SYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA

Similar documents
SYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA

BUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA

SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND

SIDEWINDER DRILLING RIG 122 CLEBURNE COUNTY, ARKANSAS

SYSCO FOODS BAHAMAS FOOD SERVICE NASSAU, BAHAMAS

PAVESTONE COMPANY CST PAVERS PEDRICKTOWN, NEW JERSEY

SYSCO BUCKHEAD BEEF COLLEGE PARK, GEORGIA

Infrared Thermography Inspection Guidelines. Date Issued:

You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services

ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,

Monitoring transformers with infrared cameras

Electrical Safety PPT-SM-ELECTSFTY V.A.0.0

Pixel Thermographics Ltd. Compressed Air Leak Detection Survey SAMPLE REPORT. Pixel Thermographics Ltd

Selection of Electrical PPE Tables

It is essential that the maintenance staff is qualified for electrical works and follows safety procedures.

DuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)

ELECTRIC OPERATING PROCEDURES Date: 11/01/06

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

MISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6

R E D I C O N T R O L S

THE OSHA LOCK-OUT/TAG-OUT STANDARD

Preparer: Owner: Approver: EHS Team Member TES Manager Site Manager

SEMEMI SQA Unit Code H2AP 04 Carrying out fault location on electrical equipment and circuits

Leader s Guide ERI Safety Videos

Inspection Recommendations

Gas Network Craftsperson

Ground Fault Circuit Interrupter(GFCI) Policy

Major Changes. Standard. TECH TOPIC standards and. By Peter Walsh, PE

AE R1 February 2015

120 PSI FAST-FILL AIR SOURCE KIT 25% Duty Compressor on 1.5 Gallon Air Tank

USER MANUAL. JET TST and JET TST S.

Innovative Techniques for Mitigating Arc Flash Exposure

Pool Inspection. Your Street San Diego, California Prepared for: Your Name Prepared by: Priority Inspection Service

Nitrogen Supply System

Leader s Guide ERI Safety Videos

University of Vermont Department of Physical Plant Burlington, Vermont

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

CONTROL OF HAZARDOUS ENERGY IN THE WORKPLACE

Operating Instructions

Electrical. Version 1.0

Risk Assessment Procedure

Effective March 2015 Supersedes S August 2002

Preview to the 2018 NFPA 70E, the Standard for Electrical Safety in the Workplace

SIX R (P ) AND SEVEN R (P ) POSITION CYLINDERS Service Information

NIOSH Task Number 18388

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

Mini Pod Press. #78H-M2 Mini Pod Press Manual-R1

Sterile Visual Flow Indicator

! Warning, refer to accompanying documents.

Operating Manual. Models AQT-02 & AQT-COO2 Manual No. MON004 (Rev 2 April 2000)

Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs.

AWG Fittings LLC. Pressure Relief Valve Up to 250 PSI. Product Number Read this instruction manual before use.

Installation and Maintenance Instructions for F5509/F6509 Differential Pressure Gauges

Lockout/Tagout Training Overview. Safety Fest 2013

COOPER POWER SERIES. D-73P3 bypass switches installation instructions. Switches MN008005EN. Effective April 2016 Supersedes S June 2013

Protection of motor circuits

WATER HEATER THERMAL EXPANSION TANKS Owner s Manual. Safety Instructions Installation Maintenance Warranty. Models: 2-5 Gallon Capacity

Low GWP R-404A Alternatives for Commercial Refrigeration. Barbara H. Minor Dr. Frank Rinne DuPont Fluorochemicals

PSSI 1 High Voltage Switching

COOPER POWER SERIES. Under-oil arrester disconnector installation/operation instructions. OEM Equipment MN800010EN

U.S. Army Corps of Engineers Poe s Ridge Permit Hunting Area Public Hunting Guide

Guidelines to the standard IEC60601

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

LOCKOUT/TAGOUT PROGRAM

NGP-250/500 Nitrogen Generator Quick Start Guide

COOPER POWER SERIES. 200 A 15, 25, and 35 kv class portable feedthru installation instructions. Loadbreak Apparatus Connectors MN650037EN

Instrument Operating Manual

Air Tractor Preventative Maintenance Manual And Troubleshooting

ELECTRICAL SAFETY. Unsafe work practices near electricity can kill you! You are responsible for protecting yourself from electrical shock.

INSTALLATION MANUAL Matheson Tri-Gas Cabinet Enclosures

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

Installation Instructions for the Walking Beam Interlock for Eaton EHD, FDB, FD, HFD, FDC, FW, HFW, FWC, Circuit Breakers and Molded Case Switches

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

RULE 1. Facilities and Equipment

Veriforce TG CCT 609OP. Training Guide

City of Crystal Lake Community Development Department

Appendix A: Energized Work Permit

Reliability engineering is the study of the causes, distribution and prediction of failure.

Lockout/Tagout Plan Environmental Health & Safety Office July 2017

Lockout/Tagout - Control of Hazardous Energy Program

USER S MANUAL BASIC HORIZONTAL OIL-LUBRICATED MICROCOMPRESSOR Reference: RCMPBH

JORDAIR/BAUER Service Manual

PRAHER PLC-MP AQUASTAR MANAUL 2009

BOTTOM HINGED FLOOD BARRIER

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

SECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual

RevolveAir / Guardian Breathing Air Cylinder Fill Station Operating Instructions

COOPER POWER SERIES. 200 A 15, 25, and 35 KV class insulated standoff bushing installation instructions. Loadbreak Apparatus Connectors MN650039EN

Electrical Safety Program

Lockout Tagout Policy

Service Parts Manual Drawer Microwave Models: MWD24-2 & MWD30-2

42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)

2017 NWHA TECHNICAL SEMINAR. Arc Flash Hazard Awareness MIKE BRENDLE LLC

EXECUTIVE SHIP MANAGEMENT PTE LTD M 24 Q 4 SINGAPORE QI 19 Page 1 of 5 (9/05 Rev 2) Decision. Implement

LOCKOUT SYSTEM AND POLICIES

Safe Schools: A Health and Safety Check

USER MANUAL ELECTRIC BLOWBACK SYSTEM

Maintenance handbook

MODEL 154XST INSTALLATION AND SERVICE INSTRUCTIONS FOR MODEL 154XST STROBE LIGHT FOR USE IN HARSH ENVIRONMENTS/ HAZARDOUS LOCATIONS

Progressive Safety Services LLC - All Rights Reserved

Transcription:

SYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA November, 2016 Infrared Inspection Report Sysco Allard 199 2e Avenue Ville de Quebec, QC, G1L 3A5 Company Contact Louis Grenier Project: C041116 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL: Logistics@usscanman.com

ORDER OF REPORT CONTENTS 1: Data To Facilitate Understanding & Utilizing Scan Report 2: Scan Results Overview & Action Taken Form 3: Identified Faulting Conditions, Information & Photographs 4: List Of Facility Equipment Identified By The Customer Representative & Notations Of Faulting Conditions Found DISCLAIMER This report and the recommendations contained in it are based upon conditions and practices observed and information made available to United Spectrographics personnel. This report does not purport to list all hazards or faulty conditions. It is not intended to indicate that other hazards or faulty conditions do not exist. Severity ratings in the report are based on the criteria shown in this report and are intended as guidelines only. No responsibility is assumed for the control of the facility s condition, maintenance practices or correction of conditions indicated herein. By issuing this report, neither United Spectrographics nor any of its employees makes any warranty, expressed or implied, concerning the contents of this report. Furthermore, neither United Spectrographics nor any of its employees shall be liable in any manner (other than liability that may be expressed in any policy of insurance that may be issued by United Spectrographics) for personal injury or property damage or loss of any kind arising from or connected with this inspection or failure to inspect.

November 4, 2016 Sysco Allard, Inc Attn: Louis Grenier 199 2e Avenue1 Ville de Quebec, QC Canada Dear Mr. Grenier; During the course of our November 2016 Infrared Inspection of your facility s electrical equipment, no equipment indicating a faulty thermal signature was located at the Sysco Allard, Inc Quebec City, QC facility. Locating no faults is an unusual occurrence for us; we generally encounter only a small percentage of facilities a year with no faults. Your maintenance people appear to be doing an outstanding job. We greatly appreciated the opportunity to complete this project for you and look forward to the next one. If you have any questions concerning this infrared inspection, please call 1-800-737-1787. Sincerely, S Richard P. Lincourt United Spectrographics, LLC. 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227 PHONE: 800-737-1787 & 501-228-5001 FAX: 501-228-5001 EMAIL: Logistics@usscanman.com

Utilizing Report Contents Included in this report are Photographs and Thermographs of problem areas found during our recent Infrared Inspection of your facility. Each problem area picture is accompanied by: Date Location Information Temperature Calculations Color-coded Temperature Intensity and/or Condition Significance Data A Brief Comment Relating The Item In The Photograph To Its Corresponding Thermograph Suggested Corrective Recommendations. In most cases, problems (faults) found will be listed according to the date and order that they were located, rather then by significance or priority, as we feel that you and/or your personnel can best judge this, keeping in mind circuit importance and thermograph intensity. Thermal intensity is indicated by use of a color-coded data inserts that locate a fault s position on the standard electrical failure curve. The color of the insert represents the temperature range of the hottest item, or a portion of the item's circuitry, pointed out in the thermograph. The temperature ranges which the colored inserts represent are grouped as follows: INSERT Red Orange Yellow Green Temperature Range 70ºC/126ºF and higher above Ambient Operating Temp. 40ºC/72ºF to 69ºC/124ºF above Ambient Operating Temp. 25ºC/45ºF to 39ºC/70ºF above Ambient Operating Temp. *10ºC/18ºF to 24ºC/43ºF above Ambient Operating Temp. ( * See page 4)

Determining Cost Effective Responses Electrical equipment failures generally follow a standard mechanical/electrical failure curve. Dividing the failure curve into temp. ranges and locating a problems position on the curve allows us to indicate the probable time to its failure. Knowing a problems probable time to failure allows you to make a cost effective response to the problem areas that we locate. Below is a depiction of the electrical fault failure curve with the thermal intensity ranges and the colors that we assign to faults detailed in our reports. STANDARD ELECTRICAL FAULT FAILURE CURVE (Does Not Include Area In Blue) MINOR INTERMEDIATE SERIOUS CRITICAL DEVICE TEMP IS AMBIENT, BUT DEVICE IS EITHER FAULTY OR UNSAFE. 10ºC * 18ºF 25ºC 45ºF 40 C 72ºF 70 C 126ºF AMBIENT TEMP YEARS MONTHS MONTHS TO WEEKS WEEKS TO NOW FAULTY EQUIP Built In Trend Monitoring When yearly scans are accomplished, report results allow you to trend monitor your electrical equipment without having to cross reference previous report findings. If a previous years problem is not repaired it will show up again in the current scan report and its current intensity range indicates a current effective response.

Defining Total Temperature and Ambient Operating Temperature And Explanation For Their Use Total Temperature: Total Temperature = Ambient Operating Temperature + Fault temperature Allows you, the customer, to evaluate possible damage to equipment. Leads fail between 90ºC/194ºF and 110ºC/230º Phenolic fails around 200ºC/392ºF Transformers and Motor Insulation failure temperature depends on insulation class rating. Contacts start to fail around 130ºC/266ºF Ambient Operating Temperature (AOT*) for Infrared Scanning Purposes: Temperature within a device container (Box or Cabinet) that is not directly affected by faulting component = Normal Equipment Operating Temperature Contained By Box or Cabinet. If there is no container (Example: Device mounted to a wall) it is the temperature adjacent to the device not affected by the fault. Allows you, the customer, to determine if device will operate at intended amperage. Most switchgear is rated to operate at approximately 40ºC/104ºF (Industrial) to 50ºC/122ºF (Marine) If AOT is enough above normal rated temperature, either of the following conditions can cause an unanticipated trip. 1. An intermittent high load. 2. A minor (Green) or intermediate (Yellow) fault. Report pages with photographs: PH stands for Visible Light Photograph TH stands for Infrared Light Thermograph *AOT stands for Ambient Operating Temperature Both black & white and color infrared thermographs are presented to better depict the fault condition.

In addition to the corrective response time frame suggested below and the failure curve located on the previous page, you may want to consider using the military standard responses presented below. Military Standard For Evaluating Faults Located In Electrical Equipment Utilizing Temperature Data Obtained With Infrared Imaging Equipment: Temperatures rise above Ambient Operating Temperature: *10ºC/18ºF to 24ºC/43ºF component failure unlikely, but corrective measures required at next scheduled routine maintenance period or as scheduling permits. (Green Label) 25ºC/45ºF to 39ºC/70ºF component failure probable, unless corrected. (Yellow Label) 40ºC/72ºF to 69ºC/124ºF component failure almost certain, unless corrected. (Orange Label) 70ºC/126ºF and above component failure imminent. Immediately inform the person responsible for continued operation of equipment. (Red Label) Note: United Spectrographics uses a Blue Label to indicate faults that require attention due to either ambient temperature (Ex: Phase Not Operating), faulty equipment elements or unsafe conditions. * Note: Temperature conditions below 10ºC/18ºF rise above AOT are not considered significant enough to record and are usually not included in the reports unless the fault temperature is being affected by a cooling medium such as oil or wind. Fault Correction Recommendation When Our Source Assessment Is Inaccurate: When a fault is indicated in a connection or component and examination by your electrician does not turn up a loose connection or faulty component where we have indicated, a fault does exist. The electrician should continue to investigate the next connection or component to be found in the direction that the heat is coming from until a source is located. Example: If a molded case breaker line side lead connection lug is indicated as a fault source and is found to be secure, but not frozen in place, look for a loose connection or sign of over temp. in the lead holder lug.

SCAN RESULTS OVERVIEW PROMPT ATTENTION ITEMS: Because of: 1. The intensity or heat level indicated at the time of the scan. 2. Deterioration caused by excessive temperature not present at the time of the scan. 3. Physical condition irregularities observed at the time of the scan. We recommend that the following faults be given prompt attention: Faults: No Faults Found Items With Asterisks Have High Total or Ambient Operating Temperatures. United Spectrographics November, 2016

SUMMARY OF FINDINGS FAULTS BY CATEGORY NUMBER OF FAULTS FAULT NO./ITEM NO. MINOR 0 0 INTERMEDIATE 0 0 SERIOUS 0 0 CRITICAL 0 0 SERIOUS 0 0 Number of items located at facility: 32 Number of faults: 0

ACTION TAKEN Sysco Allard, Inc Quebec City, QC November, 2016 None Required

AREA/EQUIPMENT LIST Following is a list of the electrical equipment located at the Sysco Allard, Quebec City, QC, Canada facility and data relating to its operating condition at the time the scan was performed. NOTE: Items noted as visually inspected were not operational or show no visible load at the time of the inspection. No. Equipment Operating Visually Inspected EQUIPMENT LIST Fault # MAINTENANCE SHOP 1 Breaker Panel, Panneau 4 (Panel 4) X RECEIVING AREA 2 Breaker Panel, Panneau 8 (Panel 8) X OFFICE 3 Breaker Panel, 1962 X MAIN ELECTRICAL ROOM 4 Fused Disconnect Panel, Main Switch, 600A X 5 Breaker Panel, I A X 6 Splitter Panel, 6 X 7 Breaker Panel, II X 8 Panel, III, (Unable to Open) X 9 Breaker Panel, I X 10 Fused Disconnect, 5 (Single Phase) X 11 Fused Disconnect, 4 (Single Phase) X 12 Splitter Panel, D X 13 Transformer, A (On Floor) X 14 Transformer, B (On Floor) X 15 Transformer, C (On Floor) X LUNCH ROOM (SECOND FLOOR) 16 Breaker Panel, Lunch Room X

No. Equipment Operating Visually Inspected COMPRESSOR ROOM Fault # 17 Starter Panel, B X 18 Control Panel, Compressor, AB200, A X 19 Fused Disconnect, # 10 X 20 Splitter Panel, 3 X 21 Fused Disconnect, 1 X 22 Fused Disconnect, 2 X 23 Fused Switch, CH 5 X 24 Fused Switch, CH 2 A X 25 Fused Disconnect, 4 X STAIRWAY - SHIPPING AREA 26 Breaker Cabinet, C.D.P. X 27 Breaker Panel, A X 28 Breaker Panel, B X GARAGE 30 Control Panel, Freezer Z Compressor X 31 Fused Disconnect, 1 X 32 Fused Disconnect, 2 X