1 24th International Conference & Exhibition on Electricity Distribution (CIRED) June 2017 Session 1: Network components Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers Young Zaidey Yang Ghazali Asset Management Department, Tenaga Nasional Berhad, Petaling Jaya, Selangor, Malaysia ISSN doi: /oap-cired Abstract: TNB has developed an asset management framework in accordance with ISO 55001:2014. One of the key elements of the framework is the asset life cycle management. This study presents TNB experience in managing the on-load tap changers (OLTC) over their complete lifecycle to improve performance and reliability. Using failure mode, effect and criticality analysis based on the previous failure data, lifecycle management strategies for OLTC have been identified. It covers the main activities over the lifecycle stages namely design, operation and. Adoption of new technology in the design, enhancement in condition assessment and effective implementation of conditionbased were amongst the strategies implemented. Finally, these strategies were validated through field evaluation and lifecycle cost analysis prior to the successful implementation throughout TNB. 1 Introduction Presently, there are 1260 power transformers rated up to 33 kv with on-load tap changer (OLTC), installed in TNB medium-voltage distribution network with capacity ranging from 7.5 to 30 MVA. About 70% of the power transformers and their respective OLTC are aged between 15 and 25 years. Out of the total population, 95% of the OLTC is of in-tank oil-immersed selector switch type with transition resistors or also known as oil-switch-type OLTC as shown in Fig. 1, which combines both functions of tap selector and diverter switch in one oil-filled compartment. The typical number of tap change operation of the OLTC in TNB distribution ranged between 2000 and 5000 tap change per year. Most power transformers studies indicated that the main cause of power transformers failures is the OLTC [1] since it has mechanical parts that are in constant movement. In TNB distribution network, there are seven cases involving permanent damage of OLTC since In most failure cases, it has caused prolonged power interruption, often due to severity of damage and timely replacement, as the result of unavailability of spares and incompatibility with the existing design. The root causes of failures are often attributed to degradation and carbonization of oil as well as contact problems as illustrated in Fig. 2. During normal tap change operation, switching arcs occur in oil due to the making and breaking of currents. These arcs cause degradation and carbonization that contaminate and reduce the dielectric strength of the oil [2]. The carbonization over time causes accumulation of carbon deposits on the surface of the fiberglass cylinder that resulted in the formation of electrical treeing (Fig. 3). Without proper, the electrical treeing develops into tracking and finally phase-to-phase arcing in OLTC. This is the common mode of failure found in most of the cases resulting in the permanent damage of the OLTC involved. On the other hand, coking or low conductivity film buildup was often observed on fixed and roller contacts during OLTC. This film consists of layer of pyrolytic carbon formation that bond to the oxide layer, which was formed as the result of surface oxidation of the contacts [2]. In some cases, coking has led to erosion or contact ware and pitted marks can be visibly observed. This occurs as the result of continuous overheating, as coking worsen over time due to increased contact resistance [3]. Prolonged condition of such phenomenon may result in excessive arcing that could trip the transformer protection (Fig. 4). Realising the needs to reduce the risk of OLTC failures, asset management strategies for OLTC have been proposed and implemented over its complete lifecycle. Thus, this paper describes TNB approach and experience in managing the lifecycle of OLTC in distribution power transformer to improve its performance and reliability. 2 Failure mode effect and criticality analysis (FMECA) FMECA as shown in Table 1 has been used to determine the most appropriate asset lifecycle management strategy for OLTC based on the actual findings on OLTC failures [4]. FMECA evaluation on other components of the OLTC such as motor drive and oil surge relay are not discussed in this paper since severity of failure of these components are still low. In addition, these components follow the standard design based on the manufacturer and type of OLTC. Furthermore, the operation and requirement of these components only involve visual inspection and functional check, which are very minimal. 3 OLTC lifecycle management strategies The complete lifecycle of an asset in accordance with asset management requirements of ISO 55001:2014 is illustrated in Fig. 5, where the activities at every stage of the lifecycle are also shown. Based on the FMECA in Table 1, TNB has identified the key activities at various lifecycle stages that can contribute to mitigate the causes of failure and improve the performance and reliability of power transformers as a whole. The lifecycle management strategies for OLTC based on these key activities are further discussed in the following subchapters. 3.1 Improving design and specification Adoption of vacuum switch OLTC to mitigate the degradation and carbonization of oil in the OLTC 303

2 Fig. 1 In-tank oil-immersed selector switch type OLTC with transition resistors used in TNB distribution Fig. 2 Root cause analysis of typical OLTC failures in TNB distribution power transformers compartment as well as coking of arcing contacts: Degradation and carbonization of oil as described above are the most common causes of failure that has resulted in failure and permanent damage of the OLTC. In order to mitigate this problem, TNB has adopted the use of vacuum switch OLTC, shown in Fig. 6, that confines switching in interrupted vacuum bottles. As the results, this helps to prevent contamination of oil due to carbonization and hence lower the rate of oil degradation due to switching arcs. Furthermore, with the absence of oil inside the vacuum switch, formation of low conductivity film and deposition of carbon that lead to coking on the contacts surface will no longer occur. With the arc quenching property of the vacuum switch, contact erosion and thus contact wear is minimised and thus reduces costs. Prior to the adoption of the use of vacuum switch type OLTC in 2011, a field trial was conducted in 2007 to evaluate its performance Adoption of free self-dehydrating breather to mitigate the degradation of oil in the OLTC compartment: Degradation of oil in the OLTC is not only influenced by the switching arcs that occur due to making and braking of currents during on-load tap change operation, but also affected by the presence of moisture in the oil. Even with the use of vacuum switch type OLTC, moisture can still be presence due to leakage or in most cases due to lack of of the OLTC dehydrating breather (Fig. 7). In order to mitigate this problem, TNB has adopted the use of free self-dehydrating breather as depicted in Fig. 8. The breather has a heating element mounted within the container to heat the desiccant at selected intervals with temperature sensor to monitor the correct operation of the heater. A moisture sensor measure the humidity of the air to ensure only dehydrated air goes through the piping into the OLTC conservator. Both sensors are controlled by an electronic controller. The condensed moisture formed on the surface of the container will be expelled outwards by gravity. A field trial on the use of the self-dehydrating breather was conducted in 2007 prior to its adoption in Lifecycle cost analysis: Prior to the adoption on the use of vacuum switch type OLTC together with free self-dehydrating breather, a lifecycle cost analysis (LCCA) over the expected transformer life span of 40 years is performed to validate and compare the net present value of the total lifecycle cost of using vacuum switch type OLTC together with self-dehydrating breather, and the oil switch type OLTC. The LCCA of the two systems shown in Table 2 reveals that the use of vacuum switch type OLTC together with self-dehydrating breather could generate saving of more than RM 600,000 a year for the entire transformer population, not including saving on the avoidance of loss revenue due to OLTC failure. 3.2 Enhancing methods for condition assessment Fig. 3 Formation of electrical treeing on the cylinder s surface transition resistors used in TNB distribution resulted in tracking and arcing between phases The adoption of vacuum switch OLTC is only applied for the new power transformers. Therefore, for the existing in-service power transformers, emphasis is given on the utilisation (operation) and lifecycle stages which are discussed below assessment using oil quality analysis to detect degradation of oil in OLTC: The implementation of the condition assessment for OLTC by means of oil quality analysis involved breakdown voltage and moisture content has started since Table 3 summarises the oil quality indicator limits used for OLTC. Fig. 4 Erosion and pitted marks on the roller contacts (left) as well as carbon buildup on the fixed contacts (right) were observed during assessment using dissolved gas analysis (DGA) to detect coking of contacts: DGA has been applied to assess the condition of the OLTC since owever, the health condition of the OLTC then was not truly understood due to unavailable guide for interpretation of DGA results. In 2011, with the issue of IEEE Std. C [5], a more enhanced condition assessment method using DGA data was formulated to 304

3 Table 1 FMECA based on common findings of OLTC failures Failure mode Failure effect S Failure cause Failure mechanism Failure consequence P C arcing between phases excessive arcing between contacts permanent tracking on fibreglass cylinder damage of metal parts damage of contact contact wear off degradation and carbonisation of oil tracking as the result of accumulation of carbon deposits on the surface of cylinder M coking of contacts overheating due to increased contact resistance transformer trip by protection relays transformer trip by protection relays M M Note: S = Severity of failure, P = Probability of failure, C = Criticality, = igh, M = Medium, L = Low. Fig. 5 Lifecycle activities of an asset Fig. 8 Use of free self-dehydrating breather Table 2 Comparison of the net present value of the total lifecycle cost over the life span of 40 years per OLTC system OLTC system Initial cost, RM Operation and cost, RM Total lifecycle cost, RM oil switch type OLTC and conventional breather vacuum switch type OLTC and self-dehydrating breather 160, , , , , , Fig. 6 Vacuum switch type OLTC used in TNB distribution power transformers Table 3 Property indicators for OLTC oil quality analysis Limits Good Fair Poor Bad breakdown voltage, kv > <30 water content, ppm < >45 Fig. 7 OLTC Lack of of silica gel in the dehydrating breather of the interpret the health condition of the OLTC. The statistical model used follows the method described in Annex B of IEEE Std. C to determine two types of condition indicator limits i.e. gas concentration and gas ratio limits. The model was initially based on DGA data up to the year 2011 taken from 503 units of oil-immersed selector switch type OLTC classified as ARAB type OLTC in accordance with IEEE Std. C classification scheme. The gas concentration limits is defined in terms of a statistical outlier limit identifying extreme values of gas concentration suspected to be the results of faults or unusual stresses. The gases that are used as indicators to discriminate between normal and faulty conditions are C 2 2,C 2 4 and C 4 together with the sum of C 4,C 2 6 and C 2 4 called the total dissolved heating gases. The upper outlier limits U1, U2 and U3 were calculated for each set of gas concentration data. U3 is introduced to represent the extreme values requiring the highest attention (U3 = Q IQR where Q3: third quartile, IQR: interquartile range). Table 4 summarises the gas concentration limits for OLTC. The gas ratios that are used as indicators to discriminate between normal and faulty conditions are C 2 4 /C 2 2 and TDG/C 2 2. The gas ratio values of non-faulty OLTC operating under normal 305

4 Table 4 OLTC gas concentration limits Concentration, ppm codes Generic C 4 C 2 4 C 2 2 TDG C U1 C 2083 C 3522 C C 7000 normal (1) U1 > C U > C > C ,598 > C > C caution (2) U2 > C U > C > C ,004 > C ,029 > C warning (3) C >U3 C > 4423 C > 7617 > > danger (4) Note: C = gas concentration. Table 5 Ratio OLTC gas ratio limits Generic C 2 4 /C 2 2 TDG/C 2 2 codes R C 090 R R normal (1) C 090 > R C > R > R caution (2) C 095 > R C > R > R warning (3) R >C 099 R > R > danger (4) Note: R = gas ratio. Table 6 Results codes Interpretation of DGA results for OLTC indicator Interpretation R = 1 and C 2 good normal OLTC operation R = 1 and fair light coking or deterioration of arcing contacts, or unusually high frequency of tap change operation or high load current causing heating of transition resistors 1<R 3 and poor coking or increased deterioration of R = 4 and bad arcing contacts or severe deterioration Table 6 gives the overall interpretation to facilitate the understanding on the condition of the arcing contacts based on the results of the gas concentrations and ratios. Table 7 compares the outcome of the DGA results on 745 units of OLTC interpreted using the above method with the same DGA results using the Duval s triangle method for load tap changers [6]. 3.3 Effective implementation of condition-based Based on the enhanced condition assessment method above, an overall health condition of the OLTC is derived as shown in Table 8 that provides recommended actions for mitigations as tabulated in Table 9. Based on the health condition and recommended mitigating actions, more effective planning can be executed where work can now be prioritised according to the criticality of the OLTC condition as shown in the example given in Table 10. The assessment was validated through visual inspection of the OLTC condition. Fig. 9 shows typical observations found during. Validation of the assessment was also carried out by means of dynamic current measurement using dynamic winding resistance technique and it is discussed elsewhere [7]. Table 8 Overall health condition of the OLTC Table 7 Comparison on the number of problematic OLTCs detected using TNB condition assessment method derived from IEEE Std. C and Duval s triangle for OLTC Fault identification TNB OLTC assessment method OLTC Duval s triangle method Overall health condition Oil quality analysis results Good Fair Poor Bad DGA results good fair poor bad total no. of possible faults detected no. of severe thermal faults with moderate or no. of thermal faults in progress with light coking or heating of transition resistors Table 9 Recommended mitigating actions based on the overall health condition of the OLTC codes indicator Recommended actions conditions are described by the percentiles of the lognormal distribution representing the non-outlier gas ratios. The gas ratio limits calculated for the study are based on 90th (C 090 ), 95th (C 095 ), and 99th (C 099 ) percentiles of the lognormal distribution with significance level of 0.1, 0.05 and 0.01, respectively. Table 5 summarises the gas ratio limits for OLTC. It should be noted that the ratio limits in Table 5 are applied only when any of the gas concentration has reached warning limit or condition 3 in Table 4. 1 normal continue oil sampling at 12 month interval 2 caution continue oil sampling at 6 month interval 3 warning inspect for leaks and condition of silica gels. Conduct internal inspection on arcing contacts. Perform overhaul and replace oil 4 danger inspect for leaks and silica gels condition. Possible replacement of arcing contacts. Perform overhaul and replace oil 306

5 Table 10 Example of planning sheet based on the criticality of the OLTC health condition State Site TX no. TNB OLTC assessment Duval s triangle method DGA Oil quality ealth condition selangor commerce square T1 or severe selangor commerce T2 or severe square selangor proton T2 or severe selangor taman T2 coking or increased deterioration berjaya klang selangor labur bina T1 or severe selangor subang T2 or severe selangor jaya TC taman berjaya klang T1 coking or increased deterioration light contact or increased contact resistance light contact or increased contact resistance fault T3 ort2 in progress or severe arcing D2 (X3) light coking or increased contact resistance light coking or increased contact resistance bad bad warning have been identified for the implementation of the lifecycle strategy, which includes design, operation and of OLTC. Finally, validation through field evaluation and LCCA was performed to evaluate for technical and economic feasibility of the proposed technologies and methodology, prior to the successful adoption of all the strategies throughout TNB since Fig. 9 Surface erosion with pitted marks and coking of the roller contacts (left) and carbon deposits on the cylinder (right) were observed during OLTC at several sites 4 Conclusions Managing asset lifecycle is the main focus of asset management system starting from the creation of the asset, utilisation, up to its retirement. Thus, each aspect of the lifecycle activities must be strategised to optimise the usage of the asset and to strike a balance between cost, risk and performance of the asset. This paper has presented all possible mitigating actions that have become the OLTC asset management strategy at various stages of its lifecycle. Based on the FMECA, three main lifecycle activities 5 References 1 Jongen, R., Morshuis, P., Smit, J., et al.: A statistical approach to processing power transformer failure data. CIRED 19th Int. Conf., Paper 546, Erbrink, J.J., Gulski, E., Seitz, P.P.: Advanced on-site diagnosis of transformer OLTC. IEEE Int. Symp. on Electrical Insulation, 2008, pp Erbrink, J.J., Gulski, E., Smit, J.J.: assessment of OLTC using dynamic resistance measurements. Int. Conf. on V Engineering, 2010, pp BS : Guide to failure modes, effects and criticality analysis (FMEA and FMECA) 5 IEEE Std C57.139: IEEE guide for dissolved gas analysis in transformer load tap changers, Duval, M.: The Duval triangle for load tap changers, non-mineral oils and low temperature faults in transformers, IEEE Electr. Insul. Mag., 2008, 24, (6), pp Shahril, M., anum, Y., Zaidey, Y., et al.: Diagnosis of OLTC via Duval triangle method and dynamic current measurement, Proc. Eng., 2013, 68, pp

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers

Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling

More information

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS Zohra Khan 1, Avinash Paranjpe 2 1 ME Student, Electrical Power System, PES COE/ Dr. B.A.M. University, (India)

More information

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS

DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS DISSOLVED GAS ANALYSIS OF NATURAL ESTER FLUIDS UNDER ELECTRICAL AND THERMAL STRESS M. Jovalekic 1*, D. Vukovic 1 and S. Tenbohlen 1 1 Institute of Power Transmission and High Voltage Technology (IEH) University

More information

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption

Mathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption Mathieu Guertin Director Europe, Russia and Africa Morgan Schaffer Inc. Canada A cost effective strategy for smart grid technology adoption Why protecting assets? Cost of fault: $52 MILLIONS!!! Easy ROI

More information

Categorizing Faults via DGA. GE Grid Solutions M&D

Categorizing Faults via DGA. GE Grid Solutions M&D ategorizing Faults via DGA GE Grid Solutions M&D First, What Is Transformer Dissolved Gas Analysis? Sample Test Doc Diagnosis Doctors extract information about our health from our blood. Technicians extract

More information

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations

Understanding Dissolved Gas Analysis (DGA) Techniques and Interpretations By Jeff Golarz ABSTRACT The use of Dissolved Gas Analysis (DGA) as a method for determining the types of pending or occurring faults within power transformers has been in practice for many years. It has

More information

A Revised Framework for the Transformer DGA Guide

A Revised Framework for the Transformer DGA Guide A Revised Framework for the Transformer DGA Guide Jim Dukarm for WG C57.104 Spring 2007 Presentation Topics Purpose and scope of the Guide Main departures from earlier versions Definition of transformer

More information

DGA Tools: Duval Triangles and Pentagons

DGA Tools: Duval Triangles and Pentagons DGA Tools: Duval Triangles and Pentagons C. Beauchemin, TJH2b Analytical Services Inc. Initially presented at the TechCon SE Asia, Kuala Lumpur, April 10, 2017 This presentation use some material from

More information

Development of a Plant Health Index for Eskom Distribution Substations

Development of a Plant Health Index for Eskom Distribution Substations Development of a Plant Health Index for Eskom Distribution Substations by Elton Brand, Eskom Distribution and Ulrich Minnaar, Eskom ERID and Wilfred Fritz, School of Electrical Engineering, Cape Peninsula

More information

Dissolved Gas Analysis - Past, Present and Future

Dissolved Gas Analysis - Past, Present and Future I. INTRODUCTION Dissolved Gas Analysis - Past, Present and Future Fredi Jakob Weidmann-ACTI Inc. It has been well over thirty years since dissolved gas analysis, DGA, was introduced as a diagnostic tool

More information

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION

A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION A REVIEW OF DISSOLVED GAS ANALYSIS AND TRANSFORMER HEALTH CONDITION Athira K Anil 1, Archana R 2 1 PG Student, Electrical and Electronics Engineering, FISAT, Kerala, India 2 Associate Professor, Electrical

More information

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS The 9 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 25 EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS

More information

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks Proceedings of the 4th International Conference on Systems and Control, Sousse, Tunisia, April 28-30, 2015 TuCA.2 Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks

More information

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO Atsushi Toya, Tokyo Electric Power Company, (Japan), toya.atsushi@tepco.co.jp Shinsuke Nasukawa, Tokyo Electric Power Company, (Japan), nasukawa.shinsuke@tepco.co.jp

More information

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil

Research Article. Fault diagnosis of power transformer based on chemical properties of insulation oil Available online www.jocpr.com Journal of Chemical and Pharmaceutical Research, 015, 7(3):83-88 Research Article ISSN : 0975-7384 CODEN(USA) : JCPRC5 Fault diagnosis of power transformer based on chemical

More information

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing

TRANSFORMER SERVICE. Dissolved gas analysis and oil condition testing TRANSFORMER SERVICE Dissolved gas analysis and oil condition testing D I S S O LV E D G A S A N A LY S I S A N D O I L C O N D I T I O N T E S T I N G Transformer diagnostic services at ABB perform dissolved

More information

Testing Distribution Switchgear for Partial Discharge

Testing Distribution Switchgear for Partial Discharge Testing Distribution Switchgear for Partial Discharge Mr. Neil Davies Affiliation: EA Technology Ltd, UK; neil.davies@eatechnology.com ABSTRACT Over the past 30 years handheld instrumentation has been

More information

For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated

For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated COLUMN For many applications, there is no technical reason anymore to keep the oil volumes of a transformer with vacuum type OLTC separated 20 TRANSFORMERS MAGAZINE Volume 4, Issue 2 Rainer FROTSCHER Common

More information

Technical Standards and Legislation: Risk Based Inspection. Presenter: Pierre Swart

Technical Standards and Legislation: Risk Based Inspection. Presenter: Pierre Swart Technical Standards and Legislation: Risk Based Inspection Presenter: Pierre Swart Agenda Change in Legislation. Where RBI fits in. Application to implement RBI. RBI concepts. Elements of an RBI analysis.

More information

Simple Time-to-Failure Estimation Techniques for Reliability and Maintenance of Equipment

Simple Time-to-Failure Estimation Techniques for Reliability and Maintenance of Equipment F E A T U R E A R T I C L E Simple Time-to-Failure Estimation Techniques for Reliability and Maintenance of Equipment Key Words: Reliability and maintenance, time-to-failure estimation, reactive maintenance

More information

C Dissolved Gas Analysis Of Load Tap Changers. Working Group

C Dissolved Gas Analysis Of Load Tap Changers. Working Group C57.139 Dissolved Gas Analysis Of Load Tap Changers Working Group Data Analysis Update Spring 2007 Data Analysis Agenda 1. 1. Update of of activity 2. 2. Data analysis 3. 3. Review examples in in reverse

More information

Availability analysis of railway track circuit

Availability analysis of railway track circuit Availability analysis of railway track circuit A P Patra * and U Kumar Luleå Railway Research Center, Division of Operation and Maintenance Engineering, Luleå University of Technology, Sweden Abstract:

More information

Since the beginning of production of oil for transformers

Since the beginning of production of oil for transformers EVENTS DIAGNOSTICS Photo courtesy of Končar D&ST, Zagreb, Croatia Chromatographic analysis of gases from the transformer The process of creating and detecting gases in the transformers ABSTRACT Given the

More information

Hydro Plant Risk Assessment Guide

Hydro Plant Risk Assessment Guide September 2006 Hydro Plant Risk Assessment Guide Appendix E10: Compressed Air System Condition Assessment E10. 1 GENERAL Compressed air systems are key components at hydroelectric power plants. Compressed

More information

MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC

MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC MITIGATE GAS COMBUSTION IN CASE OF INTERNAL ARC Jérôme DOUCHIN Yann CRESSAULT Raphael Danjoux Schneider Electric France Toulouse University France FLIR France Jerome.douchin@ cressault@laplace.univ-tlse.fr

More information

A New Approach for Transformer Incipient Fault Diagnosis Based on Dissolved Gas Analysis (DGA)

A New Approach for Transformer Incipient Fault Diagnosis Based on Dissolved Gas Analysis (DGA) Nova Explore Publications Nova Journal of Engineering and Applied Sciences Vol. 3(2), 2014: 1-7 PII: S229279211400008-3 www.novaexplore.com Research Article A New Approach for Transformer Incipient Fault

More information

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI

Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI Dissolved Gas Analysis An Early Identification of Faults in High Voltage Power Equipment using MATLAB GUI A THESIS SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF Master of Technology

More information

You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services

You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services Why Failures Occur Insulation Failure - Every electrical component is comprised of

More information

Online DGA-monitoring of power transformers

Online DGA-monitoring of power transformers Online DGA-monitoring of power transformers Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 Vaisala Webinar content 1. Dissolved gases why and which gases 2. Fault

More information

Nandkumar Wagh, D.M. Deshpande

Nandkumar Wagh, D.M. Deshpande International Journal of Scientific & Engineering Research, Volume 4, Issue 9, September-2013 2503 Fuzzy Decision on Transformer Fault Diagnosis using Dissolved Gas Analysis and IEC Ratio Codes Nandkumar

More information

COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE SUMMARY

COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE SUMMARY COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE R. L. Middleton, P. Eng. Manitoba Hydro, Winnipeg, Canada SUMMARY Very low temperatures stress

More information

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM.

PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM. Australasian Universities Power Engineering Conference (AUPEC 2004) 26-29 September 2004, Brisbane, Australia PROPOSAL FOR AN IMPROVEMENT IN TRANSFORMER DIAGNOSIS BY DGA USING EXPERT SYSTEM. N.K.Dhote*

More information

Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany

Dynamic Behaviour of Fault Gases and Online Gas Sensors. Germany 21, rue d Artois, F-75008 PARIS A2-116 CIGRE 2016 http : //www.cigre.org Dynamic Behaviour of Fault Gases and Online Gas Sensors S. TENBOHLEN 1, I. HÖHLEIN 2, M. LUKAS 3, A. MÜLLER 4, K. SCHRÖDER 5, U.

More information

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers

Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers Comparison of Different DGA (Dissolved Gas Analysis) Methods for the Condition Assessment of Power Transformers P. Werle, C. Radigk ABB Transformatoren GmbH Halle, Gemany peter.werle@de.abb.com W. Sorgatz

More information

Using Reliability Centred Maintenance (RCM) to determine which automated monitoring systems to install to new and existing equipment

Using Reliability Centred Maintenance (RCM) to determine which automated monitoring systems to install to new and existing equipment Using Reliability Centred Maintenance (RCM) to determine which automated monitoring systems to install to new and existing equipment CHRIS JAMES RELIABILITY MANAGEMENT LTD Cairo, November 2018 The rate

More information

i) Filtration machine, measuring equipment and other related machinery

i) Filtration machine, measuring equipment and other related machinery 5 MVA TRANSFORMER SERVICE AND MAINTENANCE FOR TATA CHEMICALS MAGADI. SAFETY MEASURES AND REQUIREMENTS i) A thorough site risk assessment to be done before commencement of work. ii) All personnel involved

More information

Fitness for Service Assessment of Ageing Pressure Vessel Experiencing External Corrosion: A Case Study

Fitness for Service Assessment of Ageing Pressure Vessel Experiencing External Corrosion: A Case Study The International Journal Of Engineering And Science (IJES) Volume 6 Issue 2 Pages PP 12-16 2017 ISSN (e): 2319 1813 ISSN (p): 2319 1805 Fitness for Service Assessment of Ageing Pressure Vessel Experiencing

More information

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA

TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS. Delta-X Research Inc, Victoria BC, and 2 IREQ, Varennes QC CANADA 21, rue d Artois, F-75008 PARIS CIGRÉ-807 2016 CIGRÉ Canada Conference http : //www.cigre.org Vancouver, BC Canada, October 17-19, 2016 TRANSFORMER RELIABILITY AND DISSOLVED-GAS ANALYSIS J. J. DUKARM 1

More information

C I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005

C I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005 RELIABILITY AND LONG TIME BEHAVIOUR OF MV-DISTRIBUTION SWITCHGEAR IN SEVERE ENVIRONMENTAL CONDITIONS - EXAMINATION OF SF 6 -INSULATED RING MAIN UNITS (RMU) UP TO 20 YEARS IN SERVICE. B. I. Oftedal, Siemens

More information

Proof Testing A key performance indicator for designers and end users of Safety Instrumented Systems

Proof Testing A key performance indicator for designers and end users of Safety Instrumented Systems Proof Testing A key performance indicator for designers and end users of Safety Instrumented Systems EUR ING David Green BEng(hons) CEng MIET MInstMC RFSE Ron Bell OBE BSc CEng FIET Engineering Safety

More information

Infrared Thermography Inspection Guidelines. Date Issued:

Infrared Thermography Inspection Guidelines. Date Issued: Infrared Thermography Inspection Guidelines Date Issued: 2002 01 29 Created By: Approved By: L. Henderson G. Durnford Table Of Contents Table Of Contents...i POLICY STATEMENT...1 APPLICABLE INTERNATIONAL

More information

Monitoring transformers with infrared cameras

Monitoring transformers with infrared cameras APPLICATION NOTE Monitoring transformers with infrared cameras Most transformers are cooled by either oil or air while operating at temperatures much higher than ambient. In fact, operating temperatures

More information

This presentation provides an overview of modern methods for minimizing the arc-flash hazard.

This presentation provides an overview of modern methods for minimizing the arc-flash hazard. Electricity is all around us. An uncontrolled release of electric energy is extremely dangerous, posing a threat to human life, causing equipment damage, and jeopardizing the manufacturing process that

More information

EZI-DRY Pty Limited ABN:

EZI-DRY Pty Limited ABN: EZI-DRY Pty Limited ABN: 98 114 507 443 PO Box 370 Phone: 02 49711993 Swansea NSW 2281 Fax: 02 49716320 Mobile: 0427587900 Email: ezidry@exemail.com.au 1. Breather operation Why EZI-DRY Breathers? Most

More information

Reliability engineering is the study of the causes, distribution and prediction of failure.

Reliability engineering is the study of the causes, distribution and prediction of failure. Reliability engineering: Reliability is the probability that a system or component will perform without failure for a specified period of time under specified operating conditions. Reliability engineering

More information

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Test instruments and recommended testing sequence 1 Outcomes of this Session describe the different

More information

TECHNICAL NOTE THROUGH KERBSIDE LANE UTILISATION AT SIGNALISED INTERSECTIONS

TECHNICAL NOTE THROUGH KERBSIDE LANE UTILISATION AT SIGNALISED INTERSECTIONS TECHNICAL NOTE THROUGH KERBSIDE LANE UTILISATION AT SIGNALISED INTERSECTIONS Authors: Randhir Karma NDip: Eng (Civil) B. Tech Eng (Civil) M Eng (Hons) (Transportation) Auckland Traffic Service Group Manager

More information

Analysis of Pressure Rise During Internal Arc Faults in Switchgear

Analysis of Pressure Rise During Internal Arc Faults in Switchgear Analysis of Pressure Rise During Internal Arc Faults in Switchgear ASANUMA, Gaku ONCHI, Toshiyuki TOYAMA, Kentaro ABSTRACT Switchgear include devices that play an important role in operations such as electric

More information

Instrumentation & Data Acquisition Systems

Instrumentation & Data Acquisition Systems Instrumentation & Data Acquisition Systems Section 3 -Level Robert W. Harrison, PE Bob@TheHarrisonHouse.com Made in USA 1 Level Section Question Which level measuring technology is the best solution when

More information

Chapter 5: Comparison of Inspection and Testing Results

Chapter 5: Comparison of Inspection and Testing Results Chapter 5: Comparison of Inspection and Testing Results Visual inspection, on-board testing, and laboratory analyses have distinct sensitivities and limitations. The results of the on-board testing can

More information

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL PRESSURE REDUCING STATION INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 0700 67 Registered in England and Wales No. 05058855

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

Advanced Test Equipment Rentals ATEC (2832) OMS 600

Advanced Test Equipment Rentals ATEC (2832) OMS 600 Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OMS 600 Continuous partial discharge monitoring system for power generators and electrical motors Condition monitoring

More information

" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>

 High Voltage Switch Yards & How Safe are these really <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd> " High Voltage Switch Yards & How Safe are these really" High Voltage Forum Brisbane 2013 Duty of Care As part of an asset owner Duty of care

More information

INTERIM ADVICE NOTE 171/12. Risk Based Principal Inspection Intervals

INTERIM ADVICE NOTE 171/12. Risk Based Principal Inspection Intervals INTERIM ADVICE NOTE 171/12 Risk Based Principal Inspection Intervals Summary This Interim Advice Note sets out the requirements and guidance for service providers using risk based inspection intervals.

More information

Optimized Maintenance Planning for Transmission Power Systems.

Optimized Maintenance Planning for Transmission Power Systems. Optimized aintenance Planning for Transmission Power Systems. Improvement of the condition indexing process Name : - Adesh Soemeer Thesis committee: - Prof. dr. Johan Smit - Ing. Peter Oomens (Joulz) -

More information

CHAPTER 4 FMECA METHODOLOGY

CHAPTER 4 FMECA METHODOLOGY CHAPTER 4 FMECA METHODOLOGY 4-1. Methodology moving into Criticality Analysis The FMECA is composed of two separate analyses, the FMEA and the Criticality Analysis (CA). The FMEA must be completed prior

More information

ANALYTICAL SERVICES MAHANGA HOLDINGS LTD

ANALYTICAL SERVICES MAHANGA HOLDINGS LTD Body ANALYTICAL SERVICES 1.PURPOSE AND SCOPE The correct use of syringe results in oil samples is of a much higher quality than other containers particularly for Dissolved Gas Analysis and Moisture measurements.

More information

PROCEDURE. April 20, TOP dated 11/1/88

PROCEDURE. April 20, TOP dated 11/1/88 Subject: Effective Date: page 1 of 2 Initiated by: Failure Modes and Effects Analysis April 20, 1999 Supersedes: TOP 22.019 dated 11/1/88 Head, Engineering and Technical Infrastructure Approved: Director

More information

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL CPX EMERGENCY STANDBY MANIFOLD INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 0700 67 Registered in England and Wales No. 05058855

More information

Leaks, contamination and closed loop control how RGAs make coating processes more profitable

Leaks, contamination and closed loop control how RGAs make coating processes more profitable Leaks, contamination and closed loop control how RGAs make coating processes more profitable Backup: What s an RGA Residual Gas Analyzer An instrument that is measuring the gas composition in a chamber

More information

Evaluation of Effectiveness and Safety of CO 2 Cleaning of Energized Contaminated Pad-Mounted Gear

Evaluation of Effectiveness and Safety of CO 2 Cleaning of Energized Contaminated Pad-Mounted Gear 1 Evaluation of Effectiveness and Safety of CO 2 Cleaning of Energized Contaminated Pad-Mounted Gear Peter Tyschenko Manager, Distribution Standards Commonwealth Edison Company Shay Bahramirad and Terry

More information

CO 2 and O 2 scrubbers

CO 2 and O 2 scrubbers CO 2 and O 2 scrubbers The CO2 scrubber Fruit breathes : it uses oxygen (O2) and produces carbon dioxide (CO2). If the concentration of carbon dioxide (carbonic acid) gets too high, the quality of the

More information

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank

MODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is

More information

Newsletter of Jointing, Welding & Cold-Formed Steel Group, HKISC UNDERWATER WELDING. Ir Dr Chan Wai Tai. Chairman of Welding Group, HKISC

Newsletter of Jointing, Welding & Cold-Formed Steel Group, HKISC UNDERWATER WELDING. Ir Dr Chan Wai Tai. Chairman of Welding Group, HKISC UNDERWATER WELDING Ir Dr Chan Wai Tai Chairman of Welding Group, HKISC When I was young, I was always fascinated by welding carried out in underwater environment. Basically, flame and water are mutual

More information

Impact Fatigue on Suction Valve Reed: New Experimental Approach

Impact Fatigue on Suction Valve Reed: New Experimental Approach Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2004 Impact Fatigue on Suction Valve Reed: New Experimental Approach Michele Libralato ACC

More information

Distribution Transformer Instruction Manual

Distribution Transformer Instruction Manual Distribution Transformer Instruction Manual TABLE OF CONTENTS SHIPPING.. 3 INSPECTION ON RECEIPT 3 HANDLING.. 4 INTERNAL INSPECTION 5 STORAGE.. 6 LOCATION 6 PREPARING FOR SERVICE 7 PUTTING INTO SERVICE

More information

Maintenance handbook

Maintenance handbook Maintenance handbook ontents HPU IDENTIFIATION SHEET... 4 1. MAINTENANE... 5 1.1 Filling level... 5 1.2 Fluid top-up... 5 1.3 Fluid replacing... 5 1.4 Fluid temperature control... 6 1.5 Functional control...

More information

HNP. HNP073 Series. Flows up to 70 L/min Fluid viscosities to 700 cst PME HNP073

HNP. HNP073 Series. Flows up to 70 L/min Fluid viscosities to 700 cst PME HNP073 F L U I D C O N D I T I O N I N G P U R I F I E R S Flows up to 70 L/min Fluid viscosities to 700 cst PME HNP073 Introduction Extending service life Reliability of systems and the life of system components

More information

Selecting Maintenance Tactics Section 4

Selecting Maintenance Tactics Section 4 ARE 24 Facilities Maintenance Management Prepared By: KAMAL A. BOGES # 2321 November 2 nd, 2003 Selecting Maintenance Tactics Section 4 Uptime Strategies for Excellence in Maintenance Management By: John

More information

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda.

ON-LINE MONITORING OF REGULATOR TRANSFORMER AT THE MARGEM DIREITA SS IN ITAIPU. M. E. G. ALVES* Treetech Sistemas Digitais Ltda. Décimo Tercer Encuentro Regional Iberoamericano de CIGRÉ [13 th Iberian- American Regional Conference of CIGRÉ] Puerto Iguazú, Argentina - May 24 to 28, 2009 ON-LINE MONITORING OF REGULATOR TRANSFORMER

More information

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys

PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys (Feb 2010) PASSENGER SHIPS Guidelines for preparation of Hull Structural Surveys Contents 1 Introduction 2 Preparations for Survey 2.1 General 2.2 Conditions for survey 2.3 Access to structures 2.4 Survey

More information

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE

MODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock

More information

Gas Network Craftsperson

Gas Network Craftsperson Gas Network Craftsperson Unit EIAU016 Carrying out Fault Diagnosis on Electrical Equipment and Circuits This assessment specification has been developed as part of the network maintenance craftsperson

More information

User Information Sheet 015

User Information Sheet 015 User Information Sheet 015 Formerly LPGA Guidance NO.84 March 2007 Inspection and Maintenance of LPG Pipework at Commercial and Industrial Premises 1. Introduction LPG pipework may, under certain conditions,

More information

MAKING ELECTRICAL A GUIDE ON HOW TO INSPECT AND TEST PORTABLE APPLIANCES SAFELY AND EFFECTIVELY

MAKING ELECTRICAL A GUIDE ON HOW TO INSPECT AND TEST PORTABLE APPLIANCES SAFELY AND EFFECTIVELY MAKING ELECTRICAL A GUIDE ON HOW TO INSPECT AND TEST PORTABLE APPLIANCES SAFELY AND EFFECTIVELY 'Published in consultation with The Health & Safety Executive' TECHNOLOGY WORK - SAFELY The Electrical Contractors'

More information

444C DUAL PERFORMANCE VALUE PACK

444C DUAL PERFORMANCE VALUE PACK (Chrome) PART NO. 44432 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of this manual before installing and using this product. SAVE THIS MANUAL

More information

LOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES

LOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES LOW-CURRENT INTERRUPTION IN SF 6-ALTERNATIVES Magne SAXEGAARD Elham ATTAR Martin KRISTOFFERSEN ABB - Norway ABB - Norway ABB - Norway magne.saxegaard@no.abb.com elham.attar@no.abb.com martin.kristoffersen@no.abb.com

More information

The Criticality of Cooling

The Criticality of Cooling Reliability Solutions White Paper January 2016 The Criticality of Cooling Utilities, power plants, and manufacturing facilities all make use of cooling towers for critical heat transfer needs. By cycling

More information

Axpo Power Ltd. 2) GE Grid Solutions

Axpo Power Ltd. 2) GE Grid Solutions PS 3 SF6-free 123 kv Substation Solution to meet Axpo s sustainability strategy C. LINDNDER 1), D. GAUTSCHI 2) 1) Axpo Power Ltd. 2) GE Grid Solutions SUMMARY As it is the strategic goal of Axpo Power

More information

Ground Fault Circuit Interrupter(GFCI) Policy

Ground Fault Circuit Interrupter(GFCI) Policy NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com

More information

Relative Pressure Sensor for Automobile Fuel Tanks

Relative Pressure Sensor for Automobile Fuel Tanks Relative Pressure Sensor for Automobile Fuel Tanks KATO, Hirofumi ASHINO, Kimihiro SATO, Eisuke ABSTRACT In recent years, there has been increasing regulation to reduce the environmental burden of automobiles.

More information

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers

Diagnostics of HV bushings through oil sampling and analysis. Experience with GSU transformers DIAGNOSTICS Bushings are a critical part of the transformer, and their failures often have destructive consequences for the transformer, with a high risk of fire ABSTRACT Bushings are highly stressed parts

More information

DATA ITEM DESCRIPTION Title: Failure Modes, Effects, and Criticality Analysis Report

DATA ITEM DESCRIPTION Title: Failure Modes, Effects, and Criticality Analysis Report DATA ITEM DESCRIPTION Title: Failure Modes, Effects, and Criticality Analysis Report Number: Approval Date: 20160106 AMSC Number: N9616 Limitation: No DTIC Applicable: Yes GIDEP Applicable: Yes Defense

More information

Service & Support. Questions and Answers about the Proof Test Interval. Proof Test According to IEC FAQ August Answers for industry.

Service & Support. Questions and Answers about the Proof Test Interval. Proof Test According to IEC FAQ August Answers for industry. Cover sheet Questions and Answers about the Proof Test Interval Proof Test According to IEC 62061 FAQ August 2012 Service & Support Answers for industry. Contents This entry originates from the Siemens

More information

6.6 Relief Devices. Introduction

6.6 Relief Devices. Introduction 6.6 Relief Devices Introduction Relief devices are used to help prevent a catastrophic failure of equipment and/or minimize the effects of any unanticipated or uncontrolled events. As such, relief devices

More information

MICRO DIAPHRAGM GAS PUMPS

MICRO DIAPHRAGM GAS PUMPS MICRO DIAPHRAGM GAS PUMPS DATA SHEET E 5 NMP83KNE NMP85KPDC NMP85.1.2KPDC-B Concept The micro diaphragm gas pumps from KNF are based on a simple principle an elastic diaphragm, fixed on its edge, moves

More information

Understanding safety life cycles

Understanding safety life cycles Understanding safety life cycles IEC/EN 61508 is the basis for the specification, design, and operation of safety instrumented systems (SIS) Fast Forward: IEC/EN 61508 standards need to be implemented

More information

testo Leakage detector for refrigerants Instruction manual

testo Leakage detector for refrigerants Instruction manual testo 316-3 Leakage detector for refrigerants Instruction manual 2 1 Contents 1 Contents 1 Contents... 3 2 Safety and the environment... 4 2.1. About this document... 4 2.2. Ensure safety... 4 2.3. Protecting

More information

Every things under control High-Integrity Pressure Protection System (HIPPS)

Every things under control High-Integrity Pressure Protection System (HIPPS) Every things under control www.adico.co info@adico.co Table Of Contents 1. Introduction... 2 2. Standards... 3 3. HIPPS vs Emergency Shut Down... 4 4. Safety Requirement Specification... 4 5. Device Integrity

More information

Diagnosing EVAP systems By: Bernie Thompson

Diagnosing EVAP systems By: Bernie Thompson Diagnosing EVAP systems By: Bernie Thompson Perhaps one of the toughest jobs in the automotive field is diagnosing small leaks, especially A/C and Fuel Vapor (EVAP) leaks. Finding these leaks can be time

More information

Planning Daily Work Trip under Congested Abuja Keffi Road Corridor

Planning Daily Work Trip under Congested Abuja Keffi Road Corridor ISBN 978-93-84468-19-4 Proceedings of International Conference on Transportation and Civil Engineering (ICTCE'15) London, March 21-22, 2015, pp. 43-47 Planning Daily Work Trip under Congested Abuja Keffi

More information

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100

Information Sheet. About this information sheet. Floor and wall loadings. Attachment of process module to floor. PlasmaPro Estrelas100 Information Sheet PlasmaPro Estrelas100 About this information sheet This data sheet provides basic information about the installation of a PlasmaPro Estrelas100 tool. Some of the information in this sheet

More information

Hazard Identification

Hazard Identification Hazard Identification Most important stage of Risk Assessment Process 35+ Techniques Quantitative / Qualitative Failure Modes and Effects Analysis FMEA Energy Analysis Hazard and Operability Studies HAZOP

More information

MECHANICAL EQUIPMENTS: COMPRESSORS, PUMPS, SEALS, SPEED DRIVES, CONTROL VALVES & ACTUATORS & SAFETY RELIEF VALVES

MECHANICAL EQUIPMENTS: COMPRESSORS, PUMPS, SEALS, SPEED DRIVES, CONTROL VALVES & ACTUATORS & SAFETY RELIEF VALVES Training Title MECHANICAL EQUIPMENTS: COMPRESSORS, PUMPS, SEALS, SPEED DRIVES, CONTROL VALVES & ACTUATORS & SAFETY RELIEF VALVES Training Duration 5 days Training Venue and Dates REF Mechanical Equipments:

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

Nordel GRID DISTURBANCE AND FAULT STATISTICS

Nordel GRID DISTURBANCE AND FAULT STATISTICS Nordel GRID DISTURBANCE AND FAULT STATISTICS Table contents Table contents Page 1 Introduction... 3 1.1 Contact persons... 4 1.2 Guidelines the statistics... 4 1.3 Voltage levels in the Nordel network...

More information

A Journal of Practical and Useful Vacuum Technology. By Phil Danielson

A Journal of Practical and Useful Vacuum Technology. By Phil Danielson A Journal of Practical and Useful Vacuum Technology From By Phil Danielson Thermal Conductivity Gauges Thermal conductivity pressure gauges are extremely common in vacuum technology, but an understanding

More information

Life Cycle Benefits: Maintenace (Control Valve Diagnostic and Field Device Diagnostic Management)

Life Cycle Benefits: Maintenace (Control Valve Diagnostic and Field Device Diagnostic Management) Life Cycle Benefits: Maintenace (Control Valve Diagnostic and Field Device Diagnostic Management) Yasushi Kudo Yamatake Corporation Aaron Chen Azbil Taiwan Contents I. Prologue II. Possibilities of CV

More information

NEW IGC CODE AND IGF CODE

NEW IGC CODE AND IGF CODE NEW IGC CODE AND IGF CODE SAFETY ASPECTS Raffaele Piciocchi Gas Center - Greece SAFETY4SEAS - Athens 1 October 2014 Content NEW IGC CODE DRAFT IGF CODE 2 The New IGC Code A new IGC Code has been approved

More information