BBC BETA BURNERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel.

Size: px
Start display at page:

Download "BBC BETA BURNERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel."

Transcription

1 INSTRUCTIONS BBC BETA BURNERS NOTE These instructions are intended for BBC burners firing gas or light oil. For heavy oil BBC applications using compressed air atomization, see.1 WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components, by unqualified personnel, can result in fire, explosion, severe personal injury, or even death. TABLE OF CONTENTS Subject Page A. General Information.. 2 B. Receiving And Inspection. 2 C. Burner Capacity Tables 3 D. Pre Installation Recommendations 4 E. Installation.. 5 F. Initial Burner Set-Up. 10 G. Burner Operation H. Maintenance Appendix: Dimensions BBC X Dimensions BBG_106 - _118 Y Dimensions BBC_106 - _118 Y Dimensions BBG_124 Y Dimensions BBC 1124 Y Tile Dimensions BBC/BBG X Attachment: IPG-9 These instructions are intended to serve as guidelines covering the installation, operation, and maintenance of Hauck equipment. While every attempt has been made to ensure completeness, unforeseen or unspecified applications, details, and variations may preclude covering every possible contingency. WARNING: TO PREVENT THE POSSIBILITY OF SERIOUS BODILY INJURY, DO NOT USE OR OPERATE ANY EQUIPMENT OR COMPONENT WITH ANY PARTS REMOVED OR ANY PARTS NOT APPROVED BY THE MANUFACTURER. Should further information be required or desired or should particular problems arise which are not covered sufficiently for the purchaser's purpose, contact Hauck Mfg. Co. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA /06 Fax:

2 Page 2 WARNING This equipment is potentially dangerous with the possibility of serious personal injury and property damage. Hauck Manufacturing Company recommends the use of flame supervisory equipment and fuel safety shutoff valves. Furthermore, Hauck urges rigid adherence to National Fire Protection Association (NFPA) standards and insurance underwriter s requirements. Operation and regular preventative maintenance of this equipment should be performed only by properly trained and qualified personnel. Annual review and upgrading of safety equipment is recommended. A. GENERAL INFORMATION Beta burners are baffle type burners designed for low-pressure air operation in furnace environments with temperatures up to 2100 F with the stainless steel baffle and up to 2700 F with the refractory baffle. Preheated air versions are available. The BBC and BBG burners fire any clean industrial fuel gas or No. 2 fuel oil, as appropriate for the model selected. (For heavy oil fuel see instruction sheet.1). Capacities range from 2.5 million to 90 million Btu/Hr. Higher capacity models are available upon request. The Beta Burner flame shapes are well-defined throughout the burner s operating range. Two tile options are available. The diverging tile produces a slow mixing, long, wide flame. The converging tile produces a shorter, narrower more well-defined flame. Turndown is approximately 8:1 on gas and 5:1 on oil. If operating with excess air, thermal turndown is greater. B. RECEIVING AND INSPECTION Upon receipt, check each item on the bill of lading and/or invoice to determine that all equipment has been received. A careful examination of all parts should be made to ascertain if there has been any damage in shipment. Please review all drawings and instruction materials to become familiar with burner components, piping schematics, installation and operating procedures and safety precautions. IMPORTANT If the installation is delayed and the equipment is stored outside, provide adequate protection as dictated by climate and period of exposure. Special care should be given to all motors, bearings, refractory material and control panels, if applicable, to protect them from rain or excessive moisture.

3 Page 3 C. BURNER CAPACITY TABLES Model Designations: 11XX = 1100 Series Stainless Steel Baffle, 21XX = 2100 Series Refractory Baffle, 31XX = 3100 Series Refractory Baffle With Insulating Inserts BBC Models Natural Gas Fired Burner Atomizing Air Model 4 OSI Number (SCFH) Main Air 8 OSI (SCFH) Total Burner Air Flow (SCFH) Nominal Natural Gas Flow Rate (SCFH) Nominal Capacity Btu/hr BBC_104 1,200 23,200 24,440 2,440 2,440,000 BBC_106 5,500 49,000 54,500 5,450 5,450,000 BBC_108 5,500 88,000 93,500 9,350 9,350,000 BBC_110 5, , ,500 14,150 14,200,000 BBC_112 8, , ,800 20,680 20,700,000 BBC_114 15, , ,500 28,550 28,600,000 BBC_118 15, , ,500 45,950 45,950,000 BBC_124 15, , ,500 88,550 88,550,000 BBC Models No. 2 Fuel Oil Fired Burner Model Number Atomizing Air Flow (SCFH) Main Air 8 OSI (SCFH) Total Burner Air Flow (SCFH) Nominal No. 2 Oil Flow Rate (GPH) Nominal Capacity Btu/hr BBC_104 2,400 23,200 25, ,560,000 BBC_106 11,000 49,000 60, ,000,000 BBC_108 11,000 88,000 99, ,900,000 BBC_110 11, , , ,700,000 BBC_112 17, , , ,600,000 BBC_114 31, , , ,100,000 BBC_118 31, , , ,500,000 BBC_124 37, , , ,500,000 BBG Models Natural Gas Fired Burner Model Number Main Air 8 OSI (SCFH) Total Burner Air Flow (SCFH) Nominal Natural Gas Flow Rate (SCFH) Nominal Capacity Btu/hr BBG_104 22,000 22,000 2,200 2,200,000 BBG_106 49,000 49,000 4,900 4,900,000 BBG_108 88,000 88,000 8,800 8,800,000 BBG_ , ,000 13,600 13,600,000 BBG_ , ,000 19,800 19,800,000 BBG_ , ,000 27,000 27,000,000 BBG_ , ,000 44,400 44,400,000 BBG_ , ,000 87,000 87,000,000 Notes: 1. Fuel flow rates based on natural gas at 1000 Btu/ft 3 (S.G. = 0.60) and No. 2 fuel oil at a higher heating value of 138,000 Btu/gal. (S.G. = 0.87). 2. Fuel flow rates listed at Stoichiometric operation. 3. Nominal fuel turndown ratio is approximately 8:1 on natural gas and 5:1 on No. 2 oil; a greater thermal turndown ratio can be achieved with excess air operation. 4. Air flows listed are for air at 100 F and sea level. 5. Main and atomizing air pressures listed are static pressures measured at their respective air pressure taps. 6. Oil pressure required for the high fire flow rates listed is 5 psig at the burner oil inlet. 7. Natural gas pressure required at the burner varies with furnace conditions. Typically, 4 OSI or less is required. 8. Atomizing air pressure required on oil firing for BBC_104 is 16 OSI and for BBC_124 is 20 OSI. All other sizes require a minimum of 14 OSI atomizing air pressure for oil firing. (Atomizing air pressures above minimum rating {up to 20 osi} enhance performance.) 9. Higher capacities than listed are available. Consult factory for specific details.

4 Page 4 D. PRE INSTALLATION RECOMMENDATIONS WARNING Adjustment of this equipment, and its components, by unqualified personnel, can result in fire, explosion, severe personal injury, or even death. The following guidelines and recommendations are made to assist personnel in avoiding potentially hazardous situations. 1. It is essential for those involved in installation and operation of burner equipment to become familiar with all instruction materials, including burner components, piping schematics and installation, start-up and operating procedures. 2. Proper weather protection of equipment before installation will help ensure optimum system performance. 3. Hauck Beta Burners must be mounted on properly braced, rigid furnace structures capable of supporting burner weight. Burner Model Approximate Burner Weight Pounds Approximate Tile Weight Pounds BBC/BBG-_104 BBC/BBG-_ BBC/BBG-_ BBC/BBG-_ BBC/BBG-_ BBC/BBG-_ BBC/BBG-_ BBC/BBG-_ All piping must be properly supported and aligned to avoid stresses at the burner connections. Use flexible pipe nipples in the fuel & air lines to alleviate stress. 5. Initial adjustment and burner start-up should be performed only by trained and experienced personnel who are familiar with combustion systems, control and safety circuitry, and overall system installation and operation. 6. Manual ignition or torch lighting is not recommended. 7. Do not attempt to bypass established control and flame safety procedures under normal operating conditions. 8. Avoid exposure to products of combustion and be sure of proper ventilation at all times; improper ventilation of combustion products can quickly lead to a hazardous environment. 9. Always be sure burner internals have cooled sufficiently before attempting to disassemble any components. 10. Before any attempt is made to start burner equipment, check bolted joints for tightness of fasteners and conduct a gas leak test in accordance with accepted practices.

5 Page 5 E. INSTALLATION Burner Mounting 1. The furnace shell plate must be provided with studs to match the mounting plate as shown on dimension drawing X6677, Y4115 or Y5527 SEE APPENDIX. 2. For installation in an existing soft wall furnace refer to drawing W7324 (below): remove the ceramic fiber blanket or board where the burner tile will be installed, 1" (25mm) larger than the outside diameter of the tile. Wrap tile with one layer of 1" (25mm) fiber rated for a higher temperature than the furnace. Secure fiber wrap with tape or twine to compress the ceramic fiber wrap to retain the fiber during installation. Pack additional fiber to fill any remaining openings completely. It is important to make sure the fiber is well packed around the burners silicon carbide firing tube. Fiber must be repacked after the initial firing of the burners. 3. For installation in an existing hard refractory wall refer to drawing W7324 (below): make the holes in the hard refractory where the burner tile will be installed, 1" (25mm) larger than the outside diameter of the tile. Wrap tile with one layer of 1" (25mm) fiber rated for a higher temperature than the furnace. Secure fiber wrap with tape or twine to compress the ceramic fiber wrap to retain the fiber during installation. Pack additional fiber to fill any remaining openings completely. It is important to make sure the fiber is well packed around the burners silicon carbide firing tube. Fiber must be repacked after the initial firing of the burner. W7324 (NOT TO SCALE)

6 Page 6 4. If the burner has not been supplied with a self-supporting tile, a burner port will be needed. Refer to drawing X4195 or X5565 (below) for recommended burner port layout. If the self-supporting tile is being used, proceed to step #7. X4195 (NOT TO SCALE) X5565 BBC/BBG_124 (NOT TO SCALE) 5. Form the burner port to dimensions per drawing X4195 or X5565, using wood or metal mandrels centered on mounting plate studs. Mandrel dimensions include sufficient draft or taper for easy removal.

7 Page 7 6. Use only good quality plastic or castable refractory with a temperature rating of 2400 F, or 400 F above the maximum furnace design temperature, whichever is higher. 7. Hauck recommends refractory brick or high temperature alloy anchors to secure the burner refractory mass to the furnace shell. Use suggestions per drawing X4195 or X5565 as to spacing of anchors and provision for expansion joints, or follow the refractory manufacturer s recommendations. 8. After the refractory has set properly, remove the burner port mandrel. 9. If the self-supporting tile is used, mount it to the furnace shell plate using 1" studs positioned as shown on the dimensional drawings in the appendix. Place the burner tile mounting plate gasket over the studs, and then the burner tile assembly. Secure with lock washers and hex nuts. 10. Mount the burner to the furnace shell plate (or to the self-supporting tile mounting plate) as follows: a. Position the main air inlet in the desired direction. b. Place the mounting plate gasket provided over the burner mounting studs. c. Cover the outside surfaces of the burner tile with a 1/8" thick layer of hightemperature cement or bonding mortar. d. Gently position the burner on its mounting studs and insert the body into the burner tile or port. Check to make sure the main air inlet is positioned in the desired direction. e. Position lock washers and mounting nuts on studs and tighten. f. Wipe off any excess cement which has been forced into the combustion chamber at the joint between the burner body and the burner tile or port. If this cannot be done from inside the furnace, it will be necessary to remove the burner backplate assembly to permit access to clean off the inside surface of the tile (See Maintenance Section). g. Cast refractory around the tile as needed or in a ceramic fiber wall, stuff the joint between the tile and fiber lining with extra fiber to compensate for eventual fiber shrinkage. Air & Fuel Connections 11. Install the main air line at the burner body connection. 12. If necessary, the atomizing (primary) air connection and/or gas connection may be rotated in 45 degree increments as follows: a. Remove the hex nuts and washers holding the atomizing (primary) air/gas body to the main air body. b. Rotate the atomizing (primary) air/gas body to the desired position(s). c. Make sure the gaskets between the atomizing (primary) air/gas body and the main air body are properly seated. d. Replace washers, hex nuts and securely tighten. 13. BBC AND BBG MODELS: Install and connect the gas line. 14. BBC MODELS ONLY: Install and connect the atomizing (primary) air line.

8 Page 8 IMPORTANT All piping must be properly supported and aligned to avoid stresses on the burner and associated equipment. Hauck recommends that unions and flexible connections be used on all air and fuel lines. The unions will allow the burner to be more easily serviced when required, and the flexible connections will help isolate the burner from piping movement due to expansion, contraction and vibration. 15. BBC MODELS ONLY: Install the oil valve on burner oil inlet connection. 16. BBC MODELS ONLY: Connect the oil supply line to the inlet of the oil valve. 17. Install the pilot tip in the center port of one of the two sets of accessory ports on the burner body. Consult appendix drawings Y4115 or Y5527 and instructions that accompany the pilot for additional information. IMPORTANT All burner models are provided with two sets of connections for observation port, pilot and scanner mounting. If the main air connection is at 6 or 12 o clock, the accessory ports at either 3 or 9 o clock can be used. However, both the pilot and scanner MUST be in adjacent ports on the SAME side of the burner. If the main air connection is at 3 or 9 o clock, use the pilot and scanner connection ports located 180 from the main air connection. Neither the pilot nor the flame scanner should be located below the horizontal centerline of the burner, where they could be adversely affected by dirt and debris. Scanner connection should be supplied with 1 psi of purge air. NOTE The BBC/BBG_124 scanner connections are positioned at 45 and 225 clockwise from the air connection center line. Use above guidelines to choose scanner port. 16. If the observation port, pilot, and UV scanner must be relocated during installation due to interferences with piping, etc., the alternate ports can be utilized as follows (see drawing Y7205): a. Remove the pipe plugs (or caps) from the alternate port connections. b. Remove the ceramic fiber insulation from the ports. c. Insert screwdriver or rod into each port and gently tamp on the plug of high temperature cement to dislodge the plug. Use caution not to chip away refractory from the opening in the refractory ring. d. Insert the ceramic fiber insulation into the original parts. Failure to insert ceramic fiber insulation into the unused ports may result in damage to the outer metal burner housing. e. Secure the pipe plugs (or caps) in the original port connections.

9 f. Install a thin coat of high temperature cement over the original ports from the inside of the burner (Hauck recommends Resco Adamant or equivalent) to contain the ceramic fiber insulation. Page 9 CY If an ultraviolet flame detection scanner is used, install it in the correct accessory port adjacent to the pilot connection. Provide a 1 psi air source for the scanner air purge by connecting the atomizing (primary) air line to the 3/8" NPT bushing on the scanner adapter using 3/8" OD tubing and a suitable isolating valve. 18. Complete the mounting of pilot components and connection of air, gas and mixture lines. 19. Inspect all bolted joints on the burner. Be sure all fasteners are tight. 20. Before the burner is placed in service, a gas leak test should be conducted in accordance with standard, accepted practices. One method is to apply a soap and water solution to ALL threaded and flanged joints in the gas body and the gasket around the burner backplate (including the bolts) and any other area where the possibility of a gas leak exists. Pressure should be present for this test. CAUTION In order to ensure an adequate seal, it is important that the burner backplate bolts be sufficiently tight. Before any attempt is made to start the burner, check to ensure that the bolts are sufficiently tight and conduct a gas leak test. Failure to check and ensure that a satisfactory seal exists by conducting a leak test could result in the formation of a hazardous gas leakage condition. Whenever burner internals are removed for cleaning or replacement, be sure to tighten the backplate bolts and conduct a gas leak test.

10 Page 10 F. INITIAL BURNER SETUP CAUTION Initial adjustment and burner start-up should be undertaken only by trained and experienced personnel familiar with combustion systems, control and safety circuitry and overall installation procedures. NOTE Beta Burner Model _104 uses a Hauck #1 pilot IPG5411A. Beta Burner Models _106 through _118 use a Hauck #3 pilot IPG5413A. The _124 model uses a forced air premix pilot system. For pilot operation with burner sizes _106 through _118, see sheet IPG-9. For pilot operation with the _124 model burner, see appendix. CAUTION Ensure that all safety equipment and limits are working properly before proceeding. CAUTION Failure to achieve ignition of pilot or main flame within a safe period (10 sec.) could result in a build-up of a combustible gas mixture which could lead to an explosion. In the event that the pilot or main flame does not light within the above time period, shut off fuel valves and re-purge the chamber before attempting further adjustment.

11 Page 11 G. BURNER OPERATION IMPORTANT The burner tile should be subjected to rapid heat increases at initial start-up. Allow low fire drying for at least 6 8 hours before exposing the system to normal firing operation. Thereafter, if the tile is exposed to excessive moisture or extended periods of dampness, allow at least 30 minutes of low fire drying before beginning normal operation. a. Atomizing (primary) air pressure should be 14 osi (16 osi for BBC_104 and 20 osi for BBC_124) for No. 2 oil, and 4 osi for gas-fired BBC models. No atomizing (primary) air is needed for gas-fired BBG models. All models will operate with up to 20 osi atomizing air pressure. b. Main air pressure ranges from approximately 0.1 osi (minimum rating) to 8 osi (maximum rating) static pressure at the burner inlet. c. Oil pressure required for the high fire rates listed is 5 psig at the burner oil connection. d. Nominal natural gas pressure required at the burner is 4 osi (7" wc). Actual pressure required may vary. e. Ignite the burner by proceeding as follows: (1) BE SURE all fuel shutoff valves are closed and all control valves are in the LOW FIRE position. (2) Start the combustion air blower. (3) Ensure that the pilot gas cock is closed. (4) Turn the pilot air cock to the full open position. (5) Energize the ignition transformer. (6) Open the pilot gas cock. (7) Once the pilot flame has been established, (confirm using observation port), discontinue the spark. (8) Slowly open the main fuel shutoff valve(s). (9) Allow the burner to remain on low fire for a few seconds before repositioning the firing rate control valve. (10) Close the pilot gas cock, while leaving the pilot air cock open. (11) Modulate the burner up and down to be sure the system responds properly and the fuel/air ration does not exceed the limits of the burner. (12) Lock all linkage adjustments and return all control system functions to normal, if changed during initial adjustment. To shut down the burner: 1. Return the burner to the low fire position. 2. Close all fuel shutoff valves. 3. Allow the furnace to cool to 800 F or less before shutting off the combustion air blower. Daily Operation 1. The specific operation of the burner will depend on the individual system components comprising the combustion system. Refer to the instruction sheets and system piping schematics which accompany the individual items. 2. The burner should always be ignited under low fire conditions.

12 Page If the burner ignition tile is exposed to excessive moisture or extended periods of dampness, allow at least 30 minutes of low fire drying before beginning normal operation. Failure to do so will cause any moisture present to expand rapidly, causing damage to the refractory. H. MAINTENANCE Hauck Beta Burners have been carefully engineered to provide dependable performance while requiring low maintenance. As with any product, it is very important to follow operating instructions and all procedures carefully to obtain optimum performance. Please refer to the applicable Beta Burner Parts List to become familiar with the various burner components and assemblies. CAUTION Be sure burner internals have cooled sufficiently before attempting to disassemble any components. Use care when separating gasket surfaces to avoid damage to the gaskets. 1. Burner components which should be checked periodically and cleaned, if necessary, include: a. Oil valve (separated purchase item BBC models only b. Oil atomizer (BBC models only) (1) Disconnect oil line from burner. (2) Remove bolts from atomizer backplate. (3) Completely remove backplate/oil tube/atomizer from burner. (4) Measure the distance from the inside of the backplate to the rear of the oil nozzle. (5) Inspect parts and disassemble to clean, if needed. (6) Reassemble after cleaning, making sure that above dimension (step #4) is maintained. (7) Reinsert the assembly into burner body, making sure that the gasket is properly seated. (8) Replace bolts and securely tighten. (9) Reconnect oil line to oil valve. c. Atomizer assembly (BBC models only) (1) Disconnect oil and atomizing (primary) air lines from burner. (2) Remove rear set of hex bolts from gas body backplate. (3) Remove atomizer assembly from burner. (4) Inspect and clean, if needed. (5) Inspect gas tube, looking into rear of gas body, and clean if any oil or residue exists. (6) Reinsert atomizer assembly into burner body, making sure that the gasket is properly seated and the primary air inlet is properly repositioned. (7) Replace hex bolts and securely tighten. (8) Reconnect oil and atomizing (primary) air lines. d. Gas body assembly (All Models) (1) Disconnect fuel and atomizing (primary) air lines (if used). (2) Remove front set of hex bolts from air body backplate. (3) Remove gas body assembly from burner.

13 Page 13 (4) Inspect internal parts. Clean the interior walls of gas body assembly and gas tube assembly of any oil or residue. (5) Check condition of internal baffle and clean main air openings in baffle, if needed. (6) Clean the atomizer assembly, if necessary. (7) Reinsert gas body assembly, making sure that the gasket is properly seated and inlets are properly repositioned. (8) Replace hex bolts and securely tighten. (9) Reconnect fuel and atomizing (primary) air lines. 2. Replacement of Internal Baffle In certain situations, it may become necessary or desirable to replace the internal baffle of the burner. The baffle on Beta Burner 1100 series models is made of high temperature stainless steel, while the baffles on 2100 and 3100 series burners are made of high temperature refractory. In order to replace the internal baffle, use the following procedure: a. Disconnect fuel and atomizing (primary) air lines (if used). b. Loosen the backplate bolts. c. Remove burner internals after breaking the seal between the internal baffle and the main tile. Be careful not to damage the internal body liners (BBC-3100 models). d. For 1100 series models (stainless steel baffle): (1) Remove (3) ¼" hex head cap screws and baffle from gas tube. (2) Place new baffle on gas tube. (3) Replace hex screws and tighten. e. For 2100 and 3100 series models (refractory baffle): (1) Remove the backplate flange bolts. (2) Remove the backplate with the gas tube attached. (3) Replace the Fiberfrax gasket on the gas tube end. (4) Remove the refractory baffle from the burner. (5) Coat the outside of the new baffle with liquid Fiberfrax. (6) Install in the burner. f. For all models: (1) Coat the outer rear edge of the plate forming a seal between the burner shell and the refractory baffle. (2) Reinstall the burner backplate with the fiber gasket in place on the gas tube end. (3) Tighten the flange bolts (torque to 30 ft-lbs). (4) Reinstall all piping and check for gas leaks before restarting burner. CAUTION Failure to check and ensure that a satisfactory seal exists by conducting a gas leak test could result in a hazardous condition.

14 Page Replacement of Self-Supporting Refractory Tile Refractory tiles should be checked for coke/residue build-up or damage. If this cannot be done from inside the furnace, it will be necessary to gain access to the tile by removing the burner backplate assembly as described in step 2. Should it ever become necessary to replace the burner refractory tile, use the following procedure: a. Disconnect all fuel and air piping from burner. b. Remove flame scanning equipment and pilot from accessory ports. c. Support the burner weight before loosening mounting nuts. d. Loosen the (4) 1" burner mounting nuts from the burner mounting studs and remove the burner assembly from the furnace. e. Loosen and remove the (8) 1" tile mounting nuts from the mounting plate studs. f. Remove the existing burner tile from the furnace wall and clean the tile port opening. g. Inspect the refractory in the area surrounding the tile and repair any damage. h. Replace the burner tile mounting gasket, if necessary. i. Mount the new burner refractory tile. j. Replace tile mounting nuts and tighten. k. Scrape off any excess mortar from the face of the burner. l. Repeat steps 8 through 18 in the installation section (G.) of these instructions.

15 APPENDIX A Page 15

16 APPENDIX B Page 16

17 APPENDIX C Page 17

18 APPENDIX D Page 18

19 APPENDIX E Page 19

20 APPENDIX F Page 20

21 Page 21 APPENDIX G BBC/BBG-_124 Burner Pilot System The BBC/BBG-_124 can employ a Hauck forced air premix pilot. The pilot uses a Hauck Retain- A-Flame tip. Nominal capacity is 250,000 Btu/hr. Minimum air pressure differential required: 14"wc Minimum gas pressure differential required: 3"wc Spark gap: 1/8" Operation: Before connecting the pilot assembly, the fuel line should be purged to remove any dirt. Pipe the pilot gas supply line to the inlet of the pilot shutoff valve, check for leaks. Size the pilot gas supply line to avoid excessive pressure drops. For supply lines up to 25', use ½" pipe. Constant gas pressures ranging from psig must be available at the inlet of the Hauck gas pilot manifold. Note: the gas pressure must not exceed 20 psig, and pressure lower than 12 psig can result in a weak, unreliable pilot. The spark wire gap is factory set at 1/8" This gap can be changed by carefully removing the pilot internals. Bend the spark wire to adjust, reinsert and check the gap. The thickness of a nickel can be used as a gauge for adjusting the spark gap. Complete the initial adjustment as follows: 1. Make sure the spark igniter is connected to the ignition transformer. 2. Place the pilot butterfly valve at the ½ open position Remove the protective hex cover from the Hauck Adjustable Gas Limiting Valve (LVG) and rotate the adjustment screw 3 to 4 turns from the fully closed position. This initial recommended setting may be changed during the final adjustment of the pilot. 4. Remove the protective cover from the pilot gas regulator and rotate the adjustment screw until the scale on the regulator indicates that it is one-half open. This is only a preliminary setting and may be changed to provide optimal pilot performance. 5. Adjust the LVG (and if necessary the air valve) until a good strong pilot is obtained. 6. The pilot flame can be observed through one of the observation ports on the side of the burner. CAUTION Avoid contact with the ignition wire as a painful shock can result.

22 Page 22 This page left intentionally blank. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA Fax:

23 INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified personnel can result in fire, explosion, severe personal injury, or even death. TABLE OF CONTENTS Subject Page A. General Information B. Receiving and Inspection C. Capacities.. 3 D. Dimensions E. Installation.. 8 F. Ignition. 8 G. Operation. 11 H. Shutoff Valve Leak Testing.. 11 I. Maintenance 13 These instructions are intended to serve as guidelines covering the installation, operation, and maintenance of Hauck equipment. While every attempt has been made to ensure completeness, unforeseen or unspecified applications, details, and variations may preclude covering every possible contingency. WARNING: TO PREVENT THE POSSIBILITY OF SERIOUS BODILY INJURY, DO NOT USE OR OPERATE ANY EQUIPMENT OR COMPONENT WITH ANY PARTS REMOVED OR ANY PARTS NOT APPROVED BY THE MANUFACTURER. Should further information be required or desired or should particular problems arise which are not covered sufficiently for the purchaser s purpose, contact Hauck Mfg. Co. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA /07 Fax: IPG-9

24 Page 2 IPG-9 WARNING This equipment is potentially dangerous with the possibility of serious personal injury and property damage. Hauck Manufacturing Company recommends the use of flame supervisory equipment and fuel safety shutoff valves. Furthermore, Hauck urges rigid adherence to National Fire Protection Association (NFPA) standards and insurance underwriter s requirements. Operation and regular preventative maintenance of this equipment should be performed only by properly trained and qualified personnel. Annual review and upgrading of safety equipment is recommended. A. GENERAL INFORMATION The Hauck Series IPG Blast Type Back-Loaded Gas Pilot provides a means of lighting the flame of Hauck burners and many other industrial gas or oil burners. IPG pilots are engineered for exceptional flame stability and long life, even under the most severe and adverse operating conditions. IPG pilots are designed for electric spark ignition. The standard IPG Back-Loaded Pilots are suitable for firing into neutral, negative or positive pressure applications. The back-loaded feature offers the capability to compensate the pilot air/fuel ratio for variations in furnace or burner pressure. B. RECEIVING AND INSPECTION Upon receipt, check each item on the bill of lading and/or invoice to determine that all equipment has been received. A careful examination of all parts should be made to ascertain if there has been any damage in shipment. IMPORTANT If the installation is delayed and the equipment is stored outside, provide adequate protection as dictated by climate and period of exposure. Special care should be given to all motors and bearings, if applicable, to protect them from rain or excessive moisture.

25 C. CAPACITIES Page 3 IPG-9 PILOT SIZE SPECIFICATIONS Port Area (in 2 ) Stoichiometric Air/Fuel (Btu/hr) 21,800 40,800 80,500 Air 27.7"wc (scfh) NOTES: 1. Capacities based on natural gas with HHV of 1034 Btu/ft 3, a stoichometric air/gas ratio of 9.74:1 with a 6"wc mixture pressure and the pilot firing into burner. 2. Ambient combustion air is required at a constant air pressure to the inlet of the mixing tee in the 14-55"wc range; capacities listed based on static air pressure of 27.7"wc. 3. Ambient gas should be supplied to the inlet of the gas regulator at a nominal 14"wc; maximum gas supply pressure is 27.7"wc. Table 1. IPG Capacities PILOT SIZE SPECIFICATIONS Port Area (nm 2 ) Stoichiometric Air/Fuel (kw) Air 6.9 kpa (nm 3 /hr) NOTES: 1. Capacities based on natural gas with LHV of MJ/nm 3, a stoichometric air/gas ratio of 9.74:1with a 1.5 kpa mixture pressure and the pilot firing into burner. 2. Ambient combustion air is required at a constant air pressure to the inlet of the mixing tee in the kpa range; capacities listed based on static air pressure of 6.9 kpa. 3. Ambient gas should be supplied to the inlet of the gas regulator at a nominal 3.5 kpa maximum gas supply pressure is 6.9 kpa. Table 2. IPG Metric Capacities

26 D. DIMENSIONS Page 4 IPG-9 Y8131 (NOT TO SCALE) Figure 1. Dimensions Back-Loaded Gas

27 D. DIMENSIONS (Continued) Page 5 IPG-9 Y8131 METRIC (NOT TO SCALE) Figure 2. Metric Dimensions Back-Loaded Gas

28 D. DIMENSIONS (Continued) Page 6 IPG-9 Y2375 (NOT TO SCALE) Figure 3. Dimensions Back-Loaded Gas Less Solenoid Valves

29 D. DIMENSIONS (Continued) Page 7 IPG-9 Y2375 METRIC (NOT TO SCALE) Figure 4. Metric Dimensions Back-Loaded Gas Less Solenoid Valves

30 Page 8 IPG-9 E. INSTALLATION 1. Ensure that all components of the factory assembled pilot are present and properly connected. The pilot unit consists of a low pressure gas regulator, air ball valve, gas ball valve, gas mixer, pilot nozzle assembly, union (threaded pilots only), and flexible pipe nipple. 2. Install the pilot assembly in the air and gas lines. The gas pressure regulator is used as a zero governor and is suitable for any mounting position without restriction. a. Connect the air piping to the inlet side of the air ball valve. Low pressure air should be supplied at a constant pressure ranging from 14-55"wc ( kpa) at the inlet of the ball valve. b. Connect the gas piping to the inlet side of the gas ball valve. Low pressure gas should be supplied at approximately 14"wc (3.5 kpa) at the inlet of the regulator. The regulator is designed to operate from "wc ( kpa); maximum allowable inlet pressure is 1 psig (6.9 kpa). c. Ensure that the air and gas ball valves are fully closed. F. IGNITION WARNING Adjustment of this equipment by unqualified personnel can result in fire, explosion, severe personal injury, or even death. NOTE To reduce pressure losses, use adequate sized pipe and minimize elbows in the air and gas lines to the pilot assembly. It is recommended that the air and gas supply be equal to or greater than their respective pilot air and gas connection sizes. If the pilot is installed at the end of a long run of pipe or will be operated in a dirty environment, it is recommended that a sediment trap be installed in the pilot air line. 1. Be sure the spark plug is set as shown in Figure 5. Ideally, initial pilot set-up should be done with the pilot outside of the burner. 2. Connect a 5000/6000 volt standard coil type ignition transformer to the spark plug on the spark igniter using a high voltage ignition wire. Ensure that the spark plug s wire electrode is centered in the pilot nozzle.

31 F. IGNITION Continued) Page 9 IPG-9 S4241 (NOT TO SCALE) Figure 5. Spark Gap Setting and Electrode Positioning NOTE Ensure pilots are properly grounded to prevent equipment damage or personal injury. Exercise care to avoid over-tightening the spark plug holding nut as this may crack the ceramic insulator of the plug. Avoid, where possible, the use of long ignition wires. Long ignition wire can cause rapid spark plug wear or erosion. Suggested methods to avoid this problem are explained in Application Sheet GJ57. CAUTION Ignition of the pilot results in a high voltage spark in excess of 5000 volts and an open flame. Remain clear of ignition wire, spark plug and pilot nozzle while firing the pilot. 3. Ensure that the gas ball valve is closed. 4. Start the blower or air supply. 5. Open the air ball valve to the full open position.

32 6. Energize the ignition transformer and verify that an adequate spark is produced. Page 10 IPG-9 7. Open the gas ball valve fully. This ball valve should be open fully at all times when the pilot is burning. NOTE When lighting grouped pilots, as soon as one pilot in a group (supplied by one large mixer) is ignited, light the others in the group at once before starting a new group or igniting the main burners. 8. Adjust the pilot until the proper flame is achieved. The best flame is a sharp, high velocity, blast type, blue flame. The tangential holes around the nozzle should have small sharp flames coming out of them and the edges of the nozzle should begin to glow red. However, if this flame is achieved when the nozzle is outside of the burner port, the pilot can burn rich (i.e., excess fuel) when properly seated in the burner. Therefore, when adjusting the pilot outside of the burner port, a slightly lean (i.e., excess air) flame is recommended. When the pilot nozzle is inserted into the burner, the flame will burn on ratio (i.e., stoichiometric air/fuel ratio) and have the characteristics desired. Air/Fuel ratio adjustment is accomplished as follows: a. Loosen the lock nut on the mixer. b. Rotate the mixture adjusting screw clockwise for a leaner flame or counterclockwise for a richer flame. c. Tighten the lock nut. S4243 (NOT TO SCALE) Figure 6. Pilot Mixer Adjustment 9. To extinguish the pilot: a. Close gas ball valve first. b. Close air ball valve last (if desired).

33 Page 11 IPG Insert a slip-fit pilot into the burner and tighten the setscrew on the burner to lock the pilot nozzle in place (if applicable). 11. Insert a threaded pilot as follows: a. Disconnect the union between the pilot nozzle and flex nipple. b. Thread the pilot into the port and wrench tighten until snug. c. Reconnect the union. NOTE The pilot nozzle tip should be located slightly behind the main burner nozzle discharge area so that it will not obstruct or be affected by the air/fuel discharge of the main burner. G. OPERATION When properly adjusted, the pilot should produce a sharp, high velocity, blast type, blue flame. If adjustment is necessary, refer to the Ignition section. H. SHUTOFF VALVE LEAK TESTING Both safety shutoff valves in the gas pilot manifold should be leak tested on a yearly basis at minimum. Refer to the gas pilot piping diagram for leak testing shown in Figure 7. W8151 (NOT TO SCALE) Figure 7. Gas Pilot Piping Diagram for Leak Testing

34 Page 12 IPG-9 H. SHUTOFF VALVE LEAK TESTING (Continued) 1. Shutoff the burner (s) and furnace. 2. Close the manual shutoff valve downstream of Safety Shutoff Valve No Open the equipment isolation valve downstream of Safety Shutoff Valve NO Bleed off trapped gas by opening both Leak Test Valves No. 1 and No Close Leak test Valve No Connect 3/16" (4.8mm) ID tubing to Leak Test Valve No. 1 and immerse the open end of the tubing in a container of water. Hold the tubing vertically 1/8 to 1/4" (3 to 6mm) below the surface. If bubbles appear, record the leakage rate in bubbles/min and refer to the IMPORTANT note at the end of this section. 7. Close Leak Test Valve No. 1 and apply auxiliary power to open Safety Shutoff Valve No Wait several minutes so that any leakage through Safety Shutoff Valve No. 2 will have time to fill the pipe between Safety Shutoff Valve No. 2 and the manual shutoff valve. 9. Connect the tubing to Leak Test Valve No. 2 and immerse the open end in water as before. Open Test Valve No. 2. If bubbles appear, record the leakage rate in bubbles/min and refer to the IMPORTANT note at the end of this section. 10. When no leaks are detected, open the shutoff valve at the outlet of the PGM and return to normal operation. IMPORTANT The fact that bubbles are present during the leak test does not necessarily mean that a safety shutoff valve is not functioning properly in the closed position. Refer to the National Fire Protection Association s publication NFPA 86 for acceptable leakage rates for a given pipe size per UL, ANSI, CSA, FM or EN standards. If the acceptable bubbles/min leakage rate is exceeded, the safety shutoff valve is leaking and the manufacturer s instructions should be referenced for corrective action. WARNING Do not attempt to operate the combustion system until all leaks are repaired.

35 Page 13 IPG-9 I. MAINTENANCE All components of the pilot assembly are engineered to provide relatively maintenance free operation. It is sometimes necessary, however, to clear the mixer jet of any debris as this causes mixer capacity to diminish. The mixer jet is easily cleaned by removing the air piping downstream of the air ball valve and running a wire into the mixing tee opening through the jet. The gas inlet of the mixer can also be cleaned by the same method. Fully removing the adjustment screw also provides access to clean the mixer. The pilot nozzle may become plugged with debris or carbon buildup. To clean the nozzle, remove the pilot assembly from the burner. Disconnect the nozzle from the pilot assembly and remove the spark plug assembly. Check carefully to ensure the ceramic insulator is not broken. Clean the small tangential holes that surround the main hole and blow the nozzle out with air when complete. Reassemble the pilot assembly, test fire, and reinsert the pilot into the burner (see Figure 8). Periodically remove and inspect the spark plug. If the ceramic insulator is cracked or broken, replace it. Clean the unit of any carbon buildup. When replacing the plug, avoid overtightening the nut holding the plug to avoid cracking the plug s ceramic insulator. Before use, ensure the plug s wire electrode is centered in the pilot nozzle (see Figure 5 for setting spark plug). Gas Pilot Body Gas Pilot Shell Pilot Air/Gas Mix Inlet Main Pilot Orifice. Clean As Necessary Clean Pilot Nozzle Orifices With Thin Wire & Air. If any dirt or buildup accumulates on Gas Pilot Shell, clean with wire brush. Keep holes around Gas Pilot Shell Clear. (NOT TO SCALE) Figure 8. Cleaning Pilot Nozzle and Piloting Holes

36 Page 14 IPG-9 This page left intentionally blank. HAUCK MANUFACTURING CO., P.O. Box 90 Lebanon, PA Fax:

IPG IGNITION GAS PILOTS BACK-LOADED GAS

IPG IGNITION GAS PILOTS BACK-LOADED GAS INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components

More information

BBG BETA BURNER GAS SERIES

BBG BETA BURNER GAS SERIES BBG BETA BURNER GAS SERIES INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by

More information

PGM PREPIPED GAS MANIFOLD

PGM PREPIPED GAS MANIFOLD INSTRUCTIONS PGM PREPIPED GAS MANIFOLD WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified

More information

BVA BUTTERFLY VALVES

BVA BUTTERFLY VALVES INSTRUCTIONS BVA BUTTERFLY VALVES WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by unqualified

More information

GAS LIMITING ORIFICE VALVES LVG SERIES

GAS LIMITING ORIFICE VALVES LVG SERIES GAS LIMITING ORIFICE VALVES LVG SERIES INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components,

More information

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION DUAL FUEL EXCESS AIR BURNER MODEL: 3610, 3651 Revision: 0 FEATURES Burns all fuel gases or light oils Nozzle mix design for on ratio control or excess air 350% excess air all sizes on gas or oil Turndown

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

G96 Series BASOTROL Dual Operator Valve

G96 Series BASOTROL Dual Operator Valve Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION

More information

GM-7000 Series CE Approved Gas Control Valve

GM-7000 Series CE Approved Gas Control Valve Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

G92 Series BASOTROL Automatic Pilot Gas Valve

G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These

More information

ORIFICE METERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel.

ORIFICE METERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. INSTRUCTIONS ORIFICE METERS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components, by unqualified

More information

BUTTERFLY VALVES Series 800

BUTTERFLY VALVES Series 800 BUTTERFLY VALVES Series 800 WARNING Before proceeding read ALL instructions and become familiar with the equipment and associated drawings. Follow ALL applicable safety regulations and codes for pressurized

More information

Installation Instructions

Installation Instructions Page 5750-S-1 Installation Instructions General These mounting instructions for Circular INCINO- PAK Burners are in addition to the specific instructions offered for other Maxon component items: Shut-Off

More information

Installation and Maintenance Instructions

Installation and Maintenance Instructions KINEMAX Burners Page 4200-S-1 Air Inlet Arrangement Installation and Maintenance Instructions KINEMAX Burners are furnished in standard position illustrated at right. Since burner block is round, the entire

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! INLET PRESS TAP WHITE-RODGERS 36E93-304 Delay-Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

ACCESSORY KIT INSTALLATION MANUAL

ACCESSORY KIT INSTALLATION MANUAL ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions

More information

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator.

RS(H)10,15 USER MANUAL. Read the complete manual before installing and using the regulator. RS(H)10,15 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

SPECIFICATIONS CAPACITY

SPECIFICATIONS CAPACITY DMV-ZRD(LE)/6 SERIES Installation Instructions SPECIFICATIONS DMV-ZRD/6 DMV-ZRDLE/6 Two normally closed safety shutoff valves in one housing. V1 and V2 are fast opening, fast closing. Two stage and adjustable

More information

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local

More information

Typical Piping Layouts for PREMIX Blower Mixer Systems

Typical Piping Layouts for PREMIX Blower Mixer Systems PREMIX Blower s Page 3103 Block & Bleed system is frequently required by insurance authorities. Typical Piping Layouts for PREMIX Blower Systems Maxon assumes no responsibility for the use or misuse of

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

North American Orifice Metering System

North American Orifice Metering System Combustion North American Orifice Metering System 8697 and M8697 Metering Orifices accurately measure gas flows to industrial burners. They are compact, inexpensive, and can be installed in individual

More information

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) P/N 126905-01 Rev. B 11/2016 INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) For All Single, Dual and Triple Burner Natural and Propane/LP Gas Logs P126905-01 For

More information

Installation and Maintenance Instructions

Installation and Maintenance Instructions RAMFIRE Burners Page 4300-S-1 Air Inlet Arrangement Installation and Maintenance Instructions RAMFIRE Burners are furnished in standard position illustrated at right. Since burner block is round, the entire

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

Installation and Maintenance Instructions

Installation and Maintenance Instructions VORTIFLARE Radial Flame Burners Page 4400-S-1 Air Inlet Arrangement Installation and Maintenance Instructions VORTIFLARE Burners are furnished in standard position illustrated at right. Since burner block

More information

Design and Application Details MICRO-RATIO Valves

Design and Application Details MICRO-RATIO Valves Flow Control Valves Page 7003 Design and Application Details MICRO-RATIO Valves Principle of Operation MICRO-RATIO Valve assemblies typically consist of a fixed-gradient air butterfly valve mechanically

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , & REDQ Regulators Model 411B Barstock Design Powreactor Dome Regulator OPERATION AND MAINTENANCE Contents Scope..............................1 Installation..........................1 General Description....................1

More information

BGA158 Series CE Approved Class B Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve

More information

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM-20/25 GM-40/45 Issue Date 1298 UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function

More information

BGC258 Series BASOTROL Gas Valve

BGC258 Series BASOTROL Gas Valve Installation Instructions BGC258 Issue Date September 6, 2017 BGC258 Series BASOTROL Gas Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing

More information

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve

BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Installation Instructions BGA Series Issue Date October 3, 2017 BGA158, BGA171 and BGA110 Series Shutoff Gas Valve Applications The BGA Series shutoff gas valve is an electrically operated gas valve that

More information

Installation Instructions

Installation Instructions PREMIX Blower Mixers Page 3100-S-1 Installation Instructions General Instructions Important: Do not discard packing materials until all loose items are accounted for. To prevent damage in transit, spark

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections

More information

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS 36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 80% AFUE Gas Furnace, BGS80 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information

Installation Instructions

Installation Instructions 48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical

More information

RD(H)20/25 Pressure-Reducing Regulator User Manual

RD(H)20/25 Pressure-Reducing Regulator User Manual RD(H)20/25 Pressure-Reducing Regulator User Manual Read the complete manual before installing and using the regulator. 2 Safe Product Selection When selecting a product, the total system design must be

More information

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series

Installation Operating Instructions for Simple Duplex Manual Manifolds PX-TSD Series Introduction Powerex manifolds are cleaned, tested and prepared for the indicated gas service and are built in accordance with the Compressed Gas Association guidelines. The manifold consists of a regulator

More information

Booster Pump PB4-60 Replacement Kits

Booster Pump PB4-60 Replacement Kits Booster Pump PB4-60 Replacement Kits FOR YOUR SAFETY - This product must be installed and serviced by a contractor who is licensed and qualified in pool equipment by the jurisdiction in which the product

More information

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GS-20/25 GS-40/45 Issue Date 1298 GS-20/25 and GS-40/45 Series Single-block Multi-function Gas

More information

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

KTM OM-2 SPLIT BODY FLOATING BALL VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS Before installation these instructions must be fully read and understood SECTION 1 - STORAGE 1.1 Preparation and preservation for storage All valves should be properly packed in order to protect the parts

More information

Installation Instructions

Installation Instructions LP and High Altitude LP Gas Conversion Kit For United States Installations Installation Instructions For Model Series *G6/PGF1 Furnaces, *L1/PGC1 Furnaces, and *R4/PPG1 Gas/Electric Appliances using Honeywell

More information

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WHITE-RODGERS 36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL

ATD LB PRESSURE BLASTER INSTRUCTION MANUAL ATD-8402 90LB PRESSURE BLASTER INSTRUCTION MANUAL SAVE THESE INSTRUCTIONS SAFETY INSTRUCTIONS FOR SANDBLASTER 1. Before opening the tank release the air pressure on the sand tank. To do this, turn off

More information

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A

APCO ARV CLEAN WATER AIR RELEASE VALVES. Model 50A APCO ARV CLEAN WATER AIR RELEASE VALVES Model 50A Instruction D12013 February 2017 Instructions These instructions provide installation, operation and maintenance information for APCO ARV Clean Water Air

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Type 36C67 Combination (24 Volt Models) INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 96% AFUE Gas Furnace, BGH96 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please

More information

1200B2 Series Service Regulators. Instruction Manual

1200B2 Series Service Regulators. Instruction Manual 00B Series Service Regulators Instruction Manual 00B Series Service Regulators 0 Elster American Meter 00B Series Service Regulators General Information The 00B Series Service Regulators are available

More information

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual I854000.D Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Manual Introduction This manual presents guidelines for the Installation, Operation and

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions

Anderson Greenwood Series 93 Positive Pressure POSRV Installation and Maintenance Instructions Before installation these instructions must be fully read and understood Installation and maintenance instructions for Series 93 Positive Pressure Pilot Operated Safety Relief Valves (POSRV). The intent

More information

TECHNICAL DATA CAUTION

TECHNICAL DATA CAUTION Page 1 of 6 1. DESCRIPTION The Viking Model D-2 Accelerator is a quick-opening device, with an integral anti-flood assembly, used to increase the operating speed of a differential type dry pipe valve.

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 SL 40-399 G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P-303) from your authorized IBC Distributor.

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0501 FOR USE WITH 95% MODELS: TG9S, GG9S (130,000 BTU ONLY) FOR USE WITH 80% MODELS: TG(8,L)S, GG(8,L)S (130,000

More information

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage.

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. Operating instructions GB VD Burners Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. To the Equipment Owner: Please read

More information

FLOMIXERS SELECTION DATA ALL GASES

FLOMIXERS SELECTION DATA ALL GASES MODEL: 2301 Revision: 0 BULLETIN 2301-2311 FLOMIXERS are proportional mixing devices that utilize the energy of a stream of air at pressures up to several pounds to (1) entrain a combustible gas, and (2)

More information

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS Installation Instructions For Model Series *G7/*GC2 Furnaces and Appliances Using Honeywell Gas Valves. BEFORE THE CONVERSION

More information

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator.

PRS(TC)4,8 USER MANUAL. Read the complete manual before installing and using the regulator. PRS(TC)4,8 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to

More information

INSTALLATION, OPERATION, SERVICE & PARTS MANUAL FOR STOCK POT RANGE MODELS VSP100, VSP200 & VSP300

INSTALLATION, OPERATION, SERVICE & PARTS MANUAL FOR STOCK POT RANGE MODELS VSP100, VSP200 & VSP300 INSTALLATION, OPERATION, SERVICE & PARTS MANUAL FOR STOCK POT RANGE MODELS VSP100, VSP200 & VSP300 MODEL VSP100 VULCAN-HART COMPANY, P.O. BOX 696, LOUISVILLE, KY 40201-0696, TEL. (502) 778-2791 FORM 30780

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE PERSAL INJURY AND/OR PROPERTY DAMAGE.

More information

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator.

LRS(H)4 USER MANUAL. Read the complete manual before installing and using the regulator. LRS(H)4 USER MANUAL Read the complete manual before installing and using the regulator. WARNING INCORRECT OR IMPROPER USE OF THIS PRODUCT CAN CAUSE SERIOUS PERSONAL INJURY AND PROPERTY DAMAGE. Due to the

More information

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. RIVERSIDE HYDRONICS

More information

VR46.5V(A)/VR86.5V(A) SERIES

VR46.5V(A)/VR86.5V(A) SERIES VR46.5V(A)/VR86.5V(A) SERIES COMACT COMBINATION GAS CONTROS WITH INTEGRATED 1:1 GAS/AIR REGUATOR FOR AUTOMATIC IGNITION SYSTEMS SECIFICATIONS INSTRUCTION SHEET Subject to change without notice. rinted

More information

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles

INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles INSTALLATION & OPERATION MANUAL FOR Teppan-Yaki Griddles MODELS MLS TYG48C ML-769368-Z1 TYG60C ML-766505-Z www.wolfrange.com TYG48C ITW Food Equipment Group, LLC An Illinois Tool Works Company 3600 North

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND Placement in Pipeline System When installing Process Development & Control s ElastoTITE Elastomer-Hinged Check Valves in a pipeline, a minimum of five pipe diameters should

More information

SL G3. Warning

SL G3. Warning Important: If converting from Propane to Natural Gas - order the Natural Gas Conversion Parts Kit (IBC Part # P-307) from your authorized IBC Distributor. Use the Propane Gas conversion parts kit if the

More information

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Type 36C04, 36C14 Step-Opening Combination Gas Control (24 Volt, 120 Volt & 750 mv Models) INSTALLATI INSTRUCTIS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW

More information

Series MG Mixing Tubes

Series MG Mixing Tubes Series MG Mixing Tubes Fuel gas / air mixers 30-60.8-1 Air/fuel gas mixing devices for use with all MAXON premix burner systems to provide thorough blending of air/gas mixture. Mixing tubes available for

More information

3/8" Dr. Air Butterfly Impact Wrench

3/8 Dr. Air Butterfly Impact Wrench 8192106 3/8" Dr. Air Butterfly Impact Wrench Owner s Manual Read and understand all instructions before use. Retain this manual for future reference. Specifications Construction: Polished aluminum and

More information

GAS SUPPLY APPLICATION GUIDE

GAS SUPPLY APPLICATION GUIDE GAS SUPPLY APPLICATION GUIDE Natural Gas or Propane Modulating & Condensing Boilers and Water Heaters This document applies to the following models: Boilers AM 399B AM 500B AM 750B AM 1000B Gas-Fired Boilers

More information

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK

V5197A. Firing Rate Gas Valve APPLICATION FEATURES PRODUCT HANDBOOK V5197A Firing Rate Gas Valve PRODUCT HANDBOOK APPLICATION The V5197A are firing rate valves used to provide variable flow control of air, natural gas, liquefied petroleum (LP), and manufactured gases.

More information

MEGR-1627 Instruction Manual

MEGR-1627 Instruction Manual MEGR-1627 HIGH FLOW GAS REGULATOR Instruction Manual- Look Inside For: Description Installation Remote Vent Line Installations Startup and Adjustment Shutdown Maintenance Body Maintenance Procedures Diaphragm

More information

KC Series Gas Components and Supply Design Guide

KC Series Gas Components and Supply Design Guide Technical Bulletin KC Series Gas Components and Supply Design Guide GF-1030 General AERCO KC Series gas fired potable water heaters and boilers are modulating input devices that require an adequate volume

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

GAS CONVERSION KIT Installation Instructions Range/Rangetop

GAS CONVERSION KIT Installation Instructions Range/Rangetop GAS CONVERSION KIT Installation Instructions Range/Rangetop FOR SERVICE PERSONNEL ONLY IMPORTANT - READ ALL INSTRUCTIONS BEFORE YOU BEGIN THE INSTRUCTIONS HEREIN MUST ONLY BE PERFORMED BY A QUALIFIED SERVICE

More information

VR8305 Direct Ignition Combination Gas Control

VR8305 Direct Ignition Combination Gas Control Honeywell VR8305 Direct Ignition Combination Gas Control Application These direct ignition combination gas controls are used in gas-fired appliances with capacities up to 300 feet 3 /hour at inch wc pressure

More information

VENTITE Inspirator Mixers

VENTITE Inspirator Mixers Bulletin 30 VENTITE Inspirator Mixers Premix Burner Systems Use kinetic energy of higher gas pressures to provide air/gas mixture for all Maxon premix-type burner systems Uses most clean fuel gases 00-

More information

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED VULCAN 36RB 36IRB WOLF C36RB C36IRB This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not

More information

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002

Type ACE97. Introduction. Installation. P.E.D. Categories. Specifications. Overpressure Protection. Installation Guide English May 2002 Installation Guide English May 2002 Type ACE97 Introduction This installation guide provides instructions for installation, startup, and adjustment. To receive a copy of the instruction manual, contact

More information

INSTALLATION & MAINTENANCE INSTRUCTION

INSTALLATION & MAINTENANCE INSTRUCTION ARCHON Industries, Inc Liquid Level Gauges Models: BT-LLG ND-LLG INSTALLATION & MAINTENANCE INSTRUCTION Instruction No.: 1014.2 Revision Issued: 3/01/03 Approved: Engineering Manager Warning ONLY QUALIFIED

More information

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls

V8200A,C,H,M and VR8200A,C,H,M Continuous Pilot Combination Gas Controls V800A,C,H,M and VR800A,C,H,M Continuous Pilot Combination Gas Controls APPLICATION These continuous pilot combination gas controls are used in gas-fired appliances up to 00 cfh capacity of natural gas.

More information

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A.

Gas Lines. Technical Manual. Sumitomo (SHI) Cryogenics of America, Inc Vultee Street Allentown, PA U.S.A. Gas Lines Technical Manual Sumitomo (SHI) Cryogenics of America, Inc. 1833 Vultee Street Allentown, PA 18103-4783 U.S.A. Revision F: April 2008 261320A TABLE OF CONTENTS Page DESCRIPTION...1 SPECIFICATIONS...2

More information

Constant Pressure Crude Oil Container Model CPCCP

Constant Pressure Crude Oil Container Model CPCCP Installation, Operations, and Maintenance Manual Constant Pressure Crude Oil Container Model CPCCP The information in this manual has been carefully checked for accuracy and is intended to be used as a

More information

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax:

EASTERN ENERGY SERVICES PTE LTD. 60 Kaki Bukit Place #02-19 Eunos Tech Park Singapore, SG Singapore Telephone: Fax: 2 Table Of Contents 1. Introduction 3 2. About this Manual 3 3. Contacting YZ Systems 3 4. Vessel Components 4 5. Specifications 5 6. Application 6 7. Theory of Operation 7 8. DuraSite Installation & Use

More information

Summary of Accumulators These operating instructions apply to the accumulators listed in the table shown below.

Summary of Accumulators These operating instructions apply to the accumulators listed in the table shown below. Page 1 of 15 Summary of Accumulators These operating instructions apply to the accumulators listed in the table shown below. Model Number A25-XXXX-3.6K Series A40-XXXX-3K Series A40X-XXXX-3.6K Series A60-XXXX-3K

More information

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E54-214 DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

installation instructions

installation instructions installation instructions GAS CONVERSION KIT PROPANE-TO-NATURAL P/N 315572-71201 4GAD 6GAD Cancels: IIK 4G-50-4 IIK 4G-50-5 7/15/91 NOTE: Read the entire instructions before starting the installation.

More information