1 Mathieu Guertin Director Europe, Russia and Africa Morgan Schaffer Inc. Canada A cost effective strategy for smart grid technology adoption
2 Why protecting assets? Cost of fault: $52 MILLIONS!!! Easy ROI calculations for transformer dissolved gas monitoring
3 Combustible Gas Generation rates 3 key learnings
4 DGA Understanding process and operations jar Sampling point syringe Sampling techniques & location Packaging & handling Transportation Sample preparation Gas extraction Gas separation and measurement Multiple and varied steps Hard to control variables Multiples operators along the complet analysis process
5 Your DGA results: Accurate or not? Every Laboratory should be able to demonstrate their precision and accuracy, if this is not possible or by any reason unknown, the below chart is recommended to use as a guide of IEC/CIGRE laboratories, from roundrobin tests using DGA standards. Medium gas concentrations Low gas concentrations Best lab ±3% ±22% Average ±15% ±30% Worst Lab ±65% ±64% IEEE August 2005, M. Duval, J. Dukarm, Improving the reliability of transformer in gas-in-oil diagnosis
6 Your DGA results: Accurate or not? Diagnostic reliability is affected by the accuracy of the DGA measurement results CIGRE result for Round Robin Test (RRT) at low concentration levels.. Results of individual laboratories x prepared DGA standard value () IEEE August 2005, M. Duval, J. Dukarm, Improving the reliability of transformer in gas-in-oil diagnosis +/- 15% variation limit of absolute values
7 DGA as a tool From Information to Action
8 Diagnosing transformer condition A good rule is: Never make a decision based only on a ratio if either of the two gases used in a ratio is less than 10 times the amount the gas chromatograph can detect FIST 03-30, USA Bureau of reclamation
9 Diagnosing transformer condition TDG (Total Dissolved Gases) expressed in % to ppm, i.e. in the picture TRN1 we see 7%, meaning there is a total of ppm of gases (all the gases) TDCG (Total Dissolved Combustible Gases) all the gases except N2, O2 and CO2, also in % to ppm, that s why we see 0% (less than 1ppm, as almost all the gases are N2, O2 and CO2) THCG (Total Headspace Combustible Gases) are the gases on the headspace at the transformers (especially in sealed transformers with N2 blanket) as the gases dissolved in the oil are in equilibrium with the headspace, we calculate, based on the Ostwald coefficient, each gas at the headspace level.
10 Diagnosing transformer condition 1 The Duval Triangle method, like any other DGA diagnostic method, should be applied only when there is some suspicion of a fault, based on an increase in combustible gas or some other suspicious symptom. The diagnostic method itself is not a means of fault detection. Because of the relative inaccuracy of gas-in-oil concentration measurements at low concentrations, DGA diagnostic methods, including the Duval Triangle, should not be applied unless the gas concentrations are well above the detection limit. If reasonably stable concentrations of the gases were present before the onset of the suspected fault, it is advisable to subtract out the background concentrations, provided that the differences are large enough for interpretation. The diagnosis should be based on recently-formed gas if possible, and including pre-fault gas in the diagnostic calculations can lead to misleading results 2. 1 PPMreport, Morgan Schaffer Myrkos s operating system 2
11 Diagnosing transformer condition Rogers used these relationships and determined that if a certain ratio existed, then a specific temperature had been reached. By comparing a large number of transformers with similar gas ratios and data found when the transformers were examined, Rogers could then say that certain faults were present. Like the Key Gas Analysis above, this method is not a sure thing and is only an additional tool to use in analyzing transformer problems. FIST 03-30, USA Bureau of reclamation
12 Summary of gases used by the diagnostics tools IEEE test: Duval test: Rogers test: Doerneburg CO2/CO H2 CH4 C2H2 C2H4 C2H6 CO CO2 CH4 C2H2 C2H4 H2 CH4 C2H2 C2H4 C2H6 H2 CH4 C2H2 C2H4 C2H6 CO CO2 Standards tests support the decision making process 1) What is the current situation of the transformer? 2) What is the nature and severity of the fault?
13 Operationalizing and integrating And being SMART about it
14 Transformers monitoring: 3 key values Value no.1 Ability to Detect a change in condition In ALL cases = Protection Value. Value no.2 Ability to Monitor the Evolution of the Condition = Monitoring Value. Value no.3 Ability to Diagnose the nature of the bad condition = Diagnostic Value.
15 Defining the needs 1) Review current resources & operations Diagnostic value Diagnostic 2) Defining Asset Criticality 3) Review needs 4) Plan & budget Detect Monitor 5) Implement, deploy, and integrate # of Gases analyzed
16 Transformer Condition evolution economical costs $$$$ Worst Case $ Best Case Time
17 Transformer: Electrical network $ The Global Picture Significant savings occur when a large number of transformers are being monitored Failures will happen it s a matter of probability!! Time
18 Monetizing Online monitoring What you actually pay for Diagnostic Diagnostic Value : Value Approx. : Monitoring Monitoring Value : Value Approx. 0 : 0$ Detection Value : Approx Years If no problem arises during the life of the transformer, only the Detection value of the instrument is of benefit.
19 Monetizing Online monitoring Condition change Condition : better change allocation of budget Diagnostic Value Monitoring Value Detection Value Years When a condition change occurs, Diagnostics capabilities are important, but otherwise only Detection and/or Monitoring
20 Deploying online monitors Maximizing coverage of electrical assets New Detect Monitor Diagnose Sub-station So when a transformer s condition changes abnormally Critical 1 Critical 2
21 Deploying online monitors Alarm New Detect Monitor Diagnose Sub-station Evolving fault triggers a signal to substation for action 1 Critical 1 Critical 2
22 Deploying online monitors Alarm triggers on-site inspection and Myrkos DGA New Detect Monitor Diagnose Sub-station Field team quickly addresses the alert On-site AND channels the DGA results. Communicate with Asset Manager for DGA-based action plan Critical <<<< 1 day to provide results for diagnostics by Asset manager or Lab DGA Critical 2
23 Deploying online monitors Multigas can be used effectively to closely monitor transformer New Detect Monitor Diagnose After condition assessment and decision taken on faulty transformer Sub-station 1 ASTM D3612 IEC Critical 1 2 On-site Condition assessment Critical 2 3 When needed : on-line multigas monitor for problematic/concerning fault gases evolution (temp/perm)
24 Deploying online monitors Budget allocation efficiency Detect Detect New Monitor New Monitor Diagnose A Sub-station 1x 3-4X B Critical 1 Critical 1 Critical 2 Critical 2 Diagnose
25 A Deploying online equal budget B Detect A B Detect New Monitor Equal budget New Monitor Diagnose Sub-station Sub-station - Extended coverage - Diagnostics - Easier data management Critical 1 Critical 1 Critical 2 Critical 2 Diagnose
26 Interchangeability concept: key pointers Maximizing coverage of electrical assets Aiming for minimal downtime Leveraging the current infrastructure Maximizing monitoring value while maintaining Detect Monitor Critical 1 Diagnose Critical 2
27 Balancing values: interchangeability concept in action
28 Interchangeability concept in action: from a detection monitor alarm, to multigas diagnostics Details : Normal operation **Change in condition This case study is about 18.4/23 MVA power transformer, 19/6.3 kv, Dyn1, manufactured in Early in 2013, the Calisto 2 monitor installed on the transformer detected an increase on the H 2 values. The Calisto 2 was replaced with a Calisto 9 for further investigation (interchangeable units) Interchangeability concept From Detection To Diagnostics
29 Interchangeability concept in action: from a detection monitor alarm, to multigas diagnostics Details : The Calisto 9 measured high values were recorded for H2, C2H4, C2H6 and most importantly for C2H2. The measurements were double checked by the customer: Samples were sent to ABB Sweden for DGA and all measurements were confirmed. Electrical measurements were performed locally and the winding resistance measurements (static and dynamic) showed a loose contact of one winding with the OLTC selector.
30 Interchangeability concept in action: from a detection monitor alarm, to multigas diagnostics
31 Interchangeability concept in action: from a detection monitor alarm, to multigas diagnostics Duval Triangle 1) Adjusted for the actual oil type used in the transformer 2) 2 nd level analysis with Triangle no.4 and no.5 3) Only triggered when proper gas alarm limits have been reached, reducing false positive
32 Interchangeability concept in action: from a detection monitor alarm, to multigas diagnostics Additional diagnostics 1) Rate of change (Day, Week, Month, Year) 2) Rogers ratios 3) IEC ) Doernenburg 5) Key gas method 6) IEEE
33 Interchangeability concept in action: from a detection monitor alarm, to multigas diagnostics The loose contacts were one of the connecting points of the transformer windings with the OLTC tap positions. These contacts are located inside the transformer tank, not the OLTC tank Details : The transformer was opened, the oil was removed and the loose contacts were indeed found and fixed. Measurements from the Calisto 9 shown on the previous slide demonstrate the situation has stabilized after the problem had been fixed. The customers expressed their satisfaction regarding the early warning they received from the Calisto 2 that allowed them to fix the problem at no practical cost.
34 AUW booth C4 Questions? Thank you!
35 Process excellence: empowering the field On-site Dissolved Gas Analysis Speed of reaction to particular event: field DGA Unstable H 2 condition? Alert On-site visit / visual inspection X X X T on-site/sampling T packing/shipping/customs T lab analysis T results/condition assessment/decision 1-10 Hours 1-10 Hours 1-5 days 1-5 days Critical early detection in H 2 change Elimination of time consuming and wasteful steps
36 Process excellence: empowering the field On-site Dissolved Gas Analysis Up to 98% * reduction in Cycle time = faster results = more up time Unstable H 2 condition? Critical early detection in H 2 change Alert On-site visit / visual inspection T on-site/sampling T on-site DGA/ immediate result T lab analysis 1-10 Hours 0.1 Hours 1-5 days PLUS with MYRKOS you tremendously increase your Diagnose * When normal cycle takes 2.5 months
Categorizing Faults via DGA. GE Grid Solutions M&D
ategorizing Faults via DGA GE Grid Solutions M&D First, What Is Transformer Dissolved Gas Analysis? Sample Test Doc Diagnosis Doctors extract information about our health from our blood. Technicians extract
More informationUnderstanding Dissolved Gas Analysis (DGA) Techniques and Interpretations
By Jeff Golarz ABSTRACT The use of Dissolved Gas Analysis (DGA) as a method for determining the types of pending or occurring faults within power transformers has been in practice for many years. It has
More informationOnline DGA-monitoring of power transformers
Online DGA-monitoring of power transformers Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 Vaisala Webinar content 1. Dissolved gases why and which gases 2. Fault
More informationA Revised Framework for the Transformer DGA Guide
A Revised Framework for the Transformer DGA Guide Jim Dukarm for WG C57.104 Spring 2007 Presentation Topics Purpose and scope of the Guide Main departures from earlier versions Definition of transformer
More informationDISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS
DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University
More informationPortable Gas Analyzers
Portable Gas Analyzers Accuracy Matters To make informed decisions on site, you need fast and reliable data. Myrkos portable gas analyzers provide lab quality DGA data. Where you need it, when you need
More informationMODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS
MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS Zohra Khan 1, Avinash Paranjpe 2 1 ME Student, Electrical Power System, PES COE/ Dr. B.A.M. University, (India)
More informationDGA Tools: Duval Triangles and Pentagons
DGA Tools: Duval Triangles and Pentagons C. Beauchemin, TJH2b Analytical Services Inc. Initially presented at the TechCon SE Asia, Kuala Lumpur, April 10, 2017 This presentation use some material from
More informationManaging on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers
24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution
More informationPower Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers
Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling
More informationDissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI
Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Master of Technology
More informationTransformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks
Proceedings of the 4th International Conference on Systems and Control, Sousse, Tunisia, April 28-30, 2015 TuCA.2 Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks
More informationDissolved Gas Analysis - Past, Present and Future
I. INTRODUCTION Dissolved Gas Analysis - Past, Present and Future Fredi Jakob Weidmann-ACTI Inc. It has been well over thirty years since dissolved gas analysis, DGA, was introduced as a diagnostic tool
More informationSince the beginning of production of oil for transformers
EVENTS DIAGNOSTICS Photo courtesy of Končar D&ST, Zagreb, Croatia Chromatographic analysis of gases from the transformer The process of creating and detecting gases in the transformers ABSTRACT Given the
More informationA New Approach for Transformer Incipient Fault Diagnosis Based on Dissolved Gas Analysis (DGA)
Nova Explore Publications Nova Journal of Engineering and Applied Sciences Vol. 3(2), 2014: 1-7 PII: S229279211400008-3 www.novaexplore.com Research Article A New Approach for Transformer Incipient Fault
More informationTRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing
TRANSFORMER SERVICE Dissolved gas analysis and oil condition testing D I S S O LV E D G A S A N A LY S I S A N D O I L C O N D I T I O N T E S T I N G Transformer diagnostic services at ABB perform dissolved
More informationDynamic Behaviour of Fault Gases and Online Gas Sensors. Germany
21, rue d Artois, F-75008 PARIS A2-116 CIGRE 2016 http : //www.cigre.org Dynamic Behaviour of Fault Gases and Online Gas Sensors S. TENBOHLEN 1, I. HÖHLEIN 2, M. LUKAS 3, A. MÜLLER 4, K. SCHRÖDER 5, U.
More informationA REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION
A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION Athira K Anil 1, Archana R 2 1 PG Student, Electrical and Electronics Engineering, FISAT, Kerala, India 2 Associate Professor, Electrical
More informationEXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS
The 9 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 25 EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS
More informationComparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers
Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers P. Werle, C. Radigk ABB Transformatoren GmbH Halle, Gemany peter.werle@de.abb.com W. Sorgatz
More informationImproved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS)
CIGRÈ 23 BRUGGE 2007 Improved Monitoring of Dissolved Transformer Gases on the Basis of a Natural Internal Standard (NIS) E. Bräsel, U. Sasum Gatron Germany Eckhard.Braesel@gatron.de J. Aragon-Patil, S.
More informationAdvanced Test Equipment Rentals ATEC (2832) OMS 600
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OMS 600 Continuous partial discharge monitoring system for power generators and electrical motors Condition monitoring
More informationDraft Guide for the Interpretation of Gases in Oil Immersed Transformers
Draft Guide for the Interpretation of Gases in Oil Immersed Transformers Sponsored by the Transformers Committee of the IEEE Power Engineering Society Copyright 2004 by the Institute of Electrical and
More informationNeil Kane Managing Director EMT UK
Neil Kane Managing Director EMT UK SF6 Measurement, Analysis, Diagnostics and Leak Detection Our goals at EMT are to supply Maintenance Operatives with the very best tools to protect both personnel and
More informationChapter 5: Methods and Philosophy of Statistical Process Control
Chapter 5: Methods and Philosophy of Statistical Process Control Learning Outcomes After careful study of this chapter You should be able to: Understand chance and assignable causes of variation, Explain
More informationNandkumar Wagh, D.M. Deshpande
International Journal of Scientific & Engineering Research, Volume 4, Issue 9, September-2013 2503 Fuzzy Decision on Transformer Fault Diagnosis using Dissolved Gas Analysis and IEC Ratio Codes Nandkumar
More informationPROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.
Australasian Universities Power Engineering Conference (AUPEC 2004) 26-29 September 2004, Brisbane, Australia PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM. N.K.Dhote*
More informationOnline Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society
Online Publication Date: 19 January, 2012 Publisher: Asian Economic and Social Society Prediction of Faults using Hydrocarbon Gases Data of Mineral Oil Immersed Power Transformers using Computer Intelligence
More informationC Dissolved Gas Analysis Of Load Tap Changers. Working Group
C57.139 Dissolved Gas Analysis Of Load Tap Changers Working Group Data Analysis Update Spring 2007 Data Analysis Agenda 1. 1. Update of of activity 2. 2. Data analysis 3. 3. Review examples in in reverse
More informationDISSOLVED GAS ANALYSIS OF POWER TRANSFORMERS
International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN(P): 2250-155X; ISSN(O): 2278-943X Vol. 3, Issue 5, Dec 2013, 1-10 TJPRC Pvt. Ltd. DISSOLVED GAS ANALYSIS OF POWER
More informationLife Cycle Benefits: Maintenace (Control Valve Diagnostic and Field Device Diagnostic Management)
Life Cycle Benefits: Maintenace (Control Valve Diagnostic and Field Device Diagnostic Management) Yasushi Kudo Yamatake Corporation Aaron Chen Azbil Taiwan Contents I. Prologue II. Possibilities of CV
More informationFully integrated solutions for improving safety, emissions control and product integrity
Fully integrated solutions for improving safety, emissions control and product integrity Total Tank Protection - Inside and Out Overcome Operational Challenges Mismatched and incompatible multi-vendor
More informationDevelopment of a Plant Health Index for Eskom Distribution Substations
Development of a Plant Health Index for Eskom Distribution Substations by Elton Brand, Eskom Distribution and Ulrich Minnaar, Eskom ERID and Wilfred Fritz, School of Electrical Engineering, Cape Peninsula
More informationThe Criticality of Cooling
Reliability Solutions White Paper January 2016 The Criticality of Cooling Utilities, power plants, and manufacturing facilities all make use of cooling towers for critical heat transfer needs. By cycling
More informationResearch Article. Fault diagnosis of power transformer based on chemical properties of insulation oil
Available online www.jocpr.com Journal of Chemical and Pharmaceutical Research, 015, 7(3):83-88 Research Article ISSN : 0975-7384 CODEN(USA) : JCPRC5 Fault diagnosis of power transformer based on chemical
More informationYou Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services
You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services Why Failures Occur Insulation Failure - Every electrical component is comprised of
More informationWhite Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology:
Title: Comparison of Chemical Sensor and NDIR Technologies TSN Number: 25 File:\\MII- SRV1\Metron\Bridge_Analyzers\Customer_Service_Documentation\White_Papers\25_G en EGA NDIR vs Chemical Sensor.docx Created
More informationUltima. X Series Gas Monitor
Ultima X Series Gas Monitor Safety Manual SIL 2 Certified " The Ultima X Series Gas Monitor is qualified as an SIL 2 device under IEC 61508 and must be installed, used, and maintained in accordance with
More informationNordel GRID DISTURBANCE AND FAULT STATISTICS
Nordel GRID DISTURBANCE AND FAULT STATISTICS Table contents Table contents Page 1 Introduction... 3 1.1 Contact persons... 4 1.2 Guidelines the statistics... 4 1.3 Voltage levels in the Nordel network...
More informationRICK FAUSEL, BUSINESS DEVELOPMENT ENGINEER TURBOMACHINERY CONTROL SYSTEM DESIGN OBJECTIVES
RICK FAUL, BUSINESS DEVELOPMENT ENGINEER TURBOMACHINERY CONTROL SYSTEM DESIGN OBJECTIVES The primary design objective for any turbomachinery control system should be to maintain or maximize machine and
More informationPower Transformer Fault Diagnosis Based on Dissolved Gas Analysis Using a Fuzzy Neural Network Approach in a Real Data Base
Power Transformer Fault Diagnosis Based on Dissolved Gas Analysis Using a Fuzzy Neural Network Approach in a Real Data Base Michel B. Hell 1, Marcos F. S. V. D`Angelo and Pyramo P. Costa Jr. 1 1 Programa
More informationDescribe Flammable Gas Measurement
Training Module Describe Flammable 100% 90% C 80% No Combustion 70% 60% 50% 40% 30% 20% UEL B Combustion No Combustion 10% 0% LEL A Human Development HDC Human Development All rights reserved. No part
More informationTyres are a major cost centre on any site
Tyres are a major cost centre on any site How do you engage a maximum return on your tyre investment? TyreSafe Australia delivers a tyre pressure monitoring system (TPMS) to constantly check your tyres
More informationANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS
Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This
More informationDiagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers
DIAGNOSTICS Bushings are a critical part of the transformer, and their failures often have destructive consequences for the transformer, with a high risk of fire ABSTRACT Bushings are highly stressed parts
More informationTRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA
21, rue d Artois, F-75008 PARIS CIGRÉ-807 2016 CIGRÉ Canada Conference http : //www.cigre.org Vancouver, BC Canada, October 17-19, 2016 TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS J. J. DUKARM 1
More informationChapter Pipette service & maintenance. Pipette specifications according to ISO Repair in the lab or return for service?
Pipette specifications according to ISO 8655 Chapter 5 5.1 The ISO 8655 standard gives the accuracy and precision limits as both absolute and relative values. Specifications will depend on the technique
More information* Analysis of TCG ( Total Combustible Gas ) and 6 kinds of Gases * High Sensitivity for C 2
Portable DGA Dissolved Gas Analyzer MITSUBISHI Portable Dissolved Gas Analyzer (PGA-300) is used to analyze 6 kinds of dissolved gases in transformer oil, thereby improving prompt action
More informationTotal Tank Protection
Total Tank Protection Inside and Out Fully integrated solutions for advancing safety, emissions control and maintaining product integrity. Overcome Operational Challenges Mismatched and incompatible multi-vendor
More informationFail Operational Controls for an Independent Metering Valve
Group 14 - System Intergration and Safety Paper 14-3 465 Fail Operational Controls for an Independent Metering Valve Michael Rannow Eaton Corporation, 7945 Wallace Rd., Eden Prairie, MN, 55347, email:
More informationIST-203 Online DCS Migration Tool. Product presentation
IST-203 Online DCS Migration Tool Product presentation DCS Migration Defining the problem Table of contents Online DCS Migration Tool (IST-203) Technical background Advantages How to save money and reduce
More informationOxygen Measurement Systems High Reliability and Wide Application Coverage
Introduction High Process Efficiency Under Any Condition Oxygen Measurement Systems High Reliability and Wide Application Coverage METTLER TOLEDO provides sensors to measure dissolved oxygen (DO) in demanding
More informationApplications Note: Use of "pentane equivalent" calibration gas mixtures
Introduction The gas that is used to verify accuracy is every bit as important as the detector itself when it comes to worker safety. Choosing (and using) the right mixture is critical to the success of
More informationReliability of Safety-Critical Systems Chapter 4. Testing and Maintenance
Reliability of Safety-Critical Systems Chapter 4. Testing and Maintenance Mary Ann Lundteigen and Marvin Rausand mary.a.lundteigen@ntnu.no RAMS Group Department of Production and Quality Engineering NTNU
More information5.1 Introduction. Learning Objectives
Learning Objectives 5.1 Introduction Statistical Process Control (SPC): SPC is a powerful collection of problem-solving tools useful in achieving process stability and improving capability through the
More informationThe Role of Gas Monitoring in the Prevention and Treatment of Mine Fires
University of Wollongong Research Online Coal Operators' Conference Faculty of Engineering and Information Sciences 28 The Role of Gas Monitoring in the Prevention and Treatment of Mine Fires D. Brady
More informationDegassing ERC KK Saitama, Japan
Degassing Degassing Solutions IDEX Health & Science degassers improve fluidic instrument precision and reliability by removing dissolved gases from fluids before they outgas and form problem-causing bubbles
More informationON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.
Décimo Tercer Encuentro Regional Iberoamericano de CIGRÉ [13 th Iberian- American Regional Conference of CIGRÉ] Puerto Iguazú, Argentina - May 24 to 28, 2009 ON-LINE MONITORING OF REGULATOR TRANSFORMER
More informationCourse Reactor & Auxiliaries - Module 3 - Moderator Cover Gas. Module 3 GAS SYSTEM
Approval/ssue Module 3 Course 233 - Reactor & Auxiliaries - Module 3 - Moderator Cover Gas MODERATOR COVER GAS SYSTEM OBJECTIVES: Mter completing this module you will be able to: 3.1 State the lowerexplosive
More informationUnderstanding safety life cycles
Understanding safety life cycles IEC/EN 61508 is the basis for the specification, design, and operation of safety instrumented systems (SIS) Fast Forward: IEC/EN 61508 standards need to be implemented
More information2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications
Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity
More informationImproving Smelt Dissolving Tank TTA Control at Zellstoff-Celgar. Coyle, Irene; Russell, Shawn; Zellstoff Celgar LLP
Improving Smelt Dissolving Tank TTA Control at Zellstoff-Celgar Coyle, Irene; Russell, Shawn; Zellstoff Celgar LLP Vivek Rajbhandari, Mario Leclerc, Morissette, Laurier; TEXO Consulting and Controls Inc.
More informationTime Pressure Dispensing
Time Pressure Dispensing by Doug Dixon, GDM Product Manager What is time pressure dispensing? Time pressure is a method of dispensing liquid materials (surface mount adhesives and gasketing materials)
More informationThe Real Cost of Not Testing!
The Real Cost of Not Testing! Michael J Smith Smithmj@btinternet.com 1 Nordic Test Forum Agenda Market Trends Manufacturing Test and Inspection Strategies Cost of Test Models Where are the costs in Test
More informationSession Number: 3 High Voltage Power Transformer Dissolved Gas Analysis, Measurement and Interpretation Techniques
Session Number: 3 High Voltage Power Transformer Dissolved Gas Analysis, Measurement and Interpretation Abstract Norazhar Abu Bakar and A.Abu-Siada Department of Electrical and Computer Engineering, Curtin
More informationOverview. SEMEMI216 SQA Unit Code HF4G 04 Carrying out fault location on fluid power equipment and circuits
Overview This standard identifies the competences you need to locate faults on fluid power equipment and circuits, on mobile or static plant, in accordance with approved procedures. You will be required
More informationThe use of Control Charts with Composite materials. E. Clarkson, Statistician ASQ Certified Quality Engineer
The use of Control Charts with Composite materials E. Clarkson, Statistician ASQ Certified Quality Engineer Control Charts Everything varies at least a little bit. How can you tell when a process is just
More informationPreliminary Biology Assessment Task #1. Part 1 is to be completed and handed in before the start of period 1 on Friday 13/05/2016.
Preliminary Biology Assessment Task #1 Assessment Overview: There are THREE (3) parts to this assessment. Part 1: Research and planning; To be done in own time. Part 1 is to be completed and handed in
More information" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>
" High Voltage Switch Yards & How Safe are these really" High Voltage Forum Brisbane 2013 Duty of Care As part of an asset owner Duty of care
More informationSF 6 Product Guide. Gas Analysis Instruments and Accessories
SF 6 Product Guide Gas Analysis Instruments and Accessories Cambridge Sensotec Ltd specialises in the design and manufacture of gas analysis equipment under the Rapidox brand name. Based in the UK, the
More informationFLOWSIC100 Flare Challenges in Ultrasonic Flare meter field installations. History of Evolution
FLOWSIC100 Flare Challenges in Ultrasonic Flare meter field installations Mart Gloudemans, Sebastian Stoof, Sven Holzbächer SICK Germany History of Evolution 1 Introduction SICK FLOWSIC100 has track record
More informationOUR EXPERIENCE WITH THE PREDICTIVE MONITORING SYSTEM FOR HIGH VOLTAGE TRANSFORMERS INSTALLED IN BRASKEM'S PLANTS
OUR EXPERIENCE WITH THE PREDICTIVE MONITORING SYSTEM FOR HIGH VOLTAGE TRANSFORMERS INSTALLED IN BRASKEM'S PLANTS José Rafael dos Santos (2) 2 Silas Sampietri Costa (3) 3 Gilberto Amorim Moura (4) 4 Daniel
More informationWhat I have learned about SF 6 gas testing.a Practical explanation
What I have learned about SF 6 gas testing.a Practical explanation Over the past few years, testing of SF6 gas quality has become increasingly important and with the EPA in USA, setting guidelines for
More informationMechanical Ventilation
Mechanical Ventilation Understanding Modes Rob Chatburn, RRT-NPS, FAARC Research Manager Respiratory Therapy Cleveland Clinic Associate Professor Case Western Reserve University 1 Overview Characteristics
More informationPREDICTING HEALTH OF FINAL CONTROL ELEMENT OF SAFETY INSTRUMENTED SYSTEM BY DIGITAL VALVE CONTROLLER
PREDICTING HEALTH OF FINAL CONTROL ELEMENT OF SAFETY INSTRUMENTED SYSTEM BY DIGITAL VALVE CONTROLLER Riyaz Ali FIELDVUE Business Development Manager Fisher Controls Int'l., LLC. Marshalltown, IA 50158
More informationVariable Area Flow Meters
Variable Area Flow Meters Over sixty years of variable area meter expertise Brooks started designing and manufacturing variable area (VA) meters, also referred to as rotameters, in 1946. Now, with more
More informationPTB Ex PT Scheme. Procedure Instruction of program Explosion Pressure - Test Round 2017
Procedure Instruction of program Explosion Pressure - Test Round 2017 Content 1 General Performance... 2 2 Measurand / Characteristic of interest... 2 3 Test Item and Configurations... 2 3.1 Components...
More informationAccelerate Your Riverbed SteelHead Deployment and Time to Value
SteelHead Implementation Service Accelerate Your Riverbed SteelHead Deployment and Time to Value Proven Methodologies to Increase Adoption and Utilization Your organization has selected SteelHead appliances
More informationDETERMINATION OF SAFETY REQUIREMENTS FOR SAFETY- RELATED PROTECTION AND CONTROL SYSTEMS - IEC 61508
DETERMINATION OF SAFETY REQUIREMENTS FOR SAFETY- RELATED PROTECTION AND CONTROL SYSTEMS - IEC 61508 Simon J Brown Technology Division, Health & Safety Executive, Bootle, Merseyside L20 3QZ, UK Crown Copyright
More information29th Monitoring Research Review: Ground-Based Nuclear Explosion Monitoring Technologies
IMPROVED CALIBRATION AND OPERATION OF A STABLE-GAS QUANTIFICATION MANIFOLD AS PART OF A RADIOXENON COLLECTION SYSTEM ABSTRACT Richard M. Williams, James C. Hayes, and Randy R. Kirkham Pacific Northwest
More informationModel Description
LEAKHUNTER Plus LEAKHUNTER Plus Model 8066 Description The MATHESON LEAKHUNTER Plus is a truly universal leak detector. Extensive R&D has produced a multi-functional leak detector engineered to perform
More informationUsing Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands
21, rue d Artois, F-75008 PARIS CIGRE US National Committee 2012 Grid of the Future Symposium http : //www.cigre.org Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems
More informationLow gas volume & flow measurements made easier Gas Endeavour
Low gas volume & flow measurements made easier Gas Endeavour www.bioprocesscontrol.com Low gas volume and flow high accuracy and precision Measure gas volume and flow for a wide range of applications The
More informationEtO Micro-Dose Sterilization
EtO Micro-Dose Sterilization www.sterility.com www.anpro.com Gas Diffusion Technolog y Andersen Products has been in the gas sterilization business for over three decades. Our sterilizers are the most
More informationSEMEMI SQA Unit Code H2AP 04 Carrying out fault location on electrical equipment and circuits
Carrying out fault location on electrical equipment and circuits Overview This unit identifies the competences you need to locate faults on electrical equipment and circuits, in accordance with approved
More informationFUGITIVE EMISSIONS EXPERIMENTAL MEASUREMENTS AND EQUIVALENCY
FUGITIVE EMISSIONS EXPERIMENTAL MEASUREMENTS AND EQUIVALENCY ABSTRACT Jay Abrahimzadeh Joe Steinke Control Components Inc. Fugitive Emissions requirements, compliance, and use have gained momentum in the
More informationIngersoll Rand. X-Series System Automation
Ingersoll Rand -Series System Automation Energy Savings on Demand! Ingersoll Rand As much as 20% to 60% of the energy used to operate compressed air systems is wasted. This is primarily due to operating
More informationHydronic Systems Balance
Hydronic Systems Balance Balancing Is Misunderstood Balancing is application of fundamental hydronic system math Balance Adjustment of friction loss location Adjustment of pump to requirements By definition:
More informationOxygen & Binary Gas Measurement and Analysis
Oxygen & Binary Gas Measurement and Analysis Protect processes, reduce costs and maintain quality Oxygen & Binary Gas Measurement and Analysis A range of quality process analyzers from experts in control
More informationThe M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions
The M-Series Eletta Flow Meter High accuracy DP Flow Meter with multiple functions Flow Meter with multiple functions for gases and liquids M3 The M-series Flow Meter, with its versatile and user-friendly
More informationKeeping your critical equipment up and running. What the LifeSense system can do for you. LifeSense technology: monitors in real time
Keeping your critical equipment up and running Unexpected hydraulic hose failure poses a significant challenge to hydraulic customers around the globe. Asset downtime and production loss, human safety,
More informationAxpo Power Ltd. 2) GE Grid Solutions
PS 3 SF6-free 123 kv Substation Solution to meet Axpo s sustainability strategy C. LINDNDER 1), D. GAUTSCHI 2) 1) Axpo Power Ltd. 2) GE Grid Solutions SUMMARY As it is the strategic goal of Axpo Power
More informationRapid and Reliable Detection of Dissolved Gases in Water
Rapid and Reliable Detection of Dissolved Gases in Water Andrea Caruso and Massimo Santoro Thermo Fisher Scientific, Milan, Italy Application Note 005 Key Words Chromeleon CDS, Environmental, Fracking,
More informationCASE STUDY. Compressed Air Control System. Industry. Application. Background. Challenge. Results. Automotive Assembly
Compressed Air Control System Industry Automotive Assembly Application Savigent Platform and Industrial Compressed Air Systems Background This automotive assembly plant was using over 40,000 kilowatt hours
More informationBusiness Plan Presentation
2019 Department of Water Resources Business Plan Presentation Wednesday, August 29, 2018 Mission To Provide Superior Water Services at an Excellent Value Vision To be widely recognized as a leader in the
More informationUsing P-T Analysis As A Service Tool
Using P-T Analysis As A Service Tool Manufacturers of refrigerants, controls, other suppliers distribute hundreds of thouss of pressure-temperature charts to the trade every year. It would be rare indeed
More informationTransformer Reliability
Transformer Reliability A prac'cal approach to achieving life expectancy Garth Cuthbert Nov 2015 Transformer Reliability 3 x 1000 kva OFW 1ph 11,000 800 Volts In service since 1915 What contributes to
More informationAutomated Determination of Dissolved Gases in Water Anne Jurek
Automated Determination of Dissolved Gases in Water Anne Jurek Abstract: Tapping the natural gas reservoirs throughout the United States has long been a viable solution for energy independence; however
More informationApplied Technology and Best Practices in CEE. Conference
Geoinform Applied Technology and Best Practices in CEE Conference THE DEVELOPMENT OF MUD GAS LOGGING SYSTEMS AND THEIR ROLE IN HYDROCARBON EXPLORATION Sándor Pugner GEOINFORM Ltd. Budapest, 17 November
More informationCourses of Instruction: Controlling and Monitoring of Pipelines
Courses of Instruction: Controlling and Monitoring of Pipelines Date December 2010 Dr. Peter Eschenbacher Partner Angergraben 4 85250 Altomünster Germany Tel. +49-(0)8254 / 99 69 57 Fax +49-(0)8254 / 99
More information