National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Size: px
Start display at page:

Download "National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:"

Transcription

1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mechanical Systems Jeanne Moreau DATE: November 1, 2010 SUBJECT: NFPA 99 HEA-MEC ROC TC Letter Ballot (A11) The ROC letter ballot for NFPA 99 is attached. The ballot is for formally voting on whether or not you concur with the committee s actions on the comments. Reasons must accompany all negative and abstention ballots. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. Please complete and return your ballot as soon as possible but no later than Monday, November 15, As noted on the ballot form, please return the ballot to Jeanne Moreau either via to jmoreau@nfpa.org or via fax to The return of ballots is required by the Regulations Governing Committee Projects. Attachments: Comments

2 99-5 Log #CC403 HEA-MEC Technical Committee on Mechanical Systems, Revise text to read as follows: Globally change "Heating, cooling, ventilating, humidity control and process systems" to "HVAC systems" throughout the document. Delete sections and it's subsections and Delete the column called "process" from table A.9.2. Delete the column called "process air" from table A.8.2. The term Heating, cooling, ventilating, humidity control and process systems was changed to HVAC and it needs to be changed throughout for correlation purposed. The requirements for "process" was deleted and this was deleted throughout to correlate Log #150 HEA-MEC Delete the reference to humidity, or humidity control in Sections: (4) (4) A.9.2 Delete entire sections and Delete the references to humidity. The only reasons that have been identified for requiring humidity have been clinical. without any risk of injury, fire, or explosion there is no need for humidity requirements in this code except within hyperbaric chambers. We support the TCC s direction to remove the references to humidity which are already covered in other standards such as the FGI Guidelines and ASHRAE 170. Delete as proposed except for Also delete "Humidity Control" from Humidity does not appear in section

3 99-26 Log #7c HEA-MEC Technical Correlating Committee on Health Care Facilities, The scope of NFPA 99 does include all levels of anesthesia, therefore the definition must be all inclusive and the TC should review and change their action at the ROC stage. All the TC's should review their categories of patient care where anesthetics are used. This is a direction from the Technical Correlating Committee on Health Care Facilities in accordance with and of the Regulations Governing Committee Projects. The committee reviewed its chapters and did not find a need to make any modifications based on the new definitions for anesthesia. No action was needed Log #8c HEA-MEC Technical Correlating Committee on Health Care Facilities, The scope of NFPA 99 does include all levels of anesthesia, therefore the definition must be all inclusive and the TC should review and change their action at the ROC stage. All the TC's should review their categories of patient care where anesthetics are used. This is a direction from the Technical Correlating Committee on Health Care Facilities in accordance with and of the Regulations Governing Committee Projects. The committee reviewed its chapters and did not find a need to make any modifications based on the new definitions for anesthesia. No action was needed Log #10c HEA-MEC Technical Correlating Committee on Health Care Facilities, The scope of NFPA 99 does include all levels of anesthesia, therefore the definition must be all inclusive and the TC should review and change their action at the ROC stage. All the TC's should review their categories of patient care where anesthetics are used. This is a direction from the Technical Correlating Committee on Health Care Facilities in accordance with and of the Regulations Governing Committee Projects. The committee reviewed its chapters and did not find a need to make any modifications based on the new definitions for anesthesia. No action was needed. 2

4 Log #312 HEA-MEC Mark Jelinske, Cator, Ruma, and Associates Reject this proposal in it's entirety. This proposal goes way beyond the scope of NFPA 99 The scope of this code is to establish criteria to minimize the hazards of fire, explosion, and electricity in health care facilities providing services to human beings. The regulation of plumbing systems has no business being in NFPA 99. The submitted substantiation for the proposal states These systems are used in health care facilities with very little guidance until now. This is grossly inaccurate. Health Care Facility plumbing systems are subject to multiple prescriptive requirements such as state and local plumbing codes and state and local public health codes. In addition, the FGI/AIA Guidelines for Design and Construction of Health Care Facilities are considered the industry standard, and are adopted as code in many jurisdictions. There are multiple terms in this proposal that are not defined in this Code, such as non-potable water, black/grey/clear waste water, special use water systems. Actually, these terms are defined and regulated quite well in the multiple guidelines and codes that the proposer states are not available. So even if there is no need to define the terms in this Code, there is also no reason to regulate these systems in a Code limited to minimize the hazards of fire, explosion, and electricity in health care facilities, particularly since they are so well defined and regulated elsewhere. At best, this proposal is a waste of ink: Potable water systems shall comply with applicable plumbing codes. (what happened to very little guidance?) Plumbing fixtures shall be suitable for the intended use. At worst, this proposal adds one more level of regulation that has the potential to conflict with and confuse the implementation of model codes and guidelines and developed over decades by plumbing industry experts. The TC was following the direction of the TCC which was to include plumbing in NFPA 99. The TCC wanted to have a first-stop document that addressed many facets of systems and directed the TC to address this subject. Section of the scope addresses plumbing Log #CC400 HEA-MEC Technical Committee on Mechanical Systems, Add new section as follows: The category of risk applied to each plumbing system serving a space shall be independent of the category of risk applied to other systems serving that same space. A There are no interdependencies for each type of system (e.g., medical gas, electrical, potable water, non-potable water, non-medical compressed air, heating). A risk assessment of each system should be conducted to evaluate the risk to the patient, staff and visitors. It is possible when applying this section to identify multiple categories of systems serving a single patient. For example see table A.8.2 and A.4.1. This clarifies that a risk assessment of each building system should be conducted. The results of each risk assessment are independent for each system. There are no interdependencies for each type of system (e.g., medical gas, electrical, potable water, non-potable water, non-medical compressed air, heating). A risk assessment of each system should be conducted to evaluate the risk to the patient, staff and visitors. 3

5 Log #207 HEA-MEC James R. (Skip) Gregory, Health Facility Consulting Category Potable Water. Redundant or standby potable water sources shall be provided for Category 1 uses such that if the primary source of potable water fails, then the Category 1 uses of nonpotable water shall be capable of operating Nonpotable Water. Redundant or standby nonpotable water sources shall be provided for Category 1 uses such that if the primary source of nonpotable water fails, then the Category 1 uses of nonpotable water shall be capable of operating Water Heating. Redundant or standby water heating sources shall be provided for Category 1 uses such that if the largest piece of potable water heating equipment fails, the remaining potable water heating equipment shall be capable of maintaining the minimum temperature at all times Water Conditioning. Redundant or standby water conditioning systems shall be provided for Category 1 spaces such that if the largest piece of water conditioning equipment fails, the remaining water conditioning equipment shall be capable of maintaining the load Nonmedical Compressed Air. Redundant or standby nonmedical compressed air sources shall be provided for Category 1 spaces such that if the largest piece of nonmedical compressed air source equipment fails, the remaining non-medical compressed air source equipment shall be capable of maintaining the required flow and pressure to serve all Category 1 uses Special Use Water Systems. Redundant or standby special use water sources shall be provided for Category 1 spaces such that if the largest piece of special use water equipment fails, the remaining special use water equipment shall be capable of maintaining the flow and pressure to serve all Category 1 uses. Delete Entire Section. There has been no data or substantiation of adverse patient outcomes submitted to support this new section to the code, requiring redundant potable water, nonpotable water, water heating, water conditioning, nonmedical gas, and special use water systems. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers". The potential for the failure of this system to cause death or major injury is very unlikely. At the most a failure of these systems could cause discomfort, but not death or major injury. There is no justification to require redundant systems to this extent. A failure to these systems does not constitute an immediate danger to the health and safety of the patient and when these systems are renovated, patients are removed from the areas affected by the renovation. To require this type of redundancy for these systems will increase the cost of health care construction with no appreciable improved patient outcomes. Before this requirement is added, there should be data collected from hospitals that will provide the necessary justification for this added cost. This comment is supported by the Codes and Standards Review Committee of the Health Care Section of NFPA. 4

6 Log #131 HEA-MEC Redundant or standby potable water sources shall be provided for Category 1 uses such that if the primary source of potable water fails, then the Category 1 uses of nonpotable water shall be capable of operating. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically Log #230 HEA-MEC Sharon S. Gilyeat, Koffel Associates, Inc. N/A Revise text to read as follows: Redundant or standby potable water sources shall be provided for Category 1 uses such that if the primary source of potable water fails, then the Category 1 uses of secondary nonpotable water shall be capable of operating. Editorial, secondary source refers to nonpotable but should refer to potable. Also wording previously not clear. 5

7 Log #132 HEA-MEC Revise text to read as follows: Redundant or standby nonpotable water sources shall be provided for Category 1 uses such that if the primary source of nonpotable water fails, then the Category 1 uses of nonpotable water shall be capable of operating. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically Log #231 HEA-MEC Sharon S. Gilyeat, Koffel Associates, Inc. N/A Revise text to read as follows: Redundant or standby nonpotable water sources shall be provided for Category 1 uses such that if the primary source of nonpotable water fails, then the Category 1 uses secondary nonpotable water shall be capable of operating. Editorial, previous wording unclear. 6

8 Log #133 HEA-MEC Redundant or standby water heating sources shall be provided for Category 1 uses such that if the largest piece of potable water heating equipment fails, the remaining potable water heating equipment shall be capable of maintaining the minimum temperature at all times. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically Log #128 HEA-MEC Redundant or standby water conditioning systems shall be provided for Category 1 spaces such that if the largest piece of water conditioning equipment fails, the remaining water conditioning equipment shall be capable of maintaining the load. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically. 7

9 Log #129 HEA-MEC Redundant or standby nonmedical compressed air sources shall be provided for Category 1 spaces such that if the largest piece of nonmedical compressed air source equipment fails, the remaining non-medical compressed air source equipment shall be capable of maintaining the required flow and pressure to serve all Category 1 uses. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically Log #130 HEA-MEC Redundant or standby special use water sources shall be provided for Category 1 spaces such that if the largest piece of special use water equipment fails, the remaining special use water equipment shall be capable of maintaining the flow and pressure to serve all Category 1 uses. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically. 8

10 Log #208 HEA-MEC James R. (Skip) Gregory, Health Facility Consulting Category Potable Water. Provisions to allow the potable water system to continue to operate shall be provided On-site redundant or standby potable water sources shall not be required Mobile or temporary systems shall be acceptable Nonpotable Water. Provisions to allow the nonpotable water system to continue to operate shall be provided On-site redundant or standby nonpotable water sources shall not be required Mobile or temporary systems shall be acceptable Water Heating. Provisions to allow the water heating system to continue to operate shall be provided On-site redundant or standby water heating sources shall not be required Mobile or temporary systems shall be acceptable Water Conditioning. Provisions to allow the water conditioning system to continue to operate shall be provided On-site redundant or standby water conditioning sources shall not be required Mobile or temporary systems shall be acceptable Nonmedical Compressed Air. Provisions to allow the nonmedical compressed air system to continue to operate shall be provided On-site redundant or standby nonmedical compressed air sources shall not be required Mobile or temporary systems shall be acceptable. Delete Entire Section. This section is unclear and vague as to what is being required. For Category 2, redundant systems are not required, however mobile or temporary systems are required to supply these utilities but there is no definition or description of what a mobile or temporary system might be and there is no specified length of time these systems must operate. It is hard to imagine how a mobile or temporary system of potable or nonpotable water, for instance, could be provided that would take the place of the permanently installed utility system, for an unspecified length of time that could be construed as forever. How much water must be temporarily provided to satisfy this requirement is not clearly stated and therefore cannot be enforced. In addition, there is no data regarding adverse patient outcomes to substantiate this section that will add substantial cost to the design of health care facilities. This comment is supported by the Codes and Standards Review Committee of the Health Care Section of NFPA. Category 2 systems needs to be defined and specified within section 8.5. This is the direction of the TCC and needs to be there for consistency. The submitter has raised issues that will be addressed in a committee comment. See action on (Log #CC402). 9

11 Log #CC402 HEA-MEC Technical Committee on Mechanical Systems, Revise text to read as follows: 8.5 Category Potable Water. Provisions to allow the potable water system to continue to operate shall be provided On-site redundant or standby potable water sources shall not be required Mobile or temporary systems shall be acceptable. An emergency physical connection shall be provided to permit connection of temporary or mobile systems to the potable water system in the event of failure. A A temporary mobile system could be a tanker truck, tank, well, a bladder, etc as determined by the facility Nonpotable Water. Provisions to allow the nonpotable water system to continue to operate shall be provided On-site redundant or standby nonpotable water sources shall not be required Mobile or temporary systems shall be acceptable. An emergency physical connection shall be provided to permit connection of temporary or mobile systems to the non-potable water system in the event of failure. A A temporary mobile system could be a tanker truck, tank, well, a bladder, etc as determined by the facility Water Heating. Provisions to allow the water heating system to continue to operate shall be provided On-site redundant or standby water heating sources shall not be required Mobile or temporary systems shall be acceptable. An emergency physical connection shall be provided to permit connection of temporary or mobile systems for the purpose of restoring the water heating system in the event of failure. A A temporary mobile system could be a heat exchanger, a heating element, a burner, complete water heater or a mobile system as determined by the facility Water Conditioning. Provisions to allow the water conditioning system to continue to operate shall be provided On-site redundant or standby water conditioning sources shall not be required Mobile or temporary systems shall be acceptable. An emergency physical connection shall be provided to permit connection of temporary or mobile systems to the water condtioning system in the event of failure. A A temporary mobile system could be a water softener, filter or other temporary water conditioning or treatment system as determined by the facility Nonmedical Compressed Air. Provisions to allow the nonmedical compressed air system to continue to operate shall be provided On-site redundant or standby nonmedical compressed air sources shall not be required Mobile or temporary systems shall be acceptable. An emergency physical connection shall be provided to permit connection of temporary or mobile systems to the nonmedical compressed air system in the event of failure. A A temporary mobile system could be air compressors connected to the manifold Special Use Water Systems. Provisions to allow the special use water system to continue to operate shall be provided On-site redundant or standby special use water sources shall not be required Mobile or temporary systems shall be acceptable. An emergency physical connection shall be provided to permit connection of temporary or mobile systems to the special use water system in the event of failure. A A temporary mobile system could be a tanker truck, tank, well, a bladder, etc as determined by the facility. The new wording provides more guidance on what is required for mobile or temporary water and nonmedical compressed air systems. Examples are given for each. The intent was the provisions for the connection to the system be provided and not to describe the specific mobile or temporary device. 10

12 Log #134 HEA-MEC Provisions to allow the potable water system to continue to operate shall be provided. Delete Entire Section. There are no bookends for this section it is very difficult if not impossible to determine what provisions should be designed into a system to ensure that it continues to operate. This should at least be moved to the appendix. Category 2 systems needs to be defined and specified within section 8.5. This is the direction of the TCC and needs to be there for consistency. The submitter has raised issues that will be addressed in a committee comment. See action on (Log #CC402) Log #209 HEA-MEC James R. (Skip) Gregory, Health Facility Consulting Category Potable Water. Redundant or standby potable water systems shall not be required Nonpotable Water. Redundant or standby nonpotable systems shall not be required Water Heating. Redundant or standby water heating systems shall not be required Water Conditioning. Redundant or standby water conditioning systems shall not be required Nonmedical Compressed Air. Redundant or standby nonmedical compressed air systems shall not be required Special Use Water Systems. Redundant or standby special use water systems shall not be required. Delete Entire Section. The NFPA codes and standards contain minimum requirements that must be met. This section contains no such requirements. It should either be deleted or moved to the annex as advisory material. This material is needed as it is consistent with the other categories in this chapter which identifies what is required and what is not required. The lack of any requirements in Category 3 is specifically stated to avoid potential misinterpretation that plumbing systems should only be Category 1 and Log #17 HEA-MEC Technical Correlating Committee on Health Care Facilities, The TCC directs the TC on MEC to eliminate all references to humidity and humidity control systems as this document does not address clinical practices. This is a direction from the Technical Correlating Committee on Health Care Facilities in accordance with and of the Regulations Governing Committee Projects. See action on comment 99-9 (Log #150). 11

13 Log #61 HEA-MEC Bill Payne, Alamance Regional Medical Center N/A Revise text to read as follows: Chapter 9 Heating Heating, Ventilation and Air Conditioning (HVAC). Chapter 9 addresses issues such as cooling, humidity control, ventilation and Airborne Contaminants. Titling this chapter "Heating" is too limiting and misleading. The fuel requirements in this chapter are not just for the boilers that produce the heat, it includes the fuel for the generator that keep the rest of HVAC system running. With a chapter heading of "Heating", the immediate assumption is that this only pertains to boilers. 12

14 Log #162 HEA-MEC John Williams, Washington State Dept. of Health Redundant or standby heat generating sources shall be provided for Category 1 spaces such that if the largest piece of heat generating equipment fails, the remaining heat generating equipment shall be capable of maintaining the minimum temperature at all times Redundant or standby humidity control sources shall be provided for Category 1 spaces such that if the largest piece of humidity control source equipment fails, the remaining humidity control source equipment shall be capable of maintaining the maximum temperature at all times Redundant or standby supply air sources shall be provided such that if the largest piece of supply air source equipment fails, the remaining supply air source equipment shall be capable of maintaining the supply air flow Redundant or standby return air sources shall be provided such that if the largest piece of return air source equipment fails, the remaining return air source equipment shall be capable of maintaining the return air flow Redundant or standby exhaust air sources shall be provided such that if the largest piece of exhaust air source equipment fails, the remaining exhaust air source equipment shall be capable of maintaining the exhaust air flow Process Systems. Process heating, cooling, and ventilating systems necessary to support equipment essential to the function of Category 1 areas shall be provided with standby or redundant generation sources such that if the largest piece of source equipment serving the processes fails, the remaining source equipment serving the processes shall be capable of serving the load. The addition of redundant air tempering and exhaust systems is a significant scope change that is unwarranted. At no point in recent history has this code required redundant equipment for these systems. No substantiation has been provided during this process to identify what risks are being mitigated by this addition. What risks are these minimum criteria specifically designed to address: hazards due to downtime for maintenance or hazards related to disasters? The failure of an exhaust system may pose an immediate hazard to the occupants of a healthcare facility if those systems serve highly sensitive areas. However, the failure of sources of heat generation, humidity control, return air, etc do not create an immediate hazard. The building will remain tenable for a period of time which will allow for repair of a failed system. There are many viable temporary HVAC solutions that have successfully been employed prior to this code change. It is unlikely that a wide-scale disaster would affect something so specific as an individual piece of equipment. If it did, the redundant equipment would be subject to the same conditions and might also fail. Regardless, chapter 12 requires an approach to management of essential utilities during disasters that can be appropriately tailored to the climate, location, size of facility, etc. Without an understanding of the risk that this code tries to mitigate, it is incredibly difficult to assess alternate means and methods. Until the committee clearly articulates why this should be a minimum standard and identifies the risks that are being mitigated, redundant equipment should not be required. 13

15 Log #246 HEA-MEC Sharon S. Gilyeat, Koffel Associates, Inc. N/A Revise text to read as follows: The chapter deals with all HVAC issues. Recommend change to clarify actual scope of chapter and provide consistency with terminology used in NFPA 90A. "Heating" was missing. The proper designation is to refer to the term as Heating Ventilation and Air Conditioning Log #247 HEA-MEC Sharon S. Gilyeat, Koffel Associates, Inc. Revise text to read as follows:...category X spaces systems Throughout the chapter the committee has mixed up the reference of category to systems vs. spaces. This needs to be consistent. appear in the chapter. The committee has specifically used the terms "spaces" and "systems" appropriately as they 14

16 Log #313 HEA-MEC Mark Jelinske, Cator, Ruma, and Associates Reject the Proposal in it's entirety. This proposal goes way beyond the scope of NFPA 99 The regulation of comfort and clinical performance of HVAC systems has no business being in NFPA 99. In addition, the proposed chapter goes beyond the title Heating into other systems such as cooling, ventilation, smoke removal, room pressurization, etc. Health Care Facility HVAC systems are currently subject to multiple prescriptive requirements such as state and local Mechanical, Building, and Fire codes and state and local public health codes. Multiple NFPA documents already address the Life Safety aspects of HVAC systems in Healthcare Occupancies. In addition, and of specific healthcare interest, the FGI/AIA Guidelines for Design and Construction of Health Care Facilities, and ASHRAE Standard 170 are considered industry standard of care, and are adopted as code in many jurisdictions. ASHRAE Standard 170 has recently been consolidated with the FGI/AIA Guidelines to provide the healthcare facility/design/construction industry a strong coordinated voice. It would be a step backwards to promulgate additional regulations. There are numerous technical changes embedded within this document that have not been substantiated by the submitter. The above reasoning was given to reject proposal 99-76, and that was presented as a re-write of an existing topic. The same logic should be applied to an entirely new topic. If it is felt that NFPA must address HVAC systems to this level of detail, this proposal should be extracted to a separate document as a guideline, rather than as a Code directly referenced by NFPA 101. The TC was following the direction of the TCC which was to include HVAC in NFPA 99. The TCC wanted to have a first-stop document that addressed many facets of systems and directed the TC to address this subject. Section of the scope addresses HVAC Log #144 HEA-MEC Delete entire chapter and replace with: Ventilation systems shall be installed per ASHRAE 170. The requirements of this chapter are too stringent and duplicate the requirements that are found in other resources. The entire chapter should be replaced with a reference to ASHRAE 170. This chapter could be used in the future to cover issues not addressed in ASHRAE 170, or to further enhance the requirements. The TC was following the direction of the TCC which was to include HVAC in NFPA 99. The TCC wanted to have a first-stop document that addressed many facets of systems and directed the TC to address this subject. Section of the scope addresses HVAC. 15

17 Log #CC401 HEA-MEC Technical Committee on Mechanical Systems, Add new section as follows: The category of risk applied to each HVAC system serving a space shall be independent of the category of risk applied to other systems serving that same space. A There are no interdependencies for each type of system (e.g. medical gas, electrical, potable water, non-potable water, non-medical compressed air, plumbing). A risk assessment of each system should be conducted to evaluate the risk to the patient, staff and visitors. It is possible when applying this section to identify multiple categories of systems serving a single patient. For example see table A.9.2 and A.4.1. This clarifies that a risk assessment of each building system should be conducted. The results of each risk assessment are independent for each system. There are no interdependencies for each type of system (e.g., medical gas, electrical, potable water, non-potable water, non-medical compressed air, heating). A risk assessment of each system should be conducted to evaluate the risk to the patient, staff and visitors Log #62 HEA-MEC Bill Payne, Alamance Regional Medical Center N/A Revise text to read as follows: Energy Conservation. Heating, cooling, ventilating, humidity control, and process systems serving spaces or providing health care functions covered by this code shall comply with ASHRAE 90.1 or their local Energy Code. The NC Energy Code allows the user to follow either the NC Energy Conservation Code or ASHRAE If NFPA 99 requires us to follow 90.1, then we will not have the option to follow the State Code. See action on comment (Log #149) Log #149 HEA-MEC Revise text to read as follows: Heating, cooling, ventilating, humidity control, and process systems serving spaces or providing health care functions covered by this code shall comply with ASHRAE 90.1 or other locally adopted energy code. Many jurisdictions already have an energy code adopted, either ASHRAE 90.1 with amendments or other versions of the energy codes. The facilities should be required to meet one of the codes, but not multiple codes. Additionally, it seems that energy conservation is outside the scope of NFPA 99 and is better left to performance codes such as the FGI Guidelines. Revise text to read as follows: Heating, cooling and ventilating, humidity control, and process systems serving spaces or providing health care functions covered by this code shall comply with ASHRAE 90.1 or other locally adopted energy code. The action on comments (Log #141) and (Log #215) deleted processes. This is done for consistency. 16

18 Log #301 HEA-MEC Kirk Bantz, Saint Alphonsus Regional Medical Center Cooling Category 1 cooling systems shall be provided to maintain the space at maximum temperatures listed in ASHRAE/ANSI Redundant or standby cooling sources shall be provided for Category 1 spaces such that if the largest piece of cooling source equipment fails, the remaining cooling source equipment shall be capable of maintaining the maximum temperature at all times Self-contained cooling units that connect directly with outdoors through the building envelope shall not be permitted Humidity Control Category 1 humidity control shall be provided to maintain the space humidity consistent with ASHRAE/ANSI 170 or as required for the proper operation of life support equipment within the space, whichever is more strict Redundant or standby humidity control sources shall be provided for Category 1 spaces such that if the largest piece of humidity control source equipment fails, the remaining humidity control source equipment shall be capable of maintaining the maximum temperature at all times Ventilation, Outdoor Air Ventilation systems for Category 1 spaces shall be provided to introduce outdoor air into a building as required by the applicable building code and ASHRAE/ANSI 170 to achieve acceptable indoor air quality through the dilution of indoor air contaminants The location of the source of outdoor air shall comply with ASHRAE/ANSI Supply Air Ventilation systems for Category 1 spaces shall be provided to supply air into Category 1 spaces in accordance with ASHRAE/ANSI Redundant or standby supply air sources shall be provided such that if the largest piece of supply air source equipment fails, the remaining supply air source equipment shall be capable of maintaining the supply air flow Supply air systems for Category 1 spaces shall be provided with a smoke control system per NFPA 92A Return Air Ventilation systems for Category 1 spaces shall be provided to remove air not required to be exhausted from Category 1 spaces by ASHRAE 170 in accordance with ASHRAE Redundant or standby return air sources shall be provided such that if the largest piece of return air source equipment fails, the remaining return air source equipment shall be capable of maintaining the return air flow Return air systems for Category 1 spaces shall be provided with a smoke control system per NFPA 92A Exhaust Air Ventilation systems for Category 1 spaces shall be provided to remove air that is required to be exhausted from Category 1 spaces by ASHRAE 170 in accordance with ASHRAE Redundant or standby exhaust air sources shall be provided such that if the largest piece of exhaust air source equipment fails, the remaining exhaust air source equipment shall be capable of maintaining the exhaust air flow Exhaust air systems for Category 1 spaces shall be provided with a smoke control system in accordance with NFPA 92A Airborne Contaminant Control Ventilation systems for Category 1 spaces shall be provided to control contaminants in the air using air flow, dilution, and filtration in accordance with ASHRAE Pressurization for Category 1 airborne contaminant control systems shall be a minimum of 0.01 wc (2.5 Pa) across each barrier used as an control mechanism required by ASHRAE Air movement relationships to adjacent areas (positive/negative/neutral) shall be in conformance with ASHRAE/ANSI Filtration shall be in conformance with ASHRAE/ANSI Wet coils or drain pans shall not be permitted in these spaces Process Systems. Process heating, cooling, and ventilating systems necessary to support equipment essential to the function of Category 1 areas shall be provided with standby or redundant generation sources such that if the largest piece of source equipment serving the processes fails, the remaining source equipment serving the processes shall be 17

19 capable of serving the load On-Site Fuel Storage On-site fuel or the essential electrical system or both as required for proper operation of the system including controls shall be provided to serve heating, cooling, ventilating, humidity control, and process systems for Category 1 spaces * On-site storage shall be provided for enough fuel to continue operations of Category 1 spaces for a minimum of 96 hours of normal operation On-Site Fuel Storage On-site fuel or the essential electrical system or both as required for proper operation of the system including controls shall be provided to serve heating, cooling, ventilating, humidity control, and process systems for Category 1 spaces On-site storage shall be provided for enough fuel to continue operations of Category 1 spaces for a minimum of 24 hours of normal operation. The new redundant or standby climate controls simply increase the cost of healthcare operations while adding no degree of safety. I can find no evidence of instances where mortality was directly associated with the conditions this standard would eliminate. Presumptively these proposals will only be fully met by not only doubling the cost of mechanical equipment but also by increasing the load capacity of emergency power generation to run those systems currently not supported while providing no added margin of safety. On-site storage requirements for fuel are location specific. Global minimums may not provide enough fuel or may create unneeded hazardous material storage that increases potential for both fire and environmental damage. Additionally, the requirements in and to maintain "normal operation" in Category 1 spaces creates the requirement for a non-emergency branch of emergency power along with the potential need for a secondary generation system for emergency power Log #303 HEA-MEC Darrell Fugate, Saint Alphonsus Regional Medical Center Delete all reference to redundant mechanical equipment for systems in category 1 areas. Is there data to support the added costs associated with redundant equipment? Health care dollars should be reserved for higher priority initiatives to improve care to patients and we should not spend our limited resources on additional HVAC equipment that is not necessary. 18

20 Log #308 HEA-MEC William Morgan, St. Alphonsus R.M.C. I would like to delete this proposal. Hospital areas identified needing a redundant mechanical system are not separate from the system used to maintain other areas of a facility. To add the required equipment and controls to manage this would add an additional burden to the cost of new construction that added minimal value to our patients. Other than an airborne isolation infection environment there is no need. Where would it start and stop? Twice the compressors, pumps, chillers, generators, ductwork, plumbing, electrical... Unrealistic. The TC was following the direction of the TCC which was to include HVAC in NFPA 99. The TCC wanted to have a first-stop document that addressed many facets of systems and directed the TC to address this subject. Section of the scope addresses HVAC. document must perform a risk assessment and based on the outcome of the risk assessment, they would choose the appropriate Category for the system Log #311 HEA-MEC Charles Block, Spectrum Health Eliminate redundant mechanical systems. To retroactively add the number of air handling units that a larger hospital would be required to add is extremely unreasonable and unnecessary with an implemented and monitored preventive maintenance program. It also is a matter of space Log #325 HEA-MEC John Hohman, Michigan Society for Healthcare Engineering Drop the requirement of redundant mechanical equipment. Redundancy doesn t seem necessary and we don t see support for this change. 19

21 Log #136 HEA-MEC Redundant or standby heat generating sources shall be provided for Category 1 spaces such that if the largest piece of heat generating equipment fails, the remaining heat generating equipment shall be capable of maintaining the minimum temperature at all times. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically Log #169 HEA-MEC Diane Hughes, UAMS N/A Revise text to read as follows: Shall be provided considered. Based on cost factors providing the redundancy. 20

22 Log #210 HEA-MEC James R. (Skip) Gregory, Health Facility Consulting Redundant or standby heat generating sources shall be provided for Category 1 spaces such that if the largest piece of heat generating equipment fails, the remaining heat generating equipment shall be capable of maintaining the minimum temperature at all times. Delete Entire Section. There has been no data or substantiation of adverse patient outcomes submitted to support this new section to the code, requiring redundant heating sources for Category 1 areas. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers". The potential for the failure of this system to cause death or major injury to a patient or caregiver is very unlikely. At the most a failure of these systems could cause discomfort, but not death or major injury. There is no justification to require redundant systems to this extent. A failure to these systems does not constitute an immediate danger to the health and safety of the patient and when these systems are renovated, patients are removed from the areas affected by the renovation. To require this type of redundancy for these systems will increase the cost of health care construction with no appreciable improved patient outcomes. Before this requirement is added, there should be data collected from hospitals that will provide the necessary justification for this added cost. This comment is supported by the Codes and Standards Review Committee of the Health Care Section of NFPA Log #137 HEA-MEC Redundant or standby cooling sources shall be provided for Category 1 spaces such that if the largest piece of cooling source equipment fails, the remaining cooling source equipment shall be capable of maintaining the maximum temperature at all times. Delete Entire Section. There is no technical justification or data to support redundancy of this system. The definition of Category 1 is "Facility systems in which failure of such equipment or system is likely to cause major injury or death of patients or caregivers" the potential for the failure of this system to cause Death or major injury is very unlikely. at most a failure of this system could cause discomfort. It would take prolonged exposure without caregiver intervention before death or major injury would be potential concern. There are many options available to facilities to mitigate the potential problems of this system failure - such as patient relocation, temporary units, and limited exposure. The inclusion of this requirements doubles the amount of equipment that is required in the current standard. A cost benefits analysis needs to be done before the requirements in this code are increased this drastically. 21

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Heat Recovery Steam Generators Jeanne Moreau DATE: April 23, 2010 SUBJECT: NFPA 85 F10 ROC Letter Ballot The ROC letter ballot

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Electrical Equipment

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Piping Systems

More information

MANAGEMENT PROCEDURE FOR LABORATORY VENTILATION

MANAGEMENT PROCEDURE FOR LABORATORY VENTILATION UNIVERSITY OF ALASKA FAIRBANKS SAFETY SYSTEM POLICY AND PROCEDURE DOCUMENT NUMBER: 508 ISSUE DATE: SEPTEMBER 1996 SUBJECT: Management Procedure for Laboratory Ventilation MANAGEMENT PROCEDURE FOR LABORATORY

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Pulverized Fuel Systems Jeanne Moreau-Correia DATE: August 5, 2009 SUBJECT: NFPA 85 ROP Letter Ballot The ROP letter ballot

More information

Technical Committee on Fire Department Apparatus

Technical Committee on Fire Department Apparatus Technical Committee on Fire Department Apparatus M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Department Apparatus Elena Carroll DATE: September 14, 2009 SUBJECT: NFPA 1912 ROP Letter

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Appendix C - Guidance for Integrating EFH Consultations with Endangered Species Act Section 7 Consultations

Appendix C - Guidance for Integrating EFH Consultations with Endangered Species Act Section 7 Consultations Appendix C - Guidance for Integrating EFH Consultations with Endangered Species Act Section 7 Consultations C.1 Guidance for Integrating Magnuson-Stevens Fishery Conservation and Management Act EFH Consultations

More information

Policy for Evaluation of Certification Maintenance Requirements

Policy for Evaluation of Certification Maintenance Requirements Circular No. 1-319 Policy for Evaluation of Certification Maintenance Requirements April 11, 2013 First Issue Airworthiness Division, Aviation Safety and Security Department Japan Civil Aviation Bureau

More information

Safety Assessments Revised Toy Safety Directive 2009/48/EC

Safety Assessments Revised Toy Safety Directive 2009/48/EC Toy Safety Update Safety Assessments Revised Toy Safety Directive 2009/48/EC Contents 1. Obligations of Economic Operators 2. Introduction 3. Overview 4. How to use this guide 5. Approach to Safety Assessment

More information

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY

TEMPLE UNIVERSITY ENVIRONMENTAL HEALTH AND RADIATION SAFETY Page 1 of 9 ISSUED: 5/00 REVISED: 08/06 Introduction Purpose: In accordance with applicable regulations and Temple University, this policy was developed to minimize exposure to Ethylene Oxide. Applicability

More information

NBIC Committee Action Block

NBIC Committee Action Block NBIC Committee Action Block Subject File Number Change of Service NB 08 0321 (Inspec) NB 08 0320 (Install) NB 08 0322 (R & A) Prop. on Pg. Proposal Explanation Part 2: Add a new Supplement 9, Requirements

More information

Building Code Guidelines for Residential Pools

Building Code Guidelines for Residential Pools Building Code Guidelines for Residential Pools KEEP YOUR POOL SAFE Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor Chesapeake, VA 23322 Phone: (757) 382-6018 E-mail: develop-permits@cityofchesapeake.net

More information

IGO GROUP SAFETY STANDARD 30 - WORKPLACE VENTILATION INDEPENDENCE GROUP NL

IGO GROUP SAFETY STANDARD 30 - WORKPLACE VENTILATION INDEPENDENCE GROUP NL IGO GROUP SAFETY STANDARD 30 - WORKPLACE VENTILATION INDEPENDENCE GROUP NL CONTENTS 1. INTENT... 3 2. APPLICATION... 3 3. UNDERGROUND VENTILATION... 3 3.2 Underground Ventilation Officer... 3 3.3 Risk

More information

IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring

IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring IC Sentinel Applications Guide for Healthcare Environmental Air Quality Monitoring IC Sentinel is a real-time environmental quality monitoring solution, comprised of facilitywide, low-cost, compact, multi-sensor

More information

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES NOTE: Each proposed Denver amendment to the International Codes must be justified. In order to be considered, the amendment proposal must address climate,

More information

ORDINANCE NO AN ORDINANCE OF THE CITY OF FOLSOM AMENDING CHAPTER OF THE FOLSOM MUNICIPAL CODE CONCERNING SWIMMING POOLS, SPAS AND HOT TUBS

ORDINANCE NO AN ORDINANCE OF THE CITY OF FOLSOM AMENDING CHAPTER OF THE FOLSOM MUNICIPAL CODE CONCERNING SWIMMING POOLS, SPAS AND HOT TUBS ORDINANCE NO. 1267 AN ORDINANCE OF THE CITY OF FOLSOM AMENDING CHAPTER 14.28 OF THE FOLSOM MUNICIPAL CODE CONCERNING SWIMMING POOLS, SPAS AND HOT TUBS THE CITY COUNCIL OF THE CITY OF FOLSOM HEREBY DOES

More information

Major Changes. Standard. TECH TOPIC standards and. By Peter Walsh, PE

Major Changes. Standard. TECH TOPIC standards and. By Peter Walsh, PE Major Changes to NFPA 70E Standard 2015 Edition TECH TOPIC standards and codes note 5 By Peter Walsh, PE Industrial Solutions Engineer Introduction NFPA 70E, Standard for Electrical Safety in the Workplace,

More information

J. DOUG PRUITT, Vice President ZACK BURKETT, III, Treasurer. Re: 29 CFR 1926 subpart AA - Confined Space in Construction Proposed Rule

J. DOUG PRUITT, Vice President ZACK BURKETT, III, Treasurer. Re: 29 CFR 1926 subpart AA - Confined Space in Construction Proposed Rule THE ASSOCIATED GENERAL CONTRACTORS OF AMERICA 2300 Wilson Boulevard, Suite 400 Arlington, VA 22201 Phone: (703) 548-3118 FAX: (703) 548-3119 www.agc.org STEVE L. MASSIE, President DOUGLAS E. BARNHART,

More information

FAQs: Confined Spaces in Residential Construction

FAQs: Confined Spaces in Residential Construction Provided by Marshall & Sterling, Inc. FAQs: Confined Spaces in Residential Construction A new standard for construction work in confined spaces became effective Aug. 3, 3015. The new standard (Subpart

More information

COUNTY OF SANTA CRUZ

COUNTY OF SANTA CRUZ COUNTY OF SANTA CRUZ December 5,2006 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR AGENDA DATE:

More information

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY INTERPRETATION IC 62-2001-06 OF ANSI/ASHRAE STANDARD 62-2001 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY REVISION APPROVED: 1/12/2002 Originally issued as interpretation of Standard 62-1989 (IC 62-1989-23)

More information

Significant Change to Dairy Heat Treatment Equipment and Systems

Significant Change to Dairy Heat Treatment Equipment and Systems Significant to Dairy Heat Treatment September 2008 Page 1 Significant to Dairy Heat Treatment Equipment and Systems September 2008 1 Background Requirements for the assessment of dairy heat treatment equipment

More information

Employ The Risk Management Process During Mission Planning

Employ The Risk Management Process During Mission Planning Employ The Risk Management Process During Mission Planning TSG 154-6465 Task(s) TASK NUMBER TASK TITLE Taught or 154-385-6465 Employ The Risk Management Process During Mission Planning Supported Task(s)

More information

Policy Number: 42 Title: Investigational Devices Date of Last Revision: 06/12/2008; 07/22/2010; 05/29/2013; 05/01/2016; 10/16/2018

Policy Number: 42 Title: Investigational Devices Date of Last Revision: 06/12/2008; 07/22/2010; 05/29/2013; 05/01/2016; 10/16/2018 University of California, Irvine Human Research Protections Standard Operating Policies and Procedures Policy Number: 42 Title: Investigational Devices Date of Last Revision: 06/12/2008; 07/22/2010; 05/29/2013;

More information

Every things under control High-Integrity Pressure Protection System (HIPPS)

Every things under control High-Integrity Pressure Protection System (HIPPS) Every things under control www.adico.co info@adico.co Table Of Contents 1. Introduction... 2 2. Standards... 3 3. HIPPS vs Emergency Shut Down... 4 4. Safety Requirement Specification... 4 5. Device Integrity

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Respiratory

More information

ANSI / ASSE Z88.2 American National Standard Practices for Respiratory Protection (1992 rev. versus 2015 rev.)

ANSI / ASSE Z88.2 American National Standard Practices for Respiratory Protection (1992 rev. versus 2015 rev.) ANSI / ASSE Z88.2 BACKGROUND: A substantial body of research has been published since the 1992 revision of Z88.2. This information related to the proper use and performance of respiratory protection in

More information

Amendment: To Return a portion of a Report in the form of an Identifiable Part of Proposal and related Comment 130-1

Amendment: To Return a portion of a Report in the form of an Identifiable Part of Proposal and related Comment 130-1 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M (AMENDMENT 130-1) TO: FROM: Technical Committee on

More information

(2) but does not include a shaft, trench or tunnel that is a mine or is part of the workings of a mine.

(2) but does not include a shaft, trench or tunnel that is a mine or is part of the workings of a mine. Health and Safety Procedure - Confined Spaces Section 1 - Background and Purpose (1) Confined spaces are, for the purposes of this procedure, defined as the following which is the definition under the

More information

UTAS EH&S INSTRUCTION No. 036 June 2012 Revision No. 3. Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard)

UTAS EH&S INSTRUCTION No. 036 June 2012 Revision No. 3. Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard) Purging of Flammable Gas Equipment and/or Piping (Explosion Hazard) APPLICABILITY: This EH&S Instruction applies to UTAS sites worldwide, including contractors working at UTAS facilities. The document

More information

Transport of gas tanks for motor vehicles

Transport of gas tanks for motor vehicles United Nations Secretariat ST/SG/AC.10/C.3/2016/51 Distr.: General 30 August 2016 Original: English Committee of Experts on the Transport of Dangerous Goods and on the Globally Harmonized System of Classification

More information

Confined Space in Construction

Confined Space in Construction Confined Space in Construction History OSHA has been working on a confined space rule for construction since 1994. In 1993 OSHA passed a Permit Required Confined Space Rule however the provisions applied

More information

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service

GUIDELINES. Systems. Pressure. Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service GUIDELINES Pressure Systems Guidelines Acceptance of equipment, establishment of safe operating limits and fitness for service Document Reference: PSG 16 Issue 04 Dated 13/09/16 The Safety Assessment Federation

More information

Mecklenburg County Health Ordinance Rules Governing Residential Swimming Pools

Mecklenburg County Health Ordinance Rules Governing Residential Swimming Pools Mecklenburg County Health Ordinance Rules Governing Residential Swimming Pools Mecklenburg County Health Department 700 N. Tryon Street, Suite 211 Charlotte, North Carolina 28202-2236 Phone (704) 336-5103

More information

Guidance on Enclosed Space Entry and Rescue

Guidance on Enclosed Space Entry and Rescue Guidance on Enclosed Space Entry and Rescue Preparation for the 2015 Concentrated Inspection Campaign (CIC) by the Paris MoU and Tokyo MoU Crew Familiarization for Enclosed Space Entry The Paris MoU and

More information

HS329 Risk Management Procedure

HS329 Risk Management Procedure HS329 Risk Management Procedure Work Health and Safety Act 2011 Policy hierarchy link Work Health and Safety Regulation 2011 Work Health and Safety Policy Code of Practice How to Manage Work Health and

More information

RESOLUTION MEPC.86(44) adopted on 13 March 2000 AMENDMENTS TO THE GUIDELINES FOR THE DEVELOPMENT OF SHIPBOARD OIL POLLUTION EMERGENCY PLANS

RESOLUTION MEPC.86(44) adopted on 13 March 2000 AMENDMENTS TO THE GUIDELINES FOR THE DEVELOPMENT OF SHIPBOARD OIL POLLUTION EMERGENCY PLANS MEPC 44/20 RESOLUTION MEPC.86(44) THE MARINE ENVIRONMENT PROTECTION COMMITTEE, RECALLING Article 38(a) of the Convention on the International Maritime Organization concerning the function of the Committee,

More information

II. Comments Regarding the Mitigation Goals of Net Conservation Benefit and No Net Loss

II. Comments Regarding the Mitigation Goals of Net Conservation Benefit and No Net Loss January 5, 2018 Public Comments Processing Division of Policy, Performance, and Management Programs U.S. Fish and Wildlife Service MS: BPHC 5275 Leesburg Pike Falls Church, VA 22041-3803 Attention: Attn:

More information

Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants

Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants the pressure equipment safety authority Requirements for Reduced Supervision of Power Plants, Thermal Liquid Heating Systems, and Heating Plants AB-528 Edition 2, Revision 1 Issued 2016-09-12 Table of

More information

Guideline to the Inspection of Hormone Product Manufacturing Facilities QAS/08.256, February 2008

Guideline to the Inspection of Hormone Product Manufacturing Facilities QAS/08.256, February 2008 13 May 2008 Quality Assurance Programme Quality Assurance and Safety: Medicines (QSM) Department of Medicines Policy and Standards (PSM) World Health Organization CH-1211 Geneva 27 Switzerland Guideline

More information

June 13, Dear Sir,

June 13, Dear Sir, 3833 West Oakton Street - Skokie, IL 60076 - USA - 847-674-9742 FAX 847-674-9743 email: HQ@pia.com Cliff Schmucker President June 13, 2011 FAA National Headquarters Attention: Mr. Melvin O. Cintron Division

More information

Safety assessments for Aerodromes (Chapter 3 of the PANS-Aerodromes, 1 st ed)

Safety assessments for Aerodromes (Chapter 3 of the PANS-Aerodromes, 1 st ed) Safety assessments for Aerodromes (Chapter 3 of the PANS-Aerodromes, 1 st ed) ICAO MID Seminar on Aerodrome Operational Procedures (PANS-Aerodromes) Cairo, November 2017 Avner Shilo, Technical officer

More information

BSR GPTC Z TR GM References and Reporting Page 1 of 8

BSR GPTC Z TR GM References and Reporting Page 1 of 8 Page 1 of 8 PRIMARY: 192.605 SECONDARY: 191.23 PURPOSE: Review guide material added by TR 2009-17 to 5.1(e) and consider restructuring the guide material under 192.605 as discussed further below. ORIGIN/RATIONALE

More information

MEMORANDUM. NFPA Technical Committee on Lightning Protection Systems. NFPA 780 Supplement ROC TC FINAL Ballot Results (F2012Cycle)

MEMORANDUM. NFPA Technical Committee on Lightning Protection Systems. NFPA 780 Supplement ROC TC FINAL Ballot Results (F2012Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Lightning Protection

More information

2009 NEW MEXICO SWIMMING POOL, SPA AND HOT TUB CODE

2009 NEW MEXICO SWIMMING POOL, SPA AND HOT TUB CODE TITLE 14 CHAPTER 8 PART 3 HOUSING AND CONSTRUCTION PLUMBING CODES 2009 NEW MEXICO SWIMMING POOL, SPA AND HOT TUB CODE 14.8.3.1 ISSUING AGENCY: Construction Industries Division (CID) of the Regulation and

More information

ST/SG/AC.10/C.3/2016/8. Secretariat. United Nations. Transport of gas tanks for motor vehicles. Introduction

ST/SG/AC.10/C.3/2016/8. Secretariat. United Nations. Transport of gas tanks for motor vehicles. Introduction United Nations Secretariat Distr.: General 29 March 2016 ST/SG/AC.10/C.3/2016/8 Original: English Committee of Experts on the Transport of Dangerous Goods and on the Globally Harmonized System of Classification

More information

Existing Rule Language Compared to Proposed Rule Language

Existing Rule Language Compared to Proposed Rule Language Existing Rule Language Compared to Proposed Rule Language MINNESOTA RULES, CHAPTER 4717; REVISOR S ID NUMBER 4442 The following table is a summary of existing and proposed rules. For complete regulations

More information

M-06 Nitrogen Generator (Nitrogen Making Machine)

M-06 Nitrogen Generator (Nitrogen Making Machine) Guideline No.M-06 (201510) M-06 Nitrogen Generator (Nitrogen Making Machine) Issued date: 20 th October, 2015 China Classification Society Foreword This Guideline is a part of CCS Rules, which contains

More information

MILITARY STANDARD INTERFACE STANDARD FOR SHIPBOARD SYSTEMS SECTION 106 COMPRESSED AIR SERVICE FOR SURFACE SHIPS

MILITARY STANDARD INTERFACE STANDARD FOR SHIPBOARD SYSTEMS SECTION 106 COMPRESSED AIR SERVICE FOR SURFACE SHIPS SUPERSEDING SECTION 106A 19 April 1973 (See 9.2) MILITARY STANDARD INTERFACE STANDARD FOR SHIPBOARD SYSTEMS SECTION 106 COMPRESSED AIR SERVICE FOR SURFACE SHIPS AMSC N/A FSC 1990 DISTRIBUTION STATEMENT

More information

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016)

M E M O R A N D U M. NFPA Technical Committee on Fire Tests. NFPA 252 First Draft TC FINAL Ballot Results (F2016) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Kelly

More information

Technical Committee on Heat Recovery Steam Generators and Other Combustion Turbine Exhaust Systems

Technical Committee on Heat Recovery Steam Generators and Other Combustion Turbine Exhaust Systems Technical Committee on Heat Recovery Steam Generators and Other Combustion Turbine Exhaust Systems Date: March 5, 2010 To: Technical Committee on Heat Recovery Steam Generators and Other Combustion Turbine

More information

Does not discriminate against materials, products, methods, or systems of construction of demonstrated capabilities does not discriminate

Does not discriminate against materials, products, methods, or systems of construction of demonstrated capabilities does not discriminate P6228 1 of 31 Page 38 of 80 Date Submitted 4/27/2013 Section 1 Chapter Appendix F Affects HVHZ Yes TAC Recommendation No Affirmative Recommendation with a Second Commission Action Pending Review Proponent

More information

We agree the CGA publication more adequately reflects the equipment accuracy requirements for performing a pressure test on cylinders.

We agree the CGA publication more adequately reflects the equipment accuracy requirements for performing a pressure test on cylinders. Comments regarding NPRM of 49 CFR parts 171 & 180 Page 1 of 11 Proposed 180.205(g): I believe the proposed incorporation by reference of CGA C-1 into 180.205 would be a mistake and a step backwards in

More information

WHS PROCEDURE P Confined Spaces. Approved by: Ruth Hampton Review Date: 6 th December 2015

WHS PROCEDURE P Confined Spaces. Approved by: Ruth Hampton Review Date: 6 th December 2015 5 WHS PROCEDURE P21-01 Page 1 of 7 Issue: 2 1. Intent The Salvation Army Australia Eastern Territory (TSA-AUE) is committed to the provision of a safe, healthy and injury free environment for all persons

More information

CSU Channel Islands Lead Operations and Maintenance Program

CSU Channel Islands Lead Operations and Maintenance Program CSU Channel Islands Lead Operations and Maintenance Program 1.0 Policy It is the policy of California State University Channel Islands to provide employees and visitors with a safe and healthful environment.

More information

Pressure Equipment Directive PED 2014/68/EU Commission's Working Group "Pressure"

Pressure Equipment Directive PED 2014/68/EU Commission's Working Group Pressure H. INTERPRETATION OF OTHER ESSENTIAL SAFETY REQUIREMENTS Guideline H-02 Guideline related to: Annex I Section 3.2.2 and 7.4 Final assessment (Annex I Section 3.2.2) of pressure equipment must include a

More information

LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM

LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM LABORATORY FUME HOOD SPECIFICATION AND MAINTENANCE PROGRAM Last Updated: Tuesday, January 31, 2006 1. INTRODUCTION AND SCOPE 2. RESPONSIBILITIES 3. USER GUIDELINES 4. SYSTEM DESIGN SPECIFICATIONS o The

More information

Notes Assess Transmission Future Needs SDT Project

Notes Assess Transmission Future Needs SDT Project Notes Assess Transmission Future Needs SDT Project 2006-02 2:30-4:30 p.m. EST 1. Administrative Items a. Introductions A meeting was held in the FERC Office in Washington, DC on Wednesday, with FERC staff

More information

PURE H2O FORUM. Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program

PURE H2O FORUM. Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program Shenandoah Valley Wastewater Treatment Plant Network PURE H2O FORUM Safeguarding Operations Personnel Understanding Arc Flash & Developing an Electrical Safety Program September 25, 2015 Presenter: Steve

More information

TRAFFIC IMPACT STUDY CRITERIA

TRAFFIC IMPACT STUDY CRITERIA Chapter 6 - TRAFFIC IMPACT STUDY CRITERIA 6.1 GENERAL PROVISIONS 6.1.1. Purpose: The purpose of this document is to outline a standard format for preparing a traffic impact study in the City of Steamboat

More information

NFPA 1124, Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and pyrotechnic Articles, 2006 edition.

NFPA 1124, Code for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and pyrotechnic Articles, 2006 edition. NFPA 5000-2012 and Proposed 2015 Edition Building Construction and Safety Code TIA Log No. 1139 Reference: Various Comment Closing Date: May 16, 2014 Submitters: Gary Keith, FM Global TIA language for

More information

Pressure Equipment Directive PED 2014/68/EU Commission's Working Group "Pressure"

Pressure Equipment Directive PED 2014/68/EU Commission's Working Group Pressure C. ASSEMBLIES Guideline C-03 Guideline related to: Article 4 paragraph 2 The effect of the derogation in Article 4 paragraph 2 from the introductory paragraph in the same article is not clear. In the circumstances,

More information

How to Define Your Systems and Assets to Support Reliability. How to Define Your Failure Reporting Codes to Support Reliability

How to Define Your Systems and Assets to Support Reliability. How to Define Your Failure Reporting Codes to Support Reliability BACKFED RELIABILITY How to Define Your Systems and Assets to Support Reliability How to Define Your Failure Reporting Codes to Support Reliability How to Generate Risk Prioritization Numbers (RPN) from

More information

Introduction to the NRA Design Manual for Roads and Bridges

Introduction to the NRA Design Manual for Roads and Bridges Volume 0 Section 0 Part A 0.0.A Introduction to the NRA Design Manual for Roads and Bridges July 2011 St. Martin s House, Waterloo Road, Dublin 4. Tel:+353 1 660 2511 Fax +353 1 668 0009 Email : info@nra.ie

More information

1.0 PURPOSE 2.0 SCOPE 3.0 DEFINITIONS. ANSI: American National Standards Institute. CCC: Chemical Control Centre

1.0 PURPOSE 2.0 SCOPE 3.0 DEFINITIONS. ANSI: American National Standards Institute. CCC: Chemical Control Centre Revision Date: 5/17/2016 Page: 1 of 13 Health & Safety has developed the emergency eyewash & safety shower equipment procedure which will be implemented in 3 phases over the next four years. Phase 1 will

More information

Risk Management Series Article 8: Risk Control

Risk Management Series Article 8: Risk Control Risk Management Series Foreword MEDIcept presents this ongoing series of articles focused on the implementation and practical conduct of risk management in the medical device industry to provide practitioners

More information

RACING RULES GUIDANCE

RACING RULES GUIDANCE RACING RULES GUIDANCE CHANGES TO THE RACING RULES FROM JANUARY 2017 Introduction This guidance highlights the main changes to the Racing Rules of Sailing (RRS) effective from 1 January 2017. The changes

More information

MEMORANDUM. SUBJECT: NFPA 69 Proposed Tentative Interim Amendment (TIA) No.1212

MEMORANDUM. SUBJECT: NFPA 69 Proposed Tentative Interim Amendment (TIA) No.1212 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Explosion Protection Systems

More information

Abrasive Blasting Removal Systems

Abrasive Blasting Removal Systems Appendix 6/17 Minutes of the 19 th meeting of the ALG Technical Working Group, 17 October 2017 Abrasive Blasting Removal Systems Appendices are attached to Technical Working Group minutes when the nature

More information

Procedure: Confined space safety

Procedure: Confined space safety Purpose To define the requirements for the control of hazards associated with the use of confined spaces at the Australian National University to ensure compliance with the Work Health and Safety Act 2011

More information

4/14/2015. Best Practices for Confined Space Entry-20 years later, what have we learned? Objectives. Have we solved the confined space entry problem?

4/14/2015. Best Practices for Confined Space Entry-20 years later, what have we learned? Objectives. Have we solved the confined space entry problem? Best Practices for Confined Space Entry-20 years later, what have we learned? NFPA 350-Guide for Safe Confined Space Entry and Work Nancy A. Pearce CIH Senior Fire Protection Engineer National Fire Protection

More information

Pool Standards 2014 (Amended 2017)

Pool Standards 2014 (Amended 2017) Pool Standards 2014 (Amended 2017) How Did We Get Here? Continued Challenge: Respond to New Evidence Provincial Aquatic Committee (AHS) Two anti-entrapment workshops Meetings with Industry: Anti-entrapment

More information

M E M O R A N D U M. NFPA 99 First Draft Correlating Committee FINAL Ballot Results (A2017 Cycle)

M E M O R A N D U M. NFPA 99 First Draft Correlating Committee FINAL Ballot Results (A2017 Cycle) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Correlating Committee on Health Care Facilities

More information

International One Metre International Class Association (IOM ICA) Special General Meeting Amended Agenda. October 31, 2009

International One Metre International Class Association (IOM ICA) Special General Meeting Amended Agenda. October 31, 2009 International One Metre International Class Association (IOM ICA) Special General Meeting Amended Agenda October 31, 2009 Purpose: To vote on a resolution that will determine if IOM ICA will pursue becoming

More information

Unit 5: Prioritize and Manage Hazards and Risks STUDENT GUIDE

Unit 5: Prioritize and Manage Hazards and Risks STUDENT GUIDE : Prioritize and Manage Hazards and Risks STUDENT GUIDE Objectives By the end of this unit, students will be able to: Describe several techniques that can be used to prioritize hazards for mitigation,

More information

Laboratory and Satellite Rodent Housing

Laboratory and Satellite Rodent Housing University of Louisville Institutional Animal Care and Use Committee Policies and Procedures Laboratory and Satellite Rodent Housing Policy: Although strongly discouraged, the IACUC acknowledges that there

More information

Information on work in progress in CEN

Information on work in progress in CEN Economic Commission for Europe Inland Transport Committee Working Party on the Transport of Dangerous Goods Joint Meeting of the RID Committee of Experts and the Working Party on the Transport of Dangerous

More information

City of DuBois PERMIT APPLICATION P. O. Box 408, 16 West Scribner Ave - DuBois, PA Phone: Fax:

City of DuBois PERMIT APPLICATION P. O. Box 408, 16 West Scribner Ave - DuBois, PA Phone: Fax: City of DuBois PERMIT APPLICATION P. O. Box 408, 16 West Scribner Ave - DuBois, PA. 15801 Phone: 814-371-2000 Fax: 814-375-2307 Permit No. LOCATION OF PROPOSED WORK OR IMPROVEMENT Municipality: Tax Parcel

More information

GSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS)

GSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS) GSA POLICY ON LOCAL EXHAUST AND OTHER VENTILATION (FUME CUPBOARDS) Local Exhaust Ventilation Inspection & Maintenance 1 LOCAL EXHAUST AND OTHER VENTILATION Contents 1. Introduction 2. Design specifications

More information

OPERATING CODE NO. 8 APPENDIX 2

OPERATING CODE NO. 8 APPENDIX 2 OPERATING CODE NO. 8 APPENDIX 2 (OC8B) SAFETY CO-ORDINATION IN RESPECT OF THE SCOTTISH TRANSMISSION SYSTEMS OR THE SYSTEMS OF SCOTTISH USERS Paragraph No/Title CONTENTS (This contents page does not form

More information

Calibration Requirements for Direct Reading Confined Space Gas Detectors

Calibration Requirements for Direct Reading Confined Space Gas Detectors : Calibration Requirements for Direct Reading Confined Space Gas Detectors However, the definition of bump test has always been a little slippery. Some manufacturers differentiate between a bump test that

More information

Texas Department of Insurance. Respiratory Protection. Provided by. Workers Health & Safety HS01-027B (1-06)

Texas Department of Insurance. Respiratory Protection. Provided by. Workers Health & Safety HS01-027B (1-06) Texas Department of Insurance Respiratory Protection Provided by Workers Health & Safety HS01-027B (1-06) Contents Introduction... 3 Definitions... 3 Approved Respirators... 3-4 New Respirator Selection

More information

AMENDMENTS TO PREVIOUSLY APPROVED RESEARCH 3/01/2016

AMENDMENTS TO PREVIOUSLY APPROVED RESEARCH 3/01/2016 DUKE UNIVERSITY HEALTH SYSTEM Human Research Protection Program AMENDMENTS TO PREVIOUSLY APPROVED RESEARCH 3/01/2016 The Duke University Health System Institutional Review Board (DUHS IRB) requires that

More information

Contact for service: Lindsay Fung Deer Industry New Zealand P O Box Wellington Phone:

Contact for service: Lindsay Fung Deer Industry New Zealand P O Box Wellington Phone: Proposed Ōpōtiki District Plan Chapter 8 Rural Zone Hearing Statement on behalf of the New Zealand Deer Farmers Association, Bay of Plenty Branch 27 July 2017 Contact for service: Lindsay Fung Deer Industry

More information

Technical Specification Bases Update to the NRC for Period Dated

Technical Specification Bases Update to the NRC for Period Dated ...~Entergy Entergy Operations, Inc. 7003 Bald Hill Road PO. Box 756 Port Gibson, MS 39150 Tel 601 437 6299 Christina L. Perino Manager Licensing GNRO-2009/00017 March 4, 2009 U.S. Nudear Regulatory Commission

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 10651-5 First edition 2006-02-01 Lung ventilators for medical use Particular requirements for basic safety and essential performance Part 5: Gas-powered emergency resuscitators

More information

CITY OF WEST KELOWNA COUNCIL POLICY MANUAL

CITY OF WEST KELOWNA COUNCIL POLICY MANUAL CITY OF WEST KELOWNA COUNCIL POLICY MANUAL Page 1 of 7 DEPARTMENT: Engineering Services SUBJECT: Traffic Calming Policy (Revised June 6, 2017) Policy Statement: The provision of traffic calming measures

More information

Safe Work Practices and Permit-to-Work System

Safe Work Practices and Permit-to-Work System CHAPTER 24 Safe Work Practices and Permit-to-Work System 24.1 INTRODUCTION OSHA s Process Safety Management (PSM) Standard (OSHA, 1992) requires employers to develop and implement safe work practices (SWPs)

More information

1. Review and approval of the consent document is a responsibility that FDA assigns to the IRB with jurisdiction

1. Review and approval of the consent document is a responsibility that FDA assigns to the IRB with jurisdiction Medical College of Wisconsin/Froedtert Hospital Guidance on Negotiating Consent Document Language For Clinical Trial Sponsors 1. Review and approval of the consent document is a responsibility that FDA

More information

Chapter 7: Six-Step Implementation Process

Chapter 7: Six-Step Implementation Process Chapter 7: Six-Step Implementation Process The purpose of this chapter is to explain how the perspectives of all stakeholders interested in or affected by existing or future streets can be incorporated

More information

SEMEM3-73 Maintaining medical gas pipeline systems and equipment

SEMEM3-73 Maintaining medical gas pipeline systems and equipment Maintaining medical gas pipeline systems and equipment Overview This unit identifies the competences you need to carry out maintenance activities on medical gas pipeline systems and equipment, in accordance

More information

DATA ITEM DESCRIPTION Title: Failure Modes, Effects, and Criticality Analysis Report

DATA ITEM DESCRIPTION Title: Failure Modes, Effects, and Criticality Analysis Report DATA ITEM DESCRIPTION Title: Failure Modes, Effects, and Criticality Analysis Report Number: Approval Date: 20160106 AMSC Number: N9616 Limitation: No DTIC Applicable: Yes GIDEP Applicable: Yes Defense

More information

Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits

Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits Common Discrepancies Uncovered on ADCI Diving Contractor & Training Program Audits Ways to Set Your Company or School Up For Success on ADCI Audits and Reduce Costs In most instances, all discrepancies

More information

The Florida Bicycle and Pedestrian Partnership Council

The Florida Bicycle and Pedestrian Partnership Council The Florida Bicycle and Pedestrian Partnership Council Input to the Update of the Florida Transportation Plan March 2015 This document presents input from the Florida Bicycle and Pedestrian Advisory Council

More information

WEBINARS. Hazard Communication

WEBINARS. Hazard Communication WEBINARS Hazard Communication Teaches employees the safe use and handling of hazardous chemicals in the workplace and how to protect themselves and others from those hazards. The modified standard provides

More information

SECTION LEAD-PAINT REMOVAL

SECTION LEAD-PAINT REMOVAL SECTION 02090 LEAD-PAINT REMOVAL PART 1 - GENERAL 1.1 DESCRIPTION This section specifies abatement and disposal of lead-based paint (LBP) and controls needed to limit occupational and environmental exposure

More information

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY FALL HAZARD CONTROL REQUIREMENTS SERIES & NO. SMI - 157

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY FALL HAZARD CONTROL REQUIREMENTS SERIES & NO. SMI - 157 1 of 6 1.0 PURPOSE To establish minimum requirements and guidelines for controlling hazardous exposure of personnel to falls from working elevations in conformance with Federal and State OSHA rules and

More information

The Proposed NFPA 350 Guide for Safe Confined Space Entry and Work!

The Proposed NFPA 350 Guide for Safe Confined Space Entry and Work! Coming in November! The Proposed NFPA 350 Guide for Safe Confined Space Entry and Work! Rocky Mountain AIHA/ASSE Fall Conference September 17, 2015 Nancy Pearce, CIH, Senior Fire Protection Engineer, NFPA

More information

CONFINED SPACES IN CONSTRUCTION SUBPART AA

CONFINED SPACES IN CONSTRUCTION SUBPART AA 21 st Annual Willis Construction Risk Management Conference CONFINED SPACES IN CONSTRUCTION 1926.1200 SUBPART AA 9/15/15 Jim Goss WHAT S NEW Still Happening! September 2013 Canastota NY WWTP - Worker fatally

More information