ICHEME SYMPOSIUM SERIES NO. 139 FUEL GAS EXPLOSION GUIDELINES - PRACTICAL APPLICATION

Similar documents
REQUIREMENTS FOR VALIDATION OF MATHEMATICAL MODELS IN SAFETY CASES

USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT

Journal of Applied and Industrial Sciences, 2014, 2 (4): , ISSN: (PRINT), ISSN: (ONLINE)

PRAGMATIC ASSESSMENT OF EXPLOSION RISKS TO THE CONTROL ROOM BUILDING OF A VINYL CHLORIDE PLANT

Blast Damage Consideratons for Horizontal Pressure Vessel and Potential for Domino Effects

Practical Modelling & Hazard Assessment of LPG & LNG Spills

Internal Explosion Methodologies

Part 2.5 Dispersion Modeling Using ALOHA

Fires and Explosions: What You Need to Know to Prevent Them

Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment

Comparison of Large-Scale Vented Deflagration Tests to CFD Simulations for Partially Congested Enclosures


PSM TRAINING COURSES. Courses can be conducted in multi-languages

THE EXTERNAL EXPLOSION CHARACTERISTICS OF VENTED DUST EXPLOSIONS.

Transient Analyses In Relief Systems

VENTED CONFINED EXPLOSIONS INVOLVING METHANE/HYDROGEN MIXTURES

ASSESSING RISKS TO OCCUPANTS OF EXISTING BUILDINGS ON CHEMICAL PLANTS DUE TO HAZARDS OF FIRE AND EXPLOSION

Identification and Screening of Scenarios for LOPA. Ken First Dow Chemical Company Midland, MI

THE SIGNIFICANCE OF HAZARD ENDPOINTS IN QUANTITATIVE RISK ANALYSIS

Abstract. 1 Introduction

Engineering Safety into the Design

SIMULATIONS OF HYDROGEN RELEASES FROM A STORAGE TANKS: DISPERSION AND CONSEQUENCES OF IGNITION

CONVECTION SECTION FAILURE ANALYSIS AND FITNESS-FOR-SERVICE ASSESSMENT

Uncertainty in the analysis of the risk of BLEVE Fireball in process plants and in transportation

Dow s New Practice for Locating Temporary Portable Buildings. P. Partridge 9/29/05 UNRESTRICTED - May be shared with anyone Slide 1

Prediction of gas explosion overpressure interacting with structures for blast-resistant design

A NEW PROCESS FOR IMPROVED LIQUEFACTION EFFICIENCY

CFD Modelling of LPG dispersion

Evaluation of Northwest Citizen Science Initiative (NWCSI) March 7,2015 Report Summary

Module 03 Accident modeling, risk assessment and management Lecture 04 Explosions

Describe Flammable Gas Measurement

Process Safety Management Of Highly Hazardous Chemicals OSHA 29 CFR

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

Workplace Safety and Health (Major Hazard Installations) Regulations 2017 S 202/2017

Safety in Petroleum Industry

Study on Intensity of Blast Wave Generated from Vessel Bursting by Gas Explosion

INHERENTLY SAFER DESIGN CASE STUDY OF RAPID BLOW DOWN ON OFFSHORE PLATFORM

Introduction to Emergency Response & Contingency Planning

Fire and Safety for Offshore drilling and production Ajey Walavalkar ANSYS Inc.

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 5 Utilities Gas Emergencies Revised

Misuse of Combustible Gas Meters

Analysis of the application and sizing of pressure safety valves for fire protection on offshore oil and gas installations Annex I

THE BAKER REPORT HOW FINDINGS HAVE BEEN USED BY JOHNSON MATTHEY TO REVIEW THEIR MANUFACTURING OPERATIONS

Simulation and modelling of water spray in the 3D explosion simulation program FLACS. Elin Kristin Dale

Best Practice RBI Technology Process by SVT-PP SIMTECH

Flammability Chart. Gas Formula Ignition

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

SAFETY PIPELINE. Simonette Expansion Pipeline Project

Using LOPA for Other Applications

Interchangeability Criteria.

Development of Accidental Collapse Limit State Criteria for Offshore Structures

AN APPROACH TO THE PROBLEMS OF PROCESS HAZARDS IN PLANT DESIGN

LIQUEFIED PETROLEUM GAS (LPG) AND NATURAL GAS (NG) - FIRE PREVENTION ISSUES

There are three fuelling systems which use LNG/CNG and which may be found in vehicles today:

Vented confined explosions involving methane/hydrogen mixtures

LPG TANK INFORMATION An energy company that puts

Engineering Models for Vented Lean Hydrogen Deflagrations

The Science of Quantitative Risk Assessment for Explosives Safety

MODELLING OF FUME EXTRACTORS C. R.

STORAGE OF COMPRESSED GAS CYLINDERS (SAF-SPI-15)

I.CHEM.E. SYMPOSIUM SERIES NO. 97 THE FLASH-BACK HAZARD IN STACKS DISCHARGING FLAMMABLE GASES

The Influence Of Vessel Volume And Equivalence Ratio In Vented Gas Explosions

Annexure 2: Rapid Risk Assesment RISK ANALYSIS

MAJOR INDUSTRIAL HAZARDS

Expert System for LOPA - Incident Scenario Development -

Modelling Hazardous Consequences of a Shale Gas Well Blowout

The Comparison of CFD with a Traditional Method Used in an Incident Investigation Case Happened in Taiwan

QUANTIFYING THE TOLERABILITY OF POTENTIAL IGNITION SOURCES FROM UNCERTIFIED MECHANICAL EQUIPMENT INSTALLED IN HAZARDOUS AREAS

3 rd Year Design Module Scope

HEALTH AND SAFETY PROGRAM 201 HOT TAP PERMIT/FILLET WELD REPAIRS

Abstract. Geometry Obstructions Ventilation Wind conditions

S1, S2, S3, S5, S6, S7, S8, S12 and S13 Separators

Spirax Compact FREME Flash Recovery Energy Management Equipment

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

U. S. OIL & REFINING CO. M A T E R I A L S A F E T Y D A T A S H E E T

MODELING OF HYDROGEN EXPLOSION ON A PRESSURE SWING ADSORPTION FACILITY

SUPERSONIC GAS TECHNOLOGIES

CFD Modelling of Blast Waves from BLEVEs

Risks Associated with Caissons on Ageing Offshore Facilities

DIGITAL SOLUTIONS TRAINING CATALOGUE. QRA and CFD simulation. Phast, Safeti and KFX SAFER, SMARTER, GREENER

The model of thermal response of Liquefied Petroleum Gas Tanks subjected to accidental heat input

SPONTANEOUS IGNITION OF PRESSURIZED HYDROGEN RELEASE

Gas explosion in the cat cracking and gas plant units of a refinery 9 November 1992 La Mède [Bouches du Rhône] France

ISO INTERNATIONAL STANDARD. Small craft Liquefied petroleum gas (LPG) systems

IMPERIAL CHEMICAL INDUSTRIES LIMITED PETROCHEMICALS DIVISION. SAFETY NEWSLETTER No. 53

I. CHEM. E. SYMPOSIUM SERIES NO. 85

Physical explosion analysis in heat exchanger network design

Yakima County Fire District 12 Standard Operating Guidelines SOG 5-1 Hazardous Materials Operations

Advances in Low Voltage Motor Control Center (MCC) Technology Help Reduce Arc-Flash Hazards and Minimize Risks

Hydrogen and fuel cell stationary applications: key findings of modelling and experimental work in the HYPER project

Impact on People. A minor injury with no permanent health damage

MODELLING OF POOL FIRE AND INJURY PREDICTION CONSIDERING DIFFERENT WIND SPEEDS AND DIRECTIONS IN OFFSHORE PLATFORM

IS YOUR FLAP VALVE IN COMPLIANCE WITH NFPA ?

Using Consequence Modeling to Help Make Emergency Decisions

Learning from Dangerous Occurrences in the Chemical Industries

Fitness for Service Assessment of Ageing Pressure Vessel Experiencing External Corrosion: A Case Study

GUIDELINE FOR THE LOCATION OF OCCUPIED BUILDINGS IN INDUSTRIAL GAS PLANTS

BASF Flash Fire FRC Assessment Tool

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E

Savard Labor & Marine Staffing, Inc. Compressed Gas Safety Program Rev3/14

Transcription:

FUEL GAS EXPLOSION GUIDELINES - PRACTICAL APPLICATION R.F. Barton Sedgwick Energy Ltd, London, El 8DX Sedgwick 1995 Prediction of blast and fire damage to process plant and buildings arising from a catastrophic vapour cloud explosion is important for the insurance industry in order to assess underwriting exposures. Based on fundamental research insights, a new financial consequence model has been developed. This paper describes the model basis and its practical application. Comparison with recent industry losses is presented. INTRODUCTION The accidental release of a combustible gas or vapour into the atmosphere can lead to the formation of a flammable cloud. Under particular conditions, the combustion of such clouds can produce damaging overpressures. These events are known as vapour cloud explosions. Probably the most well known occurred at Flixborough, United Kingdom in 1974 following the release of cyclohexane and, more recently, at Pasadena, USA in 1989 when a breakdown in operating and maintenance procedures resulted in the release of the contents of a high density polyethylene loop reactor. Such explosions have led to extensive property damage and, in many cases, injuries and loss of life. In addition, a company s business can be severely disrupted causing loss of revenues. The total financial loss associated with the Pasadena explosion approached US$ 1.7 billion. Although these catastrophic explosion events are considered remote and of low probability, there have been over 200 such incidents in the last 50 years [1]. Some of the more significant events are listed in Table 1 with property losses updated to reflect 1995 values. The table also highlights the diversity of operation and materials involved in the initial hydrocarbon release. The significant financial consequences reflect the large amounts of capital tied up in the refining, petrochemical and chemical industries in what are often complex, high technology facilities. 285

VAPOUR CLOUD EXPLOSION AND INSURANCE CONSIDERATIONS Vapour cloud explosions, or VCEs, are of key interest to the insurance industry since, along with jet fires and natural perils such as earthquakes and hurricanes, they can represent the estimated maximum loss (EML) to which an insurance underwriter is exposed. For the operator, knowledge of the EML ensures that optimum levels of insurance are purchased as part of any risk management programme. Confidence in EML prediction is, therefore, of prime concern to operators and insurers alike. In predicting financial property damage, the insurance industry has relied on two types of approach in recent years. The first involves empirical prediction tools based on insurance loss history, while the second is calculation of overpressure and hence, fire and blast damage by equating the amount of hydrocarbon released to an equivalent mass of TNT explosive. Review of these modelling approaches revealed a number of weaknesses which, coupled to the insights from industrial research by organisations such as Shell Research [2], British Gas [3] and TNO [4], prompted development of the Cates approach [5] into an insurance model for predicting catastrophic property damage loss. LOSS ASSESSMENT MODEL BASIS The basis for the Sedgwick model reflects current understanding of vapour cloud explosions, i.e. under practical plant conditions, fast flame speeds are only generated by regions of high congestion or semi-confinement, thereby giving rise to damaging overpressure. The model at this time is applicable to methane, LPG and most refinery and petrochemical materials. More reactive systems, including propylene oxide, ethylene oxide or acetylene, fall outside the scope of the model. The extent of flame acceleration, and hence overpressure potential, is a function of gas concentration, the degree of congestion or confinement within a plant structure, and material type. Overpressure from the explosion epicentre, which is centred on a plant structure, decays acoustically according to the relationship published by Cates, i.e. P = (R o/r)p max and r = R o + r / where P is the overpressure at a distance r / from the edge of an effective source volume V of radius R o, defined as R o = 3 (3V/2π). The volume term reflects not only the volume of the process structure, but also includes allowance for the fact that a part of the explosion will take place in the turbulent gas driven outside of the confined or congested area. A typical industry plant structure is of the order of 40,000 m 3. P max is the maximum pressure assumed uniform throughout the source volume where the vapour cloud explosion is centred. The gas concentration within the cloud is assumed to be stoichiometric, i.e. conditions whereby maximum flame temperatures and, therefore, overpressure will result. P max is material-dependent and values for different hydrocarbon types for an industry typical plant structure in terms of layout is shown in Table 2. For more highly congested structures P max will be higher, and similarly for more open structures flame speed, and hence overpressure, will be lower. Within the Sedgwick model, four types of plant congestion are defined: Minimal, Low, Typical and Severe. The choice of congestion category follows the guidelines within Cates in terms of equivalent layers and separation as a function of equipment diameter. 286

In determining the degree of congestion, a logic chart is followed, which is attached at the end of the paper. Should the hazard area be enclosed by solid walls or large obstacles such as vessels to the extent of 60% confinement or greater, then a Severe categorisation is automatically selected. The different P max potential for various hydrocarbon types is related to the different combustion kinetics of the burning processes involved. Using the fractal scaling theory of Taylor and Hirst [6], turbulent burning velocity for a given plant geometry will be proportional to the product of the laminar burning velocity and expansion ratio of the gas raised to the power of 1.36. Since overpressure is proportional to the turbulent burning velocity squared, overpressures for different materials can be computed relative to some reference molecule. Within the Sedgwick model, this corresponds to a standard saturated light aliphatic hydrocarbon mixture (ethane, propane, butane), which, for a typical industry structure, yields a P max = 0.7 bar. A review of historical VCEs where there was some knowledge of the maximum overpressure allowed fine-tuning of the estimated P max for a range of materials. The variation in P max for different levels of plant congestion is shown in Table 3 for a range of material types. Once the overpressure-distance profile has been calculated, fire and blast damage factors are applied depending on the overpressure. For practical purposes, a series of isobars are drawn overlaid on a plot plan which, if the distribution of the asset values is known, allows for computation of the EML. The fire and blast damage factors are based on analysis of actual insurance loss events, and data published by the US Department of the Interior [7]. The ability of different plant type to withstand overpressure is duly recognised, i.e. in reality, heat exchangers, pipes and vessels are inherently stronger than non-blast resistant buildings. The critical overpressure isobar is 0.35 bar, the point at which pipes can damage or flanges separate. This causes subsequent release of hydrocarbons and knock-on fires with devastating consequences in terms of financial loss. PRACTICAL APPLICATION On visiting a refinery or petrochemical site, the surveying engineer follows a number of steps in estimating the potential for damage arising from a vapour cloud explosion. The catastrophic EML reflects the loss that could be sustained under abnormal conditions with the failure of multiple protection systems. These steps, which involve detailed discussion with the operator, include: (i) (ii) (iii) (iv) (v) (vi) Allocation of asset values on to a plot plan of the site. Identification of large hydrocarbon sources, gas or liquid phase, capable of generating a gas cloud together with operating conditions. Identification of plant structures capable of generating fast flame speeds and hence overpressures. Gas cloud dispersion analysis using local average wind speed conditions. Generation of an overpressure-distance profile. Estimation of the degree of fire and blast damage arising from the explosion. 287

(vii) Adjustment of the EML for additional costs likely to arise from investigation, site clearance, engineering, commissioning, start-up and, where relevant, inflation effects. The calculation of the financial EML is greatly speeded up by use of a computerised version of the model, the Sedgwick Loss Assessment Model (SLAM), which runs in an IBM windows compatible computing environment. The potential for gas cloud drift is important since more than one structure can be engulfed, i.e. there is the possibility of multiple explosions which is in fact what has happened in some of the major insurance losses involving sizeable vapour clouds. Explosion epicentres are centred on plant structures since fast flame speeds cannot be developed in large open spaces for the materials of interest. MODEL PERFORMANCE VERSUS INSURANCE LOSSES To demonstrate the applicability of the model, two recent insurance losses are discussed involving different materials and types of plant. These losses represented tests for the model since neither was used in its development. These losses also demonstrate the significant damage that can arise from only small releases of hydrocarbon if conditions are such that fast flame speeds can be generated. La Mede Refinery. 1992 A vapour cloud of less than 10 tonnes formed following the suspected failure of a bypass around a cooling exchanger associated with an absorber deethaniser column within a gas plant. The vapour cloud drifted towards the furnaces associated with a nearby catalytic cracker unit and ignited. The subsequent vapour cloud explosion and ensuing fires caused US$ 225 million of property damage to the refinery and disrupted the operator s business. Six plant personnel died in the collapse of a control room which was non-blast resistant. Windows were damaged in the surrounding villages at distances up to 5 km from the blast epicentre. Analysis of this loss, relying on a knowledge of the plant design, and comparison of predicted overpressure against observed damage within both plant areas and the local community, is shown in Figure 1. The data fit is remarkably good. Interestingly, the shape of the overpressure-distance profile is in line with the Cates acoustic pressure wave decay hypothesis, i.e. very different from the approximate 1 r 2 decay TNT prediction. The relationship holds both in on-site ( near field ) areas, which are of interest to the property damage insurance underwriter, and outside the refinery, which is the concern of the liability insurance market. The predicted overpressure in the near field is consistent with observed plant damage in the gas plant, which was totally destroyed, and adjacent processing and tank farm areas where only partial losses of equipment occurred. Lake Maracaibo. 1993 The failure of a propane refrigeration exchanger within a multiple production platform complex in shallow water led to a release of 3 tonnes of liquid propane. A vapour cloud developed and following subsequent ignition, an explosion occurred with the loss of 11 lives, and extensive facilities damage. 288

The model is applicable to this type of facility since, in reality, it is simply a plant structure, but located above water. Unlike the confined structures of the North Sea, there is an absence of highly enclosed modules or blow-out design panel features. The main production platform, which is where the explosion was centred, separates liquefied petroleum gases from natural gas. It is connected to associated pipeline riser, control room and utility platforms by walkways above the water over an area 500 metres by 250 metres. Outlying platforms suffered only blast-related effects, while the damage to the processing platform was exacerbated by fire. The predicted blast overpressure isobars are shown in Figure 2. These are based on a 1.5 tonne vapour cloud following flashing of the liquid propane released within the congested processing structure. The model predicts a damage level of US$ 100 million, which is within a few million dollars of the insurance claim. Far field blast damage to control rooms and power generation equipment is consistent with the low overpressures predicted. RECENT EXPLOSION UNDERSTANDING DEVELOPMENTS A sister paper presented by Puttock [8] highlights important advances in the understanding of explosions arising out of the CEC sponsored MERGE project. The changes proposed to the original Cates methodology are likely to impact on the insurance model to a minor extent, and only for those scenarios where a maximum overpressure of greater than 0.9 bar is anticipated. Loss history shows that such events are few and far between. In such instances, the rate of pressure decay can be anticipated to be greater than the acoustic approximation in the far field. From an insurance perspective, this is a third party liability issue. Review of the 1974 Flixborough loss using the modified equations presented by Puttock is presented in Figure 3. Here, the predicted overpressure profile from the epicentre is compared with Sadee s data [9]. The original overpressure-distance profile has been modified to reflect an epicentre based on the Cates approach in which structure volume location is all important. The original epicentre proposed by Sadee was based on an aerial blast of 16 tonnes TNT equivalent of cyclohexane. The complexity of the Flixborough explosion in terms of a number of hydrocarbon- engulfed structures and actual epicentre is well described by Roberts and Pritchard [10]. Figure 4 reveals that the distances at which window damage was observed in the villages of Burton upon Stather and Amcotts fall below that predicted by a purely acoustic pressure wave decay format. Such effects may well be due to the changing nature of the overpressure decay relationship in the far field for very high pressures close to the epicentre. Indeed, the predicted relationship based on the equations in Reference 8 would indicate that the findings of the small-scale MERGE experiment can indeed be extrapolated to large plant installations. INHERENT RISK & EML MAGNITUDE The Sedgwick insurance model is highly sensitive to the type of operating risk. In the past, models for estimated maximum loss evaluation have tended to rely solely on a mass input term and were almost independent of hydrocarbon type or plant design layout features. Using the Sedgwick approach, higher EMLs are to be anticipated for those facilities which are petrochemical-based, for example, steam crackers, or highly congested plant with poor inter-unit separation. Relatively lower EMLs can be expected for LPG or NGL processing plant which is well laid out in terms of both intra- and inter-unit spacing. This is borne out by Table 5 in which predicted average EMLs are presented by industry sector. 289

In predicting an overpressure-distance profile, the model can also be used by designers, safety specialists and risk managers to assist in studies relating to: i ii iii iv v vi vii New plant design layout and inter-unit separation. Control room location and decision as to the need for blast-resistant construction. Location of high occupation level administration and maintenance facilities relative to process plant. Liquid hydrocarbon inventory minimisation to reduce potential gas cloud size, Location of tank farm and cooling units relative to process areas. Liability evaluation where blast effects could impact on communities and industrial neighbours outside of a company s boundary fence. Support in safety case preparation. Such studies have already been carried out for a number of companies throughout the world where existing TNT-based modelling approaches have been found to be wanting. CONCLUSIONS The findings of large and small-scale research into deflagration type processes involving hydrocarbons has been developed into a practical approach for assessing insurance exposures arising from vapour cloud explosions. Estimation of overpressure and consequential financial loss is based on specific risk type and, in particular, the type of plant process technology, equipment design layout features and overall site layout. This approach realistically models the major energy insurance industry losses of recent years, giving greater confidence in EML prediction for insurance purposes. This will be to the benefit of operators, insurers and plant designers. 290

ACKNOWLEDGEMENTS The author gratefully acknowledges the valuable contributions made in developing the model from insurance companies, operators, the Shell organisation and, in particular, Dr. J.S. Puttock, Mr. M.S.P. de Groot, and Dr. MJ. Pikaar. REFERENCES 1. E.M. Lenoir & J.A. Davenport, 1992 A Survey of Vapour Cloud Explosions, Second Update 26th Annual Loss Prevention Symposium, AIChE, New Orleans 2. AJ. Harrison & J.A. Eyre, 1987 The effect of obstacle arrays on the combustion of large pre-mixed gas/air clouds. Combustion Science & Technology, 52,121-137 3. RJ. Harris & M.J. Wickens, 1989 Understanding Vapour Cloud Explosions - an experimental study Institution of Gas Engineers, Communication 1408 4. W.P.M. Mercx, R.M.M. van Wees & G. Opschoor, 1993 Current research at TNO on Vapour Cloud Explosion modelling 27th Annual Loss Prevention Symposium, AIChE 5. A.T. Cates, 1991 Fuel gas explosion guidelines International Conference on Fire and Explosion Hazards, Institute of Energy 6. P.H. Taylor & W.J.S. Hirst, 1988 The Scaling of Vapour Cloud Explosions: a fractal model for size and fuel type 22nd International Symposium on Combustion 7. M.M. Stephens, 1970 Minimising Damage to Refineries Office of Oil & Gas, The Department of The Interior 8. J.S. Puttock, 1995 Fuel gas explosion guidelines & further development Second European Conference on Major Hazards, Manchester 9. C. Sadeeetal, 1976 The characteristics of the explosion of cyclohexane at the Nypro (UK) Flixborough plant on 1st June 1974 Journal of Occupational Accidents, 1 10. A.F. Roberts & D.K. Pritchard, 1982 Blast effect from unconfined vapour cloud explosions Journal of Occupational Accidents, 3 291

Table 1 Recent large insurance losses arising from vapour cloud explosions (US$ millions) Year Plant Type Material Fatalities Property Loss 1987 Acetic Acid Butane, oxygenates 3 265 1988 Refinery Propylene, propane 7 356 1989 HOPE Polymer Isobutane, ethylene 23 779 1992 Refinery Unsaturated LPG 6 243 1993 Offshore Processing Propane 11 105 1994 Refinery Cracked gases - 101 Table 2 P max for different materials and typical plant structure congestion (bar) Material Type Overpressure Methane, toluene 0.6 LPG, gasoline 0.7 Unsaturated LPG 1.1 Butadiene 1.5 Ethylene 1.8 292

Table 3 P max potential for different structure congestion (bar) Material Type Minimal Low Typical Severe Methane - 0.3 0.6 0.8 LPG 0.2 0.4 0.7 1.0 Propylene 0.3 0.5 1.1 1.5 Ethylene 0.4 0.9 1.8 2.0 Table 4 Fire & blast damage allocation (% of asset damaged) Overpressure (bar) Process Plant Heavy Machinery Non-blast resistant buildings Atmospheric Tankage >0.7 100 80 100 100 0.7-0.35 80 40 100 100 0.35-0.2 20-100 100 0.2-0.1 5-100 50 0.1-0.05 - - 50 - Table 5 EML & risk type (US$ millions) Risk Type No. of Sites Average EML Gas Processing 7 180 Refining 11 230 Petrochemical 12 340 293

Figure 1 La Mede overpressure versus distance profile (actual versus predicted) Figure 2 Predicted Lake Maracaibo overpressure isobars 294

Figure 3 Flixborough overpressure versus distance profile (actual versus predicted) 295

296