4m Blanco Glycol Chiller system: history, recent events, present status and plans

Size: px
Start display at page:

Download "4m Blanco Glycol Chiller system: history, recent events, present status and plans"

Transcription

1 4m Blanco Glycol Chiller system: history, recent events, present status and plans Brooke Gregory, Esteban Parkes, Chris Smith 22 May 2012 Background Information: Original configuration (from ~1975) of two glycol cooling loops: Floor loop: 10 T chiller (for cooling M floor; later its use was expanded to cool hydrostatic bearing oil, primary mirror as well) Building loop: 30 T chiller (air conditioning for computers, console room, other working spaces, etc.) Chiller system upgrade: (Jun- Oct 2011): Floor loop: 30 T (refurbished and moved from the Building Circuit) Building loop: 40 T (new Trane chiller replaced 30 T unit for cryocooler compressors, air- conditioning for Coude instrument lab and cleanroom, in addition to existing demands for computers, console room, etc.) Glycol plumbing: Glycol from each of the two chillers is circulated to the telescope via two nominally independent circuits, each with its own pump. The utilities building, which houses the pumps, also provides a system of valves and interconnecting pipes which permit: Re- routing the glycol so that a spare pump can be brought into service to replace the pump in either circuit, Connecting the circuits in series so that they may be served by a single pump and a single compressor, providing backup (with reduced capacity), in the case of a chiller failure. DECam and the glycol system: The DECam instrument is cooled by a continuous stream of liquid nitrogen pumped in a closed loop from a storage vessel. The nitrogen vapor produced in the cycle is re- liquefied in the vessel by cryocoolers. The cryocoolers use pressurized helium as the working fluid, also operating in a closed loop. The helium compressors recompress the helium returned from the cryocoolers. The compressors run continuously and are cooled by glycol from the Blanco glycol plant. Consequently, continuous operation of the glycol plant is important for continuous operation of the instrument. (The liquid nitrogen system is, however, tolerant of interruptions of the glycol system of several hours, so, in the case of failures, time is available to reconfigure the system, switch to backup compressors or chillers, without interrupting the operation of DECam.) This document reports a recent failure of the glycol system, analyzes the causes and identifies areas where the current system can and must be increased in reliability.

2 Analysis of the Events of Mar/April/May Mar 40T chiller: This chiller has two completely independent refrigerant circuits, each with two compressors. The two circuits are activated simultaneously only when cooling demand requires them. On this date, low refrigerant pressure was detected in circuit 2. The demand in this period was relatively low and the second circuit was not required for operation but steps were taken to get the circuit recharged. We did not have the refrigerant or the charging manifold when this occurred. We had asked the air conditioning contractor Creavi to quote on periodic maintenance on 19Mar. When we detected the low- pressure we insisted with Creavi and told them of the more urgent need for the recharge. Their quote for the repair work (US$4500) was excessive, so we opted to acquire the refrigerant and manifold ourselves. We received the material on 9Apr. One of our technicians was instructed to recharge the system, but hadn t gotten it done before 17Apr due to other duties. Apart from this background problem, both chillers were delivering the cooling required at the time. 17Apr - At about 22:30 [UT], the 40 T chiller had been working well controlling the temperature of the glycol at about 5 C. At that time the helium compressors were turned on by Herman Cease. Immediately, (within a few minutes) the glycol supply temperature started to rise. After about half an hour the compressors were turned off. See the second plot in the technical appendix. The near simultaneity of the chiller shutdown with the compressor turn- on is clear evidence that the load represented by the compressors caused the shutdown. Presumably this is because the chiller was working on only one circuit. As long as the load did not rise above the limit that could be handled by the single circuit, the chiller continued to operate reliably. Once that limit was exceeded, the chiller failed, not simply to be able to maintain the control temperature but by shutting down. Subsequent misbehavior of the chiller controller suggests that the controller may have responded incorrectly: there is no obvious reason why the chiller should have shut down. Steady operation of the 40 T chiller was obtained late in the day of 19Apr and compressor operation began. Shortly after noon on 20Apr, >12 hours after starting the operation of the DECam cryocoolers, during which time the supply of glycol and the operation of the cryocoolers was normal, an increase in the glycol temperature indicated that the chiller had failed again. Based on experience since that event it is becoming increasing clear that the 40 T chiller controller has become unreliable. 18Apr - The backup procedure in this case is to replace the 40 T chiller. The 30 T chiller is switched from the floor glycol loop to the building glycol loop. That was undertaken. However two unrelated problems emerged: a.) In part due to recent changes in the glycol systems and transitions in staff responsibilities, the Telescope Operations staff did not have the knowledge to reconfigure the valves to switch to the other

3 chiller. Enrique Figueroa was contacted for information, and a former CTIO glycol system technician, Eudocio Guerrero, was pulled from another project on the on the mountain to make the switch. b.) Once connected to the other loop, the 30 T chiller failed to run. After unsuccessful attempts to get help from the Creavi tech who had worked on the refurbishment of the 30 T chiller, the problem was traced to the glycol flow sensor. This sensor should have been detecting flow in the circuit flowing through the 30 T chiller. The pump was on, so Guerrero guessed that the flow sensor was connected to the wrong glycol circuit. This turned out to be the case: turning on the pump for the 40 T chiller permitted the 30 T chiller to start! Once the 30 T chiller was working, it was observed that its capacity was lower than expected. It was unable to reach its 5 C setpoint, staying at about 8 C. This is low enough to work but was indicative of a problem. 23Apr Enrique Figueroa examined the status of the 40 T chiller, out of service since its failure. He observed the Code 8 boot error with which the chiller had failed. (Repeated attempts to recover from the Code 8 boot error by resetting had failed to resuscitate the chiller.) At this time, Figueroa did a reset and the machine started normally on Circuit 1 and ran for 2 hours without failure. Circuit 2 was still without refrigerant and prevented from running. He and Guerrero proceeded to recharge Circuit 2. They disabled Circuit 2 to prevent interaction with the operation of the other circuit. They evacuated the refrigerant volume of Circuit 2 (28 inches of vacuum) and then installed the full contents (11.3 kg) of the new cylinder of refrigerant (R- 410A). (They observed that when the pressure was lowered in Circuit 2, it caused the operation of Circuit 1 to halt though there should have been no interaction between the Circuits. This was a surprise.) After recharging, the refrigerant pressure was more than sufficient for continuous operation, but a total of 14.5 kg of refrigerant is specified in the manual. An additional supply of refrigerant has been ordered. 24Apr Meanwhile, engineers from Climacor were invited to the mountain to diagnose both machines. (Climacor is a company, with a presence in La Serena, which is used by Gemini for chiller maintenance.) They found the 40 T chiller to be operating normally, and diagnosed the 30 T chiller as having a small refrigerant leak. The observatory is arranging to have Climacor return to correct the problems which are limiting the performance of the 30 T chiller Conclusions: The root cause of the failure of the 40 T chiller on 17Apr was almost certainly an intermittent fault related to the repeated faults seen in the control system since then. The Observatory is in contact with Trane and Climacor to identify the best course for implementing a repair (probably a replacement of the control module).

4 Whatever the cause of the failure of the 40 T unit, the second 30 T chiller is capable of providing the cooling required by DECam and is intended to be available as a backup in the case of a failure of the 40 T chiller. The attempt to switch to the 30 T chiller was hampered by several conditions: A previously unidentified wiring error in the (recent) refurbishment and installation of the 30 T chiller caused it to fail to start. The staff present at the time of the failure was not fully trained in the required reconfiguration of the glycol lines. The performance of the 30 T chiller was lower than normal. Though it did not play a role in the current failure, the 40 T unit was itself in a less than normally robust condition because of the loss of coolant in a second, redundant, chilling circuit. This condition was not repaired in a timely fashion for reasons of lack of tools and material (refrigerant), and lack of staff to make the repair. Improvements required: In the absence of in- house staff doing maintenance & repairs, establish contact with locally available (La Serena) contract technical expertise. Rapid response capability is important. Train of mountain- resident staff in backup procedures. Test (periodically) backup procedures for responding to failure. Notwithstanding the present incident, the glycol system is very reliable. Therefore it is important to stage failures in order to test the capacities of the backup systems and to test and/or refresh the readiness of the staff in implementing backup procedures. Provide adequate material and tools for critical repairs. Status: 11May 40T chiller: Working normally, Circuit 2 recently recharged with refrigerant. Control module is evidently very unreliable. Though the unit is now running, restarting is difficult at best. The Observatory is in contact with Trane and Climacor about repair. 30T: Working normally but at less than normal capacity. The Observatory is arranging with Climacor for repair. Plans: Complete repair/maintenance on the 30T unit to bring it up to full capacity. Timeframe: ASAP Complete repair/replacement of the 40T unit control panel. Timeframe: ASAP Identify local profession AC equipment contractors to do periodic maintenance of both 30 T and 40 T chillers. Trane, Creavi and Climacor are candidates, although Climacor has local representatives who

5 may be able to respond more rapidly. We have a reasonable quote in hand from Climacor, but AURA regulations require at least three quotes, which we are pursuing. Timeframe: ASAP Draw up detailed operations and maintenance program for system by mountain staff Timeframe: by July 1 (including documentation and training) Including: Assign staff from TELOPS/ETS (rather than Facilities as has historically been the case) to 1. Oversee routine maintenance of the glycol system 2. Startup and operate the glycol cooling system. 3. Implement standard backup procedures to assure continuous or near continuous supply of glycol for the critical cryocooler and computer facilities, in the case of a component failure. These procedures are to respond to the cases of A failure of a pump in the glycol circulation system A failure of a chiller in the glycol refrigeration system Train staff: Start- up procedures Chiller failure recovery Pump failure recovery Maintain a complete stock of maintenance equipment: Stock of refrigerant R- 22 (??) and R- 410A Scale for weighing refrigerant in charging operation Charging manifolds Vacuum pump Spare control module for 40 T Trane chiller? Timeframe: August 1

6 Technical Appendix: Record of supply and return glycol temperatures (from DECam (SISPI) log file) a) Compressors operating with 40 T chiller. There is a gap in the SISPI record from ~13:00 18Apr - 21:00 19Apr, but according to Esteban's cry for help at 9 am 20Apr, the system had been working with the compressors since the day before. (There is a gap in the data from ~19Apr 2:00 until 19Apr 22:00.) b) Failure (of chiller?) causes compressors to shut down. c) Abandon tests (not clear exactly what precedes this). d) 8 C glycol, compressors not running (30 T chiller cooling glycol). e) Switch back to 40 T (after recharging and successful restart). f) Operate compressors with glycol from 40 T. g) Chiller fails again, and is successfully restarted and compressors are restarted. h) Compressors turned off, 40 T working, but cooldown is abandoned. i) Another chiller failure? This record starts at the beginning of the warmup that starts at 7:30 pm on 17Apr and also affects the temperature in the Coude (witnessed by Observatory sensors). The temperature rises off scale to 30 C! The DECam glycol sensors show the same temperature rise. The compressors were apparently not operating during this warmup, but were turned on after restoring the 40 T chiller and before the restoration of the data logging graphed here. With the

7 compressors off, there is no differential between supply and return. The warmup was caused by the initial failure of the 40 T chiller.

8 Zooming in on incident in the evening of 17Apr:

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly

CASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly Compressed Air Control System Industry Automotive Assembly Application Savigent Platform and Industrial Compressed Air Systems Background This automotive assembly plant was using over 40,000 kilowatt hours

More information

OPERATING PROCEDURES

OPERATING PROCEDURES OPERATING PROCEDURES 1.0 Purpose This element identifies Petsec s Operating Procedures for its Safety and Environmental Management System (SEMS) Program; it applies to all Petsec operations. Petsec is

More information

Copeland Discus with CoreSense Diagnostics January 2011

Copeland Discus with CoreSense Diagnostics January 2011 Copeland Discus with CoreSense Diagnostics January 2011 Slide 1 1/27/2011 5:48 PM Discus with CoreSense Diagnostics Case Studies Supermarket In Columbus, Ohio Saves $4,500 With Discus with CoreSense Diagnostics

More information

FAILURE SCENARIOS AND MITIGATIONS FOR THE BABAR SUPERCONDUCTING SOLENOID

FAILURE SCENARIOS AND MITIGATIONS FOR THE BABAR SUPERCONDUCTING SOLENOID SLAC-PUB-11601 December 2005 FAILURE SCENARIOS AND MITIGATIONS FOR THE BABAR SUPERCONDUCTING SOLENOID EunJoo Thompson, A. Candia, W. W. Craddock, M. Racine, J. G. Weisend II Stanford Linear Accelerator

More information

GEMINI 8-M Telescopes Project

GEMINI 8-M Telescopes Project GEMINI 8-M Telescopes Project SPE-S-G0048 Facility Thermal Management System Jim Oschmann Systems Engineering Group Robert Ford Telescope and Enclosure Group 28 June 1994 GEMINI PROJECT OFFICE 950 N. Cherry

More information

Control & Maintenance. INT69 Diagnose INT69 TM Diagnose. Protect the heart of your system

Control & Maintenance. INT69 Diagnose INT69 TM Diagnose. Protect the heart of your system Control & Maintenance INT69 Diagnose INT69 TM Diagnose Protect the heart of your system R INT69 DIAGNOSE The widely known protective system INT69 and INT69 TM present on all Frascold compressors is now

More information

I. Subject: Medical Gas Systems Utility Failure Interim Procedure III. Purpose:

I. Subject: Medical Gas Systems Utility Failure Interim Procedure III. Purpose: I. Subject: Medical Gas Systems Utility Failure Interim Procedure II. Purpose: To provide a systematic response to medical gas system failure and restoration of this critical utility. III. Procedure: Systems

More information

Session One: A Practical Approach to Managing Safety Critical Equipment and Systems in Process Plants

Session One: A Practical Approach to Managing Safety Critical Equipment and Systems in Process Plants Session One: A Practical Approach to Managing Safety Critical Equipment and Systems in Process Plants Tahir Rafique Lead Electrical and Instruments Engineer: Qenos Botany Site Douglas Lloyd Senior Electrical

More information

Leak Checking Large Vacuum Chambers

Leak Checking Large Vacuum Chambers Leak Checking Large Vacuum Chambers Technical Overview Vacuum Technologies Introduction Understanding the pump-down characteristics of a large vacuum vessel is critical for determining whether the vacuum

More information

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications

2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity

More information

RHIC CRYOGENIC SYSTEMS MAINTENANCE PROGRAM

RHIC CRYOGENIC SYSTEMS MAINTENANCE PROGRAM RHIC CRYOGENIC SYSTEMS MAINTENANCE PROGRAM Brookhaven National Laboratory Major Plant Equipment Categories / Locations Compressor Refrigerator Service Buildings The Maintenance program is based on the

More information

Advanced Pump Control for Irrigation Applications

Advanced Pump Control for Irrigation Applications Advanced Pump Control for Irrigation Applications Paul Nistler VFD Applications Engineer And Julian Atchia Director of Research and Development SJE Rhombus 22650 County Hwy 6 Detroit Lakes MN 56502 Executive

More information

WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE

WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE PACIFIC LIQUID & AIR SYSTEMS WPB 5 / 7 / 10 INSTALLATION, OPERATION, & MAINTENANCE IN THE BEGINNING Before installing or operating this system, familiarize yourself with these instructions. You should

More information

Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants

Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants the pressure equipment safety authority Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants AB-528 Edition 2, Revision 1 Issued 2016-09-12 Table of

More information

Vortex Dual. Refrigerant Recovery Machine

Vortex Dual. Refrigerant Recovery Machine O P E R A T I N G M A N U A L Vortex Dual Refrigerant Recovery Machine Table Of Contents Safety First!.................................... 3 EPA Certification................................ 3 Product

More information

Control of Hazardous Energy Lockout / Tagout Program

Control of Hazardous Energy Lockout / Tagout Program Control of Hazardous Energy Lockout / Tagout Program August 2016 Table of Contents Purpose... 1 Scope and Application... 1 Responsibilities... 1 Environmental Health and Safety Personnel (EH&S)... 1 Directors

More information

HUMAN FACTORS CHECKLIST

HUMAN FACTORS CHECKLIST HUMAN FACTORS CHECKLIST Item I. Housekeeping and General Work Environment 1 Are adequate signs posted near maintenance, cleanup, or staging areas to warn workers of special or unique hazards associated

More information

Process Safety Management Of Highly Hazardous Chemicals OSHA 29 CFR

Process Safety Management Of Highly Hazardous Chemicals OSHA 29 CFR Process Safety Management Of Highly Hazardous Chemicals OSHA 29 CFR 1910.119 PSM - Definition Not all refining hazards are caused by the same factors or involve ve the same degree of potential damage.

More information

LENNOX SLP98UHV DIAGNOSTIC CODES

LENNOX SLP98UHV DIAGNOSTIC CODES Code Status of Equipment Action required to clear and recover - Idle mode (Decimal blinks at 1 Hertz -- 0.5 second ON, 0.5 second OFF) A Cubic feet per minute (cfm) setting for indoor blower (1 second

More information

Every things under control High-Integrity Pressure Protection System (HIPPS)

Every things under control High-Integrity Pressure Protection System (HIPPS) Every things under control www.adico.co info@adico.co Table Of Contents 1. Introduction... 2 2. Standards... 3 3. HIPPS vs Emergency Shut Down... 4 4. Safety Requirement Specification... 4 5. Device Integrity

More information

THE DELIVERY OF GAS SUPPLY

THE DELIVERY OF GAS SUPPLY GAS ASSIST INJECTION MOLDING THE DELIVERY OF GAS SUPPLY April 2010 www.bauerptg.com THE DELIVERY OF GAS SUPPLY Gas assist requires a source of high-pressure nitrogen gas that can be controlled and delivered

More information

Solenoid Valves used in Safety Instrumented Systems

Solenoid Valves used in Safety Instrumented Systems I&M V9629R1 Solenoid Valves used in Safety Instrumented Systems Operating Manual in accordance with IEC 61508 ASCO Valves Page 1 of 7 Table of Contents 1 Introduction...3 1.1 Terms and Abbreviations...3

More information

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide Secondary Coolant System Start-Up Procedures June 2006 Produced by the Hill PHOENIX Learning Center DISCLAIMER This

More information

Fail Operational Controls for an Independent Metering Valve

Fail Operational Controls for an Independent Metering Valve Group 14 - System Intergration and Safety Paper 14-3 465 Fail Operational Controls for an Independent Metering Valve Michael Rannow Eaton Corporation, 7945 Wallace Rd., Eden Prairie, MN, 55347, email:

More information

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout) Purpose: To provide the minimum requirements for the lockout or tagout of energy isolating devices whenever work is performed or servicing is done on County of DuPage machinery, equipment, vehicles and

More information

WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107

WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107 WESTERN CONNECTICUT STATE UNIVERSITY LOCKOUT/TAGOUT PROCEDURE S-107 Draft Issued 12/97 Revised 11/00 Please direct any questions or comments about the applicability of this document to Luigi Marcone, WCSU

More information

Modification of the CNS Helium Injection Logic

Modification of the CNS Helium Injection Logic Modification of the CNS Helium Injection Logic Alfio Arcidiacono, Ashok Sah, Paul Walsh, Haneol Park, James Spedding, Mark Ho, Guan Yeoh, Weijian Lu 1) Australian Nuclear Science and Technology Organisation

More information

TESTING SAFETY OF HYDROGEN COMPONENTS

TESTING SAFETY OF HYDROGEN COMPONENTS TESTING SAFETY OF HYDROGEN COMPONENTS Wastiaux, S. 1, Willot F. 1, Coffre E. 1 and Schaaff J.P 1. 1 Air Liquide, Centre de Technologie et d Expertise, 180 avenue Charles Floquet, 93155 Le Blanc Mesnil,

More information

BIMA cryogenics (Dick Plambeck, 18jan2007)

BIMA cryogenics (Dick Plambeck, 18jan2007) BIMA cryogenics (Dick Plambeck, 18jan2007) Normal operation. Monitor from the antennas > 6-meter > receivers multiple> cryo rtd page. Troubleshooting. sensor what is it? normal range stage1 outer dewar

More information

DeZURIK. KGC Cast Knife Gate Valve. Safety Manual

DeZURIK. KGC Cast Knife Gate Valve. Safety Manual KGC Cast Knife Gate Valve Safety Manual Manual D11036 August 29, 2014 Table of Contents 1 Introduction... 3 1.1 Terms... 3 1.2 Abbreviations... 4 1.3 Product Support... 4 1.4 Related Literature... 4 1.5

More information

Heat Pump Connections and Interior Piping

Heat Pump Connections and Interior Piping Job Sheet 3 Heat Pump Connections and Interior Piping OBJECTIVES In this job sheet, you will observe how the presence of air in the ground loop affects the geothermal heat pump performance. You will also

More information

INTRODUCTION. The Quantum Technology system has the following advantages:, as it does not need plastic gas-bags which are volume-consuming,

INTRODUCTION. The Quantum Technology system has the following advantages:, as it does not need plastic gas-bags which are volume-consuming, 1 INTRODUCTION Quantum Technology is a leading scientific equipment supplier. For the last thirty years we served our customers by tailoring our products to each customer s unique requirements. Quantum

More information

EDUCATION DEPARTMENT ACCU-TEST

EDUCATION DEPARTMENT ACCU-TEST ABN 17 100 208 964 EDUCATION DEPARTMENT ACCU-TEST GAS SAFETY SHUT OFF SYSTEM Operating & Installation Manual Head Office (Melbourne) Sydney Brisbane (Distributor) 1/5 Samantha Court 2/14 Welder Road 17

More information

AFDXXX(X)AC Series Operators Manual Please read this manual thoroughly before attempting to operate your water maker.

AFDXXX(X)AC Series Operators Manual Please read this manual thoroughly before attempting to operate your water maker. AFDXXX(X)AC Series Operators Manual Please read this manual thoroughly before attempting to operate your water maker. E & O E Danger High Voltage AFDXXX(X) Series water makers operate on a 240vAC electricity

More information

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels

Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels (Jan 2017) Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels CONTENTS 1. Application 2. Special Survey 2.1 Schedule 2.2 Scope

More information

The Discussion of this exercise covers the following points:

The Discussion of this exercise covers the following points: Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring

More information

OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N

OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80589-02 Table of Contents Components... 2 Test... 4 Recovery/Recycling... 5 Evacuation... 7 Charging...

More information

D R A F T. Operating Procedures for the NPDGamma Liquid Hydrogen Target at the BL 13. Version 1.00

D R A F T. Operating Procedures for the NPDGamma Liquid Hydrogen Target at the BL 13. Version 1.00 D R A F T Operating Procedures for the NPDGamma Liquid Hydrogen Target at the BL 13 Version 1.00 October 06, 2010 Operating Procedures for the NPDGamma Liquid Hydrogen Target V1.00 6/10/10 2 Table of Content

More information

DRAFT. Operating Procedures for the NPDGamma Liquid Hydrogen Target in TA-53, Building MPF-35

DRAFT. Operating Procedures for the NPDGamma Liquid Hydrogen Target in TA-53, Building MPF-35 Operating Procedures for the NPDGamma Liquid Hydrogen Target V0.03 11/26/05 1 DRAFT Operating Procedures for the NPDGamma Liquid Hydrogen Target in TA-53, Building MPF-35 Version 0.03 November 26, 2005

More information

R E D I C O N T R O L S

R E D I C O N T R O L S R E D I C O N T R O L S Operation & Maintenance Manual Portable Service Purger for Low Pressure Chillers Model: PSP-LP-1B For Refrigerants R-11, R-113, R-114 & R-123 & Other Similar Refrigerants File Literature

More information

Remotely-installed Hydraulic Module

Remotely-installed Hydraulic Module Remotely-installed Hydraulic Module HDM 1.1-2.2 Single or twin pump ACC-PRC001E-GB Table of Contents Application Considerations Unit sizing...4 Unit placement... 4 Minimum water volume... 4 Selection Procedure...5

More information

AC : ACCURATE CRYOCHAMBER FOR A SMALL LABORATORY WITH SMALL BUDGET

AC : ACCURATE CRYOCHAMBER FOR A SMALL LABORATORY WITH SMALL BUDGET AC 2007-1108: ACCURATE CRYOCHAMBER FOR A SMALL LABORATORY WITH SMALL BUDGET Matthew Braley, University of Idaho Paul Anderson, University of Idaho Tracey Windley, University of Idaho Kevin Buck, University

More information

Reliability Assessment of the Whistler Propane Vaporizers

Reliability Assessment of the Whistler Propane Vaporizers Reliability Assessment of the Whistler Propane Vaporizers Prepared for: Terasen & Fransen Engineering Prepared by: ClearSky Risk Management Inc. 815 23 rd Ave East Vancouver, BC V6B 5Z3 Phone: 604.899.1470

More information

Unit 24: Applications of Pneumatics and Hydraulics

Unit 24: Applications of Pneumatics and Hydraulics Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 9 ACCUMULATORS The material needed for outcome 2 is very extensive so there are

More information

Hazardous Waste Training Plan. Supersedes: 02/15/16 (Rev.02) Preparer: Owner: Approver: EHS Team Member EHS Team Member EHS Manager

Hazardous Waste Training Plan. Supersedes: 02/15/16 (Rev.02) Preparer: Owner: Approver: EHS Team Member EHS Team Member EHS Manager Procedure No.: PA-033-0006 Page: 1 of 19 Port Arthur, TX. Reviewed: 02/18 Effective: 02/06/18 (Rev.03) Supersedes: 02/15/16 Preparer: Owner: Approver: EHS Team Member EHS Team Member EHS Manager Document

More information

TECHNICAL SPECIFICATION. SPC-1 Stirling Process Cryogenerator

TECHNICAL SPECIFICATION. SPC-1 Stirling Process Cryogenerator TECHNICAL SPECIFICATION SPC-1 Stirling Process Cryogenerator Reference 80 8013 00 Issue Date August 1, 2015 1. INTRODUCTION This document contains detailed technical information and specifications for

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

PREVENTION OF EXCESSIVE PRESSURE DURING FILLING OF CRYOGENIC VESSELS

PREVENTION OF EXCESSIVE PRESSURE DURING FILLING OF CRYOGENIC VESSELS PREVENTION OF EXCESSIVE PRESSURE DURING FILLING OF CRYOGENIC VESSELS AIGA 054/08 GLOBALLY HARMONISED DOCUMENT Asia Industrial Gases Association 3 HarbourFront Place, #09-04 HarbourFront Tower 2, Singapore

More information

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS)

South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System. Designed for: Dry or Preaction Fire Protection Systems (FPS) South-Tek Systems - Nitrogen Generation Corrosion Inhibiting System Designed for: Dry or Preaction Fire Protection Systems (FPS) 1.0 Description of Work 1.1 The Fire Sprinkler Contractor shall provide

More information

TECHNICAL SPECIFICATION. SPC-4 Stirling Process Cryogenerator

TECHNICAL SPECIFICATION. SPC-4 Stirling Process Cryogenerator TECHNICAL SPECIFICATION SPC-4 Stirling Process Cryogenerator Reference 80 8043 00 Issue Date August 1, 2015 1. INTRODUCTION This document contains detailed technical information and specifications for

More information

Impact on People. A minor injury with no permanent health damage

Impact on People. A minor injury with no permanent health damage Practical Experience of applying Layer of Protection Analysis For Safety Instrumented Systems (SIS) to comply with IEC 61511. Richard Gowland. Director European Process Safety Centre. (Rtgowland@aol.com,

More information

Active Hydrophore System AHS-01

Active Hydrophore System AHS-01 BRIEF PRODUCT DESCRIPTION: Standard material Seawater exposed parts: Titanium gr. 2 Rapid Response Valves: Titanium gr. 2 Cabinet: SST AISI 316 This is a skid mounted unit, with the hydrophore tank and

More information

RULES PUBLICATION NO. 119/P

RULES PUBLICATION NO. 119/P RULES PUBLICATION NO. 119/P PERIODIC SURVEYS OF FUEL INSTALLATIONS ON SHIPS OTHER THAN LIQUEFIED GAS CARRIERS UTILIZING GAS OR OTHER LOW FLASH POINT FUELS 2019 January Publications P (Additional Rule Requirements)

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

Pressure Systems Safety Regulation

Pressure Systems Safety Regulation Pressure Systems Safety Regulation Introduction This document informs Faculty of the key requirements of the UK and Chinese Pressure Systems Safety regulations. The aim of these regulations is to prevent

More information

SALT RSS-NIR MID-TERM REVIEW MAY 20 & 21, 2009 THERMAL SYSTEM DESIGN

SALT RSS-NIR MID-TERM REVIEW MAY 20 & 21, 2009 THERMAL SYSTEM DESIGN SALT RSS-NIR MID-TERM REVIEW MAY 20 & 21, 2009 THERMAL SYSTEM DESIGN DOUG ADLER UNIVERSITY OF WISCONSIN NIR THERMAL SYSTEMS Three primary thermal systems: Predewar, Dewar, and Electronics NIR instrument

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 331a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-3000P Valve. The small profile, lightweight, pilot-operated

More information

Safety manual for Fisher GX Control Valve and Actuator

Safety manual for Fisher GX Control Valve and Actuator Instruction Manual Supplement GX Valve and Actuator Safety manual for Fisher GX Control Valve and Actuator Purpose This safety manual provides information necessary to design, install, verify and maintain

More information

DPC-30 DPC-100. Reference Manual

DPC-30 DPC-100. Reference Manual DPC-30 DPC-100 Reference Manual 1. Introduction 1.1 Description The Martel DPC Digital Pneumatic Calibrator improves upon traditional dial gauge pneumatic calibrators. The Martel DPC improves accuracy,

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Preaction 346a 1. Description The 6 Model G-6000P Electric Release Preaction System Riser Assembly can be used as a Single Interlock Preaction System with Electric Release, or as a Double Interlock Preaction

More information

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module:

FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS. This work covers part of outcome 2 of the Edexcel standard module: FLUID POWER FLUID POWER EQUIPMENT TUTORIAL ACCUMULATORS This work covers part of outcome 2 of the Edexcel standard module: UNIT 21746P APPLIED PNEUMATICS AND HYDRAULICS The material needed for outcome

More information

DeZURIK. KSV Knife Gate Valve. Safety Manual

DeZURIK. KSV Knife Gate Valve. Safety Manual KSV Knife Gate Valve Safety Manual Manual D11035 August 29, 2014 Table of Contents 1 Introduction... 3 1.1 Terms... 3 1.2 Abbreviations... 4 1.3 Product Support... 4 1.4 Related Literature... 4 1.5 Reference

More information

DeZURIK Double Block & Bleed (DBB) Knife Gate Valve Safety Manual

DeZURIK Double Block & Bleed (DBB) Knife Gate Valve Safety Manual Double Block & Bleed (DBB) Knife Gate Valve Safety Manual Manual D11044 September, 2015 Table of Contents 1 Introduction... 3 1.1 Terms... 3 1.2 Abbreviations... 4 1.3 Product Support... 4 1.4 Related

More information

All Molybdenum Hot Zone & Elements. All Insulators are made of High Alumina. Element style - 1/8 Molybdenum Wire.

All Molybdenum Hot Zone & Elements. All Insulators are made of High Alumina. Element style - 1/8 Molybdenum Wire. Specification Sheet Equipment Model: J-1600 [18x30] Furnace Type Chamber Maximum Temperature Hot Zone Frame Dimensions Power Requirements Gas Requirements Thermocouple Vertical Bell with lifting hoist

More information

Customer Responsibilities

Customer Responsibilities Thank you for purchasing an Agilent instrument. To get you started and to assure a successful and timely installation, please refer to this specification or set of requirements. Correct site preparation

More information

Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST)

Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST) Series 3730 and Series 3731 EXPERTplus Valve Diagnostics with Partial Stroke Test (PST) Application Positioner firmware for early detection of control valve faults giving maintenance recommendations. Valid

More information

AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS

AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS AIR CONDITIONING AND PRESSURIZATION CONTROLS AND INDICATORS Air conditioning control panel 1 MIN MAX Page 1 Air conditioning control panel 2 MIN MAX Page 2 Air conditioning control panel 3 MIN MAX Page

More information

VS Series Leak Detectors for Vacuum Furnaces LEAK DETECTION FOR VACUUM FURNACES

VS Series Leak Detectors for Vacuum Furnaces LEAK DETECTION FOR VACUUM FURNACES VS Series Leak Detectors for Vacuum Furnaces LEAK DETECTION FOR VACUUM FURNACES VS Series Leak Detectors for Vacuum Furnaces indicate the presence of a leak. If the vacuum level is slow to reach the original

More information

RDK-408D2 Cold Head. Technical Manual. SHI-APD Cryogenics Inc Vultee Street Allentown, PA U.S.A. Revision A: September 2005

RDK-408D2 Cold Head. Technical Manual. SHI-APD Cryogenics Inc Vultee Street Allentown, PA U.S.A. Revision A: September 2005 RDK-408D2 Cold Head Technical Manual SHI-APD Cryogenics Inc. 1833 Vultee Street Allentown, PA 18103-4783 U.S.A. Revision A: September 2005 (Reference SHI Manual: December 18, 2003 266404A CD32ZZ-160A)

More information

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3

TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 TWC Services, Inc. Structured On-The-Job Training for JT- 1, 2, 3 The following tasks parallel the Jr. Tech (JT-1, 2, 3) description and development plan and use the Refrigeration and Air conditioning

More information

Simplicity in VRU by using a Beam Gas Compressor

Simplicity in VRU by using a Beam Gas Compressor Simplicity in VRU by using a Beam Gas Compressor By Charlie D. McCoy and Mark Lancaster Abstract: Vapor Recovery Units are often expensive, complicated to operate and unable to deal with High H2S and liquids.

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 347a 1. Description Viking supervised Double-Interlocked Electric/Pneumatic Release Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated

More information

This manual provides necessary requirements for meeting the IEC or IEC functional safety standards.

This manual provides necessary requirements for meeting the IEC or IEC functional safety standards. Instruction Manual Supplement Safety manual for Fisher Vee-Ball Series Purpose This safety manual provides information necessary to design, install, verify and maintain a Safety Instrumented Function (SIF)

More information

Unifrost NV/SA and Air Products

Unifrost NV/SA and Air Products Unifrost NV/SA and Air Products Our work together Unifrost are committed to best practices in health, safety and environmental protection, and the use of nitrogen follows from this. We re very pleased

More information

In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure

In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure PPMS Service Note 1099-412 In Response to a Planned Power Outage: PPMS EverCool II Shut Down and Re-start Procedure Introduction: Loss of electricity to the PPMS EverCool II should not cause damage to

More information

E2.14 Control of Hazardous Energy. Effective Date: 03/01/2018

E2.14 Control of Hazardous Energy. Effective Date: 03/01/2018 University Policy Volume E2: Environment, Health, Safety and Security E2.14 Control of Hazardous Energy Responsible Office: Facilities Management Responsible Officer: Safety Officer POLICY STATEMENT All

More information

Earlier Lecture. In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System.

Earlier Lecture. In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System. 17 1 Earlier Lecture In the earlier lecture, we have seen Kapitza & Heylandt systems which are the modifications of the Claude System. Collins system is an extension of the Claude system to reach lower

More information

COMPRESSOR REPLACEMENT PROCEDURE (R-134A)

COMPRESSOR REPLACEMENT PROCEDURE (R-134A) 372 ROUTE 4 BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 COMPRESSOR REPLACEMENT PROCEDURE (R-134A) [ ] If possible operate the compressor with proper charge for 5 minutes

More information

Improve Reliability of Turbomachinery Lubrication and Sealing Systems

Improve Reliability of Turbomachinery Lubrication and Sealing Systems Improve Reliability of Turbomachinery Lubrication and Sealing Systems Fisher Pressure Control Solutions For Turbomachinery Applications Protect the integrity of your Turbomachinery support system Turbomachinery

More information

RICK FAUSEL, BUSINESS DEVELOPMENT ENGINEER TURBOMACHINERY CONTROL SYSTEM DESIGN OBJECTIVES

RICK FAUSEL, BUSINESS DEVELOPMENT ENGINEER TURBOMACHINERY CONTROL SYSTEM DESIGN OBJECTIVES RICK FAUL, BUSINESS DEVELOPMENT ENGINEER TURBOMACHINERY CONTROL SYSTEM DESIGN OBJECTIVES The primary design objective for any turbomachinery control system should be to maintain or maximize machine and

More information

Valve test benches. Systems overview

Valve test benches. Systems overview Valve test benches Systems overview About us In the past few years WIKA has successfully integrated renowned manufacturers of calibration equipment into the group. With these established brands within

More information

Fuel Gas Pressure Control Solutions for Fired Heaters and Boilers

Fuel Gas Pressure Control Solutions for Fired Heaters and Boilers Fuel Gas Control Solutions for Fired Heaters and Boilers Solutions for safer and more reliable operation of fired heater fuel gas systems. Prevent process downtime by keeping your critical heaters online.

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS MODEL GS2000 / GS2001 OIL-LESS REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 R01099 GS2000.DOC NRP-OM-GS2000

More information

Temperature Controllers

Temperature Controllers IM0004 April 2013 CONTENTS T-12 Thermostat PAGE Introduction 1 Scope 1 Description 1 Specification 1 Temperature Controllers 2 INTRODUCTION CAUTION Prior to installing, the instructions provided herein

More information

RAM 4021 Operation Manual

RAM 4021 Operation Manual RAM 4021 Operation Manual Worldwide Manufacturer of Gas Detection Solutions TABLE OF CONTENTS RAM 4021 For your safety...3 Description...3 Set-up mode...4 Annunciator lights/alarms...4 Operation...5 Calibration...6

More information

The Relationship Between Automation Complexity and Operator Error

The Relationship Between Automation Complexity and Operator Error The Relationship Between Automation Complexity and Operator Error presented by Russell Ogle, Ph.D., P.E., CSP rogle@exponent.com (630) 274-3215 Chemical Plant Control Control physical and chemical processes

More information

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch. Training Title GAS CONDITIONING & PROCESSING Training Duration 5 days Training Venue and Dates Gas Conditioning & Processing 5 07 11 April, 2019 $4,000 Dubai, UAE Trainings will be conducted in any of

More information

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.

Exercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler. Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure

More information

Reverse Osmosis System Installation Guide and Operation Manual.

Reverse Osmosis System Installation Guide and Operation Manual. Reverse Osmosis System Installation Guide and Operation Manual. Table of Contents 1 Introduction...2 2 Installation...3 2.1 Feed water connection...3 2.2 Permeate and concentrate plumbing...3 2.3 Electrical

More information

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N)

Exhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N) 1 APPLICABILITY Exhibit 4 Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N) Definitions common to all certification and test procedures

More information

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW

AC : MEASUREMENT OF HYDROGEN IN HELIUM FLOW AC 2010-2145: MEASUREMENT OF HYDROGEN IN HELIUM FLOW Randy Buchanan, University of Southern Mississippi Christopher Winstead, University of Southern Mississippi Anton Netchaev, University of Southern Mississippi

More information

WIKA INSTRUMENT CORPORATION

WIKA INSTRUMENT CORPORATION WIKA INSTRUMENT CORPORATION Instruction Manual DIFFERENTIAL PRESSURE GAUGE Series 1500 Series 1000 Series 300 WIKA Instrument Corporation 1000 Wiegand Boulevard Lawrenceville, GA 30043 1-888-945-2872 http://www.wika.com

More information

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward

4-7 kw/ hp. Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward GN 4-7 kw/5.5-10 hp Dual Output Compressors (Air/Nitrogen) Driving Nitrogen Forward Total capability, total responsibility Right at the heart of your business, Atlas Copco delivers quality compressed air

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

User Manual 1 P a g e Rev. V1.6-EN 11/08/2014

User Manual 1 P a g e Rev. V1.6-EN 11/08/2014 User Manual 1 P a g e Rev. V1.6-EN 11/08/2014 Copyright Disclaimer Trademarks and patents Intended use Contact info 2011 Inflotrolix, Inc. This document may not be copied in whole or in part or otherwise

More information

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES

ATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES 110 AIR CONDITIONING CHILLED WATER PLANT 1. Ensure power to water chiller controller and all fan coil unit controllers is on 2. Ensure chilled water expansion tank level is at its proper level 3. Ensure

More information

COMPRESSED AIR TEXTILES ENERGY EFFICIENCY

COMPRESSED AIR TEXTILES ENERGY EFFICIENCY TEXTILES ENERGY EFFICIENCY GUIDANCE NOTE 01 COMPRESSED AIR Compressed air often accounts for more than 10% of textile companies annual electricity use. It is referred to as the forgotten utility, as the

More information

SEMEM3-73 Maintaining medical gas pipeline systems and equipment

SEMEM3-73 Maintaining medical gas pipeline systems and equipment Maintaining medical gas pipeline systems and equipment Overview This unit identifies the competences you need to carry out maintenance activities on medical gas pipeline systems and equipment, in accordance

More information

PROVING THAT BLADDER SURGE TANKS CURED EXCESSIVE SURGE CONDITIONS IN A 30 FORCE MAIN

PROVING THAT BLADDER SURGE TANKS CURED EXCESSIVE SURGE CONDITIONS IN A 30 FORCE MAIN Background PROVING THAT BLADDER SURGE TANKS CURED EXCESSIVE SURGE CONDITIONS IN A 30 FORCE MAIN Bo, P.E., Hazen and Sawyer, P.C. Sean FitzGerald, P.E., Hazen and Sawyer, P.C. The Sanitation District No.

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S January 6, 2012 Preaction 348a 1. Description Viking supervised Surefire Preaction Systems utilize the Viking G-6000P Valve. The small profile, lightweight, pilot operated Viking G-6000P Valve comes complete

More information