III. Identify the initial installation requirements for standpipe systems

Similar documents
1 Exam Prep. Tabs and Highlights

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

ELKHART BRASS MANUFACTURING COMPANY

Operating Instructions Model and Hydrostatic Test Pump

Piped Air SCBA Refilling System Standard

5.0 INSPECTING, FILLING AND LABELING SMALL CYLINDERS

Operating Instructions Models and Hydrostatic Test Pumps

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015)

TECHNICAL DATA. Trimpac 244a. September 16, 2013

Instruction & Parts Manual

Model 420-HY Pressure Regulating Hydrant Valve

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH PNEUMATIC RELEASE

Operating Instructions Model and Hydrostatic Test Pump

TECHNICAL DATA. the Viking Pilot Pressure Regulating Valve 1 Model A-1 Speed Control Assembly: OBSOLETE. the Viking Speed Control Assembly 1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

Types 749B and R130 Changeover Manifolds

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

SERIES SAFETY VALVE

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

FIREFIGHTING EQUIPMENT

TECHNICAL DATA. Trimpac 257a. September 16, 2013

GETZ EQUIPMENT INNOVATORS PART NO.: 9G59554 MODEL: MS 36 SC-R HYDROSTATIC TEST PUMP

TECHNICAL DATA. Trimpac 256a. October 31, 2013

Installation, Operation & Maintenance Manual for Flo-Max Coupler Bracket Model FM150

DESIGN DATA OBSOLETE. C. Inspections - It is imperative that the system be inspected and tested on a regular basis. See Inspection

TOOL BOX 033- HOSEREEL SERVICE / FAULT FINDING

Operating Instructions Models 36200, , 46200, Hydrostatic Test Pumps

10 DRIP NOZZLE WATERING DRIP KIT Model / Model 46095

HYDRANT/WATER POINT INSPECTION AND MAINTENANCE

Model: 720-UL INSTALLATION OPERATION MAINTENANCE. Bermad Pressure Reducing Valve IOM. Model: FP -720-UL Sizes: 2"-12" BERMAD. Application Engineering

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

Installation and operating manual. Pneumatic control station LK product no: PCS 1-10

Warning: NEVER ALTER TEST EQUIPMENT

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

TECHNICAL DATA. Trimpac 247a_Euro. September 16, 2013

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

CITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard

SABERINDO PACIF SABERINDO PACIFIC CIFIC SABERINDO PA. A Tyco International Company

DESIGN DATA A WET PIPE BLADDER TANK FOAM/WATER SYSTEM WITH HYDRAULICALLY ACTUATED DELUGE CONCENTRATE CONTROL VALVE

TECHNICAL DATA Q= C. Table 1 - Specifications

Installation, Operation and Maintenance Manual for Back Pressure Regulator

MANUAL: Jumbo Siamese and Jumbo Wye

!!!! SERVICE MANUAL PRESSURE POT 2 GALLON. Service Manual: LT Washington St 931 Progress Ave., #7

Bermad Pressure Reducing. Model: 42T

MANUAL: IN-LINE PIVOT GAUGE IN-LINE GAUGE

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

TECHNICAL DATA. Table 1 - Specifications

29 SERIES - SAFETY VALVE

Instruction Sheet. LB Series Lifting Bags CA Series Lifting Bag Controllers. L2753 Rev. B 01/ IMPORTANT RECEIVING INSTRUCTIONS 2.

Speed control assembly model A-1

GREIG FILTERS, INC. OPERATION MANUAL

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

PDY TON HYDRAULIC CRIMPING TOOL WARNING

SALCO PRODUCTS, INC. PRESSURE RELIEF VALVE STORAGE, INSTALLATION, OPERATING, MAINTENANCE/TESTING, AND INSPECTION INSTRUCTIONS

FIRE PROTECTION PRODUCTS

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

SSFU SUPER SPRAYFAST UNIVERSAL ADHESIVE APPLICATOR

STYLE 3414/3416 & 3421/3423 Apollo Monitor with Foldaway Legs OPERATING & MAINTENANCE INSTRUCTIONS

TECHNICAL DATA. Q = C v P S

Model B-1 Pipe Line Strainer 3, 4, 6 & 8 Inch (DN80, DN100, DN150 & DN200) 175 psi (12,1 bar) General Description. Technical Data

Idaho Fire Service Technology Pumping Apparatus Driver/Operator Skill Sheet: 1

Sand Dollar Filter Owner s Manual IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

CO2 Tank Conversion Kit P.N , P.N , and P.N

TECHNICAL DATA. Page 1 of 12

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

TECHNICAL DATA. Q= Cv S

ASSE International Product (Seal) Listing Program

TECHNICAL DATA. Pressure Regulation 531a. April 24, 2009

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

Model: 43T. Bermad Pressure Relief Valve

HYDRAULIC INTENSIFIER Max. Pressure: See Intensifier Data Plate Weight: 16 Lbs. (7.26 kg)

OWNERS SERVICE MANUAL NO

VERTICAL BLADDER TANK

TECHNICAL DATA. Page 1 of 8. model f /2 (dn40) & 2 (dn50)

Flow Material Length. Weight GPM LPM. Style 3095

TECHNICAL DATA CAUTION

Manual. Bypass Feeder. Installation Maintenance Repair Manual. Chemical Addition and Filtering

APCO ASU-SCAV & ASU-CAV SINGLE BODY COMBINATION AIR VALVES

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES

OWNERS SERVICE MANUAL NO INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

COMPACT TRIPLE WALL OUTLET STATION MODEL INSTALLATION AND OPERATING INSTRUCTIONS

APOLLO HI-RISER MONITOR STYLE 3433/3431 INSTALLATION, OPERATING, ANDMAINTENANCE INSTRUCTIONS

FIRE SPRINKLER PRODUCTS PRODUCT CATALOG

MAINTENANCE FOR THE MODEL 210B-2 SRA

553 Series.

Installation, Operating and Maintenance Instructions. V914 Cast Iron Flanged Swing Check Valve V914

APPLYING VARIABLE SPEED PRESSURE LIMITING CONTROL DRIVER FIRE PUMPS. SEC Project No

Wet pipe low flow foam/water system

Method Statement: Testing Dry Riser System

Checklist for care of Respirators

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures

Latvin Luxury Shower Panel. Telephone Product Specification. ~ Minimum Working Pressure 1.0 bar ~ Maximum Working Pressure 3.

2 GALLON TWIN STACK AIR COMPRESSOR W/ HOSE REEL

Transcription:

Design Basic Design Requirements 1. Must provide 500 GPM at 65 PSI to the highest most remote standpipe riser outlet. 2. 250 GPM for each additional standpipe total not to exceed 2500 GPM

III. Identify the initial installation requirements for standpipe systems. 14-9.3 A. Initial installation 1. All devices comply with local requirement 2. Hose cabinets are not over 6 feet from the floor and accessible 3. Each Class II & III system shall be labeled with a sign that reads: FIRE HOSE and/or FIRE HOSE FOR USE BY OCCUPANTS OF BUILDING 4. Fire department connections have proper fire department hose threads and a sign reading STANDPIPE.

Identify the initial installation requirements for standpipe systems 5. Dry standpipes are posted with a sign reading DRY STANDPIPE FOR FIRE DEPARTMENT USE ONLY. 6. Piping, feed mains, and connections are flushed to remove all debris. 7. System components are tested at a pressure not less than 200 PSI for 2 hours.

Identify the initial installation requirements for standpipe systems B. Periodic inspection (usually every 6 months) 1. Proper water level is maintained in water supply tanks 2. If pressurized, a pressure of at least 75 PSI is maintained 3. Precautions against freezing must be taken when necessary 4. Fire pumps start to operate 5. Check records that indicate pumps were run 30 minutes a week for diesel pumps and 3-7 minutes for electric pumps ( 1 minute for each 10 HP)

Identify the initial installation requirements for standpipe systems 6. Check that fuel supplies exist for eight hours 7. Hose cabinets and closets are used for firefighting equipment only 8. Water control valves are open and supervised 9. Individual discharge valves a. They operate b. Gaskets are in good condition c. No evidence of leaks

Identify the initial installation requirements for standpipe systems 10. Discharge outlets a. Threads are compatible with fire department

Identify the initial installation requirements for standpipe systems 11. Fire department connection a. It s accessible b. Protective caps are in place c. Threads are compatible with fire department threads d. No thread or connector damage e. Check valve works properly f. There is no debris in the connection

Identify the initial installation requirements for standpipe systems 12. Drains are free of dirt and/or sediment 13. Hose is dry and in good condition (Class II & III) 14. Hose is properly racked (Class II & III) 15. Records of testing the hose (Class II & III) 16. Swing out racks works easily (Class II & III)

Identify the initial installation requirements for standpipe systems 17. Threads on hose and connections are not damaged (Class II & III) 18. Gaskets are in good condition (Class II & III) 19. Nozzle not obstructed (Class II & III) 20. Shutoff if so equipped is operating properly (Class II & III)

IV. Maintenance A. Performed in accordance the literature provided by the manufacturer

Maintenance B. NFPA 25 1. Hose valve outlets a. Cap missing- replace b. Fire hose connection damaged - repair c. Valve handles missing - replace

Maintenance d. Cap gaskets missing or deteriorated - replace e. Valve leaking - close or repair f. Visible obstructions - remove g. Restricting device missing - replace

Maintenance 2. Piping a. Damaged - repair b. Control valves damaged - repair or replace c. Missing or damaged pipe supports - repair or replace d. Damaged supervisory devices - repair or replace

Maintenance 3. Hose a. Inspect - follow NFPA 1962 b. Mildew, cuts, abrasions and deterioration - replace c. Coupling damage - replace or repair d. Gaskets missing or deteriorated - replace e. Incompatible threads on coupling replace or provide adapter f. Hose not connected to hose rack nipple or valve - connect g. Hose test date outdated - Retest or replace IAW NFPA 1962

Maintenance 4. Hose nozzle a. Hose nozzle missing - replace b. Gasket missing or deteriorated - replace c. Obstructions - remove d. Nozzle does not operate smoothly - repair or replace

Maintenance 5. Hose storage device a. Difficult to operate - repair or replace b. Damaged - repair or replace c. Obstruction - remove d. Hose improperly packed or rolled - remove e. Nozzle clip in place and nozzle correctly contained (?) replace if necessary f. If in a cabinet will it swing 90 degrees - repair or remove any obstructions

Maintenance 6. Cabinets a. Check overall condition - repair or replace b. Difficult to open - repair c. Cabinet door will not open fully - repair or remove obstruction d. Door glazing cracked or broken - replace e. If breaking glass type, is lock functioning - repair or replace

Maintenance f. Glass break device missing or not attached - replace or attach g. Not properly identified - provide identification h. Visible obstruction - remove i. All valves, hose, etc. are accessible - remove anything not related

V. Identify the process to conduct an in service inspection. 14-9.4 A. Process 1. All water supply valves are sealed in the open position 2. Power is available to the fire pump (in other words, the pump is in running condition) 3. Individual hose valves are free of paint, corrosion, and other impediments 4. Hose valve threads are not damaged 5. Hose valve wheels are present and not damaged 6 Hose cabinets are accessible

Identify the process to conduct an in service inspection. 7. Hose is in good condition, is dry, and is properly positioned on the rack of reel 8. Discharge outlets in dry systems are closed 9. Dry standpipe is drained of moisture 10. Access to the fire department connection is not blocked

Identify the process to conduct an in service inspection. 11. The fire department connection is free of obstruction, the swivels rotate freely, and the caps are in place 12. Water supply tanks are filled to the proper level 13. If the system is equipped with pressureregulating devices, those devices are tested as required by the manufacturer 14. Dry systems are hydrostatically tested every five years