Evaluation of Effectiveness and Safety of CO 2 Cleaning of Energized Contaminated Pad-Mounted Gear
|
|
- Kelly Edwards
- 6 years ago
- Views:
Transcription
1 1 Evaluation of Effectiveness and Safety of CO 2 Cleaning of Energized Contaminated Pad-Mounted Gear Peter Tyschenko Manager, Distribution Standards Commonwealth Edison Company Shay Bahramirad and Terry Bellei
2 Problem - Surface Contamination Surface contamination (Dust /Dirt & Moisture) is the greatest deteriorating factor for insulation. Cable terminations Interrupters Insulators (stationary & rotating) Surge arresters Barriers 2
3 3 Switchgear Failure - Typical Sequence Buildup of airborne contamination on the barriers or other components of the switchgear. Vulnerable to contamination (proximity to roadways). Contamination supports leakage currents. Standing water in the foundation can result in repetitive condensation cycles that can extend the duration & severity of tracking. Tracking can result in excessive leakage currents, which can lead to flashover. The flash develops a cloud of conductive gas which subsequently supports - and -GRD flashovers..
4 4 CO 2 Cleaning - Theory of operation Dry ice cleaning uses compressed air to accelerate frozen carbon dioxide (CO 2 ) dry ice" pellets. Theory of operation: Generate dry compressed air & mix with CO 2. Transport the mixture to the hot stick/nozzle. Direct the CO 2 at the object to be cleaned. CO 2 sublimates & lifts off contamination. Illustration: Cold Jet LLC
5 5 Testing To Evaluate Effectiveness And Safety An energized test program was conducted on a heavily contaminated S&C PMH-9 (2 line, 2 fuse) switchgear to determine whether any leakage current could cause a flashover during CO 2 cleaning.. The test switchgear was originally installed in An effectively grounded 3 test source was used to energize the gear at 14.4 kv while performing the CO 2 cleaning. The test source consisted of backfed 480V transformers. 1 resistors were connected to limit the high-side fault current. Leakage current measurements indicated : Short duration discharges (SDD) lasting ~0.5ms in duration.. leakage current never exceeded 34mA.
6 - and -GRD, spray wand to ground, and cabinet to ground leakage currents were monitored during the CO 2 cleaning process. 6
7 7 Cleaning Energized Switchgear With CO 2 Before After
8 8 Cleaning Energized Switchgear With CO 2 8
9 9 Disconnect cleaned in the CLOSED position and rotated into the OPEN position to display results. Alternate nozzle designs and cleaning techniques proven in subsequent testing have eliminated this problem. Be Aware of the Dirt Shadow
10 10 Other Observations The inadvertent CO 2 cleaning of non-insulating components within the gear (switch contacts, arc compressors, silencers, etc.) revealed that there was no damage to any of these components. Grease was not removed from the contacts as a result of this cleaning. While dust and dirt and other airborne contaminants can be successfully removed by the CO 2 cleaning process, not all switchgear units are good candidates for cleaning. Lifting/flaking paint due to rusting is deemed to pose a potential hazard. Conductive ferrous residue can become dislodged under the pressure of the compressed air, resulting in a flashover. CO 2 cleaning can effectively clean exposed insulating surfaces. CO 2 cleaning of energized equipment can be safely performed
11 APPENDIX 11
12 Lifting/Flaking Paint Due To Rusting 12
13 Lifting/Flaking Paint Due To Rusting 13
14 14 Safety Flash Zone Pad-Mounted Switchgear (PMG) Safety Zone 1 Body 2ft from PMG Qualified Operator only. HRC Level 4 Suit (40+ Cal) Safety Zone 2 Body 4ft from PMG HRC Level 2 Clothing (8+ Cal) 2ft 4ft 8ft Work Conditions Do not perform work during inclement weather. Potential to introduce conductive water Do not perform clean equipment with rust, deterioration. Disable reclosing on source circuit(s) during cleaning. Equipment must be readily accessible Truck access from an improved roadway. 14 Observation Zone
15 15 Test Setup Switchgear 480V Source Resistors For Limiting Fault Current Delta-Delta 3-1 Transformers (Set Up Test Volatge) Wye-Delta 3-1 Transformers (Grounding Bank) Resistors For Measuring Leakage Current
Inspection Recommendations
S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Styles Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Inspection
More informationSelection of Electrical PPE Tables
Selection of Electrical PPE Tables Instructions Table 1 - Starting with Table 1, select the task you plan to do (right-hand column) and the condition of the equipment you will be working on, (center column).
More informationInfrared Thermography Inspection Guidelines. Date Issued:
Infrared Thermography Inspection Guidelines Date Issued: 2002 01 29 Created By: Approved By: L. Henderson G. Durnford Table Of Contents Table Of Contents...i POLICY STATEMENT...1 APPLICABLE INTERNATIONAL
More informationPOWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH
POWER PLANT RELAY REPLACEMENT DELIVERABLE ARC FLASH ISU Senior Design Group: Dec15-22 Dan Dye Project Web Site: http://dec1522.sd.ece.iastate.edu/ Project Sponsor: CIPCO Project Advisor: Professor Mani
More informationAppendix A: Energized Work Permit
Appendix A: Energized Work Permit Part I: To be completed by the Supervisor Description of Circuit & Equipment: Job Location: Description of Work to Be Done: Justification of why the circuit cannot be
More informationGround Fault Circuit Interrupter(GFCI) Policy
NewStar Netronics, LLC American Products for the World Ground Fault Circuit Interrupter(GFCI) Policy 3926 East 3 rd Street Tulsa, OK 74112 Phone (918)894-5006 Fax (918)836-9909 tech@newstarnetronics.com
More informationElectrical Safety Program
Electrical Safety Program The University Of Iowa Environmental Health & Safety 122 Grand Avenue Court Iowa City, IA 52242-1000 Phone: 319-335-8501 Date Revised/Reviewed: 6/8/2018 Table of Contents 1. Summary...
More informationMISSOURI UNIVERSITY OF SCIENCE & TECHNOLOGY Procedure: 3.6
Procedure This electrical safety procedure structures safety procedures to meet the requirements of the NFPA-70E Standard. The program is designed for qualified employees who occasionally must perform
More informationOriginal Date of Issue: 04/09
POLICIES AND PROCEDURES DEPARTMENT: Environmental Health and Safety SUBJECT: Electrical Safety Program Original Date of Issue: 04/09 Reviewed 12/2011 Revised 12/2011 BACKGROUND ELECTRIC SHOCK It is well
More information2-1- Shipping Receiving Lifting Location on Site Installation Stages 6
NEUTRAL GROUNDING RESISTORS INSTALLATION, OPERATION & MAINTENANCE MANUAL Contents 1- SAFETY INSTRUCTIONS... 3 1-1- Compliance with Instructions in this Manual. 3 1-2- Guidance Notes Installation.... 3
More informationWHAT IS GAS TANK/CYLINDER?
Introduction To use compressed gas cylinders safely, it is important that they are stored properly, handled correctly, used with the correct equipment, and that the properties of the gases they contain
More informationDuPage County Environmental, Safety, Health & Property Loss Control Program Hazardous Energy Control (Lockout/Tagout)
Purpose: To provide the minimum requirements for the lockout or tagout of energy isolating devices whenever work is performed or servicing is done on County of DuPage machinery, equipment, vehicles and
More informationCITY AND COUNTY OF DENVER CR&CF RISK UNIT Compressed Gas Safety Standard
CITY AND COUNTY OF DENVER CR&CF RISK UNIT 65.5.11 Compressed Gas Safety Standard 1.0 Introduction 2.0 Scope This standard has been developed to protect all City and County of Denver employees and contractors
More informationElectrical. OSHA Office of Training and Education 1
Electrical OSHA Office of Training and Education 1 Introduction An average of one worker is electrocuted on the job every day There are four main types of electrical injuries: Electrocution (death due
More informationBRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS CMP SERIES. Brilliant Wonders LED BUBBLERS
R BRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS CMP 25503 SERIES Brilliant Wonders LED BUBBLERS TABLE OF CONTENTS 1. Product Overview....3 1.1 Specifications. 3 1.2 Packing List...3 2. System
More informationTVPPA Lineman Apprenticeship Program
Self-Study Modules Unit 1 Unit 2 Unit 3 Unit 4 Lineman Apprenticeship Program Skills Labs Pre-Apprentice Assessment Digger Derrick Training Fundamentals Lab 1 Construction Lab 2 Operations Lab 3 Underground
More informationOperating instructions. Surge arrester Type MVR
Operating instructions Surge arrester Type MVR Content 1 About this document...3 1.1 Validity...3 1.2 Target group...3 2 Safety...3 2.1 Symbols and advices...3 2.2 Basic safety precautions...4 2.2.1 Product
More informationNESC WORKSHOP Revisions to Part 4 (Work Rules) Sam Stonerock. October 18, 2016
NESC WORKSHOP 2017 Revisions to Part 4 (Work Rules) Sam Stonerock October 18, 2016 Work Rules for the Operation of Electric Supply and Communications Lines and Equipment 2017 edition Reconcile existing
More informationDEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers
g DEH 40050 Instructions Three-Phase, Platform-Mounted Distribution Transformers Introduction The equipment covered by these instructions should be operated and serviced only by competent technicians familiar
More informationRigel 601 CHECKBOX. Instruction Manual. 348A551 Issue 2.0. April Seaward Electronic Ltd. Issue 2.0
Rigel 601 CHECKBOX Instruction Manual 348A551 Issue 2.0 April 2006 2006 Seaward Electronic Ltd. Issue 2.0 Limited Warranty & Limitation of Liability Rigel Medical guarantees this product for a period of
More informationElectrical Safety. Introduction
Electrical Safety 1 Introduction There are four main types of electrical injuries: Electrocution (death due to electrical shock) Electrical shock Burns Falls Around 300 workers were electrocuted in 2008
More informationModel PSI Compressor with 3-Gallon Air Tank 12VDC
Model 6350 150 PSI Compressor with 3-Gallon Air Tank 12VDC IMPORTANT: It is essential that you and any other operator of this product read and understandd the contents of this manual before installing
More informationProtection of motor circuits
Protection of motor circuits Circuit breaker/contactor coordination A circuit supplying a motor may include one, two, three or four switchgear or When a number of devices are used, they must be coordinated
More informationC&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations
C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Test instruments and recommended testing sequence 1 Outcomes of this Session describe the different
More informationType CAP. CapSwitcher. Capacitor Switching Device kv 38 kv INSTALLATION & INSTRUCTION MANUAL
Type CAP CapSwitcher Capacitor Switching Device 15.5 kv 38 kv INSTALLATION & INSTRUCTION MANUAL Safety Information DANGER THE EQUIPMENT COVERED IN THIS MANUAL SHOULD BE HANDLED, INSTALLED, AND MAINTAINED
More informationCargo Hold Cleaning Solution for Cement Clinker
Cargo Hold Cleaning Solution for Cement Clinker By Captain Nick Griffith Hold Cleaning Technologies LLC HCTLLC@GMAIL.COM October 24, 2015 Cement Clinker in the Cargo Hold Cement clinker, also known as
More informationDealing with Electrical Hazards in the Workplace
Dealing with Electrical Hazards in the Workplace Presented By: Tom Norwood Sr. Safety Specialist A SUBSIDIARY OF MEGGER TRAINING INSTITUTE, INC. Dallas, Texas Introduction Several hundred electrical fatalities
More informationS Surge Arresters. Handling and Storage. Standards. Acceptance and Initial Inspection
Surge Arresters VariSTAR Type AZF Intermediate lass Installation and Maintenance Instructions Service Information S235-70-1 ontents Product Information.......................... 1 General Application Recommendations..........
More informationSafety Meeting Topic #6 Working Around /On Energized Equipment
Safety Meeting Topic #6 Working Around /On Energized Equipment Employees shall become familiar with the following general guidelines: 1. Only qualified personnel shall work on electrical equipment, systems,
More informationRecent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs.
Recent changes in workplace safety regulations have heightened the awareness of hazards associated with electrical arcs. The hazard level must be quantified and workers properly protected before entering
More informationES18 Security Theory/Regulations Answer Schedule
ES18 Security Theory/Regulations Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The marker
More informationTHE OSHA LOCK-OUT/TAG-OUT STANDARD
PRESENTER'S GUIDE "LOCK-OUT/TAG-OUT" Training for THE OSHA LOCK-OUT/TAG-OUT STANDARD Quality Safety and Health Products, for Today...and Tomorrow OUTLINE OF MAJOR PROGRAM POINTS OUTLINE OF MAJOR PROGRAM
More informationCOOPER POWER SERIES. Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions. Reclosers MN280051EN
Reclosers MN280051EN Effective May 2017 Supersedes April 2014 (S280-10-8) COOPER POWER Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions SERIES DISCLAIMER
More informationAPPENDIX A. Appendix A: Fall Hazards Lesson Test Instructor Copy (answers bold/italic), Student copy to distribute follows
APPENDIX A Appendix A: Fall Hazards Lesson Test Instructor Copy (answers bold/italic), Student copy to distribute follows 1. In general, fall protection must be provided to construction workers who are
More information: Electric Power Generation, Transmission, and Distribution. Region IV - OSHA
1910.269: Electric Power Generation, Transmission, and Distribution Region IV - OSHA Scope This standard covers the operation and maintenance of electric power generation, control, transformation transmission,
More information[USING THE VITROBOT April 9, Using the Vitrobot
Using the Vitrobot The Vitrobot Mk 3 (aka Mark III, Mark 3, etc.) can control both the local temperature and the local humidity during the process of plunge-freezing a grid for cryoem. It does require
More informationGeneral Requirements of the NEC Advanced Course. Building Officials and Inspectors Educational Association
General Requirements of the NEC Advanced Course Building Officials and Inspectors Educational Association General Requirements -NEC Course Outcome Explain general requirements found in Article 110 of the
More informationAIR BRAKE SYSTEM TROUBLESHOOTING
AIR BRAKE SYSTEM TROUBLESHOOTING Page 10 04_26125_pg10-11.pmd 10 5/27/2004, 7:59 PM Page 11 1.) Before replacing any valve with a new or remanufactured valve, be sure to blow the air lines out either using
More informationAPPENDIX D HYDRO-VAC
The City of Winnipeg Bid Opportunity No. 33-2018 Template Version: C420160226 - RW APPENDIX D HYDRO-VAC Corporate Safety & Health Division GUIDELINES FOR EXCAVATION OF CABLES BY WATER PRESSURE/VACUUM SYSTEMS
More informationR E D I C O N T R O L S
R E D I C O N T R O L S Operation & Maintenance Manual Portable Service Purger for Low Pressure Chillers Model: PSP-LP-1B For Refrigerants R-11, R-113, R-114 & R-123 & Other Similar Refrigerants File Literature
More informationBRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP SERIES
BRILLIANT WONDERS LED BUBBLERS INSTALLATION INSTRUCTIONS & PRODUCT MANUAL CMP 25503 SERIES TABLE OF CONTENTS A. PRODUCT OVERVIEW A.1 SPECIFICATIONS A. PRODUCT OVERVIEW... 3 A.1 Specifications A.2 Packing
More informationElectrical Safety Program
Electrical Safety Program For Adopted LC-1005 Rev. 06/16 Page 1 I. Introduction As part of Organization s overall safety and health program, an
More informationYou Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services
You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services Why Failures Occur Insulation Failure - Every electrical component is comprised of
More informationTABLE OF CONTENTS PART 2 - CONFINED SPACES
May 11, 2006 TABLE OF CONTENTS PART 2 - CONFINED SPACES Page DEFINITIONS... 2-1 GENERAL... 2-2 RESPONSIBILITIES... 2-2 HAZARD ASSESSMENT AND WORK PROCEDURES... 2-3 IDENTIFICATION AND ENTRY PERMITS... 2-3
More informationDistribution Transformer Instruction Manual
Distribution Transformer Instruction Manual TABLE OF CONTENTS SHIPPING.. 3 INSPECTION ON RECEIPT 3 HANDLING.. 4 INTERNAL INSPECTION 5 STORAGE.. 6 LOCATION 6 PREPARING FOR SERVICE 7 PUTTING INTO SERVICE
More information36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS
36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING
More informationThese Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National
These Electricity Safety Rules and associated National Safety Instructions are written to safeguard personnel working for or on behalf of National Grid, on or near to its electricity apparatus. National
More informationC&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.
C&G 2395 Exam Paper June 2013 Section A-All questions carry equal marks. Answer all three questions. Show all calculations. 1. The electrical installation in an industrial unit is scheduled for a periodic
More informationHealth & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY
SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY 1. CONTROL OF HAZARDOUS ENERGY POLICY AND PROCEDURES A. OSHA References: 29 CFR 1910.147, 29 CFR 1910.332, 29 CFR 1910.333, 29 CFR 1926.417 B.
More informationC I R E D 18 th International Conference on Electricity Distribution Turin, 6 th to 9 th June 2005
RELIABILITY AND LONG TIME BEHAVIOUR OF MV-DISTRIBUTION SWITCHGEAR IN SEVERE ENVIRONMENTAL CONDITIONS - EXAMINATION OF SF 6 -INSULATED RING MAIN UNITS (RMU) UP TO 20 YEARS IN SERVICE. B. I. Oftedal, Siemens
More informationOxygen Contamination
MPMS Application Note 1014-210 Oxygen Contamination This application note describes potential sources for oxygen contamination in the sample chamber and discusses its possible effects. Molecular oxygen,
More informationMAINTENANCE RECOMMENDATIONS
MAINTENANCE RECOMMENDATIONS COOLING SYSTEM: Very high secondary currents are developed in resistance welding equipment. This, coupled with compact design, high upset temperatures, and fast cycle times,
More informationInstallation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range
Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Models: DS 126 Single Pump / Single System DT 126 Twin Pump / Single System DS 160
More informationModule: Permit to work System
Module: Permit to work System Aim: To know about best practice of PTW. It is a procedure designed to ensure that work is carried out in the safest possible way by considering the potential hazards and
More informationUSER MANUAL. JET TST and JET TST S.
USER MANUAL JET TST and JET TST S www.sisteven.com Types of Jet fans: JET TST UNI: Impulse axial fan single direction JET TST S UNI: Impulse axial fan single direction (short case) JET TST REV: Impulse
More informationWhy do I need to do an Arc-Flash Analysis?
Why do I need to do an Arc-Flash Analysis? Presented By Tom Norwood for Alexander Nizov, P.E. Principal/Manager Electrical Engineering Division TRAINING INSTITUTE, INC. A SUBSIDIARY OF MEGGER Hazards Analysis
More informationNZQA Expiring unit standard version 7 Page 1 of 8. Demonstrate knowledge of safe working practices in telecommunications.
Page 1 of 8 Title Demonstrate knowledge of safe working practices in telecommunications Level 2 Credits 4 Purpose This unit standard covers basic instruction in safe working practices in the telecommunications
More informationSYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA
SYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA August, 2016 Infrared Inspection Report Sysco Buckhead Beef 3516 Green Park Circle Charlotte, North Carolina, 28217 Company Contact Mark McNeely Project: 15120816
More informationPower Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers
Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling
More informationIn This Document. OBJECTIVES Upon completion of this module, you should be able to:
Struck By Fact Sheet MODULE DESCRIPTION This module provides information that will enable you to recognize common struck-by hazards at construction worksites. OBJECTIVES Upon completion of this module,
More informationIt is essential that the maintenance staff is qualified for electrical works and follows safety procedures.
MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained
More informationInstallation and Operation
S&C TripSaver Dropout Recloser Outdoor Distribution (15 kv and 25 kv) Installation and Operation Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet....
More informationInstallation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units
Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure
More informationSYSCO BUCKHEAD BEEF COLLEGE PARK, GEORGIA
SYSCO BUCKHEAD BEEF COLLEGE PARK, GEORGIA June, 2016 Infrared Inspection Report Sysco Buckhead Beef 4500 Wickersham Drive College Park, Georgia, 30337 Company Contact: Richard Blahnik Project: 05220616
More informationSUBSTATION EXPLOSION BARRY GASS HIGH VOLTAGE TRAINING. Barry Gass Training Manager High Voltage Training South Africa
High Voltage Training Barry Gass Training Manager High Voltage Training South Africa BARRY GASS HIGH VOLTAGE TRAINING INTRODUCTION An authorised person closed an 11kV Oil Circuit Breaker (OCB) onto a fault
More informationRisk Management Resources
Risk Management Resources Machine Guarding Name: Notes: Electrical Systems: Fire Prevention Are circuit breakers accessible to personnel, protected from physical damage, and located away from ignitable
More informationSYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA
SYSCO ALLARD VILLE DE QUEBEC, QUEBEC, CANADA November, 2016 Infrared Inspection Report Sysco Allard 199 2e Avenue Ville de Quebec, QC, G1L 3A5 Company Contact Louis Grenier Project: C041116 2605 CHARTER
More informationPredicting the Remaining Life of Vacuum Interrupters in the Field
Predicting the Remaining Life of Vacuum Interrupters in the Field Applying the Magnetron Atmosphere Condition Assessment (MAC) Test in a Field Environment INTRODUCTION Historical Perspective Historically,
More informationTABLE OF CONTENTS... 2... 2... 3... 5... 6... 7... 7... 15... 16... 17... 17... 19... 20... 21 IMPORTANT INFORMATION Two Post Lifts 1. 2. - There can be no cracks in the slab within 36 in. of the base
More informationSECTION 51 NFPA 70E POLICY. Health & Safety Policy and Procedures Manual
SECTION 51 NFPA 70E POLICY Health & Safety Policy and 1. Protection Against Arc Flash A. Policy: An arc flash is a dangerous condition associated with the release of energy caused by an electric arc. An
More informationSIDEWINDER DRILLING RIG 122 CLEBURNE COUNTY, ARKANSAS
SIDEWINDER DRILLING RIG 122 CLEBURNE COUNTY, ARKANSAS March, 2015 Infrared Inspection Report Sidewinder Drilling Rig 122 Company Contact Jesse Russell Project: 07090315 2605 CHARTER OAK DRIVE, LITTLE ROCK,
More informationThis presentation provides an overview of modern methods for minimizing the arc-flash hazard.
Electricity is all around us. An uncontrolled release of electric energy is extremely dangerous, posing a threat to human life, causing equipment damage, and jeopardizing the manufacturing process that
More informationCOLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE SUMMARY
COLD-WEATHER APPLICATION OF GAS MIXTURE (SF 6 /N 2, SF 6 /CF 4 ) CIRCUIT BREAKERS: A UTILITY USER S PERSPECTIVE R. L. Middleton, P. Eng. Manitoba Hydro, Winnipeg, Canada SUMMARY Very low temperatures stress
More informationMODEL NUMBER: P PORTABLE COMPRESSOR
MODEL NUMBER: 44043-440P PORTABLE COMPRESSOR IMPORTANT: It is essential that you and any other operator of the product read and understand the contents of this manual before installing and using this product.
More informationRisk Assessment Procedure
Voltage, current testing, troubleshooting Infrared inspection Visual inspection, data collecting Risk Register ES Acc 6 4 1 1 6 36 ES < Acc 6 4 3 3 10 60 AF/AB 40 Acc 8 3 2
More informationELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR CFR , ,
ELECTRICAL (COMPREHENSIVE) SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29 CFR 1910.331 335-29 CFR 1926.302, 1926.416, 1926.417 BASIS: The National Safety Council estimates that there are at least 300 deaths
More informationBest Practices Pneumatics Machine & Design. Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016
Pneumatics Machine & Design Written by Richard F. Bullers, CFPPS as published in Fluid Power Journal, July/August 2016 Contents at Atmospheric Air The air at a compressor s intake contains about 78% nitrogen,
More informationAE R1 February 2015
February 2015 CoreSense Diagnostics for Copeland Scroll UltraTech Air Conditioning Compressors TABLE OF CONTENTS Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to
More informationELECTRIC OPERATING PROCEDURES Date: 11/01/06
Doc No.: NG-USA EOP D001 Page: 1 of 5 ELECTRIC OPERATING PROCEDURES SUBJECT: Cutouts Open/Enclosed Type SECTION: Distribution/Overhead REFERENCE: National Grid Retail Company Safety Manuals National Grid
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More informationUniversal Valve Company Inc
1975-FA34 (Air Tower Troubleshooting Manual) Overview This manual has been arranged as a tool for diagnosing, and repairing Universal Air Towers Please read closely to identify the components that are
More informationHazardous Energy Control/Lockout
This is a photographic template your photograph should fit precisely within this rectangle. Hazardous Energy Control/Lockout MESH 8.0 - Process Safety Awareness Training 2008 Eaton Corporation. All rights
More informationProgressive Safety Services LLC - All Rights Reserved
Estimated that 2,000 workers are treated in specialized burn centers each year as a result of arc flash (Electrical Safety Foundation International). According to the National Safety Council, medical costs
More informationFlorida Building Code 6 th Edition (2017) Residential. Broward County Edition Loose-leaf Supplement
Board of Rules and Appeals FBC 6 th Edition (2017)- Residential - Supplement No. 1 January 1, 2018 Florida Building Code 6 th Edition (2017) Residential File removed pages for reference. Broward County
More informationUniversal Valve Company Inc
Universal Valve Company Inc 800-223-0741 www.universalvalve.com 1975-FA34 (Air Tower Troubleshooting Manual) Overview This manual has been arranged as a tool for diagnosing, and repairing Free Air Universal
More informationAIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST
AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST OIL-LESS TYPE IMPORTANT: PLEASE READ CAREFULLY BEFORE STARTING OPERATIONS. THE CONTENTS ARE FOR GENERAL INFORMATION OF ALL THE SIMILAR MODELS. Record
More informationSYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND
SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND October, 2016 Infrared Inspection Report Sysco St. John s 10 Old Placentia Road Mount Pearl, NF A1N 4P5 Company Contact: David Shaw Project: C261016 2605 CHARTER
More information36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS
INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL
More informationPSSI 3 High Voltage Metal-Enclosed Switchgear
1. SCOPE This Safety Instruction applies the principles established by the ScottishPower Safety Rules (Electrical and Mechanical) and Company Safety Instructions to achieve Safety from the System for personnel
More informationPOTENTIAL HEALTH & SAFETY HAZARDS
Number: OH&S 18.09.1 Revision Date: 2011.06 Confined Space 1. PURPOSE 2. SCOPE 1.1. To properly designate Confined Spaces (CS) at Thompson Rivers University (TRU), to provide guidance to ensure the safety
More informationBUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA
BUZZI UNICEM USA PENSACOLA TERMINAL MILTON, FLORIDA May, 2017 Infrared Inspection Report Buzzi Unicem Terminal 6266 Da Lisa Road Milton, Florida, 32583 Company Contact Andy Rogers Project: 04110517 2605
More information11/2/2017. Course Objectives. Overview
Course Objectives The objective of this CBT module is to insure that personnel receive basic training in electrical safety. Every employee's work involves electricity. This may vary from typical electrical
More informationInstallation. S&C Vista Underground Distribution Switchgear. UnderCover, Vault-Mounted, and Pad-Mounted Styles. Instruction Sheet
S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Installation Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction
More informationSECTION 25 TESTING AND DISINFECTING WATER MAINS General
SECTION 25 TESTING AND DISINFECTING WATER MAINS 25-1.01 Scope 25-1 General This section describes the requirements for pressure and leak testing, and disinfecting of water mains and appurtenances, including
More informationLockout/Tagout Safety Policy
University of North Carolina Wilmington Environmental Health & Safety Workplace Safety Lockout/Tagout Safety Policy GENERAL The UNCW Environmental Health & Safety Department (EH&S) is authorized by UNCW
More informationEnvironmental, Health and Safety. Electrical Safety in the Workplace Program
Environmental, Health and Safety Electrical Safety in the Workplace Program September 2016 Table of Contents 1.0 Purpose... 1 2.0 Scope... 1 3.0 Definitions... 2 4.0 Responsibilities... 7 5.0 Requirements...
More informationELECTRICAL FLASHOVER HAZARDS AND SAFETY MEASURES REFERENCE TO DESIGN AND MAINTENANCE. Intrduction: B.MAHARANA, AGM(EM)/HOD NTPC,RAMAGUNDAM
ELECTRICAL FLASHOVER HAZARDS AND SAFETY MEASURES REFERENCE TO DESIGN AND MAINTENANCE By Intrduction: B.MAHARANA, AGM(EM)/HOD NTPC,RAMAGUNDAM In a large power plant Electrical system covering voltage right
More informationPortland Community College Facilities Management Services ENERGIZED ELECTRICAL WORK PERMIT AND WORK PLAN
Portland Community College Facilities Management Services ENERGIZED ELECTRICAL WORK PERMIT AND WORK PLAN Section 1 - PROJECT INFORMATION Project Work Request No. Building Room/Location Equip. Serial No.
More informationOperator: Save these instructions for future use!
WHITE-RODGERS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE PERSAL INJURY AND/OR PROPERTY DAMAGE.
More informationRight-Angle Tube Roller Model
SPECIFICATIONS Model no. Free Speed (RPM) Throttle Rotation Max. Torque Ft-Lb Air Pressure psi Air Inlet Hose Air Flow @Free Speed Spindle Weight 909-1700 95 Lever type Reversible 240 90 1/2 NPT 1/2 I.D.
More information