ISQB1 INTRINSICALLY SAFE ELECTRO-PNEUMATIC CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS HAZARDOUS AREA CLASSIFICATION

Similar documents
INSTALLATION & MAINTENANCE INSTRUCTIONS

INSTALLATION & MAINTENANCE INSTRUCTIONS DESCRIPTION SPECIFICATIONS. CE (EMC) Compliant

QBS Electronic Pressure Regulator

QBS Electronic Control Valve

INSTALLATION & MAINTENANCE INSTRUCTIONS QBX ETHERNET MODEL

GP1 & GP2. Electropneumatic Regulators FOR PRESSURE CONTROL TO 1,000 PSI

QBX QBS QBT ELECTRO-PNEUMATIC PRESSURE REGULATORS. On-Board Ethernet Option. Accurate & Repeatable. High Pressure Control. Up to 12 bar & 34 Lit/Min

Electropneumatic Transducer (I/P) Installation, Operation and

THE INSIDE STORY OF THE F-SERIES:

I/P Transducer Positioner Module

QBX QBT QBS ELECTRO-PNEUMATIC PRESSURE REGULATORS. On-Board Ethernet Option. Accurate & Repeatable. High Pressure Control. Up to 12 bar & 34 Lit/Min

DPC-30 DPC-100. Reference Manual

PRODUCT CATALOG ELECTRO-PNEUMATIC PRESSURE REGULATORS & FLOW CONTROLLERS PRESSURE FLOW FORCE TENSION POSITION TORQUE VACUUM

The Ins and Outs of I/P Transducers

BAROMETER PRESSURE STANDARD PRESSURE CONTROLLER

ASDX Series Silicon Pressure Sensors

INSTRUMENT MANUAL VP50 PROPORTIONAL CONTROL VALVE

INSTRUCTION MANUAL. FLOW CONTROL DRAWERS MANUAL / PLC CONTROL SERIES Model Version Perma Pure LLC Tel:

P-5215 Differential Pressure Transmitter

MANUAL KPS Pressure Control Valve

L 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions

Section 2 Proportional Quick Exhaust

CSA Sample Draw Aspirator Adapter Operator s Manual

Deep Submersible Level Transducer Series 300DS

Features. Main Voltage: Vdc. Input Control Signal: 0-5 Vdc or 4-20 madc (Sourcing) Monitor Output Voltage: 0-5 Vdc or 4-20 madc (Sourcing)

MODEL CALIBRATION GAS DELIVERY SYSTEM

MODEL GT820 OXYGEN SENSOR

SSL. Smart Valve Positioner.

Model PDT Dewpoint Transmitter

2/ Port G1/4

E8AA. Pressure Sensor of Stainless Steel Construction Is Ideal for a Wide Range of Applications. Pressure Sensor (Stainless Steel Diaphragm)

INSTRUCTION MANUAL MP4AR Remote Convection Gauge Range: 1 x 10-3 Torr to 1 x 10+3 Torr

NB/NBR NITROGEN BOOSTER FOR AVIATION SERVICE

PULSAR 5000 SERIES OPERATING & INSTALLATION INSTRUCTIONS SERIES 5000 PLEASE READ CAREFULLY BEFORE INSTALLING

RK LEL Sample Draw Aspirator Adapter Operator s Manual

SERVICE MANUAL MODEL BA600AMST-S1 BREATHING AIR PANEL

Design Features. General Description

Installation and Operation Manual

RK-IR Sample Draw Aspirator Adapter Operator s Manual

2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure

Digital electro-pneumatic regulators Series ER100

Pilot Check Valve: Metal Body Type

T EK-SUB 4800C 19 mm Submersible Level Transmitter

PT-400 User Manual APG

Auto-Zero Calibration Technique for Pressure Sensors

86BSD Backside Digital Output

BULLETIN E485A. Standard Interface Poppet Valve Construction Customized Solutions Plug-and-Play Design.

Instruction Manual for Intrinsically Safe - Reed Switches

SITRANS P measuring instruments for pressure

For a similar sensor with o-ring mounting, refer to the 85BSD digital output pressure sensor.

RAM 4021 Operation Manual

Model 106 DPI "Micro-switch" Installation and Operating Instructions

ASIC-Based Small Bore Submersible Level Transducer

Miniature Electronic Pressure Controllers. Precision Fluidics

P9000 DESCRIPTION. For parts requiring RoHS compliance, please contact factory. P February /6

TR Electronic Pressure Regulator. User s Manual

Smart performance with innovative and ever-strong coil drive even under harsh working environments

GasSense NDIR User Manual

KING-GAGE. Calibration Instruction Manual. D/P LiquiSeal Purge Control and D/P Purge Control

Exercise 8. Closed-Loop Pressure Control, Proportional-Plus-Integral Mode EXERCISE OBJECTIVE

SSR. Smart Valve Positioner.

RAM 4021-DPX Operation Manual

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

AFC. SDPROC and AFC Analog Mass Flow Controller ANALOG MASS FLOW CONTROLLERS. Principles of Operation. Design Features

CDS-2000 CO 2 Sensor Verification, Calibration, and Troubleshooting Bulletin

RCD - Ultra-Rugged Differential Pressure Flowmeter

! Unique Cable Seal System! Fully Temperature Compensated! Datalogger Compatible

Nitrogen Supply System

Constant Pressure Inlet (CCN) Operator Manual

Differential Pressure Transmiter

RAM Operation Manual

PT-400 User Manual APG

MASS-STREAM TM Instruction Manual. D-6200 Analog Mass Flow Meters / Controllers

TOP VALVE. Pat. #5,857,486 & 5,944,050. Mid-Range Pressure PSIG Back Pressure and Pressure Relief Valves. Instruction Manual

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

DeltaSpan Pressure Transmitters LD10 Series Owner s Manual

SERVICE MANUAL MODEL BA200AMST-S1 BREATHING AIR PANEL

RAM Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

SERVICE MANUAL MODEL BA050BMST BREATHING AIR PANEL

VACUUM REGULATORS CONTENTS

CS Controlled Dissolved Gas assembly with optional CS Air Aspirator assembly. Installation and Operation information

RAM 4021-PR. Operation Manual. Worldwide Manufacturer of Gas Detection Solutions

Technical Instructions

GFM. Typical Aluminum GFM Mass Flow Meter NIST MASS FLOW METERS. Principles of Operation. Design Features

BULLETIN E485B. Poppet Valve Construction Customized Solutions Plug-and-Play Design. Subject to technical modifications.

J21K Series DIFFERENTIAL PRESSURE SWITCH. features

Technical Manual. Liquid Level Transmitter CT801-LB/S

61R2 STANDARD REGULATOR COMPACT REGULATOR. Phone Fax

OPTIBAR P 1010 C Technical Datasheet

Instruction Manual AD 1000 / BA 1000 Absolute Pressure Sensor

SERVICE MANUAL MODEL BA100BMST 100 SCFM PORTABLE AIR PANEL

TOP VALVE. Pat. #5,857,486 & 5,944,050. High Temperature: max. 300 F (149 C) Back Pressure And Pressure Relief Valves. Instruction Manual

Variable Area Flow Meters

Mass Flow Controllers


INSTRUCTION MANUAL. CVS P37 LP Gas Reducing Regulator

[Instruments for vacuum measurement, checking and adjustment] 3

PRESSURE SENSOR - ABSOLUTE (0 TO 700 kpa)

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

Transcription:

PROPORTION AIR ISQB1 INTRINSICALLY SAFE ELECTRO-PNEUMATIC CONTROL VALVE INSTALLATION & MAINTENANCE INSTRUCTIONS Hazardous area classification Description / identification General specifications Connection procedure Re-calibration procedure Dimensions ISQB1 valve Dimensions QBT-01 bracket DESCRIPTION / IDENTIFICATION ISQB-MS1 Before you get started, please read these warnings: Examine the product. Ensure that you received what you ordered. Read this guide first before you start and save it for later use. All compressed air and power should be shut off before installing, removing or performing maintenance on this product. Installation and use of this product should be under the supervision and control of properly qualified personnel in order to avoid the risk of injury or death. Media vents through exhaust port. If the media is hazardous (classified), the exhaust port should be vented into a safe area. HAZARDOUS AREA CLASSIFICATION Ordering information and accessories Factory Mutual Approval: Class I, II, III, Division 1 Group C,D,E,F,G Entity Parameters: V Max = 29 VDC I Max = 150 MA Ci = 0.24uF Li = 0 Field Wiring Drawing ISQB-96026-2 NOTE: End user must determine fitness and suitability of the ISQB1 control valve for their application. The ISQB1 series control valve is an electronic pressure regulator designed to precisely and proportionally control the pressure of gaseous media based on an electronic control signal. The ISQB1 operates using two normally closed solenoid valves, a pressure sensor, and a control circuit. One valve is actuated to allow supply media into the system. The second valve is actuated to allow working media to vent to atmosphere. The pressure sensor provides feedback to the control circuit. The control circuit compares the pressure sensor feedback to the user supplied electronic command signal and actuates the appropriate valve until the two signals match. The ISQB1 series can be teamed with a variety of pressure volume boosters for even greater flow. 1/8

GENERAL SPECIFICATIONS ELECTRICAL Supply Voltage....Per Field Wiring Drawing & Barrier Manufacturer Specs. Supply Current.<80mA Command Signal..4-20mA Differential Command Signal Impedance...100 OHM PHYSICAL Operating temperature.....32-104ºf (0-40ºC) (T4) Weight..2 lb. (0.91 kg) Protection Rating..NEMA 4 Housing....Blue Anodized Aluminum MECHANICAL Pressure ranges... 29.9 in. Hg (VAC) -150 psig Output Pressure...0-100% of range Flow Rate.0.80 SCFM @ 80 psig Min. Closed End Volume 1 in³ Filtration Required..40 micron Linearity/Hysterisis..< 0.15% F.S. B.F.S.L Repeatability...< 0.02% F.S. Accuracy..< 0.2% F.S. Wetted Parts..Elastomers-Fluorocarbon Manifold-Brass Transducer-Silicon, Aluminum,RTV Valves-Nickel Plated Brass CONNECTION PROCEDURE Pneumatic Connections: Electrical Connections: ISQB-MS1 1. A typical 20 micron (minimum 40 micron) in-line filter is recommended on the inlet of the ISQB1. 2. Connect supply pressure to the IN inlet port (figure 1). See Table 1 for maximum supply pressure. 3. Connect the OUT outlet port (figure 1) to the device being controlled. 4. Media vents through exhaust port. If the media is hazardous (classified), the threaded exhaust port (figure 1) should be vented into a safe area. 5. Proceed with electrical connection. TABLE 1 RATED PRESSURE FOR ISQB1 VALVES For valves ordered with MAX. calibrated pressure of: Vacuum up to 10 psig (0.69 bar) Max. inlet pressure is: Consult factory 10.1 up to 30 psig (0.70 up to 2 bar) 35 psig (2.4 bar) 31 up to 100 psig (2.1 up to 7 bar) 110 psig (7.6 bar) 101 up to 150 psig (7 up to 12 bar) 150 psig (12 bar) ELECTRICAL CONNECTOR BRACKET ATMOSPHERIC REFERENCE Figure 1 ZERO & SPAN ACCESS CAP THREADED EXHAUST PORT 10-32 UNF 1. All intrinsically safe installation must conform to applicable Factory Mutual Code recommendations and the National Electric Code, as well as any applicable local codes or Fire Marshal directives. All intrinsically safe installations must be performed by personnel trained in the proper application of the above. 2. Ensure all power is off before making any electrical connections. 3. Figure 1 shows the location of the ISQB1 electrical connector and figure 2 shows the connector. Table 2 identifies each connection 4. Must be wired in accordance with the supplied field wiring drawing. TABLE 2 ISQB1 PIN DESIGNATORS PIN 1 DC COMMON (-) PIN 6 DC POWER (+) PIN FUNCTION 1 DC COMMON 2 COMMAND (-) 3 NC PIN 2 4-20 MA COMMAND (-) Figure 2 PIN 4 4-20 MA COMMAND (+) 4 COMMAND (+) 5 NC 6 POWER 2/8

FIELD WIRING DRAWING ISQB-96026-2 3/8

FIELD WIRING DRAWING ISQB-96026-2 4/8

FIELD WIRING DRAWING ISQB-96026-2 5/8

FIELD WIRING DRAWING ISQB-96026-2 6/8

RE-CALIBRATION PROCEDURE All ISQB1 valves come pre-calibrated from the factory using precision calibration equipment and trained personnel. The ISQB1 operates closed loop around a precision electronic pressure sensor. Typical drift is less than 1% over the life of the product. If your ISQB1 appears to be out of calibration by more than 1%, it is not likely the ISQB1. Try checking the system plumbing, leakage, wiring, electronic signal levels, and measure equipment before recalibrating. If the ISQB1 valve needs re-calibration, use the procedure described below: Re-calibration: 1. Wire servo according to the section titled Electrical Connections. 2. Connect a precision measuring gage or pressure transducer to the outlet port of the ISQB1. NOTE: There must be a closed volume of at least 1 cu.in. between the valve outlet and the measuring device for the valve to be stable. 3. Provide supply pressure to the inlet port of the ISQB1. (See figure 1). Make sure supply pressure does not exceed the rating for the valve. (see table 1) 4. Locate the calibration access cap on top of the ISQB1 valve and locate the ZERO and SPAN adjustment potentiometers (figure 1). NOTE: Only use this step if your device is totally out of calibration. If it is slightly out of calibration, omit this step and move on to paragraph 5. Using a small screwdriver, turn both potentiometers 15 turns clockwise. Then turn them 7 turns counter clockwise. This will put the ISQB1 roughly at mid scale. 5. Set the electrical command input to 20mADC. Adjust the SPAN potentiometer until MAXIMUM desired pressure is reached (clockwise to increase pressure). 6. Set the electrical command input to 10 percent of full value (5.6mA). 7. Adjust the ZERO potentiometer until 10 percent of maximum desired pressure is reached. (clockwise increases pressure). 8. The ZERO and SPAN potentiometers interact slightly. Repeat steps 5-10 until no error exists. 9. Verify unit shuts off by going to 4mADC command. Check linearity by going to at least six pressures throughout the full range. DIMENSIONS ISQB1 VALVE 7/8

DIMENSIONS QBT-01 BRACKET ISQB-MS1 ORDERING INFORMATION ISQB1TI- 100 S108 INTRINSICALLY SAFE SERIES * Vacuum only not available. Vacuum through positive pressure range units must have positive pressure range equal to or greater than the vacuum range. MAX. CALIBRATED PRESSURE Ranges Available VAC-150 PSIG* EXAMPLES 100 = 0-100 PSI 005 = 0-5 PSI SPECIAL OPTIONS S108 = Board Mod. S38 = Calibrate 3-15 psig Consult Factory for Available Options QBT-01 ACCESSORIES ISCBAR10 ISPBAR11 MOUNTING BRACKET COMMAND BARRIER KFD2- CD- EX1.32 POWER BARRIER KFD2- SD- EX1.32 WARRANTY Proportion-Air products are warranted to the original purchaser only against defects in material or workmanship for one (1) year from the date of manufacture. The extent of Proportion-Air's liability under this warranty is limited to repair or replacement of the defective unit at Proportion-Air's option. Proportion-Air shall have no liability under this warranty where improper installation or filtration occurred. All specifications are subject to change without notice. THIS WARRANTY IS GIVEN IN LIEU OF, AND BUYER HEREBY EXPRESSLY WAIVES, WARRANTIES OR LIABILITIES, EXPRESS, IMPLIED OR STATUTORY, INCLUDING WITHOUT LIMITATION ANY OBLI- GATION OF PROPORTION-AIR WITH REGARD TO CONSEQUENTIAL DAMAGES, WARRANTIES OF MERCHANTABILITY, DE- SCRIPTION, AND FITNESS FOR A PARTICULAR PURPOSE.... WARNING: Installation and use of this product should be under the supervision and control of properly qualified personnel in order to avoid the risk of injury or death. PROPORTION-AIR, INC. BOX 218 MCCORDSVILLE, IN USA 46055 PHONE: (317)335-2602 FAX: (317)335-3853 web site: www.proportionair.com email address: info@proportionair.com 8/8