VTL VFL VCL. Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS

Similar documents
FXT. FXT Cooling Tower RIGGING & ASSEMBLY INSTRUCTIONS

Closed Circuit Cooling Towers

Model PSI Compressor with 3-Gallon Air Tank 12VDC

BUTTERFLY VALVES Series 800

200 PSI COMPRESSORS - MODEL NUMBERS

30T A/Manual Hydraulic Shop Press

100C Air Compressor Kit

420C AIR COMPRESSOR KIT PART NO C AIR COMPRESSOR KIT PART NO

IMPORTANT SAFETY INSTRUCTIONS

Related Products: Auto Drain Valve. Model/Specifications. Model

TITAN FLOW CONTROL, INC.

DC5A. Cyclone Separator Trap for Air. Copyright 2015 by TLV Co., Ltd. All rights reserved ISO 9001/ ISO MA-03 (DC5A) 19 June 2015

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

SALCO PRODUCTS, INC. PRESSURE RELIEF VALVE STORAGE, INSTALLATION, OPERATING, MAINTENANCE/TESTING, AND INSPECTION INSTRUCTIONS

WHEATLEY Series 500 Swing Check Valve

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

INSTALLATION, MAINTENANCE & OPERATING INSTRUCTIONS 2-4 REDUCED PORT/ FULL PORT (5700/6700) ANSI CLASS 150/300/600/900/1500/2500 TRUNNION BALL VALVES

97C COMPRESSOR KIT 12V PART NO C COMPRESSOR KIT 24V PART NO C COMPRESSOR KIT PART NO

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

NGP-250/500 Nitrogen Generator Quick Start Guide

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

444C DUAL PERFORMANCE VALUE PACK

APCO ASU-SCAV & ASU-CAV SINGLE BODY COMBINATION AIR VALVES

SAPAG. Safety valves, type 5700 Storage, Use, Operation and Maintenance Instructions. IMPORTANT NOTICE

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

200 PSI FAST-FILL AIR SOURCE KIT

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

250C-IG COMPRESSOR KIT 12V PART NO C-IG COMPRESSOR KIT 24V PART NO

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

Henry Pratt Diviner Position Indicator. Operation and Maintenance Manual. Job Name: Contractor: Date: Document #:DIVPOSNOM Revision Date: 2/9/11

Model: 43T. Bermad Pressure Relief Valve

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

400C & 450C DUAL PERFORMANCE VALUE PACKS

INSTRUCTIONS AND MAINTENANCE MANUAL SERIES: RT

Float Operated Level Controllers

Atmospheric relief valve type 1100 Installation and maintenance instructions

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

INSTALLATION, OPERATING & MAINTENANCE MANUAL WATER DRAIN VALVE

200 PSI HIGH-FLOW AIR SOURCE KIT

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

FLANGED TWO-PIECE BALL VALVES

LUBRICATOR ASSEMBLY AND OPERATING INSTRUCTIONS

INSTALLATION, OPERATION AND SERVICE MANUAL ABS AIR BAG LIFT

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

75 Ton SD Shop Press Operating Instructions

Installation, Operation and Maintenance Manual for Back Pressure Regulator

20 Ton SD Shop Press Operating Instructions

WHEATLEY WHEATLEY SERIES 500 SWING CHECK VALVE. Installation, Operation and Maintenance Manual

Installation, Operation, & Maintenance Manual

35 TON HYDRAULIC PUNCH WARNING

Combination Air Valve

VL 2K LIFT D-L WINCH INSTRUCTIONS (Applies to P/Ns , , , , , )

DBML-60/80 Squeeze Tool

TECHNICAL DATA. Q = C v P S

Shoreline Cantilever Lift 2500lb Capacity Models: (108" inside width) - Part # (120" inside width) - Part #

PDY TON HYDRAULIC CRIMPING TOOL WARNING

29 SERIES - SAFETY VALVE

WALL MOUNTED EMERGENCY EYE & EYE/FACE WASH HAND OPERATED

OPERATION and MAINTENANCE Guide

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

TECHNICAL DATA. Q = C v P S

BP48-1 AND SSP48-1 IN-GROUND POST INSTALLATION INSTRUCTIONS

TECHNICAL DATA. Q = C v P S

DISASSEMBLY AND ASSEMBLY INSTRUCTIONS FOR LIQUID RING COMPRESSORS

Operation Manual Air Saver Unit ASV5000 Series

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

PEDESTAL MOUNTED EMERGENCY EYE & EYE/FACE WASH

310 SERIES TILT-TO-LOAD ROTATOR. The Specialist In Drum Handling Equipment

ROTATING DISK VALVES INSTALLATION AND MAINTENANCE 1. SCOPE 3 2. INFORMATION ON USAGE 3 3. VALVE TYPES 3 4. OPERATORS 5 5. VALVE CONSTRUCTION 6

Product Manual B-Safety ClassicLine & PremiumLine Emergency Eyewash and Eye/Face Wash Equipment

1700ESL Kamvalok Coupler

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

Manual Actuated Boiler Blowdown Valves

! WARNING. Model PFC-1-G (direct acting) PFC-1-GR (reverse acting) Modulating Pneumatic Liquid Level Controls INSTRUCTION MANUAL MM-110B

MODEL 200 KNIFE GATE VALVES INSTALLATION & MAINTENANCE MANUAL

FLANGED TWO-PIECE BALL VALVES

Product Bulletin No.: D99-RRV2015-PIB-001

INSTALLATION COMMISSIONING, OPERATION & MAINTENANCE MANUAL

To address this issue, Ariens Company has developed two cradle plates kits:

Jacuzzi. J-CQ420 Cartridge Filter Installation and Operating Instructions

GILMONT ACCUCAL FLOWMETERS

PV4 and PV6 Piston Valves

1 DRIVE INDUSTRIAL IMPACT WRENCH

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

O&M Receiving and Inspection. Storage of Water Treatment Media

2,500/4,000 LB Easy Riser Vertical Cable Feighner Lift

Installation, Operation, and Maintenance Manual

453 Series Steam Heated Vaporizing Regulator

TECHNICAL DATA. than the water inlet pressure to the concentrate

AIR/OVER HYDRAULIC JACK 20 TON

CRP INSTALLATION, OPERATING AND MAINTENANCE INFORMATION FOR INLINE SAMPLING VALVES

Constant Pressure Crude Oil Container Model CPCCP

HIGH RATE BASKET STRAINER

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

Transcription:

VTL VFL VCL Low Profile Series V RIGGING & ASSEMBLY INSTRUCTIONS

Low Profile Series VL units should be rigged and installed as outlined in this bulletin. These procedures should be thoroughly reviewed prior to the actual rigging operation to acquaint all personnel with the procedures to be followed and to assure that all necessary equipment will be available at the jobsite. Locate the unit nameplate on the connection end of the unit and record the model number for reference. Cooling Towers are identified as VTLXXX-X; Evaporative Condensers as VCLXXX-X; and Fluid Coolers as VFLXXX-X. Be sure to have a copy of the unit certified drawing available for reference. If you do not have a copy of this drawing or if you need additional information about the unit, contact the local B.A.C. Representative. His name and phone number are on a label at the connection end of your unit. Be sure to have a copy of the submittal drawings available for reference. If you do not have a copy of these drawings, or if you need additional information about this unit, contact your local BAC Representative whose name and telephone number are on the outside of the cold water basin. The model number and serial number of the unit are also located in this area.

Table of Contents RIGGING & ASSEMBLY INSTRUCTIONS» LOW PROFILE SERIES V 1 Introduction 2 Safety 2 Leveling 2 Pre-Rigging Checks Unit Weights Anchoring 3 Cold Weather Operation 3 Warranties 3 Connecting Piping 3 Purge Requirements 3 Refrigerant Connections on Site 2 Unit Rigging & Assembly 4 Rigging 5 Discharge Hood Installation 6 Bleed LIne Installation 3 Final Assembly Details 8 Instructions 1

1 LOW PROFILE SERIES V Introduction WARNING: Failure to use designated lifting points can result in a dropped load causing severe injury, death, and/or property damage. Lifts must be performed by qualified riggers following BAC published Rigging Instructions and generally accepted lifting practices. The use of supplemental safety slings may also be required if the lift circumstances warrant its use, as determined by the rigging contractor. Safety Adequate precautions appropriate for the installation and location of these products should be taken to safeguard the equipment and the premises from damage and the public from possible injury as appropriate for the installation and location of these products. The procedures listed in this manual must be thoroughly reviewed prior to rigging and assembly. Read all warnings, cautions, and notes detailed in the margins. When the fan speed of the unit is to be changed from the factory set speed, including the use of a variable speed device, steps must be taken to avoid operating at or near the fan s critical speed which could result in fan failure and possible injury or damage. Consult with your local BAC Representative on any such applications. Leveling The unit must be level for proper operation. This is especially true for Fluid Coolers (VFL units), which should be level to 0,5 mm per m over the length and width. This will help ensure proper coil draining in an emergency freeze situation (See Freeze Protection Note below). Support beams must also be level as shims should not be used between the pan and support beams to level the unit. WARNING: Only personnel qualified to do so should undertake the installation, operation, maintenance, and repair of this equipment. Proper care, procedures, and tools must be used in handling, lifting, installing, operating, maintaining, and repairing this equipment to prevent personal injury and/or property damage. 2 Pre-Rigging Checks When the unit is delivered to the jobsite, it should be checked thoroughly to ensure all required items have been received and are free of any shipping damage prior to signing the bill of lading. The following parts should be inspected: Sheaves and Belts Bearings Bearing Supports Fan Motor(s) Fan Guard(s) Fan(s) and Fan Shaft(s) Float Valve Assembly(s) Fill Water Distribution System Cold Water Basin Accessories Interior Surfaces Exterior Surfaces Louvres Mating Surfaces Between Sections/Modules Miscellaneous Items: All bolts, nuts, washers, and sealer tape required to assemble sections or component parts are furnished by BAC and shipped with the unit. A checklist inside the envelope marked Customer Information Packet indicates what miscellaneous parts are included with the shipment and where they are packed. This envelope will be attached to the side of the unit or located in a box inside the unit.

Introduction Unit Weights Before rigging any Series VL unit, the weight of each section should be verified from the unit certified drawing. WARNING: These weights are approximate only and should be confirmed by weighing before lifting when available hoisting capacity provides little margin for safety. In preparing for a lift, individuals responsible for rigging B.A.C. units must inspect the equipment before the lift to make certain that all water or other liquids have been drained from the unit. During cold weather the pre-lift procedure must include a check for and removal of accumulations of ice and snow which will not naturally drain from the equipment and would add substantially to the loading Anchoring Safety Leveling Pre-Rigging Checks Unit Weights Anchoring Cold Weather Operation Warranties Connecting Piping Purge Requirements Refrigerant Connections on Site CAUTION: Unit must be properly anchored in place before operation begins. Holes suitable for M18 bolts are provided in the bottom of the pan section for bolting the unit to the support beams. Refer to the suggested support details on the certified drawing for locations of the mounting holes. Anchor bolts must be supplied by others. Cold Weather Operation These products must be protected by mechanical and operational methods against damage and/or reduced effectiveness during sub-freezing temperatures. Please contact your local BAC Representative for recommended cold weather operation strategies. Warranties Please refer to the Limitation of Warranties (located in the submittal package) applicable to and in effect at the time of the sale/purchase of these products. Connecting Piping ATTENTION: Before an actual lift is undertaken, ensure no water, snow, ice, or debris has collected in the basin or elsewhere in the unit. Such accumulations will add substantially to the equipment s lifting weight. All refrigerant piping external to the evaporative condenser(s) must be supported separately from the equipment. In case the evaporative condenser(s) are installed in vibration rails or springs, the piping must contain compensators to eliminate vibrations carried through the refrigerant piping. Purge Requirements The installer of this equipment must ensure proper system purging of air, prior to operation of the installation. Air entrained in the system can obstruct the proper drainage of liquid refrigerant, reduce condensing capacity and result in higher operating pressures than design. To verify absence of non condensable in the system, follow the instructions of the B.A.C. Evaporative Condenser Engineering Manual. Refrigerant Connections on site All connections in the external refrigerant pipework (installed by others) must be leak free and tested accordingly. 3

2 LOW PROFILE SERIES V Unit Rigging & Assembly NOTE: For weight information, refer to the submittal drawing package. Rigging For lifts and final positioning, Low Profile Series VL equipment may be hoisted as shown by the lifting devices supplied at the base of the unit. The vertical distance between the base of the unit and the apex of the lifting cables must be no less than H dimension given in the following tables. Spreader bars the full width of the unit must be used between the lifting cables to prevent damage to the unit. The use of Safety Slings is recommended for all lifts. After the unit has been set in the final position, bolt it securely to the supporting steel before proceeding any further. COOLING TOWERS Model Minimum H in mm Spreader Bar Length in mm NOTE: Any motors or accessories shipped in the cold water basin must be removed prior to installation. VTL016 thru VTL039 2750 1250 VTL045 thru VTL079 3100 1250 VTL082 thru VTL092 4300 1250 VTL103 thru VTL137 5000 1250 VTL152 thru VTL227 4300 2450 VTL245 thru VTL272 5000 2450 Figure 1. Preferred method for rigging all Low Profile Series V Cooling Tower Units. 4

Unit Rigging & Assembly Rigging FLUID COOLERS / EVAPORATIVE CONDENSERS Model Minimum H in mm Spreader Bar Length in mm VFL016 thru VFL123 VCL016 thru VCL035 VFL241 thru VFL243 VCL038 thru VCL079 VFL382 thru VFL383 VCL087 thru VCL120 VFL483 VCL134 thru VCL155 VFL722 thru VFL723 VCL167 thru VCL234 VFL963 VCL257 thru VCL299 2750 1250 3100 1250 4300 1250 5000 1250 3100 2450 3700 2450 Figure 2. Preferred method for rigging all Low Profile Series V Fluid Cooler and Evaporative Condenser Units. Figure 3. 5

Discharge Hood Installation If the unit has been furnished with a discharge hood, discharge sound attenuation and vertical intake duct or attenuator, a separate lift is required. Sealing and rigging instructions are outlined below. 1) Be sure all mating surfaces are clean and free of dust, dirt and moisture. 2) Apply the 25mm flat (trapezoidal cross section) tape sealer around the periphery of the top flange of the casing section (See Figure 4). Apply tape with the wide side down over the centreline of the tapper holes and the centreline of the tapper holes and the centreline of the end of the end flages where thee are no tapper holes. The sealer should only be spliced along the flanges with the tapper holes. 1 Apply 25mm flat tape sealer over centerline of screw hole. 2 Apply 25mm flat tape sealer over centerline of cross flanges. Figure 4. 3) After applying sealer to the unit flanges, lift the hood (using the lifting method outlined on page 4) and position it over the unit so that the hood s flanges are about 50mm above the casing flanges. Do not let the hood swing and damage the sealer. 4) Insert drift pins downward through the four corner screw holes in the hood (See Figure 5). Continue to lower the hood slowly, maintaining alignment with the drift pins until it rests on the unit. 6 Figure 5.

Unit Rigging & Assembly Discharge Hood Installation 5) Using the 10mm self-tapping screws, drive the corner screws down through the hood and into the unit. Working from the corners toward the center, continue to install the screws using the screw holes. Bleed Line Installation Bleed Line Installation On VFL and VCL units operating with a remote sump tank and all VTL units, install a bleed line with valve between the system circulating pump discharge riser and a convenient drain. Locate the bleed line in a portion of the riser piping that drains when the pump is off. VFL and VCL units that are furnished with a factory-installed circulating pump include a belled line with valve. The bleed valve should always be open when the unit is in operation, unless the bleed rate is automatically controlled by a water treatment system. Refer to the Operating and Maintenance Manual for circulating water quality guidelines and suggested bleed rate determination. 7

3 LOW PROFILE SERIES V Final Assembly Details Inspection Prior to start-up, the following services, which are described in detail in the Operating and Maintenance Manual, must be performed. Inspect general condition of unit. Inspect fans and air inlet screens for obstructions. Check make-up valve and sump water level. Inspect spreay nozzles and heat transfer section. Lubricate all bearings and purge them of old grease. Proper start-up procedures and scheduled periodic maintenance will prolong the life of the equipment and ensure trouble-free performance for which the unit is designed. 8

Final Assembly Details Inspection 9

COOLING TOWERS CLOSED CIRCUIT COOLING TOWERS ICE THERMAL STORAGE EVAPORATIVE CONDENSERS HYBRID PRODUCTS PARTS & SERVICES w w w. B a l t i m o r e A i r c o i l. c o m. a u 120 Wisemans Ferry Road, Somersby NSW 2250 Telephone (Australia): 1300.134.622 Telephone (New Zealand): 0800.225.842