Hyquest Solutions Pty Ltd

Similar documents
Hydrological Services Pty Ltd 2012

HyQuest Solutions Pty. Ltd.

HYQUEST SOLUTIONS PTY LTD INSTRUCTION MANUAL TIPPING BUCKET RAIN GAUGE MODEL TB6

Installation and Operation Manual. Advanced Bubbler System

INSTRUCTION MANUAL TIPPING BUCKET RAIN GAUGE. MODEL TB3/0.1mm

HS Bubbler Technology. HyQuest Solutions New Zealand User Group August 2017

INSTRUCTION MANUAL TIPPING BUCKET RAINGAUGE MODEL TB3

INSTRUCTION MANUAL TIPPING BUCKET RAINGAUGE MODEL TB305-1MM

Halsey Taylor Owners Manual STOP!

Halsey Taylor Owners Manual 4410 Freeze Resistant Tubular Fountain STOP!

THE MF-400 SERIES. Operating and Service Manual. Series includes all variants of MF-400/401

THE HF-300 SERIES. Operating and Service Manual. Series includes all variants of HF-300/301

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Water Weir Flow Controller. Introduction. Safety Precautions. Mounting the Hardware

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

HYQUEST SOLUTIONS PTY LTD INSTRUCTION MANUAL TIPPING BUCKET RAINGAUGE MODEL TB6

Instruction Manual Updated 7/26/2011 Ver. 2.2

V48 Series 3-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

V46 Series 2-Way Pressure-Actuated Water-Regulating Valves With Union Fittings

VERTICAL BLADDER TANK

THE BP-690 SERIES. Operating and Service Manual. Series includes all variants of BP-LF/MF-690/691

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

HORIZONTAL BLADDER TANK

HYQUEST SOLUTIONS PTY LTD INSTRUCTION MANUAL TIPPING BUCKET RAIN GAUGE MODEL TB4

V43 Pressure Actuated Water Regulating Valve

RD(H)20/25 Pressure-Reducing Regulator User Manual

1200B2 Series Service Regulators. Instruction Manual

1800C and 1800C-HC Series Service Regulators

Dual Solenoid Gas Valve Installation

System Pressure Manager Standard & System Pressure Manager Plus

TECHNICAL DATA. Trimpac 251a. Spetember 16, 2013

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Pipe threads for tubes and fittings where pressure-tight joints are not made on the threads. (requires PTFE sealing tape or liquid sealant).

TECHNICAL DATA. Trimpac 244a. September 16, 2013

Components for air preparation and pressure adjustment. OUT port position ( ) connected Rear side. of IN port. Air tank. directly.

Installation, Operation, and Maintenance Manual

INSTALLATION INSTRUCTIONS. CVS 67CFR Pressure Reducing Instrument Supply Regulator INTRODUCTION

SIMPLAIR PIPING TOOL. JXT Company

Regulator from 1800 B series

ACCESSORY KIT INSTALLATION INSTRUCTIONS

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

OPERATION MANUAL NTF-15

PRO-50 Instrument Supply Regulator

Pressure Dump Valve Service Kit for Series 2300 Units

TECHNICAL DATA. TRIMPAC Model B-5 & B-5B

MUELLER A A Non-Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3.

Operating Procedure TITON SUBSEA BOLT TENSIONER

Premium Series. Economical Price & Reliable Performance. High Quality. Rust-Resistant. Long Life. Tamper-Resistant locking Screw.

Your safety and the safety of others are very important.

Techcon Systems TS1254 Pressure Pot

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

Combination Air Valve

Installation, Operation, and Maintenance Manual

SUMMITTM 400 & 600. Natural Gas Barbecues. Step-By-Step Guide

Installation of Your SprayMaster System

Techcon Systems TS1258 Pressure Pot

INSTRUCTION MANUAL TIPPING BUCKET RAINGUAGE MODEL TB3

MUELLER. A A Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3.

THE BP-301 SERIES. Operating and Service Manual. Series includes all variants of BP-301 (LF 0.1Cv / MF 0.5Cv)

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

THE HF-210 SERIES. Operating and Service Manual. Series includes all variants of HF-210/211. Issue A October 2014 *Section 6.

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5.

IP2, IP2A and IP2D. Spirax-Monnier International Compressed Air Filter/ Regulators

PAGE (Rev. A - 06/17)

GILMONT ACCUCAL FLOWMETERS

INSTALLATION INSTRUCTIONS FOR GRT75-PF-RFS PET FOUNTAIN

VACUUM REGULATORS CONTENTS

FRAGMENTATION INSTRUCTION & OPERATION HANDBOOK

Precision and Instrument Regulators 1/4" port size

Installation Instructions

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

O P E R ATING INSTRUCTIONS FOR MODEL SPR-45 Automatic Screen and Stencil Printer

Inflatable Packer Single & Double. Single & Double Packer Dimension. Wireline Packer. Water Testing Packer (WTP) Packer

ACCESSORY KIT INSTALLATION MANUAL

Chemical Injection Technologies Installation/Service Bulletin

P5513. Users Manual. Pneumatic Comparison Test Pump. Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.

Mounting and Operating Instructions EB EN. Type Supply Pressure Regulator. with increased air capacity

Operation Manual. Diaphragm Sensed Gas Pressure Regulators

AIR/OVER HYDRAULIC JACK 20 TON

Pressure Dump Valve Service Kit for Series 3000 Units

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

ABRASIVE REGULATOR II

product manual HM-4140, HM-4150, HM-4160 HM-4160A HM-4150 Humboldt FlexPanels

Nickel-Plated Brass Right Angle Flow Control Valves NPTF/Inch Series GSCU, GMCU, GSVU, GMVU, GSCO, GMCO

Installation Instructions

Installation Operation Maintenance. Bermad Level Control Valve with Modulating Horizontal Float Pilot valve One Way Flow IOM.

KJ4000 Operating Instructions & Parts Manual NSN

Constant Pressure Crude Oil Container Model CPCCP

ABRASIVE REGULATOR II

D05 Pressure Regulating Valves

Bermad Pressure Reducing. Model: 42T

BERMAD Waterworks. Level Control Valve with Altitude Pilot. 700 Series. Model X. Features and Benefits. Major Additional Features

Manual Solvent Purification System. Innovative Technology, Inc.

OPERATION MANUAL NTF-60 Plus

Transcription:

INSTRUCTION MANUAL BUBBLERS MODELS HS23SL / HS23DL / HS23DO QUALITY SYSTEM ISO: 9001 CERTIFIED HYQUEST SOLUTIONS PTY LTD PO BOX 332, LIVERPOOL B.C NSW 1871, AUSTRALIA Phone:(Int.) 612 9601 2022 Fax: :(Int.) 612 9602 6971 Phone:(Nat.) (02) 9601 2022 Fax: :(Nat.) (02) 9602 6971 Email: sales@hyquestsolutions.com.au Web: www.hyquestsolutions.com.au HS23 Copyright Page 1 Issue 2: 24/11/15

Contents Contents... 2 I. GENERAL... 3 II. UNPACKING YOUR HS23 BUBBLE UNIT... 3 III. SPECIFICATION... 4 IV. INSTALLATION & OPERATION OF MODEL HS23... 5 V. ADJUSTMENT OF BUBBLE RATE USING INSTRUMENT LINE... 7 VI ADJUSTMENT OF BUBBLE RATE USING RIVER LINE... 9 VII Part List... 12 Appendix... 15 IX INSTALLATION OF POLYTHENE TUBING AND ORIFICE FITTINGS... 16 X STANDARD ORIFICE... 18 XI GAS CHAMBER ORIFICE... 19 XII TYPICAL INSTALLATION... 22 HS23 Copyright Page 2 Issue 2: 24/11/15

I. GENERAL The HS23 bubble unit utilises the proven gas purge method to sense water level by bubbling gas through a small diameter tube and out from an open orifice end into the water body. Changes in water level in the water body result in a change in the pressure of gas inside the tube. A pressure transducer, connected to the HS23 then converts pressure changes in the tube to a reading of water level (in metres or feet). The HS23 provides a constant differential pressure (3 5 psi) above the pressure head at the end of the river line. The HS23 is a design which incorporates a regulator valve for setting the bubble rate. The unit is precalibrated at the factory (refer to section VII). This new design eliminates the need of a sight glass and oil reservoir for the setting of the bubble rate. It also eliminates costly and often ineffective maintenance of the bubble unit due to oil inadvertently getting into the system which is the most common cause of failure with sight glass devices. The HS23 is a low maintenance unit with minimum components ensuring increased reliability. The high quality of the construction materials ensures long life in the harshest of environments. II. UNPACKING YOUR HS23 BUBBLE UNIT This package should contain: Dry Bubble Unit Allen Key (1/32ʺ) Please verify you have received these items and that the type of dry bubble unit is as ordered. To prepare the dry bubble unit for installation: read manual carefully, it can be downloaded from our website www.hyquestsolutions.com.au lift the unit from the carton and place on secure surface remove polythene bag undo the two mounting bolts and remove from transport board Attach Dry Bubble unit to wall or edge of self using the two holes on the mounting plate. (It is preferable to set up the bubble unit in the vertical position) Your dry bubble unit is now ready for installation (refer to section V, page 7). HS23 Copyright Page 3 Issue 2: 24/11/15

III. SPECIFICATION Model Configurations: 1. Single Line Gas Purging System HS23SL: a. Inlet to suit tubing diameters 1/4" standard 3/16" alternative 3/8" alternative b. Outlet to suit tubing diameters 3/8" standard 3/16" alternative 1/4" alternative c. Gas supply dry nitrogen or dry air d. Packing details: Dimensions: Weight: 220mm x 220mm x 150mm 3.5 kg 2. Dual Orifice Gas Purging System HS23DO: a. Inlet to suit tubing diameters 1/4" standard 3/16" alternative 3/8" alternative b. Outlet to suit tubing diameters 3/8" standard 3/16" alternative 1/4" alternative c. Gas supply dry nitrogen or dry air d. Packing details: Dimensions: Weight: 220mm x 220mmx150mm 4.5 kg Compatible Pressure Transducers: Models WL3100, WL3100A and WL2100D HS23 Copyright Page 4 Issue 2: 24/11/15

IV. INSTALLATION & OPERATION OF MODEL HS23 Set gas bottle in a convenient position and fix to a wall or shelf with a bracket or chain to prevent bottle from falling over. Before fitting the gas regulator, turn on bottle to clear dust away from the outlet (also check that bottle contains gas). Fit regulator in accordance with manufacturer's instructions. Fix bubble unit in a secure vertical position to wall or edge of shelf. Install tubing as required by site conditions. Figure 1 and Figure 2 show recommended tubing arrangements for single, dual line and dual orifice systems respectively. The inlet and outlet ports are 1/4 NPT female threads and on standard units are fitted with compression fittings for use with 3/8" OD x 1/8" ID polythene tubing for outlets and 1/4" OD nylon tubing for gas inlet. An adaptor fitting can be provided to accommodate a variety of sensors and alternative tube fittings are also available on request. Refer to appendix for suggested site arrangements. Prior to opening the gas supply valve, ensure that black valve(a) to instrument and the red purge valve (C) is shut, and that black valve (B) or (E) to the river are open. In addition, ensure that the gas supply regulator is set at 500 KPa (72 psi). This supply pressure is adequate for a change of river height of 25 Metres (80 Feet). The supply pressure to the bubble unit regulator should not exceed 1,050 kpa (150 psi) under any circumstances. Open the gas supply pressure and then open the red purge valve (C) to purge the river line for approximately 10 minutes, check orifice and ensure that gas is bubbling from the orifice After purging the river line shut the red purge valve (C) and allows the bubble rate to settle for five minutes before proceeding. The HS23 is factory set to 100 ± 10% bubbles per minutes (this rate represents approximately 27 bubbles per minutes at the river line). (Refer to fig.4a) for bubble rate selection chart. For details of bubble rate adjustments (refer to section VII). Slowly open valve (A) to instrument instrument should now respond to pressure in system and soon record the true head over the orifice. Leak test all joints. Adjust the pressure sensing device to correspond to the head indicated by the reference gauge. HS23 Copyright Page 5 Issue 2: 24/11/15

HS23SL Single Line Figure 1 HS23DO Dual Orifice Figure 2 HS23 Copyright Page 6 Issue 2: 24/11/15

V. ADJUSTMENT OF BUBBLE RATE USING INSTRUMENT LINE Note: This option is only available if customer orders the optional kit for testing bubble rate using instrument line. 12 Minimum Bubble Rate as shown in table below Change in level Metres/Hr 8 4 HS23 with GCO1P/SS HS23 with BU07 HS22 with Glass Site 10 16 24 33 21 32 48 65 80 120 160 200 Graph showing relationship between follow rate and bubble rate for a selected length of tube. Please note the bubble rate changes depending on the orifice that has been used. Figure 3 HS23 Copyright Page 7 Issue 2: 24/11/15

1. Shut river line valves (B) and (E) and ensure that the purge valve is closed. 2. Shut instrument line valves (A) 3. Place Bubble Test Orifice in a container of water 4. Connect Test Orifice Line 5. Slowly open Instrument Line 6. Note: Bubble rate may not appear immediately at test orifice. Allow sufficient time for differential regulator and HS23 to stabilise pressure in test line. This may take up to 10 minutes. Once bubble rate has stabilised check bubble and if adjustment is required, refer to the chart below. 7. After checking bubble rate turn of instrument line and disconnect test orifice line 8. Reopen instrument and river line The chart below has been prepared to show the relationship between the bubble rate at the test orifice and the equivalent rates that would be observed on a sight glass bubble unit. Once the desired bubble rate has been achieved tighten the grubscrew to lock the metering valve. Bubble rate when a Gas Chamber Orifice Model (GCO1 P) in use Bubble rate when a standard orifice model BU07 in use Bubble rate when a HS22 bubble unit with sight glass is in use 10 21 80 14 27 100 16 35 120 24 48 160 33 65 200 Note: Bubble rates detailed above are only an approximate guide for the purpose of conserving gas and have no influence on the performance of the transducer. Example: To adjust the HS23 to the equivalent of 120 bubbles per minute, the metering valve should be rotated anticlockwise until 35 bubbles per minute are emerging from the test orifice of the bubble unit. HS23 Copyright Page 8 Issue 2: 24/11/15

VI ADJUSTMENT OF BUBBLE RATE USING RIVER LINE 12 Minimum Bubble Rate as shown in table below Change in level Metres/Hr 8 4 HS23 with GCO1P HS23 with BU07 HS22 with Glass Site 10 16 24 33 21 32 48 65 80 120 160 200 Graph showing relationship between follow rate and bubble rate for selected length of tube. Please note the bubble rate changes depending on the orifice that has been used. Figure 4 HS23 Copyright Page 9 Issue 2: 24/11/15

The HS23 Bubble Unit has been factory set to the equivalent rate of 100 bubbles per minute. To check and adjust the bubble rate the following method should be employed: 1. Shut the instrument line valve (A), river line valves (B) and (E) and ensure that the purge valve is closed. 2. Disconnect the river line tubing from the bubble unit. 3. Connect a one metre length of tube to the river line fitting of the bubble unit. 4. Submerge the other end of the tube to a depth of 100mm in a container of clean water. (This end of the tube should be secured at this depth, preferably in a horizontal position). The end of the tube should not be in contact with the sides or bottom of the water container. 5. The water container should be placed on a steady surface to prevent movement of the water. Ensure that the level of the water is below the level of the HS23 bubble unit, to avoid the ingress of water. 6. Ensure that the gas supply valve is open and the gas supply regulator is set at 500KPa. 7. Open the river line valve (B) or (E). (Gas should be bubbling from the orifice) 8. Allow the rate to settle for five minutes before timing the bubble rate. 9. With the aid of a stop watch, count the number of bubbles emerging from the orifice in a one minute period. The factory set rate is 27 +/ 10% bubbles per minute. 10. For recommended bubble rates (refer to figure 4). 11. To adjust the rate, release the grubscrew in the metering valve knob. (a 1/32" Allen key will be required.) The valve is now free to rotate. 12. Rotate the valve knob to adjust the rate of bubbles emerging from the tube orifice. Clockwise to reduce and anticlockwise to increase to the desired rate. Repeat step 8 and 9 until desired bubble rate is obtained. 13. Tighten the grubscrew in the metering valve knob. (a 1/32" Allen key will be required.) The valve is now shut. 14. Shut the instrument line valve (A), river line valves (B) and (E) and ensure that the purge valve is closed. 15. Disconnect the one metre length tube from the river line fitting of the bubble unit. 16. Reconnect the river line tubing to the bubble unit 17. To continue installation (refer to section V) HS23 Copyright Page 10 Issue 2: 24/11/15

The chart below has been prepared to show the relationship between the bubble rate at the test orifice and the equivalent rates that would be observed on a sight glass bubble unit. Bubble rate when a Gas Chamber Orfice Model (GCO1 P) in use Bubble rate when a standard orifice model BU07 or test orifice in use Bubble rate when a HS22 bubble unit with sight glass is in use 10 21 80 14 27 100 16 35 120 24 48 160 33 65 200 Once the desired bubble rate has been achieved tighten the grubscrew to lock the metering valve. Note: Bubble rates detailed above are only an approximate guide for the purpose of conserving gas and have no influence on the performance of the transducer. Example: To adjust the HS23 to the equivalent of 120 bubbles per minute, the metering valve should be rotated anticlockwise until 35 bubbles per minute are emerging from the test orifice of the bubble unit. HS23 Copyright Page 11 Issue 2: 24/11/15

VII Part List Part No. BU02-04 Diaphragm Spring Part No. BU02-02 Bonnet Part No. SC025-12 Nut Aluminium-1/4 Part No. SC025-13 Nylon Ferrule-1/4 Part No. SC027-12 Metering Valve Part No. SC022-02 Screw Part No. BU04 Assembly Diaphragm Part No. HS2301-04 Valve Stem Part No. SC024-18 O ring Part No. HS2301-02 Retainer Nut Part No. SC025-18 Nut Brass ¼ Part No. SC025-13 Nylon Ferrule Set ¼ Part No. SC024-19 O ring Part No. SC027-16 Adaptor Tube Part No. HS4005-03 Locking Screw Part No. HS2301-01 Unit Body Part No. SC078-03 ¼ Tube Part No. HS4005-04 ¼ Tube insert C Part No. SC027-01 Stop Valve Part No. SC078-03 ¼ Tube Part No. HS4005-04 ¼ Tube insert Part No. SC027-05 Red Knob Part No. HS2302-01 Manifold Part No. SC025-18 Nut Brass ¼ Part No. HSF02-01 Connector M x¼ Tube A B Part No. HSF02-01 Connector M x¼ Tube Part No. SC025-13 Nylon Ferrule Set ¼ Part No. HSF02-04 Connector F x 1/4 Tube Part No. HSF02-02 Connector F x 3/8 Tube Part No. SC027-01 Stop Valve Part No. SC027-03 Black Knob Part No. SC025-19 Nut Brass 3/8 Part No. SC025-11 Nylon Ferrule Set 3/8 Single Line Bubble Unit Model HS23SL HS23 Copyright Page 12 Issue 2: 24/11/15

Please Note: for the rest of the parts. Please refer to HS23-SL Part No. HSF02-01 Connector M x¼ Tube Part No. BU01-08 Cross Piece F x F x F x F C B Part No. HSF02-02 Connector F x 3/8 Tube E A Part No. HSF02-04 Connector F x 1/4 Tube Part No. SC025-19 Nut Brass 3/8 Part No. SC025-11 Nylon Ferrule Set 3/8 Part No. SC025-02 Brass Plug Part No. SC025-18 Nut Brass ¼ Part No. SC025-13 Nylon Ferrule Set ¼ Dual Orifice Bubble Unit Model HS23DO HS23 Copyright Page 13 Issue 2: 24/11/15

Please Note: for the rest of the parts. Please refer to HS23-SL Please Note: This product is no longer available; it has been superseded by the GCO1 P Part No. HSF02-01 Connector M x¼ Tube Part No. BU01-08 Cross Piece F x F x F x F C A D Part No. SC025-18 Nut Brass ¼ Part No. SC025-13 Nylon Ferrule Set ¼ Part No. HSF02-04 Connector F x 1/4 Tube Part No. SC027-15 Connector M x3/8 Tube Part No. SC025-02 Brass Plug Part No. SC025-19 Nut Brass 3/8 Part No. SC025-11 Nylon Ferrule Set 3/8 Dual Line Bubble Unit Model HS23DL HS23 Copyright Page 14 Issue 2: 24/11/15 B Part No. HSF02-02 Connector F x 3/8 Tube Part No. SC025-19 Nut Brass 3/8 Part No. SC025-11 Nylon Ferrule Set 3/8

Appendix HS23 Copyright Page 15 Issue 2: 24/11/15

VIII INSTALLATION OF POLYTHENE TUBING AND ORIFICE FITTINGS A. General The polythene tubing is provided in either ¼ (6mm) or 3/8 (10mm) OD sizes. It is an extremely durable material that has been used successfully in this application world wide for many years. The tubing is flexible, easy to handle and can be cut with a knife. The orifice fitting is comprised of a moulded polythene threaded cap, an orifice outlet and a tube fitting. The moulded cap will screw onto a standard 50 nominal bore galvanised pipe. B. Orifice Fittings The site and reference level for the orifice fittings should be resolved before installation proceeds. The length of tubing from the HS23 to the orifice should not exceed 150 metres. A suggested method for installation of the orifice fitting is shown below. The site of the orifice should be positioned in quiet water out of the mainstream to provide protection. The area should be free of silting and aquatic growth. The mounting for the orifice fitting should consist of a section of 50 nominal bore galvanised pipe threaded at one end and secured at the appropriate reference level. The securing of the orifice mounting should be such that it can withstand the forces applied by the flowing stream and associated floating debris. C. Preparation of Orifice Tubing Do not open the carton or remove the strapping. To prepare the roll of tubing for use, cut a 300 mm diameter hole in the centre of the cardboard carton, retrieve the end of the tubing from the middle of the coil, then cut the strapping retaining the coil. This method will reduce the possibility of tangling the tubing. Prevent the ingress of dirt etc. from entering the tubing, by taping up the ends. At no time should the open end of the tubing be permitted to contact the soil. D. Orifice Tubing It is recommended that a trench be dug (minimum 600 deep) between the equipment shelter and the proposed positions of the orifice The trenches should not have any low points in their length; they should have a continuous fall to the river. HS23 Copyright Page 16 Issue 2: 24/11/15

Pull the free end of the coiled tubing to the orifice position laying the tubing in the trench as you go. Refer to diagrams below Remove the protective tape from the end of the tubing, and push the tubing through the 50 nominal bore pipe mounting. Insert the tubing into the tube fitting on the rear of the orifice fitting, ensuring that both ferrules are in place. Tighten the fitting nut. (Refer to the following diagram for tightening procedure). Place the orifice fitting onto the mounting pipe and tighten. Cut the tube at the coil end (tape both ends), ensuring that there is sufficient length to make the joint at the HS23 within the shelter. Check the lay of the tubing in the trench to ensure that it is free of coils and kinks. Under no circumstances should the tube form hollows where moisture can be trapped within the tube. Lay the tubing into position in the equipment shelter as required. Remove the protective tape from the end of river line tube. Insert the end of the tube into the appropriate river line fitting on the HS23 and tighten both fittings. (Refer to diagram for tightening procedure). Open the valve to the orifice. HS23 Copyright Page 17 Issue 2: 24/11/15

IX STANDARD ORIFICE HS23 Copyright Page 18 Issue 2: 24/11/15

X GAS CHAMBER ORIFICE The HyQuest Solutions Gas Chamber Orifice (GCO1P/SS) is designed to replace the standard orifice in a gas purge water level measurement system The GCO1P/SS permits the use of extremely low bubble rates with increased sensitivity and near total reduction of lag between actual level rise and orifice pressure. It can also operate satisfactorily when buried under up to 1m of silt. Bubble rates as low as 10 bubbles per minute can be used, thereby reducing gas consumption and prolonging the life of the gas bottle, or reducing the duty cycle operation of the compressor pump on our HS 55/45/40 bubbler water level measurement systems. The main GC01P/SS chamber is constructed entirely of polyethylene with a copper coated brass screen to deter aquatic growth, and is supplied fitted with a 2" flexible coupling to suit a standard 2 threaded pipe and to allow easy installation as the coupling allows up to 30 degrees of adjustment from horizontal. The GCO1P/SS has an in built 1/4 inch NPT hex brass coupling and is supplied with 1/4 inch NPT male to 3/8. The bottom of the chamber includes a revolving copper coated brass screen for cleaning purposes The unit is designed to be fitted to existing installations preferably during low water condition. Refer reverse side for results of comparative tests and installation details. Float Operated Encoder (Level in mm) Standard Orifice 100 Bubbles/Min Gas Chamber Orifice 10 Bubbles/Min Reading Lag Reading Lag 0 0 0 810 578 232 810 0 1700 1200 500 1700 0 2400 1540 860 2398 2 3600 2294 1306 3588 12 HS23 Copyright Page 19 Issue 2: 24/11/15

Step 1: Secure Socket/Locknut to the 2 BSP pipe 2 BSP THREADED PIPE Step 2: Undo the nut and ferrules; feed the tube nut and the two ferrules onto the river line as shown in figure below Step 3: Tighten the tube nut to the GCO1P/SS fitting as shown in figure below HS23 Copyright Page 20 Issue 2: 24/11/15

Step 4: Place the GCO1P/SS assembly onto the mounting pipe, adjust coupling so the GCO1P/SS is horizontal to the water, and tighten the flexible coupling with GCO1 in position. 30 O Note: Ensure that the GCO1P/SS is horizontally level as shown. Flexible coupling allows adjustment up to 30 Parts & Dimensions HS23 Copyright Page 21 Issue 2: 24/11/15

XI TYPICAL INSTALLATION HS23 Copyright Page 22 Issue 2: 24/11/15