Operating Instructions

Similar documents
Cover Page for Lab Report Group Portion. Head Losses in Pipes

Operating Instructions

Cover Page for Lab Report Group Portion. Pump Performance

Exercise 4-2. Centrifugal Pumps EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Pumps

MEMORIAL UNIVERSITY OF NEWFOUNDLAND Faculty of Engineering and Applied Science FLUID MECHANICS LABORATORY PIPE FRICTION

PROCESS ROTATING EQUIPMENT (CENTRIFUGAL PUMPS )

Understanding Net Positive Suction Head

The Discussion of this exercise covers the following points: Pumps Basic operation of a liquid pump Types of liquid pumps The centrifugal pump.

Introduction to Pneumatics

Armfield Distillation Column Operation Guidelines

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

The Discussion of this exercise covers the following points: Range with an elevated or suppressed zero Suppressed-zero range Elevated-zero range

TUTORIAL. NPSHA for those who hate that stuffy word. by Jacques Chaurette p. eng. copyright 2006

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

The Discussion of this exercise covers the following points:

Operating Instructions

Experiment Instructions. Circulating Pumps Training Panel

Digester Processes. 1. Raw Sludge Pumping System

Easy Nest Kits. Installation Suggestions

Exercise 2-2. Second-Order Interacting Processes EXERCISE OBJECTIVE DISCUSSION OUTLINE. The actual setup DISCUSSION

HYDRAULICS. H89.8D - Hydraulic Bench

WATER CONTROL SYSTEM QUICK START

A centrifugal pump consists of an impeller attached to and rotating with the shaft and a casing that encloses the impeller.

VACUVENT Valve functions - benefits - flowpath - VG series - Sewage

CHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller

Third measurement MEASUREMENT OF PRESSURE

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels

EXPERIMENT 2 LEVEL CONTROL SYSTEM

Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION

THE INNER WORKINGS OF A SIPHON Jacques Chaurette p. eng. January 2003

Installation of Your SprayMaster System

AQUAMATIC EASY NEST KITS INSTALLATION SUGGESTIONS

TEST SPECIFICATION NYT-909-C

By Syed Ahmed Amin Shah 4 th semester Class No 8 Submitted To Engr. Saeed Ahmed

SINGLE VALVE WITH LOW-FLOW BYPASS

BACK PRESSURE / SUSTAINING

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

Chapter 3 EXPERIMENTAL: EQUIPMENT, SET-UP, AND PROCEDURE

BACK PRESSURE / SUSTAINING

Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems

TANK MATE INCLUDES: TOOLS REQUIRED: CONRADER VALVES 3/4 WRENCH **TUBING CUTTERS TEE PETCOCK TEE ASSEMBLY 8 FOOT NYLON TUBING

"INOGATE Technical Secretariat & Integrated Programme in support of the Baku Initiative and the Eastern Partnership energy objectives" Project

This portion of the piping tutorial covers control valve sizing, control valves, and the use of nodes.

Installation and operation Manual. Bermad Surge Anticipation Valve. Model No 435

User Manual for the Mars Calibration Bench

Installation Manual. Model # SF-3W 9/16/03 REV 1. Arch Chemicals, Inc Lower River Road. P.O. Box 800 Charleston, TN PULSAR

Water Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware

Inert Air (N2) Systems Manual

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL OTHER FLUID POWER VALVES. This work covers part of outcome 2 of the Edexcel standard module:

FOAM TANK (1/2) DATA SHEET

Rejuvenation Instructions

Heat Pump Connections and Interior Piping

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

2. Determine how the mass transfer rate is affected by gas flow rate and liquid flow rate.

R E D I C O N T R O L S

The Discussion of this exercise covers the following points:

Pilot Check Valve: Metal Body Type

GAS DEHYDRATION SYSTEM

Integrity Testing LifeASSURE BNA045 and BNA065 Series Filter Cartridges

Ventam 85 Installation & Commissioning Instructions

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

PumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out

Master Control Systems, Inc. Variable Speed Fire Pump Controllers

Injection Systems INSTALLATION AND OPERATING GUIDE HI FLO VERTICAL TANK SYSTEMS

The following article was authored by Jacques Chaurette of Fluide Design, Inc. ( All rights reserved. - HOW DOES A SIPHON WORK?

Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow

Experiment 8: Minor Losses

Hi-Force Limited Prospect Way Daventry Northants NN11 8PL United Kingdom Tel: +44(0) : Fax: +44(0) : Website:

PUMP CONSULTING & TRAINING LLC Joseph R. Askew 1811 Stonecrest Ct. Lakeland, Fl

Cash Valve TYPE KP PILOT OPERATED BACK PRESSURE VALVE. ISSUED - DECEMBER 2000 CAVMC-0518-US-0208 ISO 9001 Certified

OPERATION AND MAINTENANCE MANUAL

Ir HN Lam BSc(Eng), MSc(Eng), CEng, MIMechE, MCIBSE, MASHRAE, MASME, MHKIE. Test Report on Non-Return Valve for Water Closets

Tentec. Instruction Document. Mini Air Driven Pump Unit Model: HTT.627X Series. Part Identifier

Leak testing of Valves. Standards for acceptable Rates of Valve Leakage

Proper Pump Installation Practices

Priority (Swing) Motors Data and Specifications

Endo-Flush Order # ZUTR30004 OPERATION MANUAL. Zutron Medical, LLC W 98 th St #40-27 Lenexa, KS Phone Fax

1020 Industrial Drive, Orlinda, TN fax

ORB-400 BUBBLE/HAZE MACHINE. Item ref: UK User Manual

TITAN FLOW CONTROL, INC.

LAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)

Regulators/valves Compressed air regulators Without filter

Hydraulic Reliability & Preventive Maintenance Report

Basic Pneumatics. Module 8: Pressure control valves. Academic Services PREPARED BY. April 2012

B. Assemble the Method-25 sample train with a heated probe/filter.

Manual Actuated Boiler Blowdown Valves

Introduction to Pumps

INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR NPTEL ONLINE CERTIFICATION COURSE. On Industrial Automation and Control

GREIG FILTERS, INC. OPERATION MANUAL

Design Change Notification

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

CentriFlow Meter Integrated Air Entrainment System

INDUSTRIAL VALVES MODELS: C62-A; C62-D. INSTRUCTION MANUAL Installation Operation Parts Service DIAPHRAGM BYPASS PRESSURE REGULATING VALVES

TECHNICAL DATA. Page 1 of 12

Standard Operating and Maintenance Instructions for Pumping System Model PS-150

INSTALLATION AND OPERATION INSTRUCTIONS

III. Identify the initial installation requirements for standpipe systems

INSTRUCTION MANUAL FOR. Chlorinator M 3600 C Controlmatik ABW

Gas Physics Pressure and Flow Topics Covered:

Transferring and Storage

Transcription:

Operating Instructions Note: 1. Never let the centrifugal pump run dry. 2. Make sure that there is at least one open path for water flow in the pipe network before turning the pump on. Never run the pump when all outlet valves are closed. 3. Be careful when closing valves while the pump is running. Always make sure that there will still be at least one open path for the water flow after you close a valve. Otherwise, you may: Damage the pump and/or Damage the pressure gauges by a shockwave caused by a sudden stop of the water flow. 4. Most of the valves in the Fluid Flow system are ball valves. To open a ball valve, rotate its handle so that it is aligned with the pipe. To close a ball valve, rotate its handle so that it becomes perpendicular to the pipe. Figure 1. Piping around the pump and the rotameter. 1. Configuring and starting the system a. There are three sources of water in the system: The building water supply The holding tank on the 1 st floor The holding tank on the 3 rd floor 3-1

Most of the time, you will be using the tank on the 3 rd floor for your source of water. The tank on the 1 st floor can be used to experiment with effects of low NPSH on the pump performance. The building water supply should only be used to refill the tanks. b. Select a tank for your water source and decide on the path for water flow. Water should flow from the selected source, into the pump, and through the rotameter. After it leaves the rotameter, water can be either recirculated back to the supply tank (this is useful for measurement of the pump characteristic curve) or sent through the pipe network first and then recirculated back to the supply tank. c. Trace the selected path for the water flow and make sure that all valves are in the correct position (open or closed) for the flow to follow your selected path. d. Once the valves are configured correctly, the pump can be turned on by simply pressing the button for its power supply (see Figure 1). 2. Rotameter calibration a. Make sure that the 1 st floor tank is about half-full. b. Record the volume of water in the 1 st floor tank. The volume graduations are on the back of the tank. Note that it is difficult to see the graduations if the tank is less than half-full. c. Configure the system so that water follows the following path: 3 rd floor tank pump 1 st floor tank. d. Turn the pump on and adjust the globe valve until a desired flow rate is achieved. e. Record the change in the water volume ΔV in the 1 st floor tank over a period of time Δt (recommended value of Δt is 30 to 60 seconds). Use a timer to measure time. f. Turn the pump off. g. Calculate the flow rate of water through the system as Q = ΔV/Δt. h. Repeat the above steps for several flow rates and create a table of the rotameter readings vs. the actual flow rate. 3. Measurement of characteristic curves of the pump and globe valve a. To obtain the pump and valve characteristic curves, water should be recirculated back to the feed tank without going through the pipe network. This allows one to investigate a wider range of water flow rates (since sending water through the pipe network will lead to additional friction losses and, hence, smaller maximum flow rate that can be generated by the pump). b. Use the globe valve and the rotameter (see Figure 1) to adjust and measure the water flow rate. c. To measure the pressure change across the pump, use pressure gauges installed at the pump suction (inlet) and discharge (outlet), see Figure 1. 3-2

d. Use the differential pressure gauges installed on the railing of the pipe network to measure pressure drop across the globe valve. (Instructions for these pressure gauges are provided below). e. Record dependence of the flow rate, pressure change across the pump, and pressure drop across the globe valve on the number of rotations of the valve handle. (The valve handle contains a dial displaying the number of rotations; zero rotations correspond to a fully closed valve). 4. Measurement of a characteristic curve of a ball valve a. Inspect the pipe network and find a ball valve with pressure ports located near its inlet and outlet. b. Adjust other valves in the system to allow fluid flow through the selected ball valve. Make sure that only one branch of the pipe network is open. c. Fully open the globe valve and the selected ball valve and turn on the pump. d. Measure the flow rate using the rotameter and the pressure drop across the selected ball valve using a differential pressure gauge, as descried in the next section. e. Repeat the previous step with the ball valve being only partially open: rotate the valve handle so that it forms an angle with the pipe direction. Recommended angles are 30 o, 45 o, and 60 o. 5. Differential pressure measurement using the analog pressure gauges. The analog differential pressure gauges are installed on the railing of the pipe network (see Figure 2). These pressure gauges are preferred over handheld digital manometers, since the latter tend to malfunction after prolonged exposure to water. a. Select a pressure gauge to be used. There are two pressure gauges connected to the pipe network, each with a different maximum pressure. Pressures above this maximum value cannot be measured. b. Identify manometer tubes connected to the high and low pressure ports of the pressure gauge. Connect the tubes to the pressure ports on the piping network. The pressure gauges will report meaningful results only if he tubes are connected in the correct order (i.e., the high-pressure tube is connected to a pressure port with higher pressure). If the pressure gauge is not displaying a reading, try switching the tubes. 3-3

Figure 2. Analog differential pressure gauge. c. The tubing must be fully filled with water in order to obtain accurate readings. Therefore, before taking pressure readings, it is necessary to vent air bubbles from the tubes by opening the drain valves (located below the pressure gauges) for a few seconds and allowing some water to drain. If you don t see any water flow from the drain valves, this means that the water pressure is too low to push air bubbles out of the tubing. In this case, temporarily increase the water flow rate (and, hence, pressure) in the pipe until you see water draining from both drain valves. Close the drain valves after a few seconds of draining. d. To measure gauge pressure at a single point, connect the high pressure manometer tube to the corresponding pressure port. Keep the second manometer tube open to the atmosphere. e. Place the manometer tubes back onto the white rack (see Figure 2) after your measurement is complete. Do not hang them by the clips of the connectors, since this will damage the connectors. 6. Pressure measurement using the handheld digital manometer Important: The analog manometers (see above) are preferred over the digital manometer, since the latter may malfunction after prolonged exposure to water. a. Re-zero the manometer prior to measuring pressure: Leave both ports of the manometer open to atmosphere. Turn the manometer on by pressing the ON key. Press and hold the HOLD/MEMORY key until CLR appears on the screen. Then press the ZERO/HOLD key. 3-4

b. Vent air from the plastic tubes connected to manometer. This can be done, e.g. by connecting one end of a tube to a pressure port on a pipe while leaving the other end open to atmosphere. Water flowing through the pipe will displace air in the tube. c. To measure differential pressure between two points, connect the manometer ports marked HIGH and LOW to the ports on the pipe network corresponding to high and low pressures. The tubing must be filled with water in order to obtain accurate readings. Note: If HIGH and LOW are switched, the digital manometer will report a negative value. d. To measure gauge pressure at a single point, connect the manometer port marked HIGH to the corresponding pressure port on the pipe. Keep the second manometer port open to atmosphere. e. Refer to the manufacturer s manual posted on the course website for information on other features of this manometer, including the Hold and Memory functions. 3-5