resistant and provides mechanical stiffness to the splice in order to better match the cable stiffness.

for Cold-Formed Steel Framing Products

[Title of the course]

Circular Motion - Horizontal

PhysicsAndMathsTutor.com

09 - Choosing /sizing a cylinder and valve

Pneumatic Gripping Modules. Pneumatic 2-Finger Radial Grippers

Bladder Tank Installation & System Design Information

Swimming Pool Requirements

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

LGP Pneumatic 2-Finger Parallel Gripper Universal Gripper Sizes Weight Gripping force Stroke per finger Workpiece weight

Transcription:

The following data is intended as a general guide to aid individuals with the installation of cables inside ducts, raceways or conduit. These recommendations are based upon a study sponsored by the ICEA (Insulated Cable Engineers Association). The information contained herein is not a comprehensive set of instructions. An engineer or technician experienced with installations should be consulted for particular applications where out-of-the-ordinary conditions exist or could be encountered. PREFACE Before installing cables, it is recommended that the routing be thoroughly inspected to avoid bends and/or pulling tensions that exceed specified limits. Good design of the duct, raceway or conduit itself along with the routing is essential to ensure damage-free installation and the full service life of all components. MAXIMUM PULLING TENSION ON A CABLE For cable equipped with pulling eye or pulling bolt, the formula shown below is used to calculate the maximum allowable pulling tension on the cable for the entire routing. Tm = K x n x CMA (Formula 1) Where:Tm = maximum pulling tension (lbs.) (see Appendix A for calculated tensions)* K = constant 0.008 for copper conductors 0.006 for aluminum conductors n = number of conductors CMA = circular mil area for one conductor *This value is the maximum tension that can be placed on the cable or, if pulling more than one conductor at a time, group of cables. In some cases this could exceed the limitations of the pulling equipment being used. The specifications set forth by the pulling equipment manufacturer (if available) should be compared to this value, and the lower of the two should govern. CABLE GRIP TENSION When cable grip is used over non lead-jacketed cable, the pulling tension should not exceed 1,000 lbs or 1,000 lbs. per grip (when used with multi-conductor cables) and also the tension calculated in Formula 1. CALCULATED PULLING TENSION straight section of conduit Ts = L x W x f (Formula 2) Where:Ts = pulling tension at end of straight section, lbs. L = length of straight section, feet W = weight of cable, lbs./ft. f = coefficient of friction (if unknown, use 0.5) CALCULATED PULLING TENSION curved (bent) section of conduit Tb = Ts x e fa (Formula 3) Where:Tb = pulling tension at end of bend, lbs. Ts = pulling tension at end of straight section entering the bend, lbs. e = naperian log base (2.718) f = coefficient of friction (if unknown, use 0.5)

a = angle of bend (radians) (See Table 1 with e fa values for common angles and Tables 2 & 3 for minimum bend radii) MAXIMUM SIDEWALL PRESSURE AT BENDS Sidewall pressure is caused by the tension in the cable acting horizontally and the weight of the cable acting vertically. Generally, the maximum sidewall pressure should not exceed 300 lbs/foot of radius, i.e., the tension of a cable immediately as it leaves a bend must not be greater than 300 times the bend radius (in feet). Shown below are formulas to calculate the maximum allowable tension at a bend and the actual sidewall pressure. **Bend radii for training cable into final position (no tension on the cable) are shown in Tables 2 & 3. There are no published limits for bend radii when pulling cable (when the cable is under tension), however Superior-Essex recommends doubling the minimum bend radii shown on Tables 2 & 3 when pulling cable through conduit. Tb m = 300 x r (Formula 4) Where:Tb m = maximum allowable pulling tension at bend, lbs. r = bend radius, feet P = Tb / r (Formula 5) Where:P = actual sidewall pressure on cable, lbs./ft. Tb = pulling tension at and of bend, lbs. r = bend radius, feet The maximum allowable pulling tension at bend (Tb m ) is the limit that the calculated pulling tension (Tb) should be compared to. If Tb is greater than Tb m, the possibility of redesign or re-routing should be considered. TABLE 1 VALUES OF e fa FOR COMMON ANGLES BEND ANGLE f = 0.7 f = 0.6 f = 0.5 f = 0.4 f = 0.3 f = 0.15 ( ) 15 1.20 1.17 1.14 1.11 1.08 1.04 30 1.44 1.37 1.30 1.23 1.17 1.08 45 1.73 1.60 1.48 1.37 1.27 1.13 60 2.08 1.87 1.68 1.52 1.37 1.17 75 2.50 2.19 1.92 1.69 1.48 1.22 90 3.00 2.57 2.19 1.87 1.60 1.27 e fa WHITE PAPER

TABLE 2 MINIMUM BEND RADII FOR NON-SHIELDED/NON-ARMORED POWER CABLES THICKNESS CABLE O.D. (inches) of CONDUCTO R 0 to 1.000 1.001 to 2.000 2.001 and Larger INSULATIO MINIMUM BENDING RATIOS AS A MULTIPLE OF CABLE O.D. N (inches) 0 to 0.169 4 5 6 0.169 and larger 5 6 7 Values taken from ICEA S-95-658 TABLE 3 SUGGESTED MINIMUM BEND RADII FOR PORTABLE JACKETED CABLES MINIMUM BEND RADIUS AS A CABLE TYPE MULTIPLE OF CABLE O.D. THERMOSET-JACKETED 0-5kV 6 THERMOSET-JACKETED 5+kV 8 CONTROL CABLE (7 conductor & over) 20 FLAT-TWIN CABLES USE MINOR O.D. TO DETERMINE MINIMUM BEND RADIUS EXAMPLE 1/0 AWG THHN, cable weight = 0.37 lbs./ft. D 90 E A 200' 45 B 70' C 100' F 45 G 50' H MAXIMUM PULLING TENSION, Tm Tm =.008 x 1 x 105600 = 846 lbs

PULLING FROM POINT H (FEEDING IN FROM A ) Tension @ A = Zero Tension @ B (Ts 1 ) = 200 x.37 x.5 = 37 lbs Tension @ C (Tb 1 ) = 37 x 1.48 = 55 lbs Tension @ D (Ts 2 ) = 55 + [70 x.37 x.5] = 68 lbs Tension @ E (Tb 2 ) = 68 x 2.19 = 149 lbs Tension @ F (Ts 3 ) = 149 + [100 x.37 x.5] = 168 lbs Tension @ G (Tb 3 ) = 168 x 1.48 = 249 lbs Tension @ H (Ts 4 ) = 249 + [50 x.37 x.5] = 258 lbs PULLING FROM POINT A (FEEDING IN FROM H ) Tension @ H = Zero Tension @ G (Ts1) = 50 x.37 x.5 = 9 lbs Tension @ F (Tb1) = 9 x 1.48 = 13 lbs Tension @ E (Ts2) = 13 + [100 x.37 x.5] = 32 lbs Tension @ D (Tb2) = 32 x 2.19 = 70 lbs Tension @ C (Ts3) = 70 + [70 x.37 x.5] = 83 lbs Tension @ B (Tb3) = 83 x 1.48 = 123 lbs Tension @ A (Ts4) = 123 + [200 x.37 x.5] = 160 lbs P B-C = 55 / 10 = 5.5 lbs/ft P D-E = 149 / 10 = 14.9 lbs/ft P F-G = 249 / 10 = 24.9 lbs/ft P G-H = 13 / 10 = 1.3 lbs/ft P E-D = 70 / 10 = 7 lbs/ft P C-B = 123 / 10 = 12.3 lbs/ft Pulling from either direction will not result in the tension or sidewall pressure exceeding the limits (846 lbs & 300 lbs/ft). However, pulling from point A (feeding the cable from H )will result in approximately 40% less tension being placed on the cable. Therefore, it is most desirable to pull from point A. GENERAL GUIDELINES FOR CABLE PULLING PREPARATION: 1. Establish the direction of the pull based on safe pulling tensions and sidewall pressure calculations. 2. Select the correct size pulling eyes, bolts or grips. 3. Locate feeder reels, spools, etc. such that the tension at the feeding end is minimized. 4. Use pulling equipment that provides smooth speed control. 5. Choose a pulling rope that has the required tensile strength. 6. Prior to pulling, make sure the conduit is clean and free of dirt, water, scale, etc. 7. For long and/or heavy pulls, pre-lubricate the conduit and pull rope, particularly when using PVC. 8. Install a dynamometer. CABLE PULLING: 1. Apply pulling lubricant (compound) liberally during the installation. 2. If possible, utilize two-way communication at both ends of the run, particularly on long runs. 3. Accelerate slowly and smoothly to a constant pulling speed. 4. Avoid letting the cable stop part way through the pull. The friction is greatly increased when re-starting a pull. AFTER PULLING: 1. Seal the ends of the installed cable to prevent moisture from getting inside the cable. 2. High voltage testing is recommended both before and after the installation. WHITE PAPER

APPENDIX A CALCULATED MAXIMUM PULLING TENSIONS GAUGE SINGLE THREE FOUR SIZE CONDUCTOR CONDUCTOR CONDUCTOR 18 13 39 52 16 21 62 83 14 33 99 132 12 52 157 209 10 83 249 332 8 132 396 528 6 210 630 840 4 334 1,002 1,336 3 421 1,263 1,684 2 531 1,593 2,124 1 670 2,009 2,678 1/0 846 2,539 3,386 2/0 1,065 3,194 4,259 3/0 1,342 4,027 5,370 4/0 1,693 5,078 6,771 250 2,000 6,000 8,000 300 2,400 7,200 9,600 350 2,800 8,400 11,200 400 3,200 9,600 12,800 450 3,600 10,800 14,400 500 4,000 12,000 16,000 600 4,800 14,400 19,200 750 6,000 18,000 24,000 1000 8,000 24,000 32,000 These values are the maximum tensions that can be placed on the cable or, if pulling more than one conductor at a time, group of cables. In some cases these values could exceed the limitations of the pulling equipment being used. The specifications set forth by the pulling equipment manufacturer (if available) should be compared to this value, and the lower of the two should govern. EDITOR: STEVE ECKARDT ESSEX ELECTRICAL PRODUCTS ENGINEERING Copyright 2003 Essex Electric Inc.