1 Galaxy 7000 Shore Connection 500 kva Installation 04/2016

2 Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the sole property of Schneider Electric SA and its subsidiaries. They may not be used for any purpose without the owner's permission, given in writing. This guide and its content are protected, within the meaning of the French intellectual property code (Code de la propriété intellectuelle français, referred to hereafter as "the Code"), under the laws of copyright covering texts, drawings and models, as well as by trademark law. You agree not to reproduce, other than for your own personal, noncommercial use as defined in the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in writing. You also agree not to establish any hypertext links to this guide or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the guide or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.

3 Shore Connection 500 kva Table of Contents Important Safety Instructions SAVE THESE INSTRUCTIONS...5 Safety Precautions...6 Electrical Safety...8 Product-Specific Information...9 Overview...10 Specifications Input Specifications General Characteristics Line-Current Values Permissible GFC Overloads as a Function of Time Output Specifications Derating Table for Limitation and Short-Circuit Current...12 Recommended Protective Devices and Cables Sizes...12 GFC Currents...12 Selection of Protection Devices...12 Recommended Upstream Protection...13 Recommended Cable Sizes...13 Connection Terminals Characteristics...13 Environmental...14 Weights and Dimensions...14 Shipping Dimensions...14 Mechanical Assembly...15 Possible Installation...15 Single GFC...15 Parallel GFC...15 Auxiliary Cabinets (option)...15 Floor Mounting...16 GFC Cabinet...16 Auxiliary Cabinets (Empty)...17 Prepare for Installation...18 Position in Room...18 GFC Cabinet...18 Ventilation...19 Adapt Cabinet for Neutral Point Connection...19 Connect Power Cables...20 Remove the Protective Covers...20 Prepare for Cables...21 Connect the Power Cables...22 Interconnect Cabinet Earthing Bars...23 Connect the Control Cables...24 Connect Single GFC...24 Connect Parallel GFCs...24 Connect the Emergency Power Off (EPO)...26 Connect the Dry Contact Communication Card...27 Connect the Network Management Cards...28 Connect to PLC or Building Management System (BMS)

4 Shore Connection 500 kva Connect to Remote Monitoring Service (RMS)(Option)...30 Connect a Customer Q5N...32 Connect External Power Source for Ventilation...33 Couple 400 mm Auxiliary Cabinet (Option)

5 Important Safety Instructions SAVE THESE INSTRUCTIONS Important Safety Instructions SAVE THESE INSTRUCTIONS Shore Connection 500 kva Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death. DANGER DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury. WARNING WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage. NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage. Please Note Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

6 Shore Connection 500 kva Important Safety Instructions SAVE THESE INSTRUCTIONS A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. Safety Precautions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Read all instructions in the Installation Manual before installing or working on this UPS system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not install the UPS system until all construction work has been completed and the installation room has been cleaned. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The product must be installed according to the specifications and requirements as defined by Schneider Electric. It concerns in particular the external and internal protections (upstream breakers, battery breakers, cabling, etc.) and environmental requirements. No responsibility is assumed by Schneider Electric if these requirements are not respected. After the UPS system has been electrically wired, do not start up the system. Start-up must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The UPS system must be installed according to local and national regulations. Install the UPS according to: IEC (including protection against electric shock, protection against thermal effect, and protection against overcurrent), or NEC NFPA 70, or Canadian Electrical Code (C22.1, Part 1) depending on which one of the standards apply in your local area. Failure to follow these instructions will result in death or serious injury

7 Important Safety Instructions SAVE THESE INSTRUCTIONS Shore Connection 500 kva DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Install the UPS system in a temperature controlled indoor environment free of conductive contaminants and humidity. Install the UPS system on a non-flammable, level and solid surface (e.g. concrete) that can support the weight of the system. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH The UPS is not designed for and must therefore not be installed in the following unusual operating environments: Damaging fumes Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant heat from other sources Moisture, abrasive dust, steam or in an excessively damp environment Fungus, insects, vermin Salt-laden air or contaminated cooling refrigerant Pollution degree higher than 2 according to IEC Exposure to abnormal vibrations, shocks, and tilting Exposure to direct sunlight, heat sources, or strong electromagnetic fields Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Do not drill or cut holes for cables or conduits with the gland plates installed and do not drill or cut holes in close proximity to the UPS. Failure to follow these instructions will result in death or serious injury. HAZARD OF ARC FLASH WARNING Do not make mechanical changes to the product (including removal of cabinet parts or drilling/cutting of holes) that are not described in the Installation Manual. Failure to follow these instructions can result in death, serious injury, or equipment damage. RISK OF OVERHEATING NOTICE Respect the space requirements around the UPS system and do not cover the product s ventilation openings when the UPS system is in operation. Failure to follow these instructions can result in equipment damage. RISK OF EQUIPMENT DAMAGE NOTICE Do not connect the UPS output to regenerative load systems including photovoltaic systems and speed drives. Failure to follow these instructions can result in equipment damage

8 Shore Connection 500 kva Important Safety Instructions SAVE THESE INSTRUCTIONS Electrical Safety DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. The UPS system must be installed in a room with restricted access (qualified personnel only). Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. Turn off all power supplying the UPS system before working on or inside the equipment. Before working on the UPS system, check for hazardous voltage between all terminals including the protective earth. The UPS contains an internal energy source. Hazardous voltage can be present even when disconnected from the utility/mains supply. Before installing or servicing the UPS system, ensure that the units are OFF and that utility/mains and batteries are disconnected. Wait five minutes before opening the UPS to allow the capacitors to discharge. A disconnection device (e.g. disconnection circuit breaker or switch) must be installed to enable isolation of the system from upstream power sources in accordance with local regulations. This disconnection device must be easily accessible and visible. The UPS must be properly earthed/grounded and due to a high leakage current, the earthing/grounding conductor must be connected first. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH In systems where backfeed protection is not part of the standard design, an automatic isolation device (backfeed protection option or other device meeting the requirements of IEC/EN or UL1778 4th Edition depending on which of the two standards apply to your local area) must be installed to prevent hazardous voltage or energy at the input terminals of the isolation device. The device must open within 15 seconds after the upstream power supply fails and must be rated according to the specifications. Failure to follow these instructions will result in death or serious injury. When the UPS input is connected through external isolators that, when opened, isolate the neutral or when the automatic backfeed isolation is provided external to the equipment or is connected to an IT power distribution system, a label must be fitted at the UPS input terminals, and on all primary power isolators installed remote from the UPS area and on external access points between such isolators and the UPS, by the user, displaying the following text (or equivalent in a language which is acceptable in the country in which the UPS system is installed): DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and check for hazardous voltage between all terminals including the protective earth. Failure to follow these instructions will result in death or serious injury

9 Important Safety Instructions SAVE THESE INSTRUCTIONS Shore Connection 500 kva Product-Specific Information WARNING ELECTRICAL HAZARD A label must indicate the existence of multiple supplies at each disconnect device and give the adequate instructions for the removal of all power (AC and DC) from the unit. Before working on the upstream UPS supply cables, proceed to their isolation (disconnection) on both source and UPS sides in order to prevent any possibility of hazardous voltage feedback on the cables or terminals. Failure to follow these instructions can result in death, serious injury, or equipment damage. NOTE: The system is designed for connection to an IT, TT, or TN power distribution system. NOTE: The parallel cables must be run by the electrician but not attached. The field service engineer from Schneider Electric will install the parallel communication box and attach all cables to the UPS units. NOTE: Up to ten GFC units can run in parallel

10 Shore Connection 500 kva Overview Overview The Galaxy 7000 Shore Connection 500 kva GFC (Grid Frequency Converter) is part of the Schneider Electric Shore Connection solution. A. Supervisor B. Normal AC, medium voltage 5.5 to 20 kv C. Medium voltage to low voltage transformer D. GFC 50 Hz / 60 Hz E. Low voltage to medium voltage transformer F. Ship, medium voltage 6.6 to 11 kv

11 Specifications Specifications Shore Connection 500 kva Input Specifications General Characteristics Number of conductors Reference voltage (V) at Pn 3 phases 380 to 470 full rated power 250 to 380 with power derating Reference frequency (Hz) 45 to 66 THDI Typically 3% at Pn Power factor > 0,99 Line-Current Values Continuous input current for load PF=0.9, U=400 V Rated power of GFC unit Continuous input current Input current for at 1.25 In overload limited to 10 min. Input current for load at 1.5 In overload limited to 30 sec. Input/output fuse ratings 500 kva 700 A 881 A 1058 A 1000 A Permissible GFC Overloads as a Function of Time Normal mode operation Output Specifications Number of connectors 3 phases + neutral Adjustable phase-to-phase voltages (V) 380 / / 415 / 440 Adjustable phase-to-neutral voltages (V) 220 / / 240 / 254 Adjustable frequencies (Hz) 50 or 60 1 Permissible overloads 150% for 30 seconds, 125% for 10 minutes 1. Default settings

12 Shore Connection 500 kva Specifications THDU Ph / Ph and Ph / N on linear load < 2% Active Power (kw) 100% load % load 225 Efficiency 100% load 94.1% 50% load 94.2% Derating Table for Limitation and Short-Circuit Current You can set three short-circuit setting durations associated to a Isc max and a Isc min. Isc max and Isc min depend on the type of short-circuit (phase to phase, phase to ground, etc.) Duration Isc max at 35 C (A) Isc min at 35 C (A) Rating factor at 25 C Derating factor at 45 C 150 ms ms ms The short-circuit levels are adjusted for a temperature to provide the highest shortcircuit current. To obtain Isc max and Isc min for other temperature than 35 C use rating/derating factors as multiplier. Temperatures are at GFC air intake. Recommended Protective Devices and Cables Sizes GFC Currents GFC cabinet in kva Phase to phase voltage (V) I rated of Normal AC (A) I rated of load (A) 500 kva The table above is for a load power factor of 0.9. Selection of Protection Devices 2. Default setting. 3. Not supplied. A. GFC cabinet B. Circuit breaker upstream 3 C. PFC rectifier module D. Inverter module E. Downstream CB 3 F. Load

13 Specifications Shore Connection 500 kva When sizing the upstream circuit breakers, the parameters below must be taken into account. Recommended Upstream Protection Normal AC protection: Protection ratings are calculated for the maximum continuous current (at 380 V). GFC cabinet in kva SEA Circuit Breaker Trip unit 500 kva TNC or IT NS 800N 3P Micrologic 5.0 TNS NS 800N 4P Micrologic 5.0 The circuit breakers/switches recommended above respect the requirements for discrimination with the GFC fuses. Depending on the installation, the circuit breaker/switch can be replaced by a circuit breaker/switch with a higher breaking capacity. External auxiliary source for ventilation protection: Source characteristics: single phase 230 VAC, 50/60 Hz Recommended: Circuit breaker 1Ph /N, 10 A, C curve. Recommended Cable Sizes AC cable sizes are determined for: Copper single-core cables type U1000 R02V 100 m long with a line voltage drop <3% installed on perforated cable trays XLPE-type insulation, single-layer trefoil formation THDI between 15% and 33%, 35 C, at 400V grouped in four touching cables GFC Cabinet in kva Minimum size in mm² Normal AC source Load 500 kva 2 x x 240 Connection Terminals Characteristics Connections are made to predrilled terminals. Earthing cables are connected to the earthing bar. GFC cabinet in kva Phase terminal Earth terminal Number of holes and diameter in mm Number of holes and diameter in mm 500 kva 4 x 13 5 x

14 Shore Connection 500 kva Specifications Environmental Operating temperature ( C) 0 to recommended 35 to 45 with linear derating Operating relative humidity Audible noise according to ISO 3746 (NFS ) (dba) System Earthing arrangements 20 to 95%, non-condensing 75 at rated power TNC, TNS, IT TNC recommended with 3 ph + PEN Weights and Dimensions Maximum weight (kg) Height (mm) Width (mm) Depth( mm) GFC cabinet 500 kva Auxiliary cabinets 400 mm wide mm wide mm wide mm wide Shipping Dimensions Height (mm) Width (mm) Depth( mm) GFC cabinet 500 kva Auxiliary cabinets 400 mm wide mm wide mm wide mm wide

15 Mechanical Assembly Mechanical Assembly Shore Connection 500 kva Possible Installation NOTE: TNC or IT SEA on Normal AC source: 3 conductors TNS SEA on Normal AC source: 3 conductors + Neutral Single GFC A. GFC cabinet B. PFC rectifier module C. Inverter module D. Load Parallel GFC Up to ten GFCs can be put in parallel. A. GFC cabinet 1 B. PFC rectifier module C. Inverter module D. GFC cabinet 2 E. Load F. GFC cabinet 3 G. GFC cabinet n Auxiliary Cabinets (option) Layout example for two auxiliary cabinets with one GFC unit

16 Shore Connection 500 kva Mechanical Assembly A. Auxiliary cabinet 1 B. Auxiliary cabinet 2 C. GFC cabinet Floor Mounting To be mounted on a concrete floor or other non-combustible surface only. Dimensions are indicated in millimeters. GFC Cabinet Top view A. Feet B. Cable-running zone C. Front NOTE: To ensure sufficient airflow, cabinet feet must not be removed. Maximum Load on Floor per Square cm per Cabinet Foot GFC cabinet in kva Kg/cm² 500 kva

17 Mechanical Assembly Shore Connection 500 kva Auxiliary Cabinets (Empty) Top view A. Cable-running zone B. Front Maximum Load on Floor per Square cm per Cabinet Foot Auxiliary cabinet in mm Kg/cm²

18 Shore Connection 500 kva Prepare for Installation Prepare for Installation Position in Room GFC Cabinet NOTE: The GFC must be installed in a room with restricted access (qualified personnel only). For correct ventilation, leave nothing on top of the GFC. Leave one meter of free space in front of the GFC for door opening. The cabinet rests on six cylindrical feet, 45 mm in diameter, positioned in the four corners and center of the cabinet to spread the weight. If 500 mm of free space is not maintained above the GFC, abnormal temperature rise may occur. The GFC can operate correctly back to the wall, but it is preferable to leave up to 600 mm for easier maintenance

19 Prepare for Installation Shore Connection 500 kva Ventilation Size the ventilation system taking into account the values in the table below. GFC cabinet in kva 500 kva Heat losses to be evacuated 100 % load4 50 % load4 kw Cal./s Air flow (in m³/h) kw Cal./s Air flow (in m³/h) Adapt Cabinet for Neutral Point Connection For the following upstream systems: IT TNS TT (PE) TNC (PEN) For the following downstream systems: TNC TNS TT 1. Disconnect and remove the jumper on the earth bar. 4. For other values, please consult Schneider Electric

20 Shore Connection 500 kva Prepare for Installation 2. For TNC (PEN) upstream, TNC, TNS or TT downstream systems only: Install the jumper between the earth bar and the inverter neutral bar. Connect Power Cables If several GFC units are in parallel, interconnect the output neutral between the cabinets, even if the output neutral is not used by the load. Remove the Protective Covers Open the door must using the Ronis 405 key. A. Protective covers B. Tie bar

21 Prepare for Installation Shore Connection 500 kva C. To normal AC source D. Earthing bar E. To the earth F. To the load NOTE: Neutral cable (in grey) is for TNS SEA only. 1. Fold the dust protection cover as shown on the cover. 2. Remove the protective covers. Prepare for Cables NOTE: This operation must be carried out before the power cables are connected. RISK OF BURNS FROM HOT SURFACE CAUTION All the cables for the same network (normal AC line, bypass AC line, earth, load) must run through the same hole to avoid overheating of the anti-rodent grid. Failure to follow these instructions can result in injury or equipment damage. 1. Remove the tie bar. 2. Remove the anti-rodent grid. 3. Cut the anti-rodent grid to create holes for cables. 4. Install protection where the cables run through. 5. Fold the sheet downwards on the dotted lines

22 Shore Connection 500 kva Prepare for Installation 6. Reinstall the anti-rodent grid. 7. Reinstall the tie bar. Connect the Power Cables A. To normal AC source B. To the earth C. To the load 1. Check that the switches Q1 and Q5N are in the OFF position. 2. TNS SEA only: Connect the normal AC neutral to the load neutral. 3. Connect the protective conductor (PE or PEN) to the earth bar. 4. Connect the normal AC conductors taking care to respect the following order: L1, L2, L3. 5. Connect the load conductors in the following order: N 5, L1, L2, L3. 6. Reinstall the protective covers. 7. Unfold the dust protection cover. 5. For parallel (or single unit if required by load)

23 Prepare for Installation Shore Connection 500 kva Interconnect Cabinet Earthing Bars Interconnect the earthing bars of all the cabinets in the installation using an additional earthing cable (not supplied) with the characteristics below: Minimum size is half that of a phase earthing conductor, same type of cable as for phase conductors. As short as possible. 1. Fold the dust protection cover as shown on the cover. 2. Remove the protective covers from the cabinets. 3. Connect the earth cable to the earthing bar of a cabinet. 4. Connect earthing cables between the earthing bars of all the cabinets. 5. Unfold the dust protection cover

24 Shore Connection 500 kva Connect the Control Cables Connect the Control Cables Connect Single GFC A. Connectors 1. Remove the protection cover 2. Plug a blue terminator in connector XM6 in the GFC. 3. Plug a blue terminator in connector XM7 in the GFC. Connect Parallel GFCs The supplied cables are 10 m long. 20 m cables are also available (to order); the maximum total length must not exceed 180 m. Once outside the cabinet, the cables must run along the earthing and the other control cables between the cabinets

25 Connect the Control Cables Shore Connection 500 kva A. Connectors B. Cable ties C. Exchange-current and CAN cables Example for four GFCs 1. Remove the protection cover. 2. Create a loop between XM2 and XM3 connectors in the four GFCs units. NOTE: All the connectors must be used. 3. Plug a blue terminator in the GFC1 XM6 connector. 4. Interconnect the GFC connectors XM6 and XM7 as shown. 5. Plug a red terminator in the GFC4 XM7 connector. 6. Run the cables behind the protective covers, as shown in the GFC cabinet. Control cables and power cables must be separated. 7. Run the control cables with the earth cables outside the cabinet

26 Shore Connection 500 kva Connect the Control Cables Connect the Emergency Power Off (EPO) NOTE: In the GFC, the emergency power off causes GFC shutdown. The EPO notion is applicable to installations where pressing the button also causes the circuit breakers on the upstream normal AC source and bypass AC source to open. In parallel configurations, there must be a single general shutdown button with a separate contact for each GFC unit. The cables (not supplied) must have SELV insulation and the maximum size is 2.5 mm². NOTE: To ensure sufficient isolation of EPO cables, they must be run separately from the power cables. 1. Remove the jumper from the XM19 terminal block. 2. Connect the general shutdown NC contact to terminals 1 and 2 (SELV) (Free of voltage). 3. Run the cables in the cabinet as shown. 4. Use cables ties to fasten the cables. 5. Run the cables outside the cabinets with the earth and connection cables between the cabinets

27 Connect the Control Cables Shore Connection 500 kva Connect the Dry Contact Communication Card The cables (not supplied) must have SELV insulation. To ensure sufficient isolation of control-wires (contact signal) cables, they must be run separately from the power cables. Maximum characteristics of input contacts : Switched voltage: 9 VDC (supplied by the GFC) Loop current: 20 ma Wire size: 0.5 to 1.5 mm²/awg20 to AWG16 Maximum characteristics of output contacts : Permissible voltage: SELV only Permissible current: 1 A at 30 VDC/30 VAC Wire size: 0.5 to 1.5 mm²/awg20 to AWG

28 Shore Connection 500 kva Connect the Control Cables The dry contacts can be configured; see the operation manual. NOTE: When PLC remote control mode is used, some contacts are reserved for monitoring purpose. For additional information see operation manual. NOTE: To ensure sufficient isolation of contact signal cables, they must be run separately from the power cables. 1. Connect the cables to input/output contacts. 2. Pass the wires through the ferrite two times. 3. Run the cables in the cabinet as shown. 4. Use cables ties to fasten the cables. 5. Run the cables outside the cabinet with the earth and connection cables between the cabinets. 6. Reinstall the protective covers. Connect the Network Management Cards Two network management cards (NMC) are available in the GFC: Network management card 1 to connect to PLC or to connect to a building management system via Modbus RTU/RS485. Network management card 2 is dedicated to connect to remote monitoring service (option)

29 Connect the Control Cables Shore Connection 500 kva A. Network management card 2 B. Network management card 1 Connect to PLC or Building Management System (BMS) The cables (not supplied) must have SELV insulation. For two-wire Modbus connection use shielded cables only (eg. Schneider TSXCSA100). To ensure sufficient isolation of control-wires (contact signal cables), they must be run separately from the power cables. 1. Connect the cable shield to the cabinet grounding bracket

30 Shore Connection 500 kva Connect the Control Cables 2. Connect Modbus on network management card 1 as shown below. Connect to Remote Monitoring Service (RMS)(Option) Ethernet Connection The cables (not supplied) must have SELV insulation. To ensure sufficient isolation of control-wires (contact signal cables), they must be run separately from the power cables

31 Connect the Control Cables Shore Connection 500 kva 1. Connect Ethernet on network management card 2 as shown below Each network management card will be connected to an ethernet switch. Each network management card must be able to access the SMTP server. Modem Connection A dedicated phone line is required. A phone line can manage 8 GFCs maximum. The cables (not supplied) must have SELV insulation. Use shielded cables only (eg. Schneider TSXCSA100). To ensure sufficient isolation of control-wires (contact signal cables), they must be run separately from the power cables. 1. Connect the cable shield to the network management card metal bracket

32 Shore Connection 500 kva Connect the Control Cables 2. Connect Modbus on network management card 2 as shown below. The dedicated phone line must be able to access RMS center anytime. Connect a Customer Q5N For the installation to operate properly, the following must be respected: There must be only one customer Q5N switch per GFC. The auxiliary contact of an output switch must be a normally open contact when the switch is open

33 Connect the Control Cables Shore Connection 500 kva 1. Connect the auxiliary contact of the customer Q5N switch to XM4. A. Customer Q5N pin 3 B. COM pin 1 2. Run the cables behind the protective covers. Control cables and power cables must run apart. 3. Run the cables with the earth cables outside the cabinet. Connect External Power Source for Ventilation RISK OF CORROSION CAUTION If GFC installed in room with humidity, or powered off or in standby mode, ventilation must be powered by external source. Failure to follow these instructions can result in injury or equipment damage. Connecting external power source for ventilation is allowing GFC fans to run permanently: To reduce risk of corrosion. To reduce GFC starting pre-heating sequence duration when ambient temperature is low. Source characteristics: single phase 230 VAC, 50/60 Hz. Recommended: circuit breaker 1Ph /N 10A C curve. GFC doors must be open. 1. Remove the protection cover. 2. Fasten the cables to the panel

34 Shore Connection 500 kva Connect the Control Cables 3. Connect the external power sources ground, phase, and neutral cables to circuit breaker

35 Couple 400 mm Auxiliary Cabinet (Option) Couple 400 mm Auxiliary Cabinet (Option) Shore Connection 500 kva 1. Remove the two intercabinet uprights located behind the 400 mm cabinet. 2. Refit the rear panel on the 400 mm cabinet with the supplied screws. 3. Remove the side panel on the 400 mm cabinet. 4. Unscrew the side panel of the cabinet to be coupled without removing it. 5. Place the three intercabinet uprights above the side panel of the cabinet to be coupled. 6. Place the screws on the 400 mm cabinet

36 Shore Connection 500 kva Couple 400 mm Auxiliary Cabinet (Option) 7. Couple the 400 mm cabinet with the cabinet to be coupled and tighten the screws from inside the 400 mm cabinet

37

38

39

40 Printed in. Schneider Electric Schneider Electric 35 rue Joseph Monier Rueil Malmaison France + 33 (0) As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication Schneider Electric. All rights reserved

RPS900W Redundant Power Supply. Installation Guide.

RPS900W Redundant Power Supply. Installation Guide. RPS900W Redundant Power Supply Installation Guide www.edge-core.com Installation Guide RPS900W Redundant Power Supply Single DC Output Port with Dual Output Voltages RPS900W E10013-CS-R01 1500000081A

More information

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100

PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100 MPS-1100 User Manual Mega Pool Saver Ltd PLEASE READ CAREFULLY BEFORE INSTALLING OR USING MEGA POOL SAVER MPS 1100 For further up to date instructions on how to install Mega Pool Saver MPS 1100, please

More information

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073

Operating instructions Safety Rope Emergency Stop Switches ZB0052 / ZB0053 ZB0072 / ZB0073 Operating instructions Safety Rope Emergency Stop Switches UK ZB0052 / ZB0053 ZB0072 / ZB0073 7390878 / 02 03 / 2011 Contents 1 Safety instructions...3 2 Installation / set-up...4 2.1 Applications...4

More information

MODELS (2 foot Version) (4 foot Version)

MODELS (2 foot Version) (4 foot Version) INSTALLATION AND MAINTENANCE MANUAL DUROSITE LED LINEAR FIXTURE Document No: 9100-127-2571-99 Rev A April, 2016 MODELS (2 foot Version) (4 foot Version) ALL LAE ALL LBE These instructions contain important

More information

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG33KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG33KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG33KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

SM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service

SM6. instructions for use. connection with compartment for incoming cable from the top. MV distribution factory built assemblies at your service SM6 Anglais MV distribution factory built assemblies at your service instructions for use connection with compartment for incoming cable from the top foreword... 3 symbols and conventions... 3 as per iso

More information

DEEPSEA. SeaLite Lumos POWER & LIGHT. Operator s Manual Ruffin Road San Diego, CA USA.

DEEPSEA. SeaLite Lumos POWER & LIGHT. Operator s Manual Ruffin Road San Diego, CA USA. SeaLite Lumos DEEPSEA POWER & LIGHT T: (858) 576-1261 F: (858) 576-0219 4033 Ruffin Road San Diego, CA 92123-1817 USA www.deepsea.com sales@deepsea.com REV 08/27/18 Optical Specifications Specification

More information

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

KMW3000C. User Manual. Water Chiller for Xcalibur and Gemini systems. Version 1.6, September 2010

KMW3000C. User Manual. Water Chiller for Xcalibur and Gemini systems. Version 1.6, September 2010 KMW3000C Water Chiller for Xcalibur and Gemini systems User Manual Version 1.6, September 2010 Agilent Technologies XRD Products 10 Mead Road, Yarnton, Oxfordshire. OX5 1QU, UK Tel: +44 (0)1865 291600

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

SonoMeter 30 Energy Meters

SonoMeter 30 Energy Meters Data Sheet SonoMeter 30 Energy Meters Description The Danfoss SonoMeter 30 is a range of ultrasonic, compact energy meters intended for measuring energy consumption in heating and cooling applications

More information

Sorensen DCS Series. 1 3 kw V A. General Purpose Systems Power Supply

Sorensen DCS Series. 1 3 kw V A. General Purpose Systems Power Supply Sensen DCS Series General Purpose Systems Power Supply High power density / low ripple and noise High programming resolution with Ethernet interface Constant voltage and current mode Remote sensing Isolated

More information

User Manual. Quantos Automated Dosing Liquid Module

User Manual. Quantos Automated Dosing Liquid Module User Manual Liquid Module 1 Safety Information 1.1 Definition of warnings and symbols Signal Words WARNING for a hazardous situation with medium risk, possibly resulting in severe injuries or death if

More information

Automatic Valve Proving Control

Automatic Valve Proving Control ISO 9001 Automatic Valve Proving Control 7 696 LDU11 UL recognized FM approved Features Performs leak test of the gas shut-off valves before start-up and/or immediately after burner shut-down No inlet

More information

Adjustment of SF6 pressure

Adjustment of SF6 pressure General FBX is a pressurised, sealed unit device in accordance with IEC62271-1. It therefore does not require any periodic refilling. Any abnormal drop in pressure must be subject to corrective maintenance.

More information

Further technical information is available on

Further technical information is available on 1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

INSTALLATION GUIDE Gas Rangetops

INSTALLATION GUIDE Gas Rangetops INSTALLATION GUIDE Gas Rangetops Contents Wolf Gas Rangetops........................... 3 Safety Instructions............................ 4 Gas Rangetop Specifications.................... 5 Gas Rangetop

More information

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Guide for Civil Engineering Structures

Secondary Distribution Switchgear FBX. SF6 Gas-insulated switchboards. Instructions Guide for Civil Engineering Structures Secondary Distribution Switchgear FBX SF6 Gas-insulated switchboards Instructions Guide for Civil Engineering Structures Contents 1 Schneider Electric at your service................... 1 1.1 Our Service

More information

Guidelines to the standard IEC60601

Guidelines to the standard IEC60601 EUROPEAN POWER SUPPLY MANUFACTURERS ASSOCIATION (Visit the EPSMA website at www.epsma.org) Medical Approvals for Power Supplies Guidelines to the standard IEC60601 Revision Date: 2009-09-12 This document

More information

Operation manual Level sensor DC-LS-50 Operation Manual Level Sensor DC-LS-50

Operation manual Level sensor DC-LS-50 Operation Manual Level Sensor DC-LS-50 Operation Manual Level Sensor DC-LS-50 Rev.02 (2014.06) OL Page 1 of 8 Table of contents I. STRUCTURE OF THE MANUAL / CLARIFICATION... 3 II. SAFETY AND HEALTH CONCERNS... 4 1 INTRODUCTION... 5 1.1 Use

More information

Operating Instructions

Operating Instructions Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table

More information

SVEA II GSM Connector User Manual

SVEA II GSM Connector User Manual www.possio.com SVEA II GSM Connector User Manual 1. Introduction Before using SVEA II please read this manual carefully and keep it for future reference. SVEA II GSM Connector is a device for realization

More information

Storage Shelving. User Manual [Revision 3.0 May 2017]

Storage Shelving. User Manual [Revision 3.0 May 2017] User Manual [Revision 3.0 May 2017] READ THIS MANUAL CAREFULLY BEFORE USE FAILURE TO DO SO MAY RESULT IN INJURY, PROPERTY DAMAGE AND MAY VOID WARRANTY. KEEP THIS MANUAL FOR FUTURE REFERENCE. Products covered

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE15C150, VE18C150, VE25C150 PART NO: 2226010, 2226020, 2226025 OPERATION & MAINTENANCE INSTRUCTIONS LS0715 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

Dimensions [All numbers in brackets are in millimeters.] K4-2 US (supplied) 1/2" Centered (Default)

Dimensions [All numbers in brackets are in millimeters.] K4-2 US (supplied) 1/2 Centered (Default) Proportional damper actuator, non-spring return, Multi-Function Technology Torque min. Control to 0 VDC (DEFULT) Feedback to 0 VDC (DEFULT) For proportional modulation of dampers in HVC systems. The is

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

IntelliChlor Power Center (For use with IntelliChlor model IC60, IC40 and IC20)

IntelliChlor Power Center (For use with IntelliChlor model IC60, IC40 and IC20) IntelliChlor Power Center (For use with IntelliChlor model IC60, IC40 and IC20) Patents pending Certified to NSF/ANSI 50 Installation and User s Guide IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL

More information

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100 Information Sheet PlasmaPro Estrelas100 About this information sheet This data sheet provides basic information about the installation of a PlasmaPro Estrelas100 tool. Some of the information in this sheet

More information

PRAHER PLC-MP AQUASTAR MANAUL 2009

PRAHER PLC-MP AQUASTAR MANAUL 2009 PRAHER PLC-MP AQUASTAR MANAUL 2009 1. Copyrights This Operating Manual contains copyright-protected information. All rights reserved to Praher Kunststofftechnik GmbH. This Operating Manual is designed

More information

DEEPSEA POWER & LIGHT. Operator s Manual. SeaLite Six. Original Instruction Ruffin Road San Diego, CA USA

DEEPSEA POWER & LIGHT. Operator s Manual. SeaLite Six. Original Instruction Ruffin Road San Diego, CA USA SeaLite Six DEEPSEA POWER & LIGHT Record product serial number below as it appears on the nameplate. Serial # Pin-out Postive = Pin Negative = Pin Ground = Pin Dimming (if applicable) = Pin T: (858) 576-1261

More information

Model PSI Compressor with 3-Gallon Air Tank 12VDC

Model PSI Compressor with 3-Gallon Air Tank 12VDC Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing

More information

GAS FUEL VALVE FORM AGV5 OM 8-03

GAS FUEL VALVE FORM AGV5 OM 8-03 ALTRONIC AGV5 OPERATING MANUAL GAS FUEL VALVE FORM AGV5 OM 8-03 WARNING: DEVIATION FROM THESE INSTALLATION INSTRUCTIONS MAY LEAD TO IMPROPER ENGINE OPERATION WHICH COULD CAUSE PERSONAL INJURY TO OPERATORS

More information

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , , ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.331 335-29 CFR 1926.302, 1926.416, 1926.417 BASIS: The National Safety Council estimates that there are at least 300 deaths

More information

For Models: 55A00-2 (HAI UPB 1500W Wall Switch Dimmer) 55A00-3 (HAI UPB 2400W Wall Switch Dimmer) 37A00-1 (HAI Auxiliary Switch)

For Models: 55A00-2 (HAI UPB 1500W Wall Switch Dimmer) 55A00-3 (HAI UPB 2400W Wall Switch Dimmer) 37A00-1 (HAI Auxiliary Switch) HAI UPB High Power Wall Switch Dimmer and HAI Auxiliary Switch Installation and Operating Instructions For Models: 55A00-2 (HAI UPB 1500W Wall Switch Dimmer) 55A00-3 (HAI UPB 2400W Wall Switch Dimmer)

More information

Pre-filter for Brushless Blower Instruction Manual

Pre-filter for Brushless Blower Instruction Manual Pre-filter for Brushless Blower 781-70-702 Instruction Manual Minebea Co., Ltd. Industrial Machinery Business Unit 251-8531 1-1-1 Katase,Fujisawa,kanagawa Contact Us Industrial Machinery Product Sales

More information

UL TEST REPORT AND PROCEDURE

UL TEST REPORT AND PROCEDURE Issue Date: 2015-01-30 Page 1 of 24 Report Reference # E186249-A270-UL UL TEST REPORT AND PROCEDURE Standard: Certification Type: CCN: Product: Model: Rating: UL 60950-1, 2nd Edition, 2014-10-14 (Information

More information

Operating Instructions

Operating Instructions LPL Series LED Pendant Lighting Operating Instructions IM0102 COOPER Electronic Technologies (Shanghai) Co., Ltd. No. 955 Shengli Road, East Area of Zhangjiang High-Tech Park, Shanghai 201201 China 1.

More information

Norrsken Family Booklet

Norrsken Family Booklet Section 1: Introduction Low Energy Designs produce efficient and effective LED based lighting products for commercial, retail and industry purposes. Each product may contain specific details on its operation

More information

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520

Contents. Operating instructions. Pressure switch, heavy-duty version Model PSM-520 Operating instructions Contents EN Pressure switch, heavy-duty version Model PSM-520 1. General information 2. Design and function 3. Safety 4. Transport, packaging and storage 5. Commissioning, operation

More information

! Warning, refer to accompanying documents.

! Warning, refer to accompanying documents. About this Manual To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures accurate and adequate to operate this instrument

More information

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury. 2 GALLON AIR COMPRESSOR Model: 7517 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials

More information

Tightness controls TC 1 3 and TC 4

Tightness controls TC 1 3 and TC 4 Tightness controls TC 1 3 and TC 4 Test of both safety valves Short test period thanks to logical decision-making in the program sequence Adjustable test period which can be adapted to different systems

More information

Smart JVA Module WARNING. For use with AquaLink RS systems with rev R firmware or newer.

Smart JVA Module WARNING. For use with AquaLink RS systems with rev R firmware or newer. INstallation and OPERATION Manual Smart JVA Module For use with AquaLink RS systems with rev R firmware or newer. H0370200 Rev C FOR YOUR SAFETY - This product must be installed and serviced by a contractor

More information

Circuit breakers PR 60

Circuit breakers PR 60 Circuit breakers PR series are mechanical switching devices able to switch, conduct and switch-off the current under normal conditions and able to switch, conduct and automatically switch-off the current

More information

HAI UPB Wall Switch and Auxiliary Switch Installation and Operating Instructions

HAI UPB Wall Switch and Auxiliary Switch Installation and Operating Instructions HAI UPB Wall Switch and Auxiliary Switch Installation and Operating Instructions For the following Models: 35A00-1 HAI 600W Dimmer Switch, 35A00-3 HAI 600W Non-Dimming Switch (collectively referred to

More information

Model 130M Pneumatic Controller

Model 130M Pneumatic Controller Instruction MI 017-450 May 1978 Model 130M Pneumatic Controller Installation and Operation Manual Control Unit Controller Model 130M Controller is a pneumatic, shelf-mounted instrument with a separate

More information

AE R1 February 2015

AE R1 February 2015 February 2015 CoreSense Diagnostics for Copeland Scroll UltraTech Air Conditioning Compressors TABLE OF CONTENTS Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to

More information

Customer Responsibilities

Customer Responsibilities Thank you for purchasing an Agilent instrument. To get you started and to assure a successful and timely installation, please refer to this specification or set of requirements. Correct site preparation

More information

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289

3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS. Item #31289 3 GALLON, OILLESS PANCAKE COMPRESSOR INSTRUCTIONS Item #31289 The EASTWOOD 3 GALLON, OILLESS PANCAKE COMPRESSOR, with an Integral Air Regulator, efficiently supplies all compressed air requirements for

More information

Operating Manual for the Evance Iskra R9000 Wind Turbine

Operating Manual for the Evance Iskra R9000 Wind Turbine L3 CS-01 Operating Manual Operating Manual for the Evance Iskra R9000 Wind Turbine //Level 3 Procedures/L3-CS-01 Operating Manual Date of Issue : 8 th December 2009 Page 1 of 13 Description Author Checked

More information

Protection of motor circuits

Protection of motor circuits Protection of motor circuits Circuit breaker/contactor coordination A circuit supplying a motor may include one, two, three or four switchgear or When a number of devices are used, they must be coordinated

More information

Selection of Electrical PPE Tables

Selection of Electrical PPE Tables Selection of Electrical PPE Tables Instructions Table 1 - Starting with Table 1, select the task you plan to do (right-hand column) and the condition of the equipment you will be working on, (center column).

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

Why do I need to do an Arc-Flash Analysis?

Why do I need to do an Arc-Flash Analysis? Why do I need to do an Arc-Flash Analysis? Presented By Tom Norwood for Alexander Nizov, P.E. Principal/Manager Electrical Engineering Division TRAINING INSTITUTE, INC. A SUBSIDIARY OF MEGGER Hazards Analysis

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

Pressure maintenance valve SDV-P / SDV-P-E

Pressure maintenance valve SDV-P / SDV-P-E Translation of the original manual Pressure maintenance valve SDV-P / SDV-P-E Assembly and Operating Manual Superior Clamping and Gripping Imprint Imprint Copyright: This manual remains the copyrighted

More information

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures. MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained

More information

Electro-Pneumatic Converter YT-940 SERIES

Electro-Pneumatic Converter YT-940 SERIES Electro-Pneumatic Converter YT-940 SERIES PRODUCT MANUAL VERSION 1.00 Contents 1. Introduction 3 1.1 General information for the users. 3 1.2 Manufacturer Warranty 3 1.3 Explosion Proof Warning. 4 2. Product

More information

D10S/D20S Wall/Post Mount Inflator Quick Start Manual

D10S/D20S Wall/Post Mount Inflator Quick Start Manual PART NUMBER SERIAL NUMBER D10S/D20S Wall/Post Mount Inflator Quick Start Manual Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product

More information

Safety Powder Spray Systems

Safety Powder Spray Systems Instruction Sheet P/N 107 952C Safety Powder Spray Systems 1. Introduction This section contains general safety instructions for using your Nordson equipment. Task- and equipment-specific warnings are

More information

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations. C&G 2395 Exam Paper June 2013 Section A-All questions carry equal marks. Answer all three questions. Show all calculations. 1. The electrical installation in an industrial unit is scheduled for a periodic

More information

Stand-Alone Bubble Detection System

Stand-Alone Bubble Detection System Instruction Sheet P/N Stand-Alone Bubble Detection System 1. Introduction The Bubble Detection system is designed to detect air-bubble induced gaps in a bead of material as it is being dispensed. When

More information

Definitions found in several locations:

Definitions found in several locations: Definitions found in several locations: NFPA 70 - National Electric Code NFPA 70B Recommended Practice for Electrical Equipment Maintenance. NFPA 70E Electrical Safety in the Workplace OSHA 1910 Subpart

More information

STAGE, STADIUM & X-TREME SHOT.

STAGE, STADIUM & X-TREME SHOT. USER AND INSTALLATION MANUAL ENGLISH STAGE, STADIUM & X-TREME SHOT. CONFETTI & STREAMER FX PART01339 rev 01-00 DISCLAIMER WARNING Read this manual carefully before installing and/or using this product.

More information

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1.

SPECIFICATIONS Type: Twin stack, single phase Tank: 4 gallon Air Output: PSI; PSI Max PSI: 125 PSI HP: 1. 2 GALLON TWIN STACK AIR COMPRESSOR Model: 9526 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

Zelio Relays RSL Slim Interface Plug-In Relays

Zelio Relays RSL Slim Interface Plug-In Relays Zelio Relays RSL Slim Interface Plug-In Relays Catalog 8501CT0901 2009 Class 8501 CONTENTS Description............................................. Page Introduction.................................................3

More information

Model GFC 7000T CO 2 Analyzer (Addendum to GFC 7000TA Manual, PN 07272)

Model GFC 7000T CO 2 Analyzer (Addendum to GFC 7000TA Manual, PN 07272) Manual Addendum Model GFC 7000T CO 2 Analyzer (Addendum to GFC 7000TA Manual, PN 07272) P/N M07273 DATE 06/11/13 TELEDYNE ELECTRONIC TECHNOLOGIES Analytical Instruments 16830 Chestnut Street City of Industry,

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE11C150, VE15C150, VE18C150 PART NO: 2226005, 2226000, 2226015 OPERATION & MAINTENANCE INSTRUCTIONS LS0615 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

OC4000 USER'S GUIDE I O OXYGEN CONCENTRATOR FOR VETERINARY USE ONLY. by Supera Anesthesia Innovations GLOSSARY OF SYMBOLS. : ON (power switched on)

OC4000 USER'S GUIDE I O OXYGEN CONCENTRATOR FOR VETERINARY USE ONLY. by Supera Anesthesia Innovations GLOSSARY OF SYMBOLS. : ON (power switched on) by Supera Anesthesia Innovations USER'S GUIDE OC4000 OXYGEN CONCENTRATOR FOR VETERINARY USE ONLY I O : ON (power switched on) : OFF (power switched off) : Class II protection : Do not expose to open flames

More information

DEEPSEA. Sealite Sphere 6500 POWER & LIGHT. Operator s Manual. Original Instruction Ruffin Road San Diego, CA USA

DEEPSEA. Sealite Sphere 6500 POWER & LIGHT. Operator s Manual. Original Instruction Ruffin Road San Diego, CA USA DEEPSEA POWER & LIGHT Sealite Sphere 6500 Record product serial number below as it appears on the nameplate. Serial # Pin-outs Positive = Pin Negative = Pin Ground = Pin Dimming (if applicable) = Pin T:

More information

Ventam 85 Installation & Commissioning Instructions

Ventam 85 Installation & Commissioning Instructions Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoeburyness Essex SS3 9QY Phone 01702 382 307 Fax 01702 382 340 Ventam 85 Installation & Commissioning Instructions 1 General The Ventam

More information

TABLE OF CONTENTS 2 TALAS DRYER 4 TALAS MEASURER 7 TALAS PORTABLE DRYER 9 TALAS LEAKER 11 TALAS STARTER 14 TALAS AUXILIARY 17 APPENDICES

TABLE OF CONTENTS 2 TALAS DRYER 4 TALAS MEASURER 7 TALAS PORTABLE DRYER 9 TALAS LEAKER 11 TALAS STARTER 14 TALAS AUXILIARY 17 APPENDICES TABLE OF CONTENTS 2 TALAS DRYER 4 TALAS MEASURER 7 TALAS PORTABLE DRYER 9 TALAS LEAKER 11 TALAS STARTER 14 TALAS AUXILIARY 17 APPENDICES ALL PICTURES SHOWN ARE FOR REFERENCE ONLY ACTUAL PRODUCT MAY VARY

More information

MP15 Jockey Pump Controller

MP15 Jockey Pump Controller Setup and Operating Instructions MP15 Jockey Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron Model MP15 Jockey Pump

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO

400H HARDMOUNT AIR COMPRESSOR KIT PART NO H HARDMOUNT AIR COMPRESSOR KIT PART NO 400H HARDMOUNT AIR COMPRESSOR KIT PART NO. 40042 450H HARDMOUNT AIR COMPRESSOR KIT PART NO. 45042 400H 450H IMPORTANT: It is essential that you and any other operator of this product read and understand

More information

Gas density monitor With integrated transmitter Model GDM-100-TI

Gas density monitor With integrated transmitter Model GDM-100-TI SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed

More information

TeSys protection components

TeSys protection components Presentation, description -pole thermal overload relays TeSys D Presentation TeSys D thermal overload relays are designed to protect a.c. circuits and motors against: b overloads, b phase failure, b excessively

More information

MAGICFX CONFETTIPISTOL USER AND INSTALLATION MANUAL

MAGICFX CONFETTIPISTOL USER AND INSTALLATION MANUAL English MAGICFX CONFETTIPISTOL USER AND INSTALLATION MANUAL CONFETTI FX / STREAMER FX Manual trigger PART01129 rev 01-00 DISCLAIMER WARNING Read this manual carefully before installing and/or using this

More information

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions.

Oxford Instruments Plasma Technology. PlasmaPro NGP80. Installation Data Sheet. Original Instructions. Oxford Instruments Plasma Technology www.oxford-instruments.com About this data sheet This data sheet provides basic information about the installation of a tool. Floor and wall loadings Table 1 lists

More information

Position switches FP series

Position switches FP series A Position switches FP series Selection diagram 0 08 8 9 0 0 0 Ø 8 mm Ø, mm external rubber stainless steel stainless steel fiber glass rod gasket sphere sphere adjustable lever safety adjustable lever

More information

HAI UPB 15A Relay Switch and Auxiliary Switch Installation and Operating Instructions

HAI UPB 15A Relay Switch and Auxiliary Switch Installation and Operating Instructions HAI UPB 15A Relay Switch and Auxiliary Switch Installation and Operating Instructions For the following Models: 40A00-1 HAI 15A Relay Switch (referred to as HAI UPB Wall Switch, in this document), and

More information

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY 1. CONTROL OF HAZARDOUS ENERGY POLICY AND PROCEDURES A. OSHA References: 29 CFR 1910.147, 29 CFR 1910.332, 29 CFR 1910.333, 29 CFR 1926.417 B.

More information

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6 NEUTRAL GROUNDING RESISTORS INSTALLATION, OPERATION & MAINTENANCE MANUAL Contents 1- SAFETY INSTRUCTIONS... 3 1-1- Compliance with Instructions in this Manual. 3 1-2- Guidance Notes Installation.... 3

More information

Inoxair. Repair Manual. Content. Edition: 12/2010. Subject to technical changes for reasons of the continous development.

Inoxair. Repair Manual. Content. Edition: 12/2010. Subject to technical changes for reasons of the continous development. Inoxair Repair Manual Edition: 12/2010 Content 1) Serial number 2) Technical data 3) Functional principle 4) Problem analysis 5) Removal 6) Repairs 7) Circuit diagram and cable-connection-plan 8) Pneumatic

More information

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations.

C&G 2395 Exam Paper April Section A - All questions carry equal marks. Answer all three questions. Show all calculations. C&G 2395 Exam Paper April 2013 Section A - All questions carry equal marks. Answer all three questions. Show all calculations. Q.1 The electrical installation in a small food retail outlet is scheduled

More information

FTC130 Transmitter. Operating Manual

FTC130 Transmitter. Operating Manual Seite 1 von 11 FTC130 Transmitter Fast Thermal Conductivity Analyzer Operating Manual 1.09KD180724CWI1V05 Messkonzept GmbH Seite 2 von 11 1. Intended Use... 3 2. Description... 4 3. Measuring gases and

More information

100C Air Compressor Kit

100C Air Compressor Kit 10010 100C Air Compressor (standard mounting bracket, CE Spec) 10014 100C Air Compressor (no leader hose or check valve, CE Spec) 10016 100C Air Compressor (with Omega Bracket, CE Spec) IMPORTANT: It is

More information

PS Plasma 375 Plasma Cutter Kit Assembly & Operating Instructions

PS Plasma 375 Plasma Cutter Kit Assembly & Operating Instructions PS07569 201412 Plasma 375 Plasma Cutter Kit Assembly & Operating Instructions READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT. This manual provides important information on proper operation

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Installation Instructions

Installation Instructions 48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical

More information

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE

OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE OEM Manual MODEL 2305 ECONOMICAL DIGITAL SINGLE CYLINDER SCALE 1 These instructions generally describe the installation, operation, and maintenance of subject equipment. The manufacturer reserves the right

More information

BRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP SERIES

BRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP SERIES BRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP 25503 SERIES TABLE OF CONTENTS A. PRODUCT OVERVIEW A.1 SPECIFICATIONS A. PRODUCT OVERVIEW... 3 A.1 Specifications A.2 Packing

More information

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road

PROPORTIONING VALVE. Model 150 INSTRUCTION MANUAL. March 2017 IMS Company Stafford Road PROPORTIONING VALVE Model 150 INSTRUCTION MANUAL March 2017 IMS Company 10373 Stafford Road Telephone: (440) 543-1615 Fax: (440) 543-1069 Email: sales@imscompany.com 1 Introduction IMS Company reserves

More information

OEM Manual. MODEL ½ Digit DRUM SCALE

OEM Manual. MODEL ½ Digit DRUM SCALE OEM Manual MODEL 4020-3 ½ Digit DRUM SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA & Canada) Phone:

More information

Aztec ADS430 EZCLEAN Compressed air supply unit

Aztec ADS430 EZCLEAN Compressed air supply unit Operating instruction OI/ADS430/EZCLN EN Rev. A Aztec ADS430 EZCLEAN Compressed air supply unit Measurement made easy Introduction The Aztec ADS430 EZCLEAN compressed air supply unit is a rugged, reliable

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

400C & 450C DUAL PERFORMANCE VALUE PACKS

400C & 450C DUAL PERFORMANCE VALUE PACKS (Chrome) PART NO. 40013 (Silver) PART NO. 45012 (Chrome) PART NO. 45013 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before

More information

HS653 Negative Pressure Ventilation Controller

HS653 Negative Pressure Ventilation Controller HS653 Negative Pressure Ventilation Controller General Installation Notes: Make sure that power is disconnected from system prior to servicing. Installation of this equipment and related OEM equipment

More information