1200B2 Series Service Regulators. Instruction Manual

Similar documents
1800C and 1800C-HC Series Service Regulators

Regulator from 1800 B series

Model 1800 PFM Series Regulator. Technical Bulletin

SR100 Series Service Regulators. Technical Bulletin

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Series 100 Slam Shut Valve. Technical Bulletin

1800CPB2 Pilot-Loaded Service Regulators

American Meter Co. Five-Year Limited Warranty Industrial Regulators

MEGR-1627 Instruction Manual

1800C and 1800C-HC Service Regulators

MEGR-1912 Instruction Manual

299H Series. Introduction. P.E.D. Categories. Specifications. Installation. Warning. Installation Guide English September 2012

Types S100K and S102K Pressure Regulators

1805 Series Relief Valves

Types S108K and S109K Pressure Reducing Regulators with Integral Slam-Shut Device

1800CPB2 Service Regulators Maximum Inlet Pressure 125 PSIG

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

Type HSR Pressure Reducing Regulator for Residential, Commercial, or Industrial Applications

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

1305 Series Pressure Reducing Regulators

1800CPB2 Service Regulators

R122H, R222, R232A, and R232E Series Instruction Manual

Model 1800 PFM Series Regulator For Constant Outlet Pressure Precise Fixed Factor Measurement From 0.5 to 30 PSIG

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL WELKER RELIEF VALVE

Types 749B and R130 Changeover Manifolds

Combination Air Valve

2.0 INSTALLATION & SERVICE

CS800 Series Commercial / Industrial Pressure Reducing Regulators

1213B2 Service Regulators Maximum Inlet Pressure 125 PSIG

Installation, Operation, and Maintenance Manual

R600 and HSRL Series Instruction Manual

Type CT88 Backpressure Regulator

1800C & 1800C-HC Service Regulators

PRO-50 Instrument Supply Regulator

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Product Manual. Description. Specifications. CVS Type 1301F and CVS Type 1301G Regulator. Introduction

WW-730. Pressure Sustaining/Relief Control Valve

Type R622 Pressure Reducing Regulator

Industrial Regulator Series 1800/2000

Operation Manual Piston Sensed Gas Pressure Regulators

Installation, Operation and Maintenance Manual for Back Pressure Regulator

TECHNICAL DATA CAUTION

A3S Bellows Sealed Stop Valve Installation and Maintenance Instructions

64 Series Pressure Reducing Regulators

LRS(H)4 Pressure-Reducing Regulator User Manual

Types S100C and S102C Pressure

V DGX Series. Direct-Operated Regulators Manual D103834X012

Anti-flood device Model B-1

RD(H)20/25 Pressure-Reducing Regulator User Manual

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

R600 and HSRL Series Instruction Manual

Model 141-A Regulators

SUBMITTAL NOTES PROJECT: Ross Model 50RWR-A Pilot Operated Surge Relief Valve with Hydraulic Anticipation. Size: inch / mm

1301 Series High-Pressure Regulators

627 Series Pressure Reducing Regulators

V43 Pressure Actuated Water Regulating Valve

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

TECHNICAL DATA ANTI-FLOOD DEVICE MODEL B-1 1. DESCRIPTION

Type ACE95jr Tank Blanketing Valve

ANDERSON GREENWOOD SERIES 9000 POSRV INSTALLATION AND MAINTENANCE INSTRUCTIONS

61R2 STANDARD REGULATOR COMPACT REGULATOR. Phone Fax

299H Series Pressure Reducing Regulators

S300 Series. Valve Link. Features. Fisher Controls

Installation Troubleshooting Maintenance Instructions Installation / Start-up

HIGH RATE BASKET STRAINER

627 Series Pressure Reducing Regulators

Pressure Regulators. Operating Instructions. Instrumentation

299H Series Pressure Reducing Regulators

1805 Series Relief Valves

Model: 43T. Bermad Pressure Relief Valve

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Types PT and ETP Dome-Loaded Pressure Regulator Valves

299H Series Pressure Reducing Regulators

OBSOLETE DOCUMENT. VSX4 Series Slam-Shut Device. VSX4 Series. Contents. Introduction. Scope of the Manual. Product Description. !

Combination Air Valve Model

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Type 1367 High-Pressure Instrument Supply System with Overpressure Protection

OPERATING AND MAINTENANCE MANUAL

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

Radial Flow Valves. Installation Operation Control Manifold Control Loops Repair Parts. ANSI Class 150, 300 and 600 IM

299H Series Pressure Reducing Regulators

Types 95L and 95H Pressure Regulators

Commonwealth of Massachusetts Approved Product Approval code G

TECHNICAL INSTRUCTIONS

Type OS2 Slam-Shut Device

CSB400 Series Commercial / Industrial Pressure Reducing Regulators

SALCO PRODUCTS, INC. PRESSURE RELIEF VALVE STORAGE, INSTALLATION, OPERATING, MAINTENANCE/TESTING, AND INSPECTION INSTRUCTIONS

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

VSX4 Series Slam-Shut Device

Bermad Pressure Reducing. Model: 42T

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

Models 461-S, 461-8S and S Regulators. R-1330 Rev. 7

RS(H)20, 25 USER MANUAL

Type ACE97 Pad-Depad Valve

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Operation & Maintenance Manual Place this manual with valve or person responsible for maintenance of the valve

WW-720. Pressure Reducing Control Valve

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

Transcription:

00B Series Service Regulators Instruction Manual

00B Series Service Regulators 0 Elster American Meter 00B Series Service Regulators General Information The 00B Series Service Regulators are available as non-relieving or with full capacity internal relief. Optional over pressure shutoff, under pressure shutoff, or combinations are available. Available 80 valve body sizes: /" x /", /" x /", /" x ", /" x /", /" x ", and " x " NPT or BSP-TR. Available 90 valve body sizes: /" x /", /" x /", /" x ", " x " and /" x " NPT or BSP -TR. Regulator Pressure Ratings! WARNINGG Applications Preparations! WARNING Model Number 0B B B B w/ USSA 8B 9B w/ USSA Description Basic regulator, non-relieving with /" NPT vent. Basic regulator with full-capacity internal relief and /" NPT vent. Basic regulator with full-capacity internal relief and overpressure shutoff and /" NPT vent. Basic regulator with full-capacity internal relief and overpressure, underpressure shutoff and /" NPT vent. Basic regulator, non-relieving with overpressure shutoff and /" NPT vent. Basic regulator, non-relieving with overpressure, underpressure shutoff and /" NPT vent. To prevent regulator damage and possible personal injury, pressures must not exceed: Maximum inlet pressure, normal service (P ): Depending on orifice size, up to PSIG. See table on page. Maximum outlet pressure, normal service (P ): Depending on spring selection, up to PSIG. See Pressure Spring table on page. Maximum inlet pressure for abnormal or emergency service, without causing damage to regulator case is 7 PSIG. Maximum outlet pressure which can be contained by pressure carrying components (no flange leakage to atmosphere except for normal relief action) is 0 PSIG. Remove from service if regulator is subjected to these conditions. Maximum outlet pressure for abnormal service without damage to internal components is 0 PSIG. Remove from service if regulator is subjected to these conditions. Do not connect the inlet of the regulator to a pressure source higher than that recommended. Never connect the regulator outlet to the pressure source. Observe the flow direction arrow on the valve body. If inlet pressure can exceed the maximum regulator outlet pressure rating, some form of over-pressure protection in addition to internal relief may be required. Install, operate, inspect and maintain the regulators as outlined in the following instructions and in accordance with your company's policies and applicable federal, state, and local codes and laws. Failure to follow these instructions may result in damage to the regulator or personal injury..... 7. Check installation location for suitability. Physical changes may have been made to the building site since the original installation. Examine regulator for shipping damage. Check regulator and piping for foreign matter which may have accumulated during shipment or handling. Check regulator information stamped on seal plug to determine if regulator is suitable for intended service. See page. Suitable stop valve(s) should be installed and conveniently located. Filters are available from Elster American Meter for applications where pipeline contaminants are believed to be present. Regulators may be used at temperatures between -0 F and +0 F (-0 C and +6 C).

00B Series Service Regulators 0 Elster American Meter Figure Model Orifice Size Spring Range 9 6 Date Code Yr/Wk Mfg. 8 7 8 9 0 7 6 0 Disc, Valve Seat * Seal Ring, Valve Body * 7 Valve, Orifice Orifice Size Standard Part Number Part Number with OPSO Plug, Seal Spring, Relief Valve * Diaphragm Assembly * Screw, Diaphragm Case * /6" 79P0 77P0 /" 79P0 77P0 /6" 79P0 77P0 6 7 Guide, Valve Plunger Plunger, Valve Bolt, Valve Body * /8" 79P00 77P0 8 Assembly, Top 6 Spring, Pressure 8 Diaphragm Case 9 Valve, Body Outlet Pressure Color Code Part Number." to 7" W.C. Light Blue 7007P08 " to 9" W.C. Lavender 7007P08 6" to " W.C. Light Grey 7007P088 8" W.C. to PSIG Light Green 7007P08 to PSIG Pink 7007P086 to PSIG Turquoise 7007P087 9 0 Screw, Pressure Adjustment Stem, Relief Valve * Retainer, Relief Valve Spring * Lever Pin, Lever 0 Screw, Lever Pin Screen, Vent Gasket, Seal Plug * * Items available in Repair Kit 790K006 7

00B Series Service Regulators 0 Elster American Meter Installation! WARNING Inside Installation: A vent line of sufficient diameter to carry gas vented by the regulator to a safe outside location away from any opening in the building is required. For all sizes of regulators, a /" threaded vent is provided for a vent line. Do not thread a pipe into the vent more than seven turns so as to not block the vent flapper. Outside Installation: Care must be taken to prevent vent opening from freezing closed, becoming blocked, or allowing water to enter from any cause. Particular consideration should be given to sites where flooding, snow, or freezing rain may be experienced. The vent or vent line port should point vertically downward, and overhead protection should be used where necessary. c. d. e. f. g. h. i. j. k. Turn gas on slowly. Establish a low flow rate between to SCFH. Remove seal plug (). Turn pressure spring adjustment screw () clockwise to increase outlet pressure; counterclockwise to decrease outlet pressure. Establish the outlet pressure within the range limits of the pressure spring used. To test for the regulator's ability to fully shut off (lock-up), shut off all flow downstream of the regulator. At lock-up, the outlet pressure will be somewhat higher than the set pressure. However, if the pressure continues to rise after seconds, the regulator must be repaired. Observe for 0 seconds. When the set pressure has been properly adjusted, depressurize and remove gauge(s) and lines. Replace seal plug (). Pressurize and check all connections for leaks. (Numbers in parentheses refer to Figure.).... Remove all shipping plugs from the valve body. Use good piping practice. Be sure piping and regulator are free of dirt, pipe dope and other debris. Apply pipe dope to male threads only. Install regulator. Make certain it is installed correctly with inlet pipe connected to the inlet regulator connection and flow is in the direction as indicated by arrow located on valve body (). Elster American Meter suggests that the vent point downward to prevent entry of water and debris. By removing the four valve body bolts (), the diaphragm case () may be rotated in 90-degree increments in relation to the valve body (). Replace and tighten the four valve body bolts () to 60 ±0 in. lbs. A regulator installed within a building should be located as near as practical to the point of service line entrance. If the regulator is equipped with an overpressure shutoff or Universal Safety Shutoff Assembly (USSA), see page 7 for setting instructions. Make sure inlet pressure is always less than the maximum recommended inlet pressure for the orifice size. See Maximum Recommended Inlet Pressure table on the right. Turn gas on slowly. If an outlet valve is used, it should be opened first. Do not subject the regulator to a sudden surge of inlet pressure. Assure that there are no leaks and all connections are tight. The 00B Series regulator is preset at the factory. Should you decide to adjust the set pressure, perform the following: a. b. Turn gas off and depressurize the system. Install outlet pressure gauge. Figure Maximum Recommended Inlet Pressure Orifice Size This is the maximum inlet the regulator should operate at to insure complete lockup at no-flow conditions. Inlet Pressure (PSIG) /8" /6" /" /6" 00

00B Series Service Regulators 0 Elster American Meter Inspection Inspection of Valve Seat Disc and Orifice (Numbers in parentheses refer to Figure.).... 7. 8. CAUTION Regulators are pressure-control mechanisms having numerous moving parts which can wear. In addition, regulator damage may occur from external sources. For these reasons, the regulator should be periodically inspected and checked for proper operation. The frequency of inspection will depend on the severity of the service conditions and the requirements of applicable local, state, and federal codes and regulations. Inspection and maintenance of the 00B Series regulator have been simplified for practical reasons. Repair parts are offered if maintenance of the regulator is required. Inspection of the valve seat disc and orifice valve may be performed in the field. Follow the procedure described below. Care should be exercised to prevent foreign matter from entering the regulator. Shut off gas supply and depressurize the system. Remove four valve body bolts (), securing the diaphragm case () to the valve body (). Separate the diaphragm case from the valve body. Visually check the seating edge of the orifice inside the valve body (). If it is nicked or damaged, it should be replaced with a new orifice to provide positive shut off. See maintenance instructions for replacing orifice. Inspect the surface of the valve seat disc (). If it is scored or uneven, replace it as outlined in the maintenance instructions for replacing the seat disc. Install new seal ring () in the diaphragm case groove. Inspect unit for cleanliness and proper positioning of the parts. Pay particular attention to the proper positioning of the seal ring () in the groove. Install the diaphragm case () on the valve body (). Make sure the vent is positioned so that it cannot become plugged or allow water to enter. Replace and tighten the four valve body bolts () to 60 ±0 in. lbs. Proceed to Steps, and 6 of the installation instructions. Maintenance! CAUTION As a knowledgeable user of Elster American Meter Company products, you should be aware that parts in the Company's meters and regulators contain or are coated with heavy metals such as cadmium, zinc, lead and chromium. Obviously, therefore, repair or refurbishment of this equipment should take into account the presence of these materials and should comply with all state and federal requirements concerning worker protection, proper disposal and safety, including protection against exposure to dust and fumes. Replacing Seat Disc (Numbers in parentheses refer to Figure.)... Carefully insert the tip of a knife along the edge of the seat disc () and the lift the seat disc out of the plunger (6). Install a new seat disc () into the plunger (6) by pressing into place. Make sure that the disc is pressed completely into the plunger (6). Proceed to Steps, 6, 7, and 8 of the Inspection instructions. Figure 6

00B Series Service Regulators 06 Elster American Meter Maintenance! CAUTION Maintenance! CAUTION Regulators that have an orifice size different than shown on the seal plug tag must have their set pressure reestablished. Mark new orifice size on the regulator seal plug or on its tag. Replacing the Orifice (Numbers in parentheses refer to Figure.).... Shut off gas supply and depressurize the system. Remove the four valve body bolts () securing the diaphragm case () to the valve body (). Place the diaphragm case aside and protect the seat disc () from dirt particles and physical damage. Remove the orifice valve () with a 7/8" hex socket wrench. Sparingly apply Henkell G0 or Loctite "Stainless Steel PST" thread sealant or equivalent (not supplied) to the new orifice threads. Carefully start the threads of the orifice into the valve body and tighten to 0 ±0 in lbs. Care must be taken to prevent nicking the orifice. Proceed to Steps, 6, 7 and 8 of the Inspection instructions. Regulators that have a pressure spring removed or replaced must have their set pressure reestablished. If the pressure spring is different from that shown on the seal plug or tag, mark the new spring range on the regulator seal plug or on its tag. Replacing the Pressure Spring (Numbers in parentheses refer to Figure ).... Shut off gas supply and depressurize the system. Remove seal plug (). Unscrew pressure adjusting screw () with a /8" screwdriver. Completely remove the pressure adjusting screw (). Remove the pressure spring (). Install new pressure spring. Replace the pressure adjusting screw and turn adjusting screw to about mid position. Proceed to Steps,, and 6 in Installation instructions to set delivery pressure. Figure Figure

00B Series Service Regulators 07 Elster American Meter Resetting the OPSO-B and 8B only Operating and Resetting the Jeavons USSA (Numbers in parentheses refer to Figure ). Shut off gas supply and depressurize the system.. Unscrew the OPSO diaphragm case cap (body plug) ().. Pull out on the knurled plunger () until the diaphragm stem () repositions (an audible click).. Replace the OPSO diaphragm case cap (body plug) () after examining the o-ring () for damage. (Numbers in parentheses refer to Figure 7.). Turn on the gas supply and pressurize the system.. Unscrew the reset spindle end cap ().. Pull out on the reset spindle end cap and hold for about seconds until the USSA unit becomes pressurized.. Release the reset spindle end cap and screw back into place. If properly set the green indicator bulb () will be visible in the spindle dome (). Figure 6 Figure 7 Diaphragm Case Cap (Body Plug) Reset Spindle End Cap Knurled Plunger Indicator Bulb Diaphragm Stem Spindle Dome O-ring

About Elster Group A world leader in advanced metering infrastructure, integrated metering, and utilization solutions to the gas, electricity and water industries. Elster s metering and system solutions reflect over 70 years of knowledge and experience in measuring precious resources and energy. Elster provides solutions and advanced technologies to help utilities more easily, efficiently and reliably obtain and use advanced metering intelligence to improve customer service, enhance operational efficiency, and increase revenues. Elster's AMI solutions enable utilities to cost-effectively generate, deliver, manage, and conserve the life-essential resources of gas, electricity, and water. Elster has a staff of over 7,00 serving customers globally in North America, Central America, South America, Europe, Asia, Africa and the Middle East. Elster American Meter Industrial Road Nebraska City, NE 680 USA T + 0 87 800 F + 0 87 766 www.elster-americanmeter.com Elster Canadian Meter T + 90 6 89 F + 90 6 670 www.elster-canadianmeter.com 009 Elster American Meter. All rights reserved. Registered trademark of Elster American Meter. Information contained herein is subject to change without notice. Product specifications may change. Contact your Elster Perfection representative for the most current product information. Printed in the United States. EAM-IM806-EN-P - May 009 Supersedes IM 8708