HVAC Hydronic Pumps: B&G Triple Duty Valve for Proportional Balance

Similar documents
Bell & Gossett ESP-Systemwize Pump Selections

Balancing HVAC Hydronic Systems Part 3: Flow Measurement Valves

Hydronic Systems Balance

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

4x6x10M. 6x8x12M GPM CUBIC METERS PER HOUR. 8x10x20S. 8x8x17. 6x8x17M. 8x10x17S. 10x12x14. 6x8x12XL. 8x10x12L. 4x6x12A. 6x8x12M. 6x8x12S.

SECTION TESTING ADJUSTING AND BALANCING FOR HVAC

KSB Delta Compact Type Series Booklet

Expansion Tank Design (Chilled Water)

Goulds 3296 EZMAG. Chemical Process Pump

FILTER BYPASS CONTROL

BACK PRESSURE / SUSTAINING

Pumping Systems for Landscaping Pumps, Controls and Accessories. Mark Snyder, PE

BACK PRESSURE / SUSTAINING

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

Back to Basics: Pumping Systems RM ASHRAE TECH CONFERENCE

Curves GL-599 R1. Series A-C Hz

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

RadKits (Piping Packages)

Pressure Independent Control Valve (PICV) Fig DN15-32

FACHGESPRÄCH 3 NPSH NPSH3. Let us call it: CAVITATION A LOOK UNDER THE HOOD

KSB Delta Compact Type Series Booklet

PRESSURE INDEPENDENT CONTROL VALVE (PICV)

Wilo Triple Duty Valve / Triple Service Valve Installation and operating instructions

Pressure Independent Control Series

Centrifugal Pump Intro

Pump-Fan-Compressor Sizing

The Advancement of Pressure Independent Technology

SIZING THE WELL-X-TROL

HIGH FLOW PROTECTION FOR VARIABLE SPEED PUMPS

Consider the design of a central chilled water cooling system for a clubhouse and

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

Rate of Flow Valve Series 120

Lesson 6: Flow Control Valves

Dean Pump Self-Priming Chemical Process Pumps

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

Aquavar SOLO 2 Frequently Asked Questions

MULTISTAGE PUMP EFFICIENCY GAINS THROUGH THE ELIMINATION OF THE SEAL CHAMBER PRESSURE EQUALIZATION LINE

VPPL VARIABLE DISPLACEMENT AXIAL-PISTON PUMPS FOR INTERMEDIATE PRESSURE SERIES 10

On-Off switch. Selectable manual control for commissioning. Remote start input for control via an irrigation controller, or external sensor.

Multistage pump efficiency gains through the elimination of the seal chamber pressure equalization line

Joint Expo 2012 February 7-8, 2012 BASIC HYDRAULICS

CURVES S-96C. Domestic Pump Series C35 and C17 Styles PF and PVF Close Coupled Centrifugal

TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES

Pressure and/or Temperature Pilot Operated Steam Regulators Series 2000

V43 Pressure Actuated Water Regulating Valve

E.2 Series. High efficiency circulator. Technical overview

TECHNICAL DATA. than the water inlet pressure to the concentrate

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

SECTION TESTING, ADJUSTING, AND BALANCING CONTRACT NO SECTION TESTING, ADJUSTING, AND BALANCING

Displacement 12, , Maximum flow rate (at 1450 rpm) bar.

PVK OPEN LOOP PUMPS. Bulletin E

Process Dynamics, Operations, and Control Lecture Notes - 20

PDF // GRUNDFOS SUBMERSIBLE PUMP SPECIFICATIONS DOWNLOAD

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

Technical vs. Process Commissioning Final Exam: Functional Performance Testing

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

BY THOMAS M. WALSKI, BRIAN LUBENOW, AND JEFFREY SPAIDE. When they install a branch from a water distribution main,

CONSTANT FLOW REGULATOR (CFR)

ESCONDIDO FIRE DEPT TRAINING MANUAL Section DRIVER OPERATOR Page 1 of 14 Hydraulics Revised

Offshore Equipment. Yutaek Seo

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

VB-7323 Series. Application. Features. Applicable Literature. 1/2 to 2 Screwed NPT Three-Way Diverting Valves General Instructions

TECHNICAL DATA. Low-Flow Foam Preaction System with Hydraulically Actuated Concentrate Control Valve.

Model: 43T. Bermad Pressure Relief Valve

PRODUCT INFORMATIONAL BULLETIN

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

Chapter 10: Bidirectional Flow Controls

PRESSURE DROP CHARTS

Pump ED 101. Intro to Centrifugal Pumps. Joe Evans, Ph.D. Script for Power Point Presentation. Part 1 Elementary Mechanics & Hydraulics

SUBMERSIBLE PUMP HEAD CALCULATION

SELECTION & APPLICATION

50Hz. water solutions. O SerieS DGO DRO

my SYSTEM A guide to common applications in water distribution systems

T Y P E V S A B M S E W A G E P U M P

Acoustical Modeling of Reciprocating Compressors With Stepless Valve Unloaders

MANUAL FLOW CONTROL 2-1/2" - 18" QUICKSET FLOW CHART

Installation Operation Maintenance

Liquid ring compressors

Proper Pump Installation Practices

PTF4 Pivotrol Pump (patented) version Dual Mechanism - Pressure Powered Pump

Axial piston pumps type PVC

Industrial TE-5.5-MD-CK. Applications. Features. Construction

TECHNICAL DATA. Page 1 of 12

DEEP WELL SUBMERSIBLE PUMPS. An ISO 9001 & Company

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

TECHNICAL DATA. Table 1 - Specifications

Sizing Pulsation Dampeners Is Critical to Effectiveness

TECHNICAL INSTRUCTIONS Iron Body Series 597 SI

Case 12 Multistage Centrifugal Refrigeration System Halocarbon Refrigerant

ALBIN ALP PERISTALTIC PUMP

Colorado Division of Fire Prevention & Control Driver Operator Pumper JPRs (NFPA 1002, 2014 Edition)

IRC 2011 All Rights Reserved

REDUCING RELIABILITY INCIDENTS AND IMPROVING MEANTIME BETWEEN REPAIR

SINGLE VALVE WITH LOW-FLOW BYPASS

1 Exam Prep NSF/ANSI Tabs and Highlights

GROUTEC SCOTT VICKERS. Grouting Equipment

TECHNICAL DATA CAUTION

Turbo Blowers. Combustion Excellence Since Features. Benefits

Wet pipe low flow foam/water system

Transcription:

Monday, April 2, 2018 HVAC Hydronic Pumps: B&G Triple Duty Valve for Proportional Balance Monday Morning Minutes by Norm Hall, April 2, 2018 The ASHRAE Standard 90.1-2013 and the State of Michigan 2015 Energy Code both require the trimming of impellers or reduction in the maximum speed when pumps 10 HP and above are oversized and the energy savings is 5% or 3 HP, whichever is greater. Almost all pumps are oversized. So how does the construction team determine what speed to set the drive at when the pump is oversized? The contractor can use the discharge Bell & Gossett Triple Duty Valve to accomplish this code requirement. Proportional Balancing of Hydronic Systems Professional balancing contractors use a process called proportional balancing to accurately set hydronic system flow rates. This process is also required by the aforementioned code. This is a preferred method over a simple read and set method. In a read and set method, the balance valves out in the system are throttled more than would be necessary if the pump was not oversized. All of the excess pump head is distributed over the system balance valves and will be an energy waste forever. In a proportional balance, the excess pump head is captured across the discharge balancing device. The hydraulically farthest balance device is wide open and has the least pressure loss it could have at design flow. Where does the excess pressure drop or pump head show up? It is across the discharge balance valve or B&G Triple Duty Valve. Determining the Excess Pump Head after Proportional Balance

Organizations such as the National Environmental Balancing Bureau (NEBB) use the proportional balance method. Once this method is complete, the result is a throttled B&G Triple Duty Valve on the discharge of the pump. The code requires the contractor to trim the impeller or set the maximum speed to a lower point. Use the following steps to determine the speed limit of the drive under design conditions: 1. Read out and record the differential pressure of the throttled B&G Triple Duty Valve. Multiple PSIG by 2.31* to get to feet of head. 2. Record the set point of the Triple Duty Valve. 3. Using the triple duty flow curves from Bell & Gossett bulletin B-861, determine the pressure drop in feet of head of the valve if it was full open at the design flow rate. 4. Subtract the results of step 3 from step 1. This is the excess pump head. 5. Subtract the results of step 4 from the design pump head. This is the required pump head with the Triple Duty Valve open. 6. Look at the variable speed pump curve and identify a point of the design flow rate at the head from step 5. Identify what speed curve is closest to this point. 7. Refer to the drive manufacturers IOM to set the maximum speed of the drive to that speed. Open the Triple Duty Valve 100%. Let s Look at an Example The engineer specified a Bell and Gossett VSX- VSC-5X6X10.5A double suction pump in a closed chilled water system. The scheduled capacity is 1500 GPM at 100 ft. head. They selected the B&G VSC because of the great benefits to the owner, benefits that include silicon carbide unitized seals, ease of service, ANSI/OSHA coupler guard, and a good 15 other reasons. The pump curve selected is shown below. The balancing contractor completes a proportional balance. The pump discharge has a Bell & Gossett model 3DS-10B 10 triple duty combination non-slam check, balance, and shut-off valve set at about 30%. What does the contractor do to meet the 2015 Energy Code? 1. The contractor reads the pressure differential across the throttled B&G Triple Duty Valve. The difference measured is 15 PSIG (15 PSIG X 2.31 = 35 feet). 2. The contractor records the set point of 30%. This is only used to verify the pressure drop and in case you need to return it to design.

3. From the chart below we see that when we open this valve to 100%, the pressure drop will be 4 feet. 4. Subtract the results of step 3 from step 1 (35 feet 4 feet = 31 feet, this is the excess head). 5. Subtract the results of step 4 from the design pump head (100 feet 31 feet = 69 feet). 6. Look at the variable speed pump curve and identify a point of the design flow rate at the head from step 5. Identify what speed curve is closest to this point (1580 RPM).

7. Refer to the drive manufacturers IOM to set the maximum speed of the drive to that speed. Speed is proportional to hertz. If the drive does not read in RPM, new hertz setting = (1580/1780) X 60. The new hertz maximum is 53 Hz. Open the Triple Duty Valve 100%. This is a simple way to check the excess pressure drop and set the maximum speed in the drive. This will save a great deal of operating cost. Operating Cost and Energy Saving The B&G ESP-Systemwize program will help us determine if the energy savings are great enough to meet the requirements of the Energy Code. Once selected, the operating cost of the pump is simply a few clicks away. Once we change the maximum speed, the energy cost will drop.

Next week we will look at the same situation with a constant speed pump. We will also look at reasons why it may not be wise to simply allow the controls to reduce the speed instead of applying the steps listed above.