REFER TO AQUATHERM TECHNICAL BULLETIN A-AQTTB FOR ADDITIONAL INFORMATION AND SAFETY PRECAUTIONS

Similar documents
Hygienic Bubble Trap Installation and Operations Manual

PE 2708 CTS & IPS GAS PIPE

Operating Procedures for GripTight 15.5 SDR & IPS Test Plugs

Sterile Visual Flow Indicator

HIGH RATE BASKET STRAINER

Table for PP. over welding cool-down time 0,10 (PP) time pressure pressure in

Instruction Manual. PE-25/32/37 Tapping Machines. POLYTAPP Valves

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

Standard Pneumatic Test Procedure Requirements for Piping Systems

HOT SHOT OPERATING INSTRUCTIONS AND OWNER S MANUAL. Model SPC-500. (Propane Torch)

TN-20/2007. Special Precautions for Fusing Saddle Fittings to Live PE Fuel Gas Mains Pressurized on the Basis of a 0.

Quality Plastic Pipe Fittings. Technical Data. Fabricated PVC Fittings IPS Class 100, 125, 160, 200 SCH 40 & SCH 80 Solvent Weld & Gasketed

Pressure Relief Valve DHV 718

ROPV R40 E Series User Manual

INSTALLATION & MAINTENANCE INSTRUCTION

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

ACCU-PULSE Installation and Operation Instructions

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

CLASS D - SENSITIVE LEAK TEST GAS AND BUBBLE METHOD. 1.1 To provide definitive requirements for PNEUMATIC pressure testing of piping systems.

Installation and Service Manual

MAINTENANCE AND OPERATING MANUAL

PRESSURE TEST PUMP OPERATING & MAINTENANCE INSTRUCTIONS. Model No: PTP100. Part No: GC01/09

IAPMO GUIDE CRITERIA FOR BALL VALVES IAPMO IGC PURPOSE

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

Model 420-HY Pressure Regulating Hydrant Valve

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

NGP-250/500 Nitrogen Generator Quick Start Guide

Ball Float Steam Trap UNA 45 MAX, UNA 46 MAX, UNA 46A MAX PN 40/Class 300 DN 40, 50, 65

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

HYDRAULIC INTENSIFIER Max. Pressure: See Intensifier Data Plate Weight: 16 Lbs. (7.26 kg)

Coiling Tube with Twist-Proof Fitting

200 PSI HIGH-FLOW AIR SOURCE KIT

OCTOBER 2017 ISSUE Page 1 of 7

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

Nitrogen Supply System

Differential Pressure Regulator Type Type 45-6 (0.1 to 1 bar, DN 15) Mounting and Operating Instructions EB 3226 EN

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

Recommended Flexible Pipe Installation For Rental Chillers

Spot Weld Drill Spot Weld Removal System Instruction Manual

CS150 CAP STAPLER OWNER S MANUAL

HYDRAULIC PUNCH DRIVER 38456, 38520, 7306 / 7306SB, 7310 / 7310SB, 7506, 7606SB, 7610SB, 7625 / 7625Pg / 7625PgSB, 7646 / 7646Pg / 7646PgSB

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Cylinder Tilt Saddle Instruction Manual

CSA Sample Draw Aspirator Adapter Operator s Manual

Pipeline Systems PIP PLSC0019 Specification for Pressure Testing HDPE Plastic Pipeline Systems

MANUAL: IN-LINE PIVOT GAUGE IN-LINE GAUGE

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage

RevolveAir / Guardian Breathing Air Cylinder Fill Station Operating Instructions

Pneumatic retractable fitting for use with Unical 9000 and Uniclean 900 automated control systems

Installation, operation & maintenance manual - original version

I T T Pressure Reducing Valve WARNING INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

Continental Industries STEEL SERVICE TEES or FAX Visit

CO2 Tank Conversion Kit P.N , P.N , and P.N

Pressure Regulators. Operating Instructions. Instrumentation

Bermad Pressure Reducing. Model: 42T

AIR STAPLER. MODEL: CSG3KC Part No OPERATING & MAINTENANCE INSTRUCTIONS

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

MyControl Bathing System Signature Series

BGA244 Binary Gas Analyzer

PVC FASTTAP SADDLES for IPS Mains. Main Size OUTLET 1 FPT 3/4 CTS (7/8 OD) COMPRESSION 1 CTS (1 1/8 OD) COMPRESSION 3/4 IPS COMPRESSION

Standard Specifications

200 PSI FAST-FILL AIR SOURCE KIT

RK-IR Sample Draw Aspirator Adapter Operator s Manual

High Pressure Inlet Kits for CONCOA BlendMites and BlendMasters

CLASS DH - PNEUMATIC TESTING - GREATER THAN 1 BAR (15 PSIG)

Steel Spring Driven Reel Instruction Manual

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

Warning: NEVER ALTER TEST EQUIPMENT

DVS Technical Codes an Bulletins

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

HAYWARD FLOW CONTROL FLV SERIES, PVC/CPVC FILTER VESSEL INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

Submittal Package. Viega MegaPress Fitting System. Chilled Water. Hydronic Heating. Fire Protection. Low Pressure Steam. Compressed Air (no oil)

Compact Ball Valves ASAHI AV VALVES. Contents. User s Manual. (Page) (1) Be sure to read the following warranty clauses of our product 1

RE: PROPANE SYSTEM & REGULATOR TESTING/INSPECTION PROCEDURE

Lab Cock. Contents. User s Manual (1) Be sure to read the following warranty clauses of our product 1. (2) General operating instructions 2

Operation Manual - PN A MENSOR MODEL 73 SHOP AIR BOOSTER

SINGER MODEL 106/206-RPS-L&H

>B< Press Range. SALES: +44 (0) FAX: +44 (0) WEB:

TactAir PCP Fill Kit/Adapter. Operation Manual

RK LEL Sample Draw Aspirator Adapter Operator s Manual

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

Eaton Filtration, LLC

SF SERIES CNG COMPRESSOR MODEL HF-4MH. 4 Nm3/Hour Displacement OPERATION MANUAL

Manual retractable fitting with safe-to-operate rotary drive

170-CG Feed Unit SPONGE-JET USER MANUAL. Sponge-Jet, Inc. (USA) 14 Patterson Lane Newington, NH

1.1. Any ASA member who meets the following criteria will be allowed unsupervised access to ASA oxygen system

pressure reducing valves

Owner s Manual AMERICAN. LiquaGen 5 Stage (RO/DI) Aquarium Reef System. YEAR Y 1

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

APPENDIX B TESTING PROTOCOLS. Method A: Straight Test Method B: Angular Deflection Test. Method C: Shear Load Test

TITAN FLOW CONTROL, INC.

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

AIR STAPLER MODEL: CSG1C Part No

Hose Reel Instruction Manual

Transcription:

Aquatherm Standard Pressure Testing Procedure Aquatherm offers an extensive warranty to protect against damages caused by failure from manufacturer s defect. Aquatherm requires that all installations be pressure tested in accordance with the following instructions and that proof of the pressure test be submitted to Aquatherm before the coverage can go into effect. Warranty coverage begins only after the pressure test is properly completed and submitted. Aquatherm s warranty does not cover failures caused by improper installation, operation outside of the recommended parameters, freeze damage or damage from mishandling after the pipe has left the manufacturer. The Aquatherm warranty also does not cover elastomeric components (seals, gaskets, O-rings), components made by other manufacturers, or connections made to other non- Aquatherm systems or components. REFER TO AQUATHERM TECHNICAL BULLETIN 201802A-AQTTB FOR ADDITIONAL INFORMATION AND SAFETY PRECAUTIONS Step 1: Determine your testing pressure. To help ensure the integrity of the heat fusion connections, a pressure test must be performed on the completed system. The amount of pressure used depends on the type of pipe and intended pressure of the application. If the piping system has a mixture of SDR pipe, you should test to the higher SDR s (thinner walled pipe s) testing requirements. For example, if the piping system contains SDR 17.6 pipe and SDR 11 piping, you should test to the requirements of the SDR 17.6 piping. If the piping system contains SDR 17.6 pipe and has an intended operating pressure of 65 psi or lower, the system must be tested at 100 psi. If the piping system contains SDR 17.6 pipe and has an intended operating pressure higher than 65 psi, the system must be tested at 150% of the intended operating pressure or a maximum of 160 psi 1. Do not use compressed air to test SDR 17.6 1. If the system contains only SDR 11 or heavier-walled pipe (lower SDR) and has an intended operating pressure of 100 psi or less, the system must be tested at 150 psi. If the system contains only SDR 11 or heavier-walled pipe (lower SDR) and has an intended operating pressure higher than 100 psi, the system must be tested at 150% of the intended operating pressure. If you have concerns regarding your testing pressure, please contact Aquatherm. Exceptions to the required pressure test must be given via written confirmation from Aquatherm.

Pipe SDR System Operating Pressure SDR 17.6 SDR 11. 9, 7.4 </= 65 psi >65 psi </= 100 psi >100 psi Testing Pressure: 100 psi 150% 150 psi 150% Choose One:

Step 2: Determine your testing medium Water is the preferred medium for testing purposes, due to its incompressibility. However, low pressure, (15 psi or less) air testing may be used to find leaks and open-end pipes. Do not use compressed air alone on any piping system unless it is a compressed air system. If the system is intended for compressed air service, only compressed air may be used for the pressure test, regardless of the following restrictions. If the testing pressure is equal to or less than 150 psi, you may test with water only, or with a water over air combination system (water-filled piping, with air as pressure source). If the testing pressure exceeds 150 psi, the test must be performed using water only. Compressed air alone is not approved for systems with a testing pressures higher than a 15 psi leak test, unless those systems are intended for compressed air service. System Operating Medium: Compressed Air Service Water Service Testing Pressure: </=150 psi >150 psi Testing Medium: Test with Compressed Air Test with water or water over air system Choose One: Do not use compressed air to test SDR 17.6 1.

Step 3: Observe safety protocols. The full Aquatherm warranty does not take effect until the pressure test is completed and submitted and the system is in operation. Therefore, it is important for the tester to observe all safety recommendations from Aquatherm until the testing is complete. For all systems: Visually inspect the connections for signs of proper fusion, following the guidelines given in the Aquatherm Installer manual. Socket connections should have two even rings of melted plastic, and a visible depth mark. Butt welded connections should have a single bead with a rounded top. This inspection is most easily done during the fusion process. The absence of these signs may be indicative of an improper fusion. Remove all fusion equipment from the system before starting the pressure test. Set your pressure gauge near the bottom of the system, where the pressure will be highest. This reduces the risk of over- pressurizing the system. Observe the system during the test for any indications of leaks. If a leak is found, relieve all test pressure and repair the leak before continuing. Additionally, when using compressed air: Stand clear of the pipe during testing and warn others nearby to do the same. Take measures to secure loose sections of the pipe in case a rupture does occur. Do not perform the test if the ambient temperature is higher than 100 F. Use water instead. Should any transition joints leak during testing, check the joints for proper assembly and repeat the test using water before replacing any of the fittings.

REFER TO AQUATHERM TECHNICAL BULLETIN 201802A-AQTTB FOR ADDITIONAL INFORMATION AND SAFETY PRECAUTIONS Principal test: If the system has lost any pressure during the preliminary test, bring the system back up to the test pressure. Observe the system for 120 minutes. The system should be able to hold the full test pressure during that time. The loss of more than 3 psi or steadily decreasing pressure during this test is indicative of a leak. Identify the leak and repair the system before repeating this test. The test pressure must have less than 3 psi loss, and have stabilized at a value of less than 3 psi loss during the test. A successful version of this test must be completed before proceeding. Principal Test Test Pressure p Max = 3 psi Fail Point P in psi (bar) 120 min.

Final test: 150 psi Bring the system up to test pressure for two minutes. Reduce the system pressure to 15 psi for two minutes. Bring the system up to test pressure for two minutes. Reduce the system pressure to 15 psi for two minutes. Bring the system up to test pressure for two minutes. Reduce the system pressure to 15 psi for two minutes. Bring the system up to test pressure for five minutes. Reduce the system pressure to 15 psi for five minutes. 15 psi 2 min 4 min 2 min 4 min 2 min 4 min 5 min 10 min t in min.

Step five: Complete and submit the pressure test record. Submit the forms to Aquatherm within 30 days of completing the pressure test. If you are testing a system in sections, save all the pressure test records and submit them together. Include the installer numbers of all the installers who fused connections on the system. The Aquatherm standard pressure test submission form can be found online on the website. Additional installer numbers may be added to the space below. The following are maximum testing pressures for high-rise buildings or high-pressure systems. The maximum testing pressures should not exceed the following: Pipe PP-RP (RCT) SDR 9 PP-R SDR 7.4 PP-R SDR 11 PP-R SDR 17.6 Maximum Test Pressure Allowed 400 psi 400 psi 270 psi 160 psi 1. Revised 13 March 2018