VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES

Size: px
Start display at page:

Download "VAV SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES"

Transcription

1 Proceedings: Indoor Air 005 A SYSTEM INDOOR AIR QUALITY CONSIDERATIONS FOR OFFICE SPACES PH Zhang * Jacobs Civil, Inc. 60 Madison Avenue, 1 th Floor, NYC, NY10016, USA ABSTRACT This paper discusses indoor air quality considerations for office spaces when using A system. The indoor air quality is a significant concern for A system, that provides various supply air rate according to the space, especially in multiple spaces, served by a common air handling unit. For office space A system design, two procedures are used to ensure the indoor air quality: ventilation rate procedure and indoor air quality procedure. The ventilation rate procedure is a diluting method, widely used in HAC designs because of its practicability. The indoor air quality procedure is a monitoring contaminant concentration method. CO concentration in the office space is an indicator of occupied space contaminant level. This paper simulates and analyzes the ventilation for variable multi-space when the multi-space equation (6-1), ASHRAE 001, would be ineffective or not functioning in the A system at a fixed acceptable outdoor air rate. Also, it provides a design solution and ventilation control strategy at the fixed outdoor air rate for indoor air quality. INDEX TERMS A system, Building ventilation. INTRODUCTION A typical office floor plan, shown in Figure 1, includes enclosed offices around the perimeter, open interior office spaces, and conference rooms in the corner. For HAC system calculations and design, the floor is divided into ten zones from the northeast corner to the central areas. There is a common air-handling unit in the west end of the floor plan to serve the multiple spaces. Figure 1. Typical Floor Plan ENTILATION FOR INDOOR AIR QUALITY An HAC system delivers conditioned air, including the re-circulated air and outdoor air, to the occupied space to ensure human thermal comfort and acceptable indoor air quality. For multiple space ventilation with a common HAC system, the system ventilation should comply with ASHRAE 6, 001 and is adjusted according to the equation (6-1): Y = X /( 1+ X Z ) * Corresponding author pz5356@hotmail.com 1365

2 Proceedings: Indoor Air 005 where: Y = ot / st = corrected fraction of outdoor air in system supply X = on / st = uncorrected fraction of outdoor air in system supply Z = oc / sc = fraction of outdoor air in critical space. The critical space is that space with the greatest required fraction of outdoor air in supply to this space = corrected total outdoor air flow rate ot st on = total supply flow rate, i.e. the sum of all supply branches of the system = sum of outdoor air flow rates branches on the system = outdoor air flow rate required in critical spaces oc sc = supply flow rate in critical space Table 1 presents the results and analysis for outdoor air rates in the system using four methods: entilation Rates by Equation. 6-1, ASHRAE 6, 001, entilation Analysis with Adjusted Critical Spaces, System entilation Rates by CO Concentration and entilation Analysis with Adjusted Critical Spaces by CO Concentration. The first columns in each zone indicate the calculated supply air rates by space for the selected month and times during the design. The maximum air supply rates appear at 3:00 PM, when the ambient temperature appears to be the highest temperature during the day. The second columns in each zone illustrate the ventilation outdoor air rates. Acceptable outdoor air rate, which comply with ASHRAE Standard 6, 001, is brought to office spaces to dilute the indoor contaminants due to human activity and other contaminants. Typically, for office spaces, the required outdoor air rate is 9 L/s (0 CFM) per person, the maximum occupancy density is 7 people per 100 m, and the maximum occupancy density for a conference room is 50 people per 100 m. If there is a person in an office room along the perimeter area and 9 occupants in the conference room, when the conference rooms are considered to be at intermittent occupancy, then 75% of the maximum occupancy is used. Thus the ventilation rate of outdoor air is 07 L/s (440 CFM) for occupants. Zone 1 and Zone for the conference rooms are the critical spaces; the supply air rates are less than the required ventilations by ASHRAE 6, 001. The supply airflow should be 100% acceptable outdoor air; the fraction of outdoor air Z should be 1.0. By equation (6-1), Y should be 1.0. This presents 100% outdoor air would be used in the system for the common air-handling unit because of the high occupancy and low load conditions in the critical area. Based on these results, the great energy cost associated with a 100% outdoor air rate finds the HAC system to be impractical. The system would fail in the small area (fraction of supply airflow in the critical area to total supply airflow seems approximately.4%). However, if the fraction of outdoor air in the critical area is decreased by increasing the space when the required ventilation is constant, the system outdoor air would be greatly decreased. The increase of space is easily completed by the addition of heat from a heating coil or other heating equipment. With the exception of the conference areas, the central area contains the highest fraction of outdoor air. When the central area is chosen as the critical area, and the same fraction of outdoor air is taken in the conference area, the total system outdoor air would be greatly decreased. The results, shown in ventilation analysis with adjusted critical space (Table 1), confirm the approximately 0.30 outdoor air fraction and 1700 L/s (3400 CFM) outdoor air rate make sense with the practice of HAC system. 1366

3 Proceedings: Indoor Air 005 entilation Rates by Equation 6-1, ASHRAE 6, 001 Table 1. entilation analysis for A system of office spaces Zone 1 Zone Zone 3 Zone 4 Zone 5 Zone 6 L/s L/s Max. 1.0 L/s L/s Max. 1.0 L/s L/s L/s L/s L/s L/s L/s L/s 8:00 AM :00 AM :00 PM :00 PM entilation Analysis with Adjusted Critical Space Zone 1 Zone Zone 3 Zone 4 Zone 5 Zone 6 Adjusted Adjuste SA d SA L/s L/s Max. 1.0 L/s L/s L/s Max. 1.0 L/s L/s L/s L/s L/s L/s L/s L/s L/s 8:00 AM :00 AM :00 PM :00 PM System entilation Rates by CO Concentration L/s L/s Max. 1.0 L/s L/s Max. 1.0 L/s L/s L/s L/s L/s L/s L/s L/s 8:00 AM :00 AM :00 PM :00 PM entilation Analysis with Adjusted Critical Space by CO Concentration Zone 1 Zone Zone 3 Zone 4 Zone 5 Zone 6 Zone 1 Zone Zone 3 Zone 4 Adjusted Adjuste SA d SA ent. Zone 5 Zone 6 ent. OA/SA OA/SA L/s L/s Max. 1.0 L/s L/s L/s Max. 1.0 L/s L/s L/s L/s L/s L/s L/s L/s L/s 8:00 AM :00 AM :00 PM :00 PM

4 Proceedings: Indoor Air 005 entilation Rates by Equation 6-1, ASHRAE 6, 001 (Continue) Zone 7 X by Eqn.6-1 Critical Z Y st on entilation Analysis with Adjusted Critical Space (Continue) Zone 7 Zone 8 Zone 9 Zone 10 Total OA Total SA, zones, Zone 8 Zone 9 X by Eqn.6-1 Critical Z Y adjusted zones on System entilation Rates by CO Concentration (Continue) Zone 10 Total SA by Loads& Zone 7 Zone 8 Zone 9 Zone 10 Total OA by Eqn.6-1 Total SA, zones, Critical OA/SA st on X Z Y ent entilation Analysis with Adjusted Critical Space by CO Concentration (Continue) Total OA Zone 7 Zone 8 Zone 9 Zone 10 Total SA by Eqn.6-1 by Loads& Total OA Critical OA/SA adjusted zones on X Z Y ent

5 Proceedings: Indoor Air 005 Alternatively, CO concentration is an indicator of indoor air quality. Human occupants produce carbon dioxide, water vapor, and contaminants including particulate matter, biological aerosols, and volatile organic compounds. Indoor air quality criteria with respect to human bioeffluents are likely to be satisfied if the ventilation results in indoor CO concentrations less than 700 ppm above the outdoor air concentration. The outdoor airflow rate is given (ASHRAE 6, 001): where: = outdoor air flow rate per person O N = CO generation rate per person C = s CO concentration in the space C = o CO concentration in outdoor air o = N / ( C C ) s o For office activity level, the ventilation flow rate is 9 L/s (0 CFM) and the CO concentration in a space maintains about 700 ppm above the outdoor air concentration. The ventilation rate of acceptable outdoor air is determined by CO sensor monitoring space CO concentration produced by human activity. The number of occupants in the spaces and the lag time between when persons enter the space and when CO level reaches the set point are considered. The numbers of occupants is an important variable in the CO concentration, which will conclude the actual ventilation rates. entilation procedure of CO monitoring, including the full occupancy, the part occupancy and the unoccupied, is a dynamic method that responds to how the building is used and occupied. For the multi-space ventilation with the common A system, the CO monitoring in the critical area (conference rooms) is more reasonable. As shown in System entilation Rates by CO Concentration (Table 1), there are four occupied cases in the critical area (conference zone): unoccupied, 50% occupied, 75% occupied and fully occupied. When unoccupied, the ventilation fraction is approximately 30%. When fully occupied, the ventilation fraction is 100%, which requires 100% outdoor air in the system, that is a significant impact on the energy cost. entilation Analysis with Adjusted Critical Space by CO Concentration in Table 1 presents the results for the ventilation analysis when the critical area is chosen and adjusted to the central area (Zone 9). The required ventilation is much less than the system ventilation rates by CO concentration without the critical area adjusted, while the indoor air quality is an acceptable level. It shows the ventilation varies with the number of occupants. When the proper control system is used in the system, great energy savings result. ENTILATION CONTROL In a variable air volume HAC system, the indoor air quality is a significant concern; under-ventilation in a critical area can often occur. As a result, when the critical space is properly ventilated, the other areas are over-ventilated, which can produce inflated energy costs. Proper ventilation control is very important to ensure the indoor air quality and an effective HAC system. DDC (direct digital control) controls system is widely used in variable air volume systems to meet ventilation for indoor air quality and human thermal comfort. The ventilation controls generally have a fixed damper control, a fixed flow rate control, and ventilation reset by ventilation analysis. The simplest fixed damper control method is easy to practice and used in many existing systems. However, the indoor air quality would not be met when the space convert from the full design condition to part- conditions. Except in extreme conditions, the HAC system will work in part-load conditions, there is under-ventilation for occupancy space, especially in critical areas. The second method, fixed outdoor flow rate, is used in the system to produce the acceptable indoor air quality. It is mostly practiced for multiple spaces with the common system, as proven in ventilation analysis (Table 1). The fixed outdoor air rate with ventilation analysis is a solution for the acceptable indoor air quality. The third strategy is the optimal option - ventilation reset. It is a complicated control procedure and requires complex programming, however, it saves a great deal of energy cost while not sacrificing the indoor air quality. entilation rates vary with operating and occupied conditions. The ventilation control system should vary the outdoor air rate. According to the analysis, the outdoor air rate is reset (see results in entilation Analysis with 1369

6 Proceedings: Indoor Air 005 Adjusted Critical Space by CO Concentration, Table 1). The ventilation-reset strategy is performed by a DDC control system. The indoor CO sensors monitor the CO concentration level in zones, then compare and choose the critical areas in order for the control system to respond. The outdoor airflow rate is calculated; the control system resets the outdoor damper, returns damper positions and fan operation to generate the required ventilation. During the operation, the outdoor airflow rate which is a dynamic procedure in the system, is reset by the ventilation requirement in zones. SUMMARY A ariable air volume system is often used in office buildings due to the energy savings. The acceptable indoor air quality through ventilation is achieved by the choice of the critical area. When the highest fraction of outdoor air in the supply is much higher than the other area, the solution is to lower the fraction to the acceptable average level. The strategy would have an advantage when the indoor air quality is at an acceptable level, as significant energy cost would be saved. The ventilation reset optimal control with carbon dioxide ( CO ) monitoring can ensure the superior air quality, substantial energy savings, and enhance occupant comfort. Compared with the fixed ventilation flow rate, excessive over-ventilation is avoided while still maintaining acceptable indoor air quality and providing the required outdoor airflow for individuals. REFERENCE: ASHRAE handbook, Fundamentals, 001. ASHRAE Standard 6-001, entilation for Acceptable Indoor Air Quality,

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY

INTERPRETATION IC OF ANSI/ASHRAE STANDARD VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY INTERPRETATION IC 62-2001-06 OF ANSI/ASHRAE STANDARD 62-2001 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY REVISION APPROVED: 1/12/2002 Originally issued as interpretation of Standard 62-1989 (IC 62-1989-23)

More information

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction

HAP e-help. Obtaining Consistent Results Using HAP and the ASHRAE 62MZ Ventilation Rate Procedure Spreadsheet. Introduction Introduction A key task in commercial building HVAC design is determining outdoor ventilation airflow rates. In most jurisdictions in the United States, ventilation airflow rates must comply with local

More information

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A

2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A 2005 CERTIFICATE OF ACCEPTANCE (Part 1 of 3) MECH-1-A PROJECT ADDRESS TESTING AUTHORITY TELEPHONE Checked by/date Enforcement Agency Use GENERAL INFORMATION OF BLDG. PERMIT PERMIT # BLDG. CONDITIONED FLOOR

More information

Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program

Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program 1 Outside Air Nonresidential HVAC Stakeholder Meeting #2 California Statewide Utility Codes and Standards Program Jim Meacham, CTG Energetics Agenda 2 In Situ Testing Results Reduced Ventilation after

More information

STUDENT SERVICES BUILDING HOWARD COMMUNITY COLLEGE COLUMBIA, MD TECHNICAL ASSIGNMENT #1 ASHRAE STANDARD VENTILATION COMPLIANCE EVALUATION

STUDENT SERVICES BUILDING HOWARD COMMUNITY COLLEGE COLUMBIA, MD TECHNICAL ASSIGNMENT #1 ASHRAE STANDARD VENTILATION COMPLIANCE EVALUATION STUDENT SERVICES BUILDING HOWARD COMMUNITY COLLEGE COLUMBIA, MD TECHNICAL ASSIGNMENT #1 ASHRAE STANDARD 62.1-2004 VENTILATION COMPLIANCE EVALUATION Jason P. Fair Mechanical Option October 5, 2005 Student

More information

Demand Control Ventilation Using CO 2

Demand Control Ventilation Using CO 2 ASHRAE Journal Ventilation Demand Control Ventilation Using By Mike Schell and Dan Int-Hout Member ASHRAE Member ASHRAE Carbon dioxide ( )-based demand controlled ventilation (DCV) is increasingly used

More information

acculink platinum zv zoning system

acculink platinum zv zoning system acculink platinum zv zoning system Components: AZONE950AC52ZA ZZONEPNLAC52ZA AZONE940 ZZONEEZPAC52ZB Platinum 950 Control Zone Panel Kit up to 4 zones Included: Discharge Air Temp sensor Static Pressure

More information

SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION

SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION SIMULATION OF STATIC PRESSURE RESET CONTROL IN COMFORT VENTILATION Chrysanthi Sofia Koulani 1, Remus Mihail Prunescu 2, Christian Anker Hviid 1, and Søren Terkildsen *1 1 Technical University of Denmark

More information

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012

PLEA th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú 7-9 November 2012 Natural Ventilation using Ventilation shafts Multiple Interconnected Openings in a Ventilation Shaft Reduce the Overall Height of the Shaft While Maintaining the Effectiveness of Natural Ventilation ABHAY

More information

Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation

Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Compliance Evaluation October 5, 2006 Table of Contents 1.0 Executive Summary... 2 2.0 Building Overview... 3 3.0 Analysis and Assumptions...

More information

Understanding Swimming Pool Ventilation. Presented by Tom Sands Mobile: CPD003/v03tcs2016

Understanding Swimming Pool Ventilation. Presented by Tom Sands Mobile: CPD003/v03tcs2016 Understanding Swimming Pool Ventilation Presented by Tom Sands Mobile: 07768 244555 Email: tom.sands@ves.co.uk CPD003/v03tcs2016 1 Learning Objectives At the end of the presentation you should have a broader

More information

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios

Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Sizing of extraction ventilation system and air leakage calculations for SR99 tunnel fire scenarios Yunlong (Jason) Liu, PhD, PE HNTB Corporation Sean Cassady, FPE HNTB Corporation Abstract Extraction

More information

HVAC Air Duct Leakage. Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA

HVAC Air Duct Leakage. Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA HVAC Air Duct Leakage Tech University 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA Learning Objectives Understand the difference between System leakage and Duct leakage Understand

More information

Adjustable Depth Air Sparging for

Adjustable Depth Air Sparging for em feature U.S. Naval Facilities Test Adjustable Depth Air Sparging for Groundwater Remediation Groundwater remediation at the Naval Weapons Industrial Reserve Plant, McGregor, TX. Photo by Erica Becvar,

More information

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS

COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS COMPARISON OF DIFFERENTIAL PRESSURE SENSING TECHNOLOGIES IN HOSPITAL ISOLATION ROOMS AND OTHER CRITICAL ENVIRONMENT APPLICATIONS APPLICATION NOTE LC-136 Introduction Specialized spaces often times must

More information

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage

Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage Experimental Characterization and Modeling of Helium Dispersion in a ¼-Scale Two-Car Residential Garage William M. Pitts, Jiann C. Yang, Kuldeep Prasad, and Marco Fernandez National Institute of Standards

More information

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL

SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL Supersedes: 100.50-CL1 (1014) Form 100.50-CL1 (517) MECHANICAL CONTRACTOR INSTALLATION CHECKLIST AND UNIT SETUP DATA SHEET CUSTOMER: ADDRESS: PHONE: SERIES 100 PACKAGED ROOFTOP UNIT WITH IPU CONTROL 035-21780-030

More information

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION

REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION REQUIREMENTS AND HAND-OVER DOCUMENTATION FOR ENERGY-OPTIMAL DEMAND-CONTROLLED VENTILATION Mads Mysen* 1, Axel Cablé 1, Peter G. Schild 1, and Kari Thunshelle 1 1 SINTEF Building and Infrastructure Forskningsveien

More information

UNIQUE CHARACTERISTICS OF THE PULMONARY CIRCULATION THE PULMONARY CIRCULATION MUST, AT ALL TIMES, ACCEPT THE ENTIRE CARDIAC OUTPUT

UNIQUE CHARACTERISTICS OF THE PULMONARY CIRCULATION THE PULMONARY CIRCULATION MUST, AT ALL TIMES, ACCEPT THE ENTIRE CARDIAC OUTPUT UNIQUE CHARACTERISTICS OF THE PULMONARY CIRCULATION THE PULMONARY CIRCULATION MUST, AT ALL TIMES, ACCEPT THE ENTIRE CARDIAC OUTPUT UNIQUE CHARACTERISTICS OF THE PULMONARY CIRCULATION THE PULMONARY CIRCULATION

More information

Question : What are some tips and recommendations and choices for roof venting?? Part One

Question : What are some tips and recommendations and choices for roof venting?? Part One Greenhouse - Q and A TIPS AND ADVICE Agroponic Industries Ltd. Calgary, Alberta, Canada ph 403 241 8234 email: agropon@agroponic.com Ask the Experts Question : What are some tips and recommendations and

More information

Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series

Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series Space Pressurization: Concept and Practice ASHRAE Distinguished Lecture Series Jim Coogan Siemens Building Technologies ASHRAE, St. Louis Chapter November10, 2014 Agenda Introduction (concept, purpose,

More information

TATTVAM ENVIRONMENTAL AND ENGINEERING SOLUTIONS, LLC. Indoor Air Quality Report for Weston Public Schools Weston, CT.

TATTVAM ENVIRONMENTAL AND ENGINEERING SOLUTIONS, LLC. Indoor Air Quality Report for Weston Public Schools Weston, CT. TATTVAM ENVIRONMENTAL AND ENGINEERING SOLUTIONS, LLC Indoor Air Quality Report for Weston Public Schools Weston, CT prepared for: Weston Public Schools 25 School Road Weston, CT November 17th, 2016 Tattvam

More information

Single- or Two-Stage Compression

Single- or Two-Stage Compression The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Improve Process Reliability

Improve Process Reliability Convenient Conductivity Calibration to Meet Pharmacopeia Regulations Pharmacopeias require that conductivity measurement systems be periodically calibrated to ensure their precision. The range of accessories

More information

How to Test Air Change Effectiveness

How to Test Air Change Effectiveness How to Test Air Change Effectiveness Presenter : Mark Jacobson Queensland Commissioning Manager 13 th June 2012 Presentation Agenda What is Air-Change Effectiveness (ACE)? Why is it important? Green Star

More information

ASHRAE WILL ILL GIVE Y OU THE W ORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique

More information

Hydronic Systems Balance

Hydronic Systems Balance Hydronic Systems Balance Balancing Is Misunderstood Balancing is application of fundamental hydronic system math Balance Adjustment of friction loss location Adjustment of pump to requirements By definition:

More information

Excellent Duct Systems Require Design, Not Guesswork!

Excellent Duct Systems Require Design, Not Guesswork! Design Advisory #2: CAS-DA2-2003 Excellent Duct Systems Require Design, Not Guesswork! Duct System Design Guide: Chapter 2 HVAC system performance is only as good as it s weakest link. Unfortunately, duct

More information

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS

CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS CROSS CONTAMINATION OF IN-SUITE MURB VENTILATION SYSTEMS Presented By: Sandra Dedesko University of Toronto Contributing Authors: Caleb Parker Kim Pressnail Marianne Touchie Dave DeRose Multi-Unit Residential

More information

Results of Field Measurements and CONTAM Simulation. Building Science

Results of Field Measurements and CONTAM Simulation. Building Science 28 Building Science Corporation Tracer Gas Testing January 26 Results of Field Measurements and CONTAM Simulation Aaron Townsend Building Science Tracer gas test of a production Building America house

More information

Kansas State University Fume Hood Operation

Kansas State University Fume Hood Operation FUME HOODS 2009, PAGE 1 FUME HOODS Kansas State University Fume Hood Operation One of the primary safety devices in a laboratory is a chemical fume hood. A well-designed hood, when properly installed and

More information

Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it

Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it Study by numerical simulations on the breathing effect in a semi-underground highway with beams and a roof above it M Hagiwara East Nippon Expressway Co., Ltd, Japan A Mizuno, T Tsutaki Kogakuin University,

More information

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS 3 rd International Conference on Energy Systems and Technologies 16 19 Feb. 2015, Cairo, Egypt ANALYSES OF THERMAL COMFORT AND INDOOR AIR QUALITY UNDER STRATUM, DISPLACEMENT, AND MIXING VENTILATION SYSTEMS

More information

The Advancement of Pressure Independent Technology

The Advancement of Pressure Independent Technology The Advancement of Pressure Independent Technology This session will look at the new pressure independent technology and its energy savings potential. Topics include: A brief review of the differences

More information

Bio-Effluents Tracing in Ventilated Aircraft Cabins

Bio-Effluents Tracing in Ventilated Aircraft Cabins Excerpt from the Proceedings of the COMSOL Conference 2009 Milan Bio-Effluents Tracing in Ventilated Aircraft Cabins Petrone G. *, Cammarata L., Cammarata G. Department of Industrial and Mechanical Engineering,

More information

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee ASHRAE WILL ILL G IVE Y OU THE W ORLD This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee Complete the Distinguished Lecturer Event Summary Critique

More information

Application Note AN-107

Application Note AN-107 SPEC Sensor TM Characterization & Calibration Considerations Scope This document is provided to describe the considerations needed to characterize, calibrate, verify and validate the measurement performance

More information

Engineering Note. Algorithms. Overview. Detailed Algorithm Description. NeoFox Calibration and Measurement. Products Affected: NeoFox

Engineering Note. Algorithms. Overview. Detailed Algorithm Description. NeoFox Calibration and Measurement. Products Affected: NeoFox Engineering Note Topic: NeoFox Calibration and Measurement Products Affected: NeoFox Date Issued: 04/18/2011 Algorithms Overview NeoFox is a dynamic measurement system that has been designed to work with

More information

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM

VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM VENTILATION EFFICIENCIES OF A DESK-EDGE-MOUNTED TASK VENTILATION SYSTEM D Faulkner *, WJ Fisk, DP Sullivan and SM Lee Indoor Environment Dept., Lawrence Berkeley National Lab, Berkeley, CA, USA ABSTRACT

More information

A FIELD STUDY OF THE AIR CHANGE EFFECTIVENESS OF OVERHEAD AIR DISTRIBUTION AND DISPLACEMENT VENTILATION IN HEALTHCARE

A FIELD STUDY OF THE AIR CHANGE EFFECTIVENESS OF OVERHEAD AIR DISTRIBUTION AND DISPLACEMENT VENTILATION IN HEALTHCARE FIELD STUDY OF THE IR CHNGE EFFECTIVENESS OF OVERHED IR DISTRIBUTION ND DISPLCEMENT VENTILTION IN HELTHCRE Julian Rimmer, P.Eng. Price Industries Senior Product Manager, Sustainable Technologies ssociate

More information

Series 3000 Layout Guidelines

Series 3000 Layout Guidelines Series 3000 Layout Guidelines Open circuit cooling towers, closed circuit cooling towers, and evaporative condensers all depend upon an adequate supply of fresh, ambient air to provide design capacity.

More information

DISTILLATION COLUMN PROCESS CONTROL STRATEGIES

DISTILLATION COLUMN PROCESS CONTROL STRATEGIES DISTILLATION COLUMN PROCESS CONTROL STRATEGIES Satyajit Deshmukh 1, Salil Rajwade 2, Atharva Pundalik 3, Anil Ranveer 4 ABSTRACT 1,2,3,4 Chemical Engineering Department, Datta Meghe College of Engineering,

More information

Increase in Evaporation Caused by Running Spa Jets swhim.com

Increase in Evaporation Caused by Running Spa Jets swhim.com Increase in Evaporation Caused by Running Spa Jets swhim.com Nomenclature A pipe cross-section area, m D water inlet diameter of the venturi tube nozzle, mm diameter of small end of the throat of the venturi

More information

A Research on the Airflow Efficiency Analysis according to the Variation of the Geometry Tolerance of the Sirocco Fan Cut-off for Air Purifier

A Research on the Airflow Efficiency Analysis according to the Variation of the Geometry Tolerance of the Sirocco Fan Cut-off for Air Purifier A Research on the Airflow Efficiency Analysis according to the Variation of the Geometry Tolerance of the Sirocco Fan Cut-off for Air Purifier Jeon-gi Lee*, Choul-jun Choi*, Nam-su Kwak*, Su-sang Park*

More information

White Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology:

White Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology: Title: Comparison of Chemical Sensor and NDIR Technologies TSN Number: 25 File:\\MII- SRV1\Metron\Bridge_Analyzers\Customer_Service_Documentation\White_Papers\25_G en EGA NDIR vs Chemical Sensor.docx Created

More information

Research on Small Wind Power System Based on H-type Vertical Wind Turbine Rong-Qiang GUAN a, Jing YU b

Research on Small Wind Power System Based on H-type Vertical Wind Turbine Rong-Qiang GUAN a, Jing YU b 06 International Conference on Mechanics Design, Manufacturing and Automation (MDM 06) ISBN: 978--60595-354-0 Research on Small Wind Power System Based on H-type Vertical Wind Turbine Rong-Qiang GUAN a,

More information

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1

Table of contents. I Drawings 33. A1 Design criteria 1 A1.1 Local thermal discomfort indices... 1 Table of contents A1 Design criteria 1 A1.1 Local thermal discomfort indices........................... 1 A2 Experiment set-up 3 A2.1 Equipment....................................... 3 A2.2 Test cases.......................................

More information

MEASURING AIR FLOW. Ventilation (Outside Air) Calculations. Derive % of OA as part of total air flow using air temperatures:

MEASURING AIR FLOW. Ventilation (Outside Air) Calculations. Derive % of OA as part of total air flow using air temperatures: MEASURING AIR FLOW 1 Ventilation (Outside Air) Calculations Derive % of OA as part of total air flow using air temperatures: % Outside Air (OSA) = [(Return Air T Mixed Air T) / (Return Air T Outside Air

More information

Examples of Carter Corrected DBDB-V Applied to Acoustic Propagation Modeling

Examples of Carter Corrected DBDB-V Applied to Acoustic Propagation Modeling Naval Research Laboratory Stennis Space Center, MS 39529-5004 NRL/MR/7182--08-9100 Examples of Carter Corrected DBDB-V Applied to Acoustic Propagation Modeling J. Paquin Fabre Acoustic Simulation, Measurements,

More information

Layout Guidelines. Overview

Layout Guidelines. Overview TECHNICA RESOURCES ayout Guidelines Included are the design layout guidelines for evaporative cooling products in several situations typically encountered by designers. These guidelines represent minimum

More information

6th Grade Quarter One Assessment Guide

6th Grade Quarter One Assessment Guide th Grade Quarter One Assessment Guide Essential Questions Corresponding Questions & Point Value Can you divide multi-digit numbers? pts Whole Numbers and Decimals Can you add, subtract, multiply and divide

More information

AIR CONDITIONERS WA14**W SERIES

AIR CONDITIONERS WA14**W SERIES FORM NO. A66-225 REV. 3 AIR CONDITIONERS Features Outdoor air conditioner designed for ground level or rooftop installations. These units offer comfort and dependability for single, multi-family and light

More information

LK-SX CO 2 +VOC. Application. Security Advice Caution. Notes on Disposal

LK-SX CO 2 +VOC. Application. Security Advice Caution. Notes on Disposal LK-SX CO 2 +VOC Sensor for detection of carbon dioxide (CO 2) and mixed gas content in air ducts Data sheet Subject to technical alteration Issue date: 24.08.2015 Application For detection of CO2 and VOC.

More information

Technical Bulletin 160. Maximum Air Pressure for Diffusers. by:

Technical Bulletin 160. Maximum Air Pressure for Diffusers. by: Technical Bulletin 160 Maximum Air Pressure for Diffusers by: Environmental Dynamics International Published: 11/2016 BULLETIN BRIEF In the design and application of diffuser systems, it is important to

More information

Kinetic-Molecular Theory

Kinetic-Molecular Theory GASES Chapter Eleven Kinetic-Molecular Theory! Recall that our only previous description of gases stated that gases completely fill and take the shape of their containers.! The Kinetic-Molecular Theory

More information

AIR CURTAIN CONTROL. Fig. 1: Options of installation and the principle of air curtain

AIR CURTAIN CONTROL. Fig. 1: Options of installation and the principle of air curtain Abstract AIR CURTAIN CONTROL Ing. Stanislav Števo, PhD., doc. Ing. Igor Hantuch, PhD., Bc. Pavol Tancík Institute of Control and Industrial Informatics Faculty of Electrical Engineering and Information

More information

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE

Practical Guide. By Steven T. Taylor, P.E., Member ASHRAE ractical Guide The following article was published in ASHRAE Journal, March 2003. Copyright 2003 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational

More information

sensors ISSN

sensors ISSN Sensors 2010, 10, 9799-9807; doi:10.3390/s101109799 OPEN ACCESS sensors SSN 1424-8220 www.mdpi.com/journal/sensors Communication A Dipping Duration Study for Optimization of Anodized-Aluum Pressure-Sensitive

More information

AIR CONDITIONERS WA14 SERIES

AIR CONDITIONERS WA14 SERIES FORM NO. A66-220 REV. 3 AIR CONDITIONERS Features Outdoor air conditioner designed for ground level or rooftop installations. These units offer comfort and dependability for single, multi-family and light

More information

=========================================================================== Section 1 PRODUCT AND COMPANY IDENTIFICATION

=========================================================================== Section 1 PRODUCT AND COMPANY IDENTIFICATION 5460 S 03 00 MATERIAL SAFETY DATA SHEET Section 1 PRODUCT AND COMPANY IDENTIFICATION PRODUCT NUMBER HMIS CODES Health 2 5460 S Flammability 0 Reactivity 0 PRODUCT NAME Athletic Field Marking Paint, HI

More information

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN

FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN FLOW CONSIDERATIONS IN INDUSTRIAL SILENCER DESIGN George Feng, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga, Ontario Vadim Akishin, Kinetics Noise Control, Inc., 3570 Nashua Drive, Mississauga,

More information

Testing the Vented, 7-Liter Induction Chamber. Report 6 April 2008

Testing the Vented, 7-Liter Induction Chamber. Report 6 April 2008 Report 6 April 2008 Page 1 of 11 Report 6 April 2008 The final review and approval of this document before its release to the client is the responsibility of the following person at Technical Safety Services.

More information

bespoke In general health and rehabilitation Breath-by-breath multi-functional respiratory gas analyser In human performance

bespoke In general health and rehabilitation Breath-by-breath multi-functional respiratory gas analyser In human performance Introduction Expired Gas Analysis or indirect calorimetry, can be used to measure ventilation and the fractions of oxygen and carbon dioxide in expired air. From these measurements, the body's oxygen consumption

More information

Gerald D. Anderson. Education Technical Specialist

Gerald D. Anderson. Education Technical Specialist Gerald D. Anderson Education Technical Specialist The factors which influence selection of equipment for a liquid level control loop interact significantly. Analyses of these factors and their interactions

More information

WP2 Fire test for toxicity of fire effluents

WP2 Fire test for toxicity of fire effluents Pagina 3 di 89 TRA SFEU VTT 22.6.2009 v.2 WP2 Fire test for toxicity of fire effluents Task 2.1.2 Development of small-scale test method for fire effluents Step 1: Use of modeling Plans according to DoW:

More information

Gas Accumulation Potential & Leak Detection when Converting to Gas

Gas Accumulation Potential & Leak Detection when Converting to Gas Gas Accumulation Potential & Leak Detection when Converting to Gas Coal to Gas / PCUG Conference Chattanooga, TN October 29, 2013 Robert G. Mudry, P.E. Airflow Sciences Corporation Introduction Coal to

More information

TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES

TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES TESTING OF BELIMO PRESSURE INDEPENDENT CHARACTERIZED CONTROL VALVES November, 25 Submitted by: Iowa Energy Center Address: DMACC, 26 S. Ankeny Blvd. Ankeny, IA 521 Phone: 515.965.755 Fax: 515.965.756 Web

More information

The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure

The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure The Use of a Process Simulator to Model Aeration Control Valve Position and System Pressure Matthew Gray 1 * and Steve Kestel 1 1 BioChem Technology, King of Prussia, PA *Email: mgray@biochemtech.com ABSTRACT

More information

Evaluation of Commercially Available Techniques and Development of Simplified Methods for Measuring Grille Airflows in HVAC Systems

Evaluation of Commercially Available Techniques and Development of Simplified Methods for Measuring Grille Airflows in HVAC Systems LBNL 51551 ERNEST ORLANDO LAWRENCE BERKELEY NATIONAL LABORATORY Evaluation of Commercially Available Techniques and Development of Simplified Methods for Measuring Grille Airflows in HVAC Systems I.S.

More information

Material Safety Data Sheet

Material Safety Data Sheet AllPurpose-RTV/WL Material Safety Data Sheet Document Code: AllPurpose-RTV/WL Date of Preparation Version: 08 March 19, 2008 Section 1 - Product and Company Identification PRODUCT NAME, NUMBERS, & COLORS

More information

Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment

Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment Improving Accuracy of Frequency Estimation of Major Vapor Cloud Explosions for Evaluating Control Room Location through Quantitative Risk Assessment Naser Badri 1, Farshad Nourai 2 and Davod Rashtchian

More information

METHOD 3C - DETERMINATION OF CARBON DIOXIDE, METHANE, NITROGEN, AND OXYGEN FROM STATIONARY SOURCES

METHOD 3C - DETERMINATION OF CARBON DIOXIDE, METHANE, NITROGEN, AND OXYGEN FROM STATIONARY SOURCES METHOD 3C - DETERMINATION OF CARBON DIOXIDE, METHANE, NITROGEN, AND OXYGEN FROM STATIONARY SOURCES 1. Applicability and Principle 1.1 Applicability. This method applies to the analysis of carbon dioxide

More information

March Madness Basketball Tournament

March Madness Basketball Tournament March Madness Basketball Tournament Math Project COMMON Core Aligned Decimals, Fractions, Percents, Probability, Rates, Algebra, Word Problems, and more! To Use: -Print out all the worksheets. -Introduce

More information

A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors

A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 A Chiller Control Algorithm for Multiple Variablespeed Centrifugal Compressors Piero

More information

Review of oxygen deficiency requirements for graham s ratio

Review of oxygen deficiency requirements for graham s ratio University of Wollongong Research Online Coal Operators' Conference Faculty of Engineering and Information Sciences 2017 Review of oxygen deficiency requirements for graham s ratio Sean Muller Simtars,

More information

Exposure Bands. Relationship to the OEL (95. Rating

Exposure Bands. Relationship to the OEL (95. Rating Rules of Thumb 1 Exposure Unit The exposure assessment process is performed independently on each physical hazard, chemical or chemical mixture in the SEG. Each chemical - SEG combination is referred to

More information

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs.

Laboratory Hardware. Custom Gas Chromatography Solutions WASSON - ECE INSTRUMENTATION. Custom solutions for your analytical needs. Laboratory Hardware Custom Gas Chromatography Solutions Custom solutions for your analytical needs. Laboratory Hardware Wasson-ECE Instrumentation offers hardware-only solutions for advanced chromatography

More information

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis

A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis 1131, Page 1 A Numerical Simulation of Fluid-Structure Interaction for Refrigerator Compressors Suction and Exhaust System Performance Analysis Shoufei Wu*, Zonghuai Wang Jiaxipera Compressor Co., Ltd.,

More information

RESPIRATOR PERFORMANCE TERMINOLOGY

RESPIRATOR PERFORMANCE TERMINOLOGY RESPIRATOR PERFORMANCE TERMINOLOGY The following terms were developed by the American Industrial Hygiene Association Respiratory Protection Committee to represent respirator performance in various contexts.

More information

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR

AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR - 9 - AN INVESTIGATION OF LONGITUDINAL VENTILATION FOR SHORT ROAD TUNNELS WITH HIGH FIRE HRR O Gorman S., Nuttall R., Purchase A. Parsons Brinckerhoff, Australia ABSTRACT Recent fire tests for tunnels

More information

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve

The Shand & Jurs Model Vapor Guard Tank Blanketing Valve Lower maintenance due to fewer parts Occupies less space, less stress to tank Teflon is inert to most chemicals; extends service life Simplifies and lowers maintenance cost Optimizes flow of blanketing

More information

Unit 3.3 Personal Protective Equipment (Core)

Unit 3.3 Personal Protective Equipment (Core) INSTRUCTOR GUIDE Unit 3.3 Personal Protective Equipment (Core) INSTRUCTOR GUIDE TERMINAL OBJECTIVE Given incident scenarios, the participant will be able to identify the basic PPE requirements for operations

More information

CORESTA RECOMMENDED METHOD N 6

CORESTA RECOMMENDED METHOD N 6 CORESTA RECOMMENDED METHOD N 6 DETERMINATION OF VENTILATION DEFINITIONS AND MEASUREMENT PRINCIPLES (2015 Revision September 2016) 1. SCOPE This CORESTA Recommended Method specifies a method for the determination

More information

SAMPLE RH = P 1. where. P 1 = the partial pressure of the water vapor at the dew point temperature of the mixture of dry air and water vapor

SAMPLE RH = P 1. where. P 1 = the partial pressure of the water vapor at the dew point temperature of the mixture of dry air and water vapor moisture starts to condense out of the air. The temperature at which this happens is called the dew point temperature, or the saturation temperature. What is commonly called saturation pressure or condensing

More information

Air Intake Placement and Design and Fresh Air to Improve Air Quality Donald Cyrus Baker & Randy Baxter

Air Intake Placement and Design and Fresh Air to Improve Air Quality Donald Cyrus Baker & Randy Baxter Air Intake Placement and Design and Fresh Air to Improve Air Quality Donald Cyrus Baker & Randy Baxter Don Baker, BS in Building Construction, University of Florida. He is currently CEO of Paddock Pool

More information

Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory

Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory Technology issues regarding Blends of Refrigerants Buffalo Research Laboratory Agenda Basic Characteristics Background Degree of Superheat, degree of subcooling, average coil temperature Handling and setting

More information

Alain PERSON, Anne-Marie LAURENT, Yvon LE MOULLEC Laboratoire d Hygiène de la Ville de Paris

Alain PERSON, Anne-Marie LAURENT, Yvon LE MOULLEC Laboratoire d Hygiène de la Ville de Paris ATMOSPHERIC EXPOSURE TO CHLORAMINES IN INDOOR SWIMMING POOLS Alain PERSON, Anne-Marie LAURENT, Yvon LE MOULLEC Laboratoire d Hygiène de la Ville de Paris yvon.lemoullec@mairie-paris.fr INTRODUCTION Swimming

More information

PLANT OPERATIONS AND TECHNOLOGY I & II: REAL TIME FURNACE AIR IN- LEAKAGE MONITORING ON COAL, OIL AND/OR GAS FIRED BOILERS

PLANT OPERATIONS AND TECHNOLOGY I & II: REAL TIME FURNACE AIR IN- LEAKAGE MONITORING ON COAL, OIL AND/OR GAS FIRED BOILERS Electric Power Conference 2010 May 19th, 2010, Baltimore, MD PLANT OPERATIONS AND TECHNOLOGY I & II: REAL TIME FURNACE AIR IN- LEAKAGE MONITORING ON COAL, OIL AND/OR GAS FIRED BOILERS Stephen Hall Senior

More information

A Conceptual Understanding of Leakage During Soil-Gas Sampling

A Conceptual Understanding of Leakage During Soil-Gas Sampling A Conceptual Understanding of Leakage During Soil-Gas Sampling Dominic C. DiGiulio, Ph.D. U.S. Environmental Protection Agency Office of Research and Development National Risk Management Research Laboratory

More information

March Madness Basketball Tournament

March Madness Basketball Tournament March Madness Basketball Tournament Math Project COMMON Core Aligned Decimals, Fractions, Percents, Probability, Rates, Algebra, Word Problems, and more! To Use: -Print out all the worksheets. -Introduce

More information

Standard Operating Procedure for H 2 S and SO 2 Converter

Standard Operating Procedure for H 2 S and SO 2 Converter Procedure No: SOP-001 Revision No: 1.0 January 24, 2011 Page No.: 1 of 6 1. INTRODUCTION AND SCOPE This procedure describes the operation and configuration of heated converters used in continuous ambient

More information

Sizing Enclosures for SCR Power Controllers

Sizing Enclosures for SCR Power Controllers INTRODUCTION Application Note 1002 Sizing Enclosures for SCR Power Controllers Author - George A. Sites, AMETEK HDR Power Systems Most applications for SCR Power Controllers require some type of enclosure.

More information

NOVEL BED INTEGRATED VENTILATION METHOD FOR HOSPITAL PATIENT ROOMS. Technical University of Denmark, Kgs. Lyngby, Denmark. Poland.

NOVEL BED INTEGRATED VENTILATION METHOD FOR HOSPITAL PATIENT ROOMS. Technical University of Denmark, Kgs. Lyngby, Denmark. Poland. In Proceedings of ROOMVENT 2014, October 19-22, Sao Paolo, Brazil, pages 49-56. NOVEL BED INTEGRATED VENTILATION METHOD FOR HOSPITAL PATIENT ROOMS Mariya P. Bivolarova 1, Arsen K. Melikov 1, Monika Kokora

More information

Part IV: Troubleshooting

Part IV: Troubleshooting Part IV: Troubleshooting Excessive Oil Carryover Pump-Up Time Test Excessive oil carryover can have adverse effects on the performance of pneumatic climate control systems. Although some oil entrainment

More information

Chapter 10 Gases. Characteristics of Gases. Pressure. The Gas Laws. The Ideal-Gas Equation. Applications of the Ideal-Gas Equation

Chapter 10 Gases. Characteristics of Gases. Pressure. The Gas Laws. The Ideal-Gas Equation. Applications of the Ideal-Gas Equation Characteristics of Gases Chapter 10 Gases Pressure The Gas Laws The Ideal-Gas Equation Applications of the Ideal-Gas Equation Gas mixtures and partial pressures Kinetic-Molecular Theory Real Gases: Deviations

More information

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels Inerting Control Systems by NTRON PROCESS ANALYZER DIVISION of NEUTRONICS INC. EXTON. PA. 19341 RJN Rev. A June 2001 Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert

More information

Aerodynamic Analysis of a Symmetric Aerofoil

Aerodynamic Analysis of a Symmetric Aerofoil 214 IJEDR Volume 2, Issue 4 ISSN: 2321-9939 Aerodynamic Analysis of a Symmetric Aerofoil Narayan U Rathod Department of Mechanical Engineering, BMS college of Engineering, Bangalore, India Abstract - The

More information

Process Dynamics, Operations, and Control Lecture Notes - 20

Process Dynamics, Operations, and Control Lecture Notes - 20 Lesson 0. Control valves 0.0 Context Controller output is a signal that varies between 0 and 100%. Putting this signal to use requires a final control element, a device that responds to the controller

More information

100 mg/m3 CEILI (aerosol) 0.12 mm. 10 mg/m3 Total Dust 5 mg/m3 Respirable Fraction

100 mg/m3 CEILI (aerosol) 0.12 mm. 10 mg/m3 Total Dust 5 mg/m3 Respirable Fraction 03-948 02 00 MATERIAL SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION PRODUCT NUMBER DATE OF PREPARATION HMIS CODES Health 2* 03-948 29-SEP-07 Flammability 0 Reactivity 0 PRODUCT NAME

More information

MATERIAL SAFETY DATA SHEET WL

MATERIAL SAFETY DATA SHEET WL WL0009056 03 00 MATERIAL SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION PRODUCT NUMBER HMIS CODES Health 2 WL0009056 Flammability 0 Reactivity 0 PRODUCT NAME WHITE LIGHTNING Siding Pro,

More information