Using the Models TA-460, PVM610, and PVM620 to Measure Pressure

Similar documents
P06 & P012 Pitot-Static Probes

CORRECTING FOR HUMIDITY EFFECTS ON TSI GENERAL PURPOSE FLOWMETERS

S-Type Pitot Tube. Operating Instructions

P8 to P60 Pitot-Static Probes

Mass Flowmeters. Mass Flowmeters for Gases

UNDERSTANDING, ACCELERATED

Positive and Negative Duct Accreditation (PANDA) System

Gas Physics Pressure and Flow Topics Covered:

AerE 343L: Aerodynamics Laboratory II. Lab Instructions

Automatic Isokinetic Sampler. ST5 Evo

Automatic Isokinetic Sampler. ST5 Evo

F&J SPECIALTY PRODUCTS The nucleus of quality air monitoring programs

TOPIC: KNOWLEDGE: K1.01 [2.5/2.7] An atmospheric pressure of 15.0 psia is equivalent to... A psig. B psig. C psig.

Quick Reference Technical Data

STANDARDS FOR COMPRESSED GAS TESTING

Unit A-2: List of Subjects

OWNER S MANUAL. AXD 530 MicroManometer

Pressure measurement explained

Cover Page for Lab Report Group Portion. Lift on a Wing

Chapter 13 Gases, Vapors, Liquids, and Solids

Operating instructions Pitot Static Tube

Lab 1c Isentropic Blow-down Process and Discharge Coefficient

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

AIR FLOW CALIBRATORS Single Sensor Designs

No E. General Information. Averaging Pitot Tube Flow Sensor HITROL CO., LTD.

EMISSION SURVEY FOR SONAE NOVOBORD: WHITE RIVER. Report No. 565/12 FR.1. March 2013 C & M CONSULTING ENGINEERS PO BOX LYNNWOOD RIDGE 0040

THERMODYNAMICS, HEAT AND MASS TRANSFER TUTORIAL NO: 1 (SPECIFIC VOLUME, PRESSURE AND TEMPERATURE)

METHOD 2A - DIRECT MEASUREMENT OF GAS VOLUME THROUGH PIPES AND SMALL DUCTS. NOTE: This method does not include all of the

FAN ENGINEERING. Field Testing of Fans FE-900. Introduction. Testing Equipment. Testing Standards. Prior to Testing

ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Squire-Cogswell

OXYGEN TRANSFER CAPABILITIES CANADIANPOND.CA PRODUCTS LTD.

International Journal of Research in Advent Technology Available Online at:

Model 4040/4043/4045 General Purpose Thermal Mass Flowmeter

OVERVIEW. Flow Coefficient C v. Operating Conditions. Specific Gravity

Gas Turbine Performance Analysis

ATTACHMENT O WIPP MINE VENTILATION RATE MONITORING PLAN

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

PROCESS MONITORING AND CONTROL

Good News From the Doctor

Gas Flow Calibration Basics

Cover Page for Lab Report Group Portion. Drag on Spheres

Pressure Measurement

METHOD 2E - DETERMINATION OF LANDFILL GAS PRODUCTION FLOW RATE. NOTE: This method does not include all of the

CTG Certification Protocol -- Version 3.0 SUMMARY

Positive and Negative Duct Accreditation (PANDA) System Airflow Instruments Model PAN341 Series (PANDA Light)

deltaflowc deltaflowc Venturi or Probe

KNOWN: Mass, pressure, temperature, and specific volume of water vapor.

Methods and Equipment for Calibration of Variable Area Meters (Rotameters)

COMPAFLOW. Compressed Air. Volumetric flow. Gas. Mass flow. Steam. Net volumetric flow. Liquid

CHEMISTRY - CLUTCH CH.5 - GASES.

Middle East Technical University Department of Mechanical Engineering ME 305 Fluid Mechanics I Fall 2018 Section 4 (Dr.

Are you really doing your job if you fail to measure static pressure every time you service a unit? The answer is no.

CRITERIA FOR LABORATORY ACCREDITATION IN THE FIELD OF PRESSURE METROLOGY

and its weight (in newtons) when located on a planet with an acceleration of gravity equal to 4.0 ft/s 2.

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow

Instructions for SMV 3000 Multivariable Configuration (MC) Data Sheets

Mass Flow Meter (MFM) for Gases

Constant Pressure Inlet (CCN) Operator Manual

Chapter 13 Fluids. Copyright 2009 Pearson Education, Inc.

Instrumentation & Data Acquisition Systems

Draft. Equipment/Instrument

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Standard Test Method for Measuring Insertion Loss of Pneumatic Exhaust Silencers 1

Bikes and Energy. Pre- Lab: The Bike Speedometer. A Bit of History

Group Quality Certification System of Performance Test for Clean Rooms (CR Mark)

Excellent Vortex Flowmeter INSERTION Type BATTERY POWERED EX DELTA

Fluke 700 Series pressure modules

Integral type Differential pressure flowmeter VNT Series

The Kinetic-Molecular Theory of Gases based on the idea that particles are always in motion

Technical Progress Report. Development of the Instrumentation and Modeling for Heat Transfer Characteristics in CFBC

Flow in a shock tube

Model 4140/4143 General Purpose Thermal Mass Flowmeter

Measurement of Atmospheric Pressure. Atmospheric Instrumentation

Ideal gas law. Introduction

CONSERVATORY DIAGNOSTIC TOOLS TO MEASURE BUILDING PERFORMANCE

CHAPTER 3 : AIR COMPRESSOR

POSITIVE AND NEGATIVE DUCT ACCREDITATION (PANDA) SYSTEM AIRFLOW INSTRUMENTS MODEL PAN341 SERIES (PANDA LIGHT)

Universities of Leeds, Sheffield and York

Particulate Emission Monitor Correlation. Camden Power Station Stack No RSL152

5 Function Indicator. Outside Air Temperature (C) Outside Air Temperature (F) Pressure Altitude Density Altitude Aircraft Voltage STD TEMP SL 15000

Cover Page for Lab Report Group Portion. Compressible Flow in a Converging-Diverging Nozzle

S265 Remote seals with capillary tube. 2600T Series Pressure Transmitters. Engineered solutions for all applications

CVEN 311 Fluid Dynamics Fall Semester 2011 Dr. Kelly Brumbelow, Texas A&M University. Final Exam

Experiment 1, Measurement and Density Chemistry 201, Wright College, Department of Physical Science and Engineering

Gas Measurement Fundamentals Certification. Curriculum

METHOD 2D - MEASUREMENT OF GAS VOLUME FLOW RATES IN SMALL PIPES AND DUCTS. NOTE: This method does not include all of the

Section 5.1 Pressure. Why study gases? An understanding of real world phenomena. An understanding of how science works.

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features

North American Orifice Metering System

Operational Settings:

GFM. Typical Aluminum GFM Mass Flow Meter NIST MASS FLOW METERS. Principles of Operation. Design Features

Mass Flow Controller (MFC) for Gases

NATIONAL CENTER FOR COMBUSTION RESEARCH AND DEVELOPMENT (NCCRD) INDIAN INSTITUTE OF TECHNOLOGY MADRAS CHENNAI , INDIA

Pressure Measurement

CLB 3 ATTRACTIVE JOINABLE LINEAR PROFILE EASILY ACCESIBLE VOLUME ADJUSTMENT INCLUDED FLEX CLAMP HEATING AND COOLING TERMINAL REHEAT AVAILABLE

CSC-2000 SERIES. Reset Volume Controllers MADE IN U.S.A. DESCRIPTION MODELS SPECIFICATIONS ORDERING

ME 449/549 Lab Assignment 2 Spring 2006 due 25 April Background. 2 Apparatus

Thermal Mass Flowmeters. 5 Mass Flowmeters

8. Now plot on the following grid the values of T (K) and V from the table above, and connect the points.

Properties of Fluids SPH4C

Transcription:

Using the Models TA-460, PVM610, and PVM620 to Measure Pressure Application Note AF-107 Models TA-460, PVM 610 and PVM 620 measure differential pressure, or in other words, the pressure difference between the two pressure ports. The (+) port connects to the higher pressure and the (-) port connects to the lower pressure (often ambient pressure). Using these instruments to measure differential pressure is like using a digital oltmeter: when the pressure is connected the same way the tubes are marked, the meter displays a positie number. When the pressure is reersed, the meter displays a negatie number. Although different terms are used to describe different types of pressure, we can think of all pressure as differential pressure. For instance, the term absolute pressure refers to the difference between an absolute acuum and the pressure of interest. The absolute pressure of ambient air is known as barometric pressure. NOTE: The differential pressure sensor cannot measure barometric pressure. If you try to measure barometric pressure (which is approximately 400 inches of water, or 101 kpa) by connecting the (-) port of the instrument to an absolute acuum, the pressure sensor inside the unit will be destroyed because it is only designed to measure ±10 inches of water (2.5 kpa). Static pressure describes the difference between the pressure inside and outside a system, disregarding any motion in the system. For instance, when referring to an air duct, static pressure is the difference between the pressure inside and outside the duct, without taking into account pressure from any air flow inside the duct. Static pressure is often measured inside ducts in order to determine how hard the blower is working. Models TA-460, PVM 610, and PVM 620 are supplied with a static pressure tip that can be used for measuring static pressure. Attach the static pressure tip to a tube on the (+) port of the instrument. Keep the (-) port free so that it can measure ambient conditions. Make sure the static pressure tip is pointed directly into the airflow. If the static pressure in the duct is positie, the instrument will display a positie number. If the static pressure is negatie, the instrument will display a negatie number. The static pressure can also be measured using a regular pitot tube as shown in Figure 1, below. A pitot tube is a tube within a tube. The inside tube is open to the air at the tip of the tube (total pressure), and the outside tube is open on the sides of the tube (static pressure). To measure static pressure with a pitot tube, you use only the static pressure port and ignore the total pressure port.

Figure 1: Measuring static pressure with pitot tube The instrument can also be used for measuring elocity pressure (Velocity Pressure = Total pressure - Static Pressure) with a pitot tube and conerting into air elocity. It is useful in locations where the thermal anemometer probe cannot be used. For instance, it may be desired to measure elocity in an exhaust stack, where high temperatures and high particle content could damage the elocity probe. Figure 2: Measuring elocity pressure with a pitot-static tube The front orifice of the pitot tube senses the total pressure, which is the static pressure in the duct plus the elocity pressure caused by air blowing into this orifice. By connecting the instrument to the pitot tube, you will get elocity pressure.

When the measurement conditions are close to standard conditions of 70 F (21.1 C) and 14.7 psia (29.92 in. mercury or 101.4 kpa), the following equations can be used with a pitot-static tube to compute elocity: V ft/min = 4004. 4 P V ft/min = elocity in feet per minute = 40 76 P V ms /. V m/s = elocity in meters per second P = elocity pressure measured by the instrument in kpa If the measurement conditions are substantially different from standard conditions of 70 F (21.1 C) and 14.7 psia (29.92 in. mercury or 101.4 kpa), the following equation can be used to calculate standard elocity: V std ft/min = 16876 PP /( T + 459.67) V std ft/min = elocity in standard feet per minute I = barometric pressure in inches of mercury T = flow temperature in F V std m / s = 25. 4 PP /( T + 27315. ) V std m/ s = elocity in standard meters per second P = barometric pressure in millimeters of mercury P = elocity pressure measured by the instrument in kpa T = flow temperature in C It is important to note that the equations aboe gie standard elocity, which is elocity corrected to standard conditions. Standard elocity is the same measurement unit that the thermal anemometer elocity probe of the instrument indicates, and is a measure of the mass of the moing air. Most people are used to computing actual elocity (not corrected to standard conditions) using the pitot-static tube, howeer. The following equations can be used to calculate actual elocity when conditions are different than standard conditions of 70 F (21.1 C) and 14.7 psia (29.92 in. mercury or 101.4 kpa):

V ft/min = 1096. 7 P / d V ft/min = elocity in actual feet per minute d = density of dry air in pounds per cubic foot To compute d, the density of dry air in pounds per cubic foot: d = 1.325 Pb / (T + 459.67) P b = barometric pressure in inches of mercury T = flow temperature in F / = 44. 63 P / d V ms V m/s = elocity in actual meters per second P = elocity pressure measured by the instrument in kpa d = density of dry air in kg/m 3 To compute d, the density of dry air in kg/m 3 : d = 0.4638 Pb / (T + 273.15) Pb = barometric pressure in mm. of mercury T = flow temperature in C Some pitot-static tube manufacturers hae slide-rule type deices that make the corrections for you automatically. The Airflow Instruments models will do these calculations for you, proided you enter the test temperature and barometric pressure. It is important to remember that if temperature or pressure is substantially different from standard conditions, the difference between actual elocity and standard elocity could likewise be substantial. This means that when using the actual elocity equations with the pitot-static tube, the result will be different than the elocity probe reading (standard elocity). Airflow Instruments recommends using the standard elocity equations for the pitot-static tube because standard elocity measures the mass of the moing air. This defines the air's heat carrying capacity and its combustion oxygen content.

AIRFLOW Instruments, TSI Instruments Ltd. Stirling Road, Cressex Park, High Wycombe, Bucks, HP12 3RT, United Kingdom UK Tel: +44 149 4 459200 E-mail: info@airflowinstruments.co.uk France Tel: +33 491 95 21 90 E-mail: tsifrance@tsi.com Germany Tel: +49 241 523030 E-mail: tsigmbh@tsi.com Contact your local AIRFLOW Distributor or isit our website www.airflowinstruments.co.uk for more detailed information. 8/4/2008 Re. B Copyright 2008 by TSI Incorporated Quality Assured to ISO 9001:2000