SAMPLE TRANSFORMER/RECTIFIER FLEET CONDITION ASSESSMENT. for. NWL Transformers. January 4, Written by:

Size: px
Start display at page:

Download "SAMPLE TRANSFORMER/RECTIFIER FLEET CONDITION ASSESSMENT. for. NWL Transformers. January 4, Written by:"

Transcription

1 TRNSORMR/RTIIR LT ONITION SSSSMNT for NWL Transformers January 4, 2010 Written by: Norman ield Senior ngineer Weidmann iagnostic Solutions

2 XUTIV SUMMRY Transformer/Rectifier leet ondition ssessment was performed for a fleet of 64 lectrostatic Precipitator (SP) Transformer/Rectifiers (T/Rs), operated by Progress nergy at the Roxboro Power Plant in Roxboro, N. This project evaluated the selected fleet of transformer/rectifiers in terms of their condition as interpreted from studying their insulating oil test results. ll 64 T/Rs belonged to Unit 4 SPs at the Roxboro Plant. Specifically, there are eight SPs (namely 41, 42, 43,,,,, and ) each being supplied power from eight T/Rs (designated through ), totalling sixty-four T/Rs. The transformer/rectifier condition assessment included a review of dissolved gas-in-oil analyses and general oil quality tests, from two points in time. One set of test results were from oil samples taken on 11/6/2009 and tested by the Weidmann iagnostic Solutions lab in ensalem, P. second set of test results were from 9/13/2007 and tested by the Progress nergy oil lab at the Roxboro Plant. Using this information, an lectrostatic Precipitator Transformer/Rectifier Oil nalysis and iagnostic valuation report was created for each T/R (copies provided herein). ach report provided diagnostic statements regarding the condition of the T/R, and summarized this condition by producing a condition code of either Normal, aution, or Warning. summary of the condition codes for each T/R, sorted by severity, is provided herein. It is important to note that the iagnostic valuation of each T/R took into account not only the results of the most recent oil tests for the samples taken on 11/6/2009, but also the results of the older oil tests for the samples taken on 9/13/2007. This was accomplished by using the dissolved gas-in-oil analysis results from both dates to calculate a rate of change (in parts-per-million per month) for each of the combustible gasses. While knowing the actual gas concentrations in the oil at a given point in time is informative, it is the rate of change of these gas concentrations over time that allow interpretation to be made as to whether there is an active problem inside the T/R or not. Weidmann iagnostic Solutions Page 1

3 SUMMRY O RSULTS The following pages of this section show two tables. The first is a listing of all 64 T/Rs sorted by their designation code (for example, 41 ) and shows the corresponding ondition ode and comments about the condition. The second table is the same list but sorted by ondition ode and then by severity of gassing, for ease of identification of the T/Rs with poorest condition. Weidmann iagnostic Solutions Page 2

4 Table 1: T/Rs sorted by esignation ode T/R ondition ode omments 41 Normal Resample oil in 6 months. 41 aution Resample oil in 3 months. igh gas concentration. 41 aution Resample oil in 3 months. igh gas concentration. 41 Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. 41 Warning onsider internal inspection. Resample oil in 1 month. Very high gas concentration. bnormal gas increase. 41 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 aution Resample oil in 3 months. Very high gas concentration. 42 aution Resample oil in 3 months. igh gas concentration. 42 aution Resample oil in 3 months. igh gas concentration. 43 Normal Resample oil in 6 months. 43 aution Resample oil in 3 months. Very high gas concentration. 43 aution Resample oil in 3 months. igh gas concentration. ielectric breakdown strength low. 43 aution Resample oil in 3 months. igh gas concentration. 43 aution Resample oil in 3 months. Moisture very excessive. ielectric breakdown strength very low. 43 aution Resample oil in 3 months. Very high gas concentration. Moisture excessive. 43 Normal Resample oil in 6 months. 43 Warning onsider internal inspection. Resample oil in 1 month. Very high gas concentration. bnormal gas increase. Moisture very excessive. Interfacial tension low. ielectric breakdown strength low. cid high. aution Resample oil in 3 months. igh gas concentration. Normal Resample oil in 6 months. Weidmann iagnostic Solutions Page 3

5 T/R ondition ode omments aution Resample oil in 3 months. Moisture very excessive. ielectric breakdown strength low. Normal Resample oil in 6 months. Normal Resample oil in 6 months. aution Resample oil in 3 months. Moisture very excessive. Normal Resample oil in 6 months. aution Resample oil in 3 months. Moisture very excessive. Interfacial tension low. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. aution Resample oil in 3 months. Interfacial tension very low. Warning onsider internal inspection. Resample oil in 1 month. Very high gas concentration. igh gas increase. Normal Resample oil in 6 months. aution Resample oil in 3 months. igh gas concentration. Normal Resample oil in 6 months. Normal Resample oil in 6 months. aution Resample oil in 3 months. igh gas concentration. Normal Resample oil in 6 months. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. Very high gas concentration. aution Resample oil in 3 months. igh gas concentration. Normal Resample oil in 6 months. Normal Resample oil in 6 months. aution Resample oil in 3 months. igh gas concentration. Warning onsider internal inspection. Resample oil in 1 month. Very high gas concentration. bnormal gas increase. Strong indication of overheating. autiion Resample oil in 3 months. igh gas concentration. Moisture very excessive. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. Normal Resample oil in 6 months. aution Resample oil in 3 months. igh gas concentration. Weidmann iagnostic Solutions Page 4

6 T/R ondition ode omments Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. aution Resample oil in 3 months. Very high gas concentration. aution Resample oil in 3 months. igh gas concentration. Moisture excessive. aution Resample oil in 3 months. Moisture very excessive. ielectric breakdwon strength low. aution Resample oil in 3 months. igh gas concentration. Moisture very excessive. ielectric breakdown strength low. Weidmann iagnostic Solutions Page 5

7 Table 2: T/Rs sorted by ondition ode and Severity of assing T/R ondition ode omments Warning onsider internal inspection. Resample oil in 1 month. Possible internal arcing activity. Very high gas concentration. igh gas increase. 43 Warning onsider internal inspection. Resample oil in 1 month. Possible arcing activity. Very high gas concentration. bnormal gas increase. Moisture very excessive. Interfacial tension low. ielectric breakdown strength low. cid high. 41 Warning onsider internal inspection. Resample oil in 1 month. Possible arcing activity. Very high gas concentration. bnormal gas increase. Warning onsider internal inspection. Resample oil in 1 month. Very high gas concentration. bnormal gas increase. Strong indication of overheating. aution Resample oil in 3 months. Very high gas concentration. 43 aution Resample oil in 3 months. Very high gas concentration. Moisture excessive. 43 aution Resample oil in 3 months. Very high gas concentration. 42 aution Resample oil in 3 months. Very high gas concentration. aution Resample oil in 3 months. Very high gas concentration. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. 43 aution Resample oil in 3 months. igh gas concentration. ielectric breakdown strength low. 43 aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. Weidmann iagnostic Solutions Page 6

8 T/R ondition ode omments aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. Moisture very excessive. ielectric breakdown strength low. 42 aution Resample oil in 3 months. igh gas concentration. 41 aution Resample oil in 3 months. igh gas concentration. autiion Resample oil in 3 months. igh gas concentration. Moisture very excessive. aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. 41 aution Resample oil in 3 months. igh gas concentration. aution Resample oil in 3 months. igh gas concentration. Moisture excessive. aution Resample oil in 3 months. Moisture very excessive. ielectric breakdown strength low. 43 aution Resample oil in 3 months. Moisture very excessive. ielectric breakdown strength very low. aution Resample oil in 3 months. Interfacial tension very low. aution Resample oil in 3 months. Moisture very excessive. aution Resample oil in 3 months. Moisture very excessive. Interfacial tension low. aution Resample oil in 3 months. Moisture very excessive. ielectric breakdwon strength low. 42 aution Resample oil in 3 months. igh gas concentration. Normal Resample oil in 6 months. Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. 43 Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. Normal Resample oil in 6 months. 43 Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Weidmann iagnostic Solutions Page 7

9 T/R ondition ode omments Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. 41 Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. 42 Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Normal Resample oil in 6 months. Weidmann iagnostic Solutions Page 8

10 pictorial representation of the ondition odes for each T/R, grouped by their corresponding precipitator, follows. red color represents a Warning condition code, yellow a aution condition code, and green a Normal condition code Weidmann iagnostic Solutions Page 9

11 Weidmann iagnostic Solutions Page 10

12 ONLUSIONS Out of the sixty-four T/Rs, four had a ondition ode of Warning as of 11/6/2009. These four T/Rs were given this condition assessment due to their severity of gas concentrations and active gassing rates. It is highly recommended to immediately resample the oil from these T/Rs for updated and OQ testing. Internal inspection of these T/Rs should also be seriously considered. nother thirty T/Rs received a ondition ode of aution. While these T/Rs did not have sufficiently high gassing rates to be classified as Warning, they did have higher than normal gas concentrations in most cases. In a few cases, the T/Rs were given a aution designation due to their poor OQ test results, and not as a result of the figures. It is recommended that the oil from these thirty T/Rs is resampled within three months from the previous sampling for updated and OQ testing. final thirty T/Rs received a ondition ode of Normal. These T/Rs did not have high gassing rates nor did they have higher than normal gas concentrations, nor oil quality problems. It is recommended that the oil from these thirty T/Rs is resampled within six months from the previous sampling for updated and OQ testing. Weidmann iagnostic Solutions Page 11

13 WIMNN INOSTI SOLUTIONS 3580 PRORSSIV RIV, SUIT K1 + NSLM, P LTROSTTI PRIPITTOR TRNSORMR/RTIIR Oil nalysis & iagnostic valuation NWL Transformers Location: Progress nergy Plant Mfr.: eneral lectric ccount No.: Rising Sun Road Serial No.: 41 ustomer I: - ordentown, NJ ank / Phase: - Year: - Order No.: LT ompartment: Transformer/Rectifier ontrol No.: reathing Type: Sealed ate Received: 11/9/2009 TTN: Joe Koszyk luid: Mineral Oil Sample ontainer I: ate Reported: 12/14/2009 PO No.: S allons: - Project I: - STM Lab ontrol Number: ate Sampled: 11/6/2009 9/13/2007 WS Report Number: Report Oil Temp. (): - - ydrogen (2) (ppm): 0 10 Methane (4) (ppm): 1 5 thane (26) (ppm): 0 5 thylene (24) (ppm): cetylene (22) (ppm): 0 0 arbon Monoxide (O) (ppm): arbon ioxide (O2) (ppm): Nitrogen (N2) (ppm): Oxygen (O2) (ppm): Total issolved as (ppm): Total issolved ombustible as (ppm): quivalent eadspace T (%): STM Moisture In Oil (ppm): STM -971 Interfacial Tension (dynes/cm): STM -974 cid Number (mg KO/g): STM olor Number (Relative): STM Visual xam (Relative): LR&SPRK - STM Sediment xam (Relative): N - STM ielectric reakdown at 1mm (kv): 38 - ondition ode as of 11/06/2009: Recommended ction: Rate of hange nalysis: issolved-as oncentration nalysis: issolved-as Ratio nalysis: Physical valuation: Normal Resample oil within 6 months. ll relevant gas concentrations are stable. ll gasses within normal limits. Ratio calculations not necessary. Moisture content acceptable. IT acceptable. ielectric reakdown Strength acceptable. Oil clear and sparkling. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann iagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. ny interpretations or opinions expressed represent the best judgement of Weidmann iagnostic Solutions. Weidmann iagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied, as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever.

14 WIMNN INOSTI SOLUTIONS 3580 PRORSSIV RIV, SUIT K1 + NSLM, P LTROSTTI PRIPITTOR TRNSORMR/RTIIR Oil nalysis & iagnostic valuation NWL Transformers Location: Progress nergy Plant Mfr.: eneral lectric ccount No.: Rising Sun Road Serial No.: 41 ustomer I: - ordentown, NJ ank / Phase: - Year: - Order No.: LT ompartment: Transformer/Rectifier ontrol No.: reathing Type: Sealed ate Received: 11/9/2009 TTN: Joe Koszyk luid: Mineral Oil Sample ontainer I: ate Reported: 12/14/2009 PO No.: S allons: - Project I: - STM Lab ontrol Number: ate Sampled: 11/6/2009 9/13/2007 WS Report Number: Report Oil Temp. (): - - ydrogen (2) (ppm): 3 10 Methane (4) (ppm): 3 5 thane (26) (ppm): 0 5 thylene (24) (ppm): cetylene (22) (ppm): 0 0 arbon Monoxide (O) (ppm): arbon ioxide (O2) (ppm): Nitrogen (N2) (ppm): Oxygen (O2) (ppm): Total issolved as (ppm): Total issolved ombustible as (ppm): quivalent eadspace T (%): STM Moisture In Oil (ppm): STM -971 Interfacial Tension (dynes/cm): STM -974 cid Number (mg KO/g): STM olor Number (Relative): STM Visual xam (Relative): LR&SPRK - STM Sediment xam (Relative): N - STM ielectric reakdown at 1mm (kv): 41 - ondition ode as of 11/06/2009: Recommended ction: Rate of hange nalysis: issolved-as oncentration nalysis: issolved-as Ratio nalysis: Physical valuation: UTION Resample oil within 3 months. ll relevant gas concentrations are stable. t least one gas exceeds normal limits. Ratio analysis not used due to overall low gas quantities. Moisture content acceptable. IT acceptable. ielectric reakdown Strength acceptable. Oil clear and sparkling. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann iagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. ny interpretations or opinions expressed represent the best judgement of Weidmann iagnostic Solutions. Weidmann iagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied, as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever.

15 WIMNN INOSTI SOLUTIONS 3580 PRORSSIV RIV, SUIT K1 + NSLM, P LTROSTTI PRIPITTOR TRNSORMR/RTIIR Oil nalysis & iagnostic valuation NWL Transformers Location: Progress nergy Plant Mfr.: eneral lectric ccount No.: Rising Sun Road Serial No.: 41 ustomer I: - ordentown, NJ ank / Phase: - Year: - Order No.: LT ompartment: Transformer/Rectifier ontrol No.: reathing Type: Sealed ate Received: 11/9/2009 TTN: Joe Koszyk luid: Mineral Oil Sample ontainer I: ate Reported: 12/14/2009 PO No.: S allons: - Project I: - STM Lab ontrol Number: ate Sampled: 11/6/2009 9/13/2007 WS Report Number: Report Oil Temp. (): - - ydrogen (2) (ppm): Methane (4) (ppm): thane (26) (ppm): thylene (24) (ppm): cetylene (22) (ppm): 2 3 arbon Monoxide (O) (ppm): arbon ioxide (O2) (ppm): Nitrogen (N2) (ppm): Oxygen (O2) (ppm): Total issolved as (ppm): Total issolved ombustible as (ppm): quivalent eadspace T (%): STM Moisture In Oil (ppm): 8 39 STM -971 Interfacial Tension (dynes/cm): STM -974 cid Number (mg KO/g): STM olor Number (Relative): STM Visual xam (Relative): LR&SPRK - STM Sediment xam (Relative): N - STM ielectric reakdown at 1mm (kv): 46 - ondition ode as of 11/06/2009: WRNIN Recommended ction: onsider internal inspection of Transformer/Rectifier. Resample oil within 1 month. Rate of hange nalysis: t least one gas has an abnormal rate of increase. issolved-as oncentration nalysis: t least one gas far exceeds normal limits. issolved-as Ratio nalysis: Indication of high temperature overheating. Physical valuation: Moisture content acceptable. IT acceptable. ielectric reakdown Strength acceptable. Oil clear and sparkling. The analyses, opinions or interpretations contained in this report are based upon material and information supplied by the client. Weidmann iagnostic Solutions does not imply that the contents of the sample received by this laboratory are the same as all such material in the environment from which the sample was taken. Our test results relate only to the sample or samples tested. ny interpretations or opinions expressed represent the best judgement of Weidmann iagnostic Solutions. Weidmann iagnostic Solutions assumes no responsibility and makes no warranty or representation, expressed or implied, as to the condition, productivity or proper operation of any equipment or other property for which this report may be used or relied upon for any reason whatsoever.

Categorizing Faults via DGA. GE Grid Solutions M&D

Categorizing Faults via DGA. GE Grid Solutions M&D ategorizing Faults via DGA GE Grid Solutions M&D First, What Is Transformer Dissolved Gas Analysis? Sample Test Doc Diagnosis Doctors extract information about our health from our blood. Technicians extract

More information

Dissolved Gas Analysis - Past, Present and Future

Dissolved Gas Analysis - Past, Present and Future I. INTRODUCTION Dissolved Gas Analysis - Past, Present and Future Fredi Jakob Weidmann-ACTI Inc. It has been well over thirty years since dissolved gas analysis, DGA, was introduced as a diagnostic tool

More information

A Revised Framework for the Transformer DGA Guide

A Revised Framework for the Transformer DGA Guide A Revised Framework for the Transformer DGA Guide Jim Dukarm for WG C57.104 Spring 2007 Presentation Topics Purpose and scope of the Guide Main departures from earlier versions Definition of transformer

More information

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling

More information

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations By Jeff Golarz ABSTRACT The use of Dissolved Gas Analysis (DGA) as a method for determining the types of pending or occurring faults within power transformers has been in practice for many years. It has

More information

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS Zohra Khan 1, Avinash Paranjpe 2 1 ME Student, Electrical Power System, PES COE/ Dr. B.A.M. University, (India)

More information

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing TRANSFORMER SERVICE Dissolved gas analysis and oil condition testing D I S S O LV E D G A S A N A LY S I S A N D O I L C O N D I T I O N T E S T I N G Transformer diagnostic services at ABB perform dissolved

More information

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION Athira K Anil 1, Archana R 2 1 PG Student, Electrical and Electronics Engineering, FISAT, Kerala, India 2 Associate Professor, Electrical

More information

DGA Tools: Duval Triangles and Pentagons

DGA Tools: Duval Triangles and Pentagons DGA Tools: Duval Triangles and Pentagons C. Beauchemin, TJH2b Analytical Services Inc. Initially presented at the TechCon SE Asia, Kuala Lumpur, April 10, 2017 This presentation use some material from

More information

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Master of Technology

More information

Online DGA-monitoring of power transformers

Online DGA-monitoring of power transformers Online DGA-monitoring of power transformers Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 Vaisala Webinar content 1. Dissolved gases why and which gases 2. Fault

More information

Transformer Lifecycle Services. Container Id: Miscellaneous Id: Second Name: Sequence #:

Transformer Lifecycle Services. Container Id: Miscellaneous Id: Second Name: Sequence #: Report # 173396 Sample # 1 Transformer Lifecycle Services Received 08/09/2016 Date August 10, 2016 Serial Number: 100413030004 Substation Name: Colorado Bend Design Type: Core Type Manufacturer: HicoA

More information

PAVESTONE COMPANY CST PAVERS PEDRICKTOWN, NEW JERSEY

PAVESTONE COMPANY CST PAVERS PEDRICKTOWN, NEW JERSEY PAVESTONE COMPANY CST PAVERS PEDRICKTOWN, NEW JERSEY October, 2015 Infrared Inspection Report Pavestone Company Company Contact Joe Dougan Project: 06051015 2605 CHARTER OAK DRIVE, LITTLE ROCK, AR 72227

More information

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University

More information

SYSCO BUCKHEAD BEEF COLLEGE PARK, GEORGIA

SYSCO BUCKHEAD BEEF COLLEGE PARK, GEORGIA SYSCO BUCKHEAD BEEF COLLEGE PARK, GEORGIA June, 2016 Infrared Inspection Report Sysco Buckhead Beef 4500 Wickersham Drive College Park, Georgia, 30337 Company Contact: Richard Blahnik Project: 05220616

More information

SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND

SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND October, 2016 Infrared Inspection Report Sysco St. John s 10 Old Placentia Road Mount Pearl, NF A1N 4P5 Company Contact: David Shaw Project: C261016 2605 CHARTER

More information

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption Mathieu Guertin Director Europe, Russia and Africa Morgan Schaffer Inc. Canada A cost effective strategy for smart grid technology adoption Why protecting assets? Cost of fault: $52 MILLIONS!!! Easy ROI

More information

Ohio EPA. Division of Air Pollution Control. Engineering Guide #78. (also known as DSIWM Guidance Document #1001 and #1002)

Ohio EPA. Division of Air Pollution Control. Engineering Guide #78. (also known as DSIWM Guidance Document #1001 and #1002) Ohio EPA Division of Air Pollution Control Engineering Guide #78 (also known as DSIWM Guidance Document #1001 and #1002) Question: The Standards of Performance for New Stationary Sources (NSPS) for municipal

More information

Since the beginning of production of oil for transformers

Since the beginning of production of oil for transformers EVENTS DIAGNOSTICS Photo courtesy of Končar D&ST, Zagreb, Croatia Chromatographic analysis of gases from the transformer The process of creating and detecting gases in the transformers ABSTRACT Given the

More information

SYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA

SYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA SYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA November, 2016 Infrared Inspection Report Sysco Allard 199 2e Avenue Ville de Quebec, QC, G1L 3A5 Company Contact Louis Grenier Project: C041116 2605 CHARTER

More information

SIDEWINDER DRILLING RIG 122 CLEBURNE COUNTY, ARKANSAS

SIDEWINDER DRILLING RIG 122 CLEBURNE COUNTY, ARKANSAS SIDEWINDER DRILLING RIG 122 CLEBURNE COUNTY, ARKANSAS March, 2015 Infrared Inspection Report Sidewinder Drilling Rig 122 Company Contact Jesse Russell Project: 07090315 2605 CHARTER OAK DRIVE, LITTLE ROCK,

More information

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO Atsushi Toya, Tokyo Electric Power Company, (Japan), toya.atsushi@tepco.co.jp Shinsuke Nasukawa, Tokyo Electric Power Company, (Japan), nasukawa.shinsuke@tepco.co.jp

More information

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers P. Werle, C. Radigk ABB Transformatoren GmbH Halle, Gemany peter.werle@de.abb.com W. Sorgatz

More information

Guide for the Sampling of Oil from Trench COTA Bushings for DGA

Guide for the Sampling of Oil from Trench COTA Bushings for DGA Instruction Guide for the Sampling of Oil from Trench COTA Bushings for DGA Forward This instruction is protected by copyright. Imparting to any third party and reproduction of any kind without written

More information

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS The 9 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 25 EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

More information

BUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA

BUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA BUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA May, 2017 Infrared Inspection Report Buzzi Unicem Terminal 6266 Da Lisa Road Milton, Florida, 32583 Company Contact Andy Rogers Project: 04110517 2605

More information

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN

COOPER POWER SERIES. EL Bay-O-Net Current-Limiting Fuse Installation Instructions. Fusing Equipment MN132023EN Fusing Equipment MN132023EN Effective November 2016 Supersedes June 2010 (S240-70-1) EL Bay-O-Net Current-Limiting Fuse Installation Instructions COOPER POWER SERIES DISCLAIMER OF WARRANTIES AND LIMITATION

More information

Discovery HP-TGA 75/750. Site Preparation Guide

Discovery HP-TGA 75/750. Site Preparation Guide Discovery HP-TGA 75/750 Site Preparation Guide Revision A Issued August 2018 Table of Contents Table of Contents... 2 Ideal Setup... 3 System Components... 4 Instrument Measurements... 5 Utility Requirements...

More information

Pub.No Flushing out your heat transfer system was a dirty job, a big expense, and a serious bummer.

Pub.No Flushing out your heat transfer system was a dirty job, a big expense, and a serious bummer. Pub.No.7239480 Flushing out your heat transfer system was a dirty job, a big expense, and a serious bummer. Now, the new Therminol FF Cleaning System makes it quicker, cheaper and easier. NOW,it s as easy

More information

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN

COOPER POWER. SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions. Surge Arresters MN235023EN Surge Arresters MN235023EN Effective November 2016 Supersedes October 2006 (S235-95-1) COOPER POWER SERIES VariSTAR type composite light-duty under-oil (CLU) MOV arrester installation instructions HIGH

More information

RB 4000 Commercial & Industrial Regulator

RB 4000 Commercial & Industrial Regulator R 4000 ommercial & Industrial Regulator The R 4000 pressure regulator is designed for industrial use: gas supply networks, district stations, industries, heating plants and all installations where accurate

More information

SYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA

SYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA SYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA August, 2016 Infrared Inspection Report Sysco Buckhead Beef 3516 Green Park Circle Charlotte, North Carolina, 28217 Company Contact Mark McNeely Project: 15120816

More information

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers g DEH 40050 Instructions Three-Phase, Platform-Mounted Distribution Transformers Introduction The equipment covered by these instructions should be operated and serviced only by competent technicians familiar

More information

East Building, PHH-30 U.S. Department New Jersey Avenue S.E. of Transportation Washington, D.C EXPIRATION DATE: June 30, 2015

East Building, PHH-30 U.S. Department New Jersey Avenue S.E. of Transportation Washington, D.C EXPIRATION DATE: June 30, 2015 November 14, 2014 East Building, PHH-30 U.S. Department 1200 New Jersey Avenue S.E. of Transportation Washington, D.C. 20590 Pipeline and Hazardous Materials Safety Administration DOT-SP 16219 EXPIRATION

More information

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers

Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers 24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution

More information

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks Proceedings of the 4th International Conference on Systems and Control, Sousse, Tunisia, April 28-30, 2015 TuCA.2 Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

More information

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)

Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS) CIGRÈ 23 BRUGGE 2007 Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS) E. Bräsel, U. Sasum Gatron Germany Eckhard.Braesel@gatron.de J. Aragon-Patil, S.

More information

THERBAN /HNBR for the Energy Sector

THERBAN /HNBR for the Energy Sector THERBAN /HNBR for the Energy Sector Victor Nasreddine*, Kevin Kulbaba, Susanna Lieber, hristian Müeller, Brian James, Larry hen, David Gerrard, Jim Goodson. *Speaker LANXESS, FAST/DI Seals USA, BAKER HUGHES

More information

Intermountain Specialty Gases 520 North Kings Rd, Nampa, Idaho Phone: Fax:

Intermountain Specialty Gases 520 North Kings Rd, Nampa, Idaho Phone: Fax: Intermountain Specialty Gases 520 North Kings Rd, Nampa, Idaho 83687 Phone: 800-552-5003 Fax: 208-466-9143 MATERIAL SAFETY DATA SHEET Page 1 Issue Date: Jan. 2006 Chemtrec 1-800-424-9300 Reviewed: March

More information

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society

Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society Prediction of Faults using Hydrocarbon Gases Data of Mineral Oil Immersed Power Transformers using Computer Intelligence

More information

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN

COOPER POWER SERIES. Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions. Tap-Changer Switch MN800015EN Tap-Changer Switch MN800015EN Effective December 2017 Supersedes February 1987 (S800-58) COOPER POWER SERIES Manual or Hostick Operable, Padlockable 150 A Tap-Changer Switch Installation Instructions DISCLAIMER

More information

Monitoring transformers with infrared cameras

Monitoring transformers with infrared cameras APPLICATION NOTE Monitoring transformers with infrared cameras Most transformers are cooled by either oil or air while operating at temperatures much higher than ambient. In fact, operating temperatures

More information

Chapter 5: Comparison of Inspection and Testing Results

Chapter 5: Comparison of Inspection and Testing Results Chapter 5: Comparison of Inspection and Testing Results Visual inspection, on-board testing, and laboratory analyses have distinct sensitivities and limitations. The results of the on-board testing can

More information

Veriforce TG CCT 609OP. Training Guide

Veriforce TG CCT 609OP. Training Guide Training Guide Directions: This training guide is to be used by a Veriforce Authorized Evaluator/Trainer and Trainee during on-thejob training (OJT) or prior to an evaluation as a resource. (S) Indicates

More information

800.Keen.Gas

800.Keen.Gas C 2 H 2 ACETYLENE Acetylene is a colorless and tasteless gas with a garlic-like odor. It is flammable and can be an asphyxiant. In order to prevent explosive decomposition, acetylene is supplied in cylinders

More information

Dow s New Practice for Locating Temporary Portable Buildings. P. Partridge 9/29/05 UNRESTRICTED - May be shared with anyone Slide 1

Dow s New Practice for Locating Temporary Portable Buildings. P. Partridge 9/29/05 UNRESTRICTED - May be shared with anyone Slide 1 Dow s New Practice for Locating Temporary Portable Buildings P. Partridge 9/29/05 UNRESTRICTED - May be shared with anyone Slide 1 Dow guidelines issued following the explosion at BP s Texas City facility

More information

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers

Draft Guide for the Interpretation of Gases in Oil Immersed Transformers Draft Guide for the Interpretation of Gases in Oil Immersed Transformers Sponsored by the Transformers Committee of the IEEE Power Engineering Society Copyright 2004 by the Institute of Electrical and

More information

Model Description

Model Description LEAKHUNTER Plus LEAKHUNTER Plus Model 8066 Description The MATHESON LEAKHUNTER Plus is a truly universal leak detector. Extensive R&D has produced a multi-functional leak detector engineered to perform

More information

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES

INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES INSTRUCTIONS FOR MODELS SG3897 AND SG3898 CROSS PURGE ASSEMBLIES THIS BOOKLET CONTAINS PROPRIETARY INFORMATION OF ADVANCED SPECIALTY GAS EQUIPMENT CORP. AND IS PROVIDED TO THE PURCHASER SOLELY FOR USE

More information

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools Protective Atmospheres, Measurement Technologies and Troubleshooting Tools Furnace atmospheres are critical to meet metallurgical specifications defined by control processes. The makeup of a furnace s

More information

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

 High Voltage Switch Yards & How Safe are these really <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd> " High Voltage Switch Yards & How Safe are these really" High Voltage Forum Brisbane 2013 Duty of Care As part of an asset owner Duty of care

More information

AMENDMENTS TO THE IMSBC CODE AND SUPPLEMENTS. Supporting information for the proposed new individual schedule for Palm kernel shells

AMENDMENTS TO THE IMSBC CODE AND SUPPLEMENTS. Supporting information for the proposed new individual schedule for Palm kernel shells E SUB-COMMITTEE ON CARRIAGE OF CARGOES AND CONTAINERS 3rd session Agenda item 5 CCC 3/INF.21 1 July 2016 ENGLISH ONLY AMENDMENTS TO THE IMSBC CODE AND SUPPLEMENTS Supporting information for the proposed

More information

OXYGEN MINERALE ABSOLUTE RANGE OWNER S MANUAL OXY MINERALE 600/1000 SERIES

OXYGEN MINERALE ABSOLUTE RANGE OWNER S MANUAL OXY MINERALE 600/1000 SERIES PURAPOOL OXYGEN MINERALE ABSOLUTE RANGE OWNER S MANUAL OXY MINERALE 600/1000 SERIES 1. PARTS IDENTIFICATION LIST 1. 5. 2. 4. 3. 6. 6. Figure 1.1 1. OXYGEN Minerale Power pack with timer option (x1) 2.

More information

Maintenance handbook

Maintenance handbook Maintenance handbook ontents HPU IDENTIFIATION SHEET... 4 1. MAINTENANE... 5 1.1 Filling level... 5 1.2 Fluid top-up... 5 1.3 Fluid replacing... 5 1.4 Fluid temperature control... 6 1.5 Functional control...

More information

AIR QUALITY. Safety is in the Air AVOIDING CARBON MONOXIDE POISONING WHILE SCUBA DIVING

AIR QUALITY. Safety is in the Air AVOIDING CARBON MONOXIDE POISONING WHILE SCUBA DIVING AIR QUALITY Safety is in the Air AVOIDING CARBON MONOXIDE POISONING WHILE SCUBA DIVING INTRODUCTION Carbon monoxide poisoning and its influence on diving safety Carbon monoxide (CO) is an odourless, colourless

More information

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS XIX IMEKO World Congress Fundamental and Applied Metrology September 6, 9, Lisbon, Portugal ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS Ana Madeira, Florbela A. Dias and Eduarda Filipe 3 Instituto Português

More information

Rev. 1. Cryogenics Thermoflasks. 2122, 2123, 2124, 2129, and 2130

Rev. 1. Cryogenics Thermoflasks. 2122, 2123, 2124, 2129, and 2130 Operating Manual Application Catalog Number 056-720-00 Rev. 1 Cryogenics Thermoflasks 2122, 2123, 2124, 2129, and 2130 Important Read these operating instructions. Failure to read, understand and follow

More information

ARTIFICIAL TURF FIELD Haddonfield High School

ARTIFICIAL TURF FIELD Haddonfield High School IFIIL F FILD addonfield igh School SB 2012 resented By rtificial urf vs. Natural rass thletic Fields rtificial urf Development addonfield thletic Demand sage aintenance ost nalysis rtificial urf Warranty

More information

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers DIAGNOSTICS Bushings are a critical part of the transformer, and their failures often have destructive consequences for the transformer, with a high risk of fire ABSTRACT Bushings are highly stressed parts

More information

TM8 On-Line Gas Chromatography DGA Monitor Site Preparation Guide Model TMx Series

TM8 On-Line Gas Chromatography DGA Monitor Site Preparation Guide Model TMx Series TMx Site Preparation Guide 810-1647-03 Rev B TM8 On-Line Gas Chromatography DGA Monitor Site Preparation Guide Model TMx Series June, 2017 Document ID: 810-1647-03 Rev B www.serveron.com Legal Information

More information

Effective March 2015 Supersedes S August 2002

Effective March 2015 Supersedes S August 2002 Reclosers MN280009EN Effective March 2015 Supersedes S280-40-11 August 2002 COOPER POWER SERIES Type R, RE, W, WE reclosers closing solenoid contactor replacement kit KA852R installation instructions DISCLAIMER

More information

TIGHTNESS. Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements.

TIGHTNESS. Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements. TIGHTNESS Glass sealing Thanks to our glass-sealing technology, ODU products can meet the most demanding tightness requirements. ODU has the necessary expertise for developing and manufacturing connectors

More information

Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices

Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices Commercial Practice Test Method Internal Vapor Analysis of Hermetic Devices Oneida Research Services, Inc. 8282 Halsey Road Whitesboro, NY 13492 Phone: (315) 736-5480 FAX: (315) 736-9321 1.0 Purpose The

More information

XIAMETER RSN-0997 Resin

XIAMETER RSN-0997 Resin XIAMETER RSN-0997 Resin Silicone Resin in solvent FEATURES Easy to use Excellent electrical properties Good bond strength retention Moisture resistance Designed to meet MIL-I- 24092B APPLICATIONS Impregnant

More information

C Dissolved Gas Analysis Of Load Tap Changers. Working Group

C Dissolved Gas Analysis Of Load Tap Changers. Working Group C57.139 Dissolved Gas Analysis Of Load Tap Changers Working Group Data Analysis Update Spring 2007 Data Analysis Agenda 1. 1. Update of of activity 2. 2. Data analysis 3. 3. Review examples in in reverse

More information

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER

LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER LINEAR TRANSFORMATION APPLIED TO THE CALIBRATION OF ANALYTES IN VARIOUS MATRICES USING A TOTAL HYDROCARBON (THC) ANALYZER Michael T Tang, Ph.D. Grace Feng Greg Merideth Rui Huang Matheson Gas Applied Lab

More information

Low GWP R-404A Alternatives for Commercial Refrigeration. Barbara H. Minor Dr. Frank Rinne DuPont Fluorochemicals

Low GWP R-404A Alternatives for Commercial Refrigeration. Barbara H. Minor Dr. Frank Rinne DuPont Fluorochemicals Low GWP R-404A Alternatives for Commercial Refrigeration Barbara H. Minor Dr. Frank Rinne DuPont Fluorochemicals Chillventa Nűrnberg October 9-11, 2012 Topics Regulatory Environment Properties of New Refrigerants

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60567 Third edition 2005-06 Oil-filled electrical equipment Sampling of gases and of oil for analysis of free and dissolved gases Guidance This English-language version is derived

More information

CO, NO, NO 2, NO x, SO 2, CH 4, HCl, CO 2 & H ² O. Extractive low cost, low maintenance devices for continuous process and emissions monitoring.

CO, NO, NO 2, NO x, SO 2, CH 4, HCl, CO 2 & H ² O. Extractive low cost, low maintenance devices for continuous process and emissions monitoring. Product Data Sheet CODEL Continuous Emission Monitoring GCEM 40 Series Extractive Gas Analyser CO, NO, NO 2, NO x, SO 2, CH 4, HCl, CO 2 & H ² O Extractive low cost, low maintenance devices for continuous

More information

14 FORTUNE DRIVE PRODUCT NAME: EPO-TEK H74 UNF, Part A BILLERICA, MA 01821

14 FORTUNE DRIVE PRODUCT NAME: EPO-TEK H74 UNF, Part A BILLERICA, MA 01821 MATERIAL SAFETY DATA SHEET PRODUCT NAME: EPO-TEK H74 UNF, Part A BILLERICA, MA 01821 EMERGENCY PHONE: *HMIS: HEALTH-2 FIRE-1 REACTIVITY- 0 US/CANANDA : 800-255-3924 INT L COLLECT: + 813-248-0585 Carcinogen:

More information

Gas Tester Competent Person Course Outline

Gas Tester Competent Person Course Outline Gas Tester Competent Person Course Outline Prerequisites: This course shall have no formal pre-requisite. Course Length: 8 hours Course length shall vary depending on the number of delegates. Total course

More information

CON ACT. Parts and Service News For the Power Transformer and

CON ACT. Parts and Service News For the Power Transformer and ABB CON ACT Parts and Service News For the Power Transformer and March 1998 Circuit Breaker Maintenance Community Special No. 1 Type 'U' "The Clock is Ticking" Up-to-the-Minute News About Type "U" Transformer

More information

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM. Australasian Universities Power Engineering Conference (AUPEC 2004) 26-29 September 2004, Brisbane, Australia PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM. N.K.Dhote*

More information

BALLYMEADE COUNTRY CLUB REDEVELOPMENT (THE CAPE CLUB)

BALLYMEADE COUNTRY CLUB REDEVELOPMENT (THE CAPE CLUB) LLYMD OUNTRY LU RDVLOPMNT (TH P LU) almouth, M December, 6 WG, LL DVLOPMNT O RGIONL IMPT TRI IMPT ND SS STUDY LLYMD OUNTRY LU RDVLOPMNT (TH P LU) LMOUTH WOODS ROD LMOUTH, MSSHUSTTS Prepared for: WG, LL

More information

The above item, as tested, is considered to comply with the above specifications. PAGE 1 OF 6

The above item, as tested, is considered to comply with the above specifications. PAGE 1 OF 6 APPLICANT: Suck UK Limited 31 Regent Studios 8 Andrews Road London E8 4QN DATE: 17 th January 2014 For the attention of Emma SAMPLE DESCRIPTION: Bottlelight REFERENCE / STYLE NO.: SK LIGHTBOTTLE 1 RETAILER:

More information

Installation & Instruction Manual For Portable Series R.O. units:

Installation & Instruction Manual For Portable Series R.O. units: Installation & Instruction Manual For Portable Series R.O. units: Please read carefully before proceeding with installation *System components and appearance may vary from above image. REPLACEMENT AND

More information

Technical Process Bulletin

Technical Process Bulletin Technical Process Bulletin RIDOLINE 53 Alkaline Immersion Cleaner 1. Introduction: Technical Process Bulletin No. 234242 This Revision: 23-11-1990 RIDOLINE 53 is a powdered, silicated, alkaline immersion

More information

COMMERCIAL ITEM DESCRIPTION RUBBER, SILICONE; SHEET, SOLID, SHAPE 15

COMMERCIAL ITEM DESCRIPTION RUBBER, SILICONE; SHEET, SOLID, SHAPE 15 INH-POUND 5 May 2011 SUPERSEDING --55759 12 September 1995 OMMERIL ITEM DESRIPTION RUER, SILIONE; SHEET, SOLID, SHPE 15 The General Services dministration has authorized the use of this ommercial Item

More information

EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant

EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant TNO Quality Services BV TNO report De Rondom 1 P.O. Box 6235 5600 HE Eindhoven The Netherlands TQS-RAP-07-271 EN1279 part 3 assessment of insulating glass: IGU with Duralite sealant Date February 7, 2007

More information

Experiment 18 Properties of Gases

Experiment 18 Properties of Gases Experiment 18 Properties of Gases E18-1 E18-2 The Task In this experiment you will investigate some of the properties of gases, i.e. how gases flow, their phase changes and chemical reactivity. Skills

More information

Material Safety Data Sheet SANTOLUBES LLC SANTOTRAC, SANTOVAC, SANTOLUBES, AND SYNERGY P.O. Box 960 St. Charles, MO

Material Safety Data Sheet SANTOLUBES LLC SANTOTRAC, SANTOVAC, SANTOLUBES, AND SYNERGY P.O. Box 960 St. Charles, MO Material Safety Data Sheet SANTOLUBES LLC SANTOTRAC, SANTOVAC, SANTOLUBES, AND SYNERGY P.O. Box 960 St. Charles, MO 63302-0960 Page 1 of 5 1. CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT NAME: Chemical

More information

Effective May 2017 Supersedes August 2005 (S )

Effective May 2017 Supersedes August 2005 (S ) Padmounted Switchgear MN285013EN Effective May 2017 Supersedes August 2005 (S285-15-1) COOPER POWER Type shrubline VFI, vacuum fault interrupter; installation, operation and maintenance instructions SERIES

More information

TENDER SPECIFICATION No: 12/ of SUPERINTENDING ENGINEER (CTI & ENQUIRIES), Dt

TENDER SPECIFICATION No: 12/ of SUPERINTENDING ENGINEER (CTI & ENQUIRIES), Dt 1 TENDER SPECIFICATION No: 12/2018-19 of SUPERINTENDING ENGINEER (CTI & ENQUIRIES), Dt. 08.01.2019 Specification for Supply of Standard Calibration Gas Mixture in the ranges of 5PPM and 100PPM filled in

More information

OCTOBER 2017 ISSUE Page 1 of 7

OCTOBER 2017 ISSUE Page 1 of 7 Field testing is performed on fully assembled pipelines for the purpose of determining pipeline acceptability. Following visual acceptance of joints and pipeline components, pressure pipelines in their

More information

CABLE PULLING GUIDELINES

CABLE PULLING GUIDELINES The following data is intended as a general guide to aid individuals with the installation of cables inside ducts, raceways or conduit. These recommendations are based upon a study sponsored by the ICEA

More information

Carcinogen: NTP (No) IARC (No) OSHA (No) DATE REVISED: 6/5/01 REV: A * HMIS CODE ratings are estimated by Epoxy Technology.

Carcinogen: NTP (No) IARC (No) OSHA (No) DATE REVISED: 6/5/01 REV: A * HMIS CODE ratings are estimated by Epoxy Technology. MATERIAL SAFETY DATA SHEET PRODUCT NAME: EPO-TEK H70E-2, Part A BILLERICA, MA 01821 EMERGENCY PHONE: *HMIS: HEALTH-2 FIRE-1 REACTIVITY- 0 US/CANADA: 800-255-3924 INT L COLLECT: + 813-248-0585 Carcinogen:

More information

AWWA Pipe Flanges. AWWA C Standard Steel Hub Flanges Class D AWWA C Standard Steel Hub Flanges Class E AWWA C Flange Manufacturer

AWWA Pipe Flanges. AWWA C Standard Steel Hub Flanges Class D AWWA C Standard Steel Hub Flanges Class E AWWA C Flange Manufacturer WW Pipe Flanges WW Flanges are commonly used in waterworks, wastewater, slurry, plant piping or other light duty applications generally requiring pressures of less than 300 psi. Pressure ratings for WW

More information

1. Which of the following is true with respect to air masses B and C on the map?

1. Which of the following is true with respect to air masses B and C on the map? Pretest 4.3 1. Which of the following is true with respect to air masses B and C on the map? (A) Air mass B is cold polar and air mass C is maritime polar. (B) Air mass B is cold polar and air mass C is

More information

Memorandum Pershing Road Suite 400 Kansas City, MO Tel Fax

Memorandum Pershing Road Suite 400 Kansas City, MO Tel Fax Memorandum 2400 Pershing Road Suite 400 Kansas ity, MO 64108 Tel 816 329 8600 Fax 816 329 8601 www.transystems.com To: Mr. avid Gurss Kansas epartment of Transportation wight. Eisenhower State Office ldg.

More information

Hot extractive multi-channel gas analyser for continuous process and emissions monitoring.

Hot extractive multi-channel gas analyser for continuous process and emissions monitoring. Product Data Sheet CODEL Continuous Emission Monitoring GCEM4100 Extractive Gas Analyser CO, CO2, NO, NO2, SO2, HCL, CH4 & H2O Hot extractive multi-channel gas analyser for continuous process and emissions

More information

SYSCO FOODS BAHAMAS FOOD SERVICE NASSAU, BAHAMAS

SYSCO FOODS BAHAMAS FOOD SERVICE NASSAU, BAHAMAS SYSCO FOODS BAHAMAS FOOD SERVICE NASSAU, BAHAMAS January, 2019 Infrared Inspection Report Sysco Bahamas Foods Gladstone Road Nassau, Bahamas Company Contact Eddie O Connor Project: 02300119 2605 CHARTER

More information

Misuse of Combustible Gas Meters

Misuse of Combustible Gas Meters Misuse of Combustible Gas Meters An incident investigation raised concerns that users of combustible gas meters may be greatly underestimating fire and explosion hazards. Errors result when meters calibrated

More information

Organic Elemental Analysis Series II Nitrogen Analyzer. proven performance. reliable results

Organic Elemental Analysis Series II Nitrogen Analyzer. proven performance. reliable results Organic Elemental Analysis 2410 Series II Nitrogen Analyzer proven performance reliable results PerkinElmer 2410 Series II Nitrogen Analyzer Advanced Combustion Method Q U I C K G L A N C E Advanced combustion

More information

Superior Contact Stability Closed-down design of each contact cavity in the insulator support each contact, minimizes contact splaying.

Superior Contact Stability Closed-down design of each contact cavity in the insulator support each contact, minimizes contact splaying. /345* I--5015 ear elease onnectors ircular tandard ircular igh nvironmental onnectors hese connectors are available for many applications, from commercial/industrial and mass transportation systems to

More information

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

COOPER POWER SERIES. Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions Underground Distribution Switchgear MN285006EN Effective March 2018 Supersedes December 2015 COOPER POWER SERIES Type VFI, Fluid-insulated Switchgear; Installation, Operation and Maintenance Instructions

More information

APPENDIX D HYDRO-VAC

APPENDIX D HYDRO-VAC The City of Winnipeg Bid Opportunity No. 33-2018 Template Version: C420160226 - RW APPENDIX D HYDRO-VAC Corporate Safety & Health Division GUIDELINES FOR EXCAVATION OF CABLES BY WATER PRESSURE/VACUUM SYSTEMS

More information

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438 CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO. 10 Jerry Paul Smith Joel Clancy JPS Measurement Consultants, Inc Colorado Engineering Experiment Station, Inc (CEESI) 13002 Walnut Lake

More information

1. PRODUCT IDENTIFICATION 2. COMPOSITION / INFORMATION ON HAZARDOUS INGREDIENTS

1. PRODUCT IDENTIFICATION 2. COMPOSITION / INFORMATION ON HAZARDOUS INGREDIENTS OPTI Medical Systems, Inc. 235 Hembree Park Drive Roswell, GA 30076 USA Tel: +1 770 510 4444 +1 800 490 OPTI Fax: +1 770 510 4445 1. PRODUCT IDENTIFICATION Product Name: ASSY, 28 psi Gas Bottle Information

More information

Owner s Manual Humiport 10/20

Owner s Manual Humiport 10/20 4201 Lien Rd Madison, WI 53704 Owner s Manual Humiport 10/20 Installation, Operation & Service Instructions Read and Save These Instructions The Phoenix Humiport line of ThermoHygrometers offers the restoration

More information

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions

200 A, 15 and 25 kv class loadbreak bushing insert installation instructions Loadbreak Apparatus Connectors Effective October 2013 Supersedes March 2011 200 A, 15 and 25 kv class loadbreak bushing insert installation instructions S500-12-1 DISCLAIMER OF WARRANTIES AND LIMITATION

More information