Transformer Reliability
|
|
- Bernadette Walton
- 5 years ago
- Views:
Transcription
1 Transformer Reliability A prac'cal approach to achieving life expectancy Garth Cuthbert Nov 2015
2 Transformer Reliability 3 x 1000 kva OFW 1ph 11, Volts In service since 1915
3 What contributes to reliability? Preven'on / Mi'ga'on Bow'e
4 What contributes to failure? Overload, Overvoltage, Overtemperature Natural ageing processes - Entropy Unexpected and unplanned operapng events Human error
5 Transformer Failure Cause Maintenance Error 10% Opera*ng Error 10% Miss- Applica*on 10% Opera*ng Error 20% Miss- Applica*on 10% Design Deficiency 20% Transporta*on Damage 25% Design Deficiency 40% Maintenance Error 30% OEM Workmanship 15% OEM Workmanship 5% Transporta*on Damage 5% Failure Rate 2.5 per 100 Failure Rate 0.5 per 100
6 RCM - Reliability Centered Maintenance Based on known, probable failure modes, both evident and hidden OpPmizes ongoing maintenance costs vs. replacement costs while maximizing availability Creates a baseline and record of cripcal equipment metrics from start- up, during warranty period, through operapng events resulpng in an accurate and informed assessment of current condipon and risk Predicts and mipgates the evolupon of latent failures
7 What needs maintenance and how frequent? IEEE C Guide for Installa*on and Maintenance of Liquid- Immersed Power Transformers Manufacturer s Opera*on and Maintenance Manual
8 External Inspec*on Component or FuncPon Dehydrator Leak Free Tank and Coolers ConnecPons Typical IEEE C57.93 and OEM Recommended Maintenance AcPon R1M InspecPon: Note/ Record Abnormal IndicaPon R1Y Infrared Thermographic Survey RCM Best PracPce/Strategy R1M InspecPon: Note/ Abnormal IndicaPon R3Y Auto Dehydrator conpnuously monitored with self checking failsafe design. Air bladder equipped conservator Galvanized air- liquid coolers Double walled water- liquid heat exchangers with integrated leak detec*on
9 Infrared Thermographic Survey Early detecpon of common faults before serious damage or failure occurs. Poor connecpon of HV bushing and evidence of compromised flow in two coolers
10 Indica*on and Control Func*onal Verifica*on Component or FuncPon Indica*on Gauges Liquid Level Liquid Temp Winding Temp Gas AccumulaPon Bushing Liquid Level Controls Fan FuncPon Typical IEEE C57.93 and OEM Recommended Maintenance AcPon R1M InspecPon: Note Abnormal IndicaPon Record levels and temperatures in stapon records R1M InspecPon: Confirm Auto and Manual FuncPonality RCM Best PracPce/Strategy R1M InspecPon Note Abnormal IndicaPon R3Y Intelligent Transformer Monitor (ITM) non mechanical (RTD) oil temperature inputs, conpnuously monitored with self checking failsafe design and remote oil temperature data R1M InspecPon Confirm Auto and Manual FuncPonality R3Y ITM Control outputs to fan circuits with self checking funcponality
11 Some failure modes are extremely difficult to detect and even more difficult to quanpfy contribupon to end of life. These tend to be design and workmanship related. A robust purchase specificapon supported by strong QA oversight of the supplier through commissioning will detect acpve and potenpal problems. This image was presented online as representapve of a manufacturer quality standards!
12 Alarm and Protec*on - Func*onal Verifica*on Component or FuncPon Mechanical Alarms Liquid Level Liquid Temp Winding Temp Gas AccumulaPon Mechanical Trips Liquid Level Liquid Temp Winding Temp Sudden Pressure Pressure Relief Typical IEEE C57.93 and OEM Recommended Maintenance AcPon D3Y Verify IndicaPon D3Y Verify Alarm to Annuciator Display D3Y Verify Trip ProtecPon RCM Best PracPce/Strategy D3Y Calibrate and Verify IndicaPon D3Y Verify Alarm to Annuciator D3Y Verify Annuciator Self Monitoring FuncPonality Redundant ITM Alarm outputs to annuciator with self checking funcponality and self calibrapon design Fiber Op*c Winding Temperature Monitors Integrated data systems
13 Fiber Op*c Winding Temperature Monitors accurately measure the winding hot spot temperature.
14 Typical insulapon degradapon due to conpnuous operapon at or above thermal rapngs Oil and Winding Temperature records would provide limited informapon on condipon and failure probability Every transformer is equipped with temperature indicapon and every transformer experiences some degree of temperature related loss of life
15 Mechanical failure due to cumulapve effect of magnepc forces subjected during external through faults SophisPcated monitoring and test programs capable of predicpng failure with reasonable confidence are available Cost prohibipve for GSU applicapons considering < 1 in 10,000 will fail due to through fault duty
16 Internal Condi*on Assessment Component or FuncPon RaPo Adjuster Typical IEEE C57.93 and OEM Recommended Maintenance AcPon No recommendapon RCM Best PracPce/Strategy D3Y Exercise the RaPo Adjuster. Measure winding resistance in all posipons InsulaPon Integrity D3Y- D7Y InsulaPon power factor (Doble ) tests including oil and bushings. Core Ground InsulaPon Resistance (Megger ) Winding Resistance Winding RaPo D3Y InsulaPon power factor (Doble ) tests including oil and bushings. D3Y Core Ground InsulaPon Resistance (Megger ) Oil Integrity R1Y- R3Y Oil Tests (1 liter sample) Dissolved Gas Analysis (Oil Syringe) Furan Analysis R2Y Oil Tests (1 liter sample) R6M Dissolved Gas Analysis R2Y Furan Analysis Online DGA Monitoring
17 Dissolved gas analysis ( DGA ) is widely used to detect incipient faults in transformers. UnPl recently it involved period sampling of the transformer s oil and lab analysis with interpretapon by chemists and transformers specialists. Available online DGA monitors have advanced significantly with diagnospc output data and display, user set points for alarm and trip funcpons for each different fault type. One manufacturer even calculates and displays diagnospc uncertainty.
18 A fiber oppc winding temperature monitor coupled with a online DGA monitor provides the transformer owner with the means to operate a transformer to its full capacity rapngs with confidence. The impact of any planned or unplanned overload is easily recognizable and quanpfied. The real Pme aspect of both devices can provide input and feedback to generapon opportunity decisions and or asset management decisions.
19 ApplicaPon to Generator Step Up Transformers Fiber OpPc Winding Temperature Monitor 1. Any transformer > 15 MVA 2. Transformers connected to single unit generator capacity above nominal transformer capacity 3. Transformers required to provide emergency connecpon for mulpple generators Online DGA Monitor 1. Any transformer > 30 MVA 2. Any transformer connecpng generapon or source voltage above 16kV 3. Any transformer with an on load tapchanger
20 Aspire to operapng your GSU transformer for 100+ years? Think again! Technology currently being developed will radically change connecpon between energy sources and the electrical grid. Look for it in 5 years! Aim for a GSU transformer life of years, celebrate achieving 35 years and repre at 40 years.
Power Transformer Maintenance. Maintenance Practices & Procedures for Substation Class Distribution Power Transformers
Maintenance Practices & Procedures for Substation Class Distribution Power Transformers Why should special maintenance practices be applied to power transformers? Power transformers utilize active cooling
More informationMonitoring transformers with infrared cameras
APPLICATION NOTE Monitoring transformers with infrared cameras Most transformers are cooled by either oil or air while operating at temperatures much higher than ambient. In fact, operating temperatures
More informationOnline DGA-monitoring of power transformers
Online DGA-monitoring of power transformers Senior Industry Expert, Vaisala Finland Member of CIGRE A2/D1.47 and D1.52 WGs April 2018 Vaisala Webinar content 1. Dissolved gases why and which gases 2. Fault
More informationInfrared Thermography Inspection Guidelines. Date Issued:
Infrared Thermography Inspection Guidelines Date Issued: 2002 01 29 Created By: Approved By: L. Henderson G. Durnford Table Of Contents Table Of Contents...i POLICY STATEMENT...1 APPLICABLE INTERNATIONAL
More informationMathieu Guertin. Morgan Schaffer Inc. Canada. Director Europe, Russia and Africa. A cost effective strategy for smart grid technology adoption
Mathieu Guertin Director Europe, Russia and Africa Morgan Schaffer Inc. Canada A cost effective strategy for smart grid technology adoption Why protecting assets? Cost of fault: $52 MILLIONS!!! Easy ROI
More informationInnovative Techniques for Mitigating Arc Flash Exposure
Innovative Techniques for Mitigating Arc Flash Exposure Presented at MEMSA 2009 Annual Meeting & Technical Symposium 2007 Eaton Corporation. All rights reserved. INTRODUCTION. As more and more industries
More informationHazard Operability Analysis
Hazard Operability Analysis Politecnico di Milano Dipartimento di Energia HAZOP Qualitative Deductive (search for causes) Inductive (consequence analysis) AIM: Identification of possible process anomalies
More informationDistribution Transformer Instruction Manual
Distribution Transformer Instruction Manual TABLE OF CONTENTS SHIPPING.. 3 INSPECTION ON RECEIPT 3 HANDLING.. 4 INTERNAL INSPECTION 5 STORAGE.. 6 LOCATION 6 PREPARING FOR SERVICE 7 PUTTING INTO SERVICE
More informationAdvanced Test Equipment Rentals ATEC (2832) OMS 600
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) OMS 600 Continuous partial discharge monitoring system for power generators and electrical motors Condition monitoring
More informationCopeland Discus with CoreSense Diagnostics January 2011
Copeland Discus with CoreSense Diagnostics January 2011 Slide 1 1/27/2011 5:48 PM Discus with CoreSense Diagnostics Case Studies Supermarket In Columbus, Ohio Saves $4,500 With Discus with CoreSense Diagnostics
More informationPerformance Monitoring Examples Monitor, Analyze, Optimize
Performance Monitoring Examples Monitor, Analyze, Optimize BETA's Performance Assessment service is a low cost remote monitoring service for reciprocating compressors, centrifugal compressors, engines,
More informationYou Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services
You Just Experienced an Electrical Failure, What Should You Do Next? By Don Genutis Hampton Tedder Technical Services Why Failures Occur Insulation Failure - Every electrical component is comprised of
More information" High Voltage Switch Yards & How Safe are these really" <Peter Rhodes> <Principal and High Voltage Solution. Com Ltd>
" High Voltage Switch Yards & How Safe are these really" High Voltage Forum Brisbane 2013 Duty of Care As part of an asset owner Duty of care
More informationTransformer Maintenance
PDHonline Course E212 (10 PDH) Transformer Maintenance Instructor: Bijan Ghayour, PE 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
More informationDevelopment of a Plant Health Index for Eskom Distribution Substations
Development of a Plant Health Index for Eskom Distribution Substations by Elton Brand, Eskom Distribution and Ulrich Minnaar, Eskom ERID and Wilfred Fritz, School of Electrical Engineering, Cape Peninsula
More informationAdvanced Pump Control for Irrigation Applications
Advanced Pump Control for Irrigation Applications Paul Nistler VFD Applications Engineer And Julian Atchia Director of Research and Development SJE Rhombus 22650 County Hwy 6 Detroit Lakes MN 56502 Executive
More informationPC10 Piezoresistive Silicon Pressure Sensor
PC10 Piezoresistive Silicon Pressure Sensor Features With constant current and constant voltage excitation options Imported highly reliable pressure die Wide temperature compensation Normalized output
More informationPRC CO ² -LASER PRESENTATION
Page 1 of 7 PRC CO ² -LASER PRESENTATION GENERAL CHARACTERISTICS - Embedded PC104 Electronics with exchangeable software allowing very easy integration of customer specified functions: such as eg. specific
More informationINTRODUCTION. The Quantum Technology system has the following advantages:, as it does not need plastic gas-bags which are volume-consuming,
1 INTRODUCTION Quantum Technology is a leading scientific equipment supplier. For the last thirty years we served our customers by tailoring our products to each customer s unique requirements. Quantum
More informationDistribution Transformer. Instruction Manual. For Domestic Use
CENTURY INFRAPOWER PVT.LTD. S-23, ALANKAR PLAZA, VIDHYADHAR NAGAR, JAIPUR-302023 (RAJ.) Distribution Transformer Instruction Manual For Domestic Use Introduction:- The three phase pad mounted distribution
More informationLECTURE 3 MAINTENANCE DECISION MAKING STRATEGIES (RELIABILITY CENTERED MAINTENANCE)
LECTURE 3 MAINTENANCE DECISION MAKING STRATEGIES (RELIABILITY CENTERED MAINTENANCE) Politecnico di Milano, Italy piero.baraldi@polimi.it 1 Types of maintenance approaches Intervention Unplanned Planned
More informationIST-203 Online DCS Migration Tool. Product presentation
IST-203 Online DCS Migration Tool Product presentation DCS Migration Defining the problem Table of contents Online DCS Migration Tool (IST-203) Technical background Advantages How to save money and reduce
More informationMODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS
MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS Zohra Khan 1, Avinash Paranjpe 2 1 ME Student, Electrical Power System, PES COE/ Dr. B.A.M. University, (India)
More informationIntelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter
Intelligent SUNTEX DC-5310(RS) Dissolved Oxygen Transmitter Overview C % ppm 4~20mA Analog Output ppb Power Supply 100~240 VAC mg/l Dimensions 96 x 96 x 132mm RS-485 Digital Output (for DC-5310-RS only)
More informationCHAPTER 28 DEPENDENT FAILURE ANALYSIS CONTENTS
Applied R&M Manual for Defence Systems Part C - Techniques CHAPTER 28 DEPENDENT FAILURE ANALYSIS CONTENTS Page 1 Introduction 2 2 Causes of Dependent Failures 3 3 Solutions 4 Issue 1 Page 1 Chapter 28
More informationNandkumar Wagh, D.M. Deshpande
International Journal of Scientific & Engineering Research, Volume 4, Issue 9, September-2013 2503 Fuzzy Decision on Transformer Fault Diagnosis using Dissolved Gas Analysis and IEC Ratio Codes Nandkumar
More informationINSTALLATION,OPERATION AND MAINTENANCE INSTRUCTIONS DRY AIR COOLER
INSTALLATION,OPERATION AND MAINTENANCE INSTRUCTIONS DRY AIR COOLER Installation Operation and Maintenance Location The unit should not be located on roofs finished with asphalt. When this is unavoidable
More informationRequired Indoor Draft Hood. Optional Outdoor Vent Cap
Pump-Mounted Water Heaters B4 - Copper Brute Water Heater Convertible Sizes 175,000-399,000 BTU/hr Indoor/Outdoor Sizes 500,000-1,825,000 BTU/hr Up to 82% Thermal Efficiency The unit will be designed and
More informationUKAS calibration laboratory 8809 Temperature, pressure and electrical signals calibration guide
ABB MEASUREMENT & ANALYTICS PRODUCT GUIDE PG/SMD140 EN REV. B UKAS calibration laboratory 8809 Temperature, pressure and electrical signals calibration guide Measurement made easy UKAS calibration laboratory
More informationTransformer Lifecycle Services. Container Id: Miscellaneous Id: Second Name: Sequence #:
Report # 173396 Sample # 1 Transformer Lifecycle Services Received 08/09/2016 Date August 10, 2016 Serial Number: 100413030004 Substation Name: Colorado Bend Design Type: Core Type Manufacturer: HicoA
More informationMODEL NUMBER: PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank
IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock or Electrocution: MODEL NUMBER: 20008 200 PSI AIR SOURCE KIT 200 PSI Compressor on 2.0 Gallon 200 PSI Air Tank IMPORTANT: It is
More informationWorkshop Information IAEA Workshop
IAEA Training Course on Safety Assessment of NPPs to Assist Decision Making Safety Assessment of General Design Aspects of NPPs (Part 2) Lecturer Lesson Lesson III III 1_2 1_2 Workshop Information IAEA
More informationCategorizing Faults via DGA. GE Grid Solutions M&D
ategorizing Faults via DGA GE Grid Solutions M&D First, What Is Transformer Dissolved Gas Analysis? Sample Test Doc Diagnosis Doctors extract information about our health from our blood. Technicians extract
More informationPoint level switches for safety systems
Point level switches for safety systems By: Bill Sholette Level Products Business Manager Northeast US - Endress+Hauser Point level switches are often used in applications designed to prevent accidents.
More informationDPC-30 DPC-100. Reference Manual
DPC-30 DPC-100 Reference Manual 1. Introduction 1.1 Description The Martel DPC Digital Pneumatic Calibrator improves upon traditional dial gauge pneumatic calibrators. The Martel DPC improves accuracy,
More informationMODEL NUMBER: M20005 AIR SOURCE KIT. 30% Duty Compressor on. 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE
MODEL NUMBER: M20005 AIR SOURCE KIT 30% Duty Compressor on 2.0 Gallon Air Tank SAVE THIS MANUAL FOR FUTURE REFERENCE USER MANUAL IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock
More informationDissolved Gas Analysis - Past, Present and Future
I. INTRODUCTION Dissolved Gas Analysis - Past, Present and Future Fredi Jakob Weidmann-ACTI Inc. It has been well over thirty years since dissolved gas analysis, DGA, was introduced as a diagnostic tool
More informationUsing Reliability Centred Maintenance (RCM) to determine which automated monitoring systems to install to new and existing equipment
Using Reliability Centred Maintenance (RCM) to determine which automated monitoring systems to install to new and existing equipment CHRIS JAMES RELIABILITY MANAGEMENT LTD Cairo, November 2018 The rate
More informationCOMPRESSOR MANUAL. (888)
COMPRESSOR MANUAL www.ultimadentalsystems.com (888) 900-8584 Table of Contents Introduction..Page 2 Quick Compressor Start Guide....Page 3-5 Compressor Pump Diagram....Page 6 Compressor Frame Diagram....Page
More informationRAMSTM. 360 Riser and Anchor-Chain Integrity Monitoring for FPSOs
RAMS 360 Riser and Anchor-Chain Integrity Monitoring for FPSOs Introduction to RAMS Tritech s RAMS is a 360 anchor-chain and riser integrity monitoring system for Floating Production Storage and Offloading
More informationManaging on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution power transformers
24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Managing on-load tap changer life cycle in tenaga nasional berhad (TNB) distribution
More informationSATURN EVO COLOR A N A E S T H E S I A S Y S T E M. Manufacturer of high quality anaesthesia products
Saturn Evo SATURN EVO COLOR A N A E S T H E S I A S Y S T E M i n t e l l i g e n t s i m p l i c i t y Manufacturer of high quality anaesthesia products SATURN EVO COLOR PATIENT SAFETY AND USER PATIENT
More informationMINUTES OF MEETING BUSHING SUBCOMMITTEE OF THE IEEE/PES TRANSFORMER COMMITTEE MINNEAPLOS, MN OCT 17, 2007
MINUTES OF MEETING BUSHING SUBCOMMITTEE OF THE IEEE/PES TRANSFORMER COMMITTEE MINNEAPLOS, MN OCT 17, 2007 8.9 Bushing Subcommittee Fred Elliott, Chair 8.9.1 Introduction/Attendance Fred Elliott - Chair
More informationOIL & GAS. MTS DP Committee. Workshop in Singapore Session 4 Day 2. Unwanted Thrust
OIL & GAS MTS DP Committee Workshop in Singapore 2018 Session 4 Day 2 Unwanted Thrust Unwanted Thrust - Definition Unwanted Thrust Thrust magnitude not what has been ordered by DP (Particularly too high
More informationA NEW RELAYING PRINCIPLE FOR TRANSFORMER OVERLOAD PROTECTION
Georgia Tech 52 nd Protective Relaying Conference May 6-8, 1998 A NEW RELAYING PRINCIPLE FOR TRANSFORMER OVERLOAD PROTECTION Glenn Swift, Dave Fedirchuk, Zhiying Zhang Alpha Power Technologies 1305 Clarence
More informationCP3R Quick Start Manual
RUN MON PRM PU EXT NET RUN D700 3 200V RUN MON PRM PU EXT NET RUN D700 3 200V CP3R Quick Start Manual for Constant Pressure Applications This CP3R Drive has been factory pre-programmed for your specific
More informationINSTRUCTION BOOK CARE AND MAINTENANCE OF OIL-IMMERSED (R-TEMP-OR SILICONE IMMERSED) TRANSFORMERS
Industrial Transformers Secondary Substation Transformers INSTRUCTION BOOK CARE AND MAINTENANCE OF OIL-IMMERSED (R-TEMP-OR SILICONE IMMERSED) TRANSFORMERS TABLE OF CONTENTS Page SHIPPING........2 INSPECTION
More informationCONTROL and INSTRUMENTATION
CONTROL and INSTRUMENTATION COURSE 500: 5 DAYS: Max 8 Candidates This course covers the key aspects of current instrumentation and process control technology and is designed to enable maintenance personnel
More informationCPN1 Quick Start Manual
RUN MON PRM PU EXT NET RUN RUN MON PRM PU EXT NET RUN CPN1 Quick Start Manual for Constant Pressure Applications This CPN1 Drive has been factory pre-programmed for your specific pressure control application.
More informationL 100. Bubble-Tube Level System. Installation, Operation and Maintenance Instructions
L 100 Bubble-Tube Level System Installation, Operation and Maintenance Instructions Figure 1 Contents Section Description Page 1.0 Introduction 2 2.0 Specifications 3 3.0 Installation 3 4.0 Warranty 6
More informationDynamic Behaviour of Fault Gases and Online Gas Sensors. Germany
21, rue d Artois, F-75008 PARIS A2-116 CIGRE 2016 http : //www.cigre.org Dynamic Behaviour of Fault Gases and Online Gas Sensors S. TENBOHLEN 1, I. HÖHLEIN 2, M. LUKAS 3, A. MÜLLER 4, K. SCHRÖDER 5, U.
More informationMarschalk Model # 94000
Marschalk Model # 94000 12-volt DC Portable oil-less Air Compressor Operation Manual 27250006 REV 1 9/13/05 Table of Contents CHAPTER 1: SYSTEM DESCRIPTION... 5 FUNCTION AND THEORY... 5 SYSTEM COMPONENTS...
More informationEXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS
The 9 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 25 EXPERIENCES WITH APPLICATION, DIAGNOSTIC VALUE AND IMPACT ON ASSET MANAGEMENT OF INSULATION OIL ANALYSIS
More informationSingle-Phase Pad-Mounted Distribution. Single-Phase Pad-Mounted Distribution Transformers KVA
62-10 Single-Phase Pad-Mounted Distribution Catolog Transformers Section Howard Industries, Inc. Certifi ed to ISO 9001:2015 62-10 Single-Phase Pad-Mounted Distribution Transformers 5-500 KVA 10002179
More informationIt is essential that the maintenance staff is qualified for electrical works and follows safety procedures.
MAINTENANCE OF POWER FACTOR CORRECTION EQUIPMENTS Procedures, suggestions and traceability The purpose of this document is to propose a maintenance method that allows to identify the elements to be maintained
More informationSPECIFICATIONS APCEPH1
APCEPH1 ph CONTROLLER SPECIFICATIONS APCEPH1 Input voltage 120 Volts AC Maximum amperage 14.5 amps @ 120 VAC ph Accuracy +/- 0.2 ph ph Control range Adjustable 4.5 8.5 ph Weight < 1 lbs Dimensions 3" x
More information200 PSI FAST-FILL AIR SOURCE KIT
200 PSI FAST-FILL AIR SOURCE KIT 55% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20007 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of
More information200 PSI HIGH-FLOW AIR SOURCE KIT
200 PSI HIGH-FLOW AIR SOURCE KIT 50% Duty Compressor on 2.0 Gallon Air Tank PART NO. 20008 IMPORTANT: It is essential that you and any other operator of this product read and understand the contents of
More informationGuidelines on Surveys for Dynamic Positioning System
Guidelines on Surveys for Dynamic Positioning System (2002) BEIJING 1 CONTENTS Chapter 1 GENERAL 1.1 General requirements 1.2 Class notation 1.3 Definitions 1.4 Plans and documents 1.5 Failure mode and
More informationUnderstanding Dissolved Gas Analysis (DGA) Techniques and Interpretations
By Jeff Golarz ABSTRACT The use of Dissolved Gas Analysis (DGA) as a method for determining the types of pending or occurring faults within power transformers has been in practice for many years. It has
More informationP499 Heavy Duty Pressure Transducer
P499 Heavy Duty Pressure Transducer Product Bulletin Code No. LIT-??? E Issued 11 2006 The P499 Series is a new global Pressure Transducer with an excellent price performance ratio. The P499 exceeds the
More informationA4s Operation Manual
A4s Operation Manual Safety Instruction Please read this manual carefully, also with related manual for the machinery before use the controller. For installing and operating the controller properly and
More informationCON ACT. Parts and Service News For the Power Transformer and
ABB CON ACT Parts and Service News For the Power Transformer and March 1998 Circuit Breaker Maintenance Community Special No. 1 Type 'U' "The Clock is Ticking" Up-to-the-Minute News About Type "U" Transformer
More informationPurpose. Scope. Process flow OPERATING PROCEDURE 07: HAZARD LOG MANAGEMENT
SYDNEY TRAINS SAFETY MANAGEMENT SYSTEM OPERATING PROCEDURE 07: HAZARD LOG MANAGEMENT Purpose Scope Process flow This operating procedure supports SMS-07-SP-3067 Manage Safety Change and establishes the
More informationGRUNDFOS industry GRUNDFOS CR MONITOR. Intelligent warning
GRUNDFOS industry GRUNDFOS CR MONITOR Intelligent warning Look into the future with the CR monitor Tired of having to overhaul your pumps on a regular basis only to find that they are operating flawlessly?
More informationPeriodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels
(Jan 2017) Periodic Survey of Fuel Installations on Ships other than Liquefied Gas Carriers utilizing gas or other low flash point fuels CONTENTS 1. Application 2. Special Survey 2.1 Schedule 2.2 Scope
More informationPERFORM Operating Document
PERFORM Operating Document Use and Maintenance of CO 2 Incubator PC-POD-CA-007-v03 Revision History Version Reason for Revision Date 01 New POD 30-Sep-13 02 Minor revisions for section 2.3, 3.1, 4.3. 14-April-16
More informationAE R1 February 2015
February 2015 CoreSense Diagnostics for Copeland Scroll UltraTech Air Conditioning Compressors TABLE OF CONTENTS Safety Safety Instructions... 2 Safety Icon Explanation... 2 Instructions Pertaining to
More informationDatasheet: K-30 ASCII Sensor
Datasheet: K-30 ASCII Sensor The K30 ASCII sensor is a low cost, infrared and maintenance free transmitter module intended to be built into different host devices that require CO2 monitoring data. The
More informationIntroduction. Part one: Identify the Hydraulic Trainer Components
The University Of Jordan School of Engineering Mechatronics Engineering Department Fluid Power Engineering Lab Experiments No.4 Introduction to Hydraulic Trainer Objective: Students will be able to identify
More informationGas density monitor With integrated transmitter Model GDM-100-TI
SF 6 gas solutions Gas density monitor With integrated transmitter Model GDM-100-TI grid Products WIKA data sheet SP 60.05 for further approvals see page 5 Applications Gas density monitoring of closed
More informationHow to specify a product. Process Sensors and Mechanical Instruments
How to specify a product Process Sensors and Mechanical Instruments Keep the overview. Here is some guideline information on how to specify our products. Intended as supplementary help to specification
More informationTransformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks
Proceedings of the 4th International Conference on Systems and Control, Sousse, Tunisia, April 28-30, 2015 TuCA.2 Transformer fault diagnosis using Dissolved Gas Analysis technology and Bayesian networks
More informationATL R/V Atlantis AUXILIARY PLANT OPERATION APPENDIX OPERATING PROCEDURES
110 AIR CONDITIONING CHILLED WATER PLANT 1. Ensure power to water chiller controller and all fan coil unit controllers is on 2. Ensure chilled water expansion tank level is at its proper level 3. Ensure
More informationGuideline No.M-05(201510) M-05 AIR COMPRESSOR. Issued date: 20 October China Classification Society
Guideline No.M-05(201510) M-05 AIR COMPRESSOR Issued date: 20 October 2015 China Classification Society Foreword This Guideline constitutes the CCS rules, and establishes the applicable technical requirements
More informationNeil Kane Managing Director EMT UK
Neil Kane Managing Director EMT UK SF6 Measurement, Analysis, Diagnostics and Leak Detection Our goals at EMT are to supply Maintenance Operatives with the very best tools to protect both personnel and
More informationTANK MANAGER FOR TWO TANKS OPERATING MANUAL. 10/31/11 C-More T6C L color touch panel
TANK MANAGER FOR TWO TANKS OPERATING MANUAL 10/31/11 C-More T6C L color touch panel 1 TABLE OF CONTENTS GENERAL...3 INSTALLATION...4 STONE TEST PROCEDURE...7 OPERATIONAL SUMMARY...7 AUTO CARBONATION...10
More informationTANKTRONIC. STANDARD CONFIGURATION Single Tank. ADVANCED CONFIGURATION Multiple Tanks. Twin Tank (common valve) Twin Tank (separate valves) Vent box
TANKTRONIC STANDARD CONFIGURATION Single Tank control unit Twin Tank (common valve) control unit Twin Tank (separate valves) control unit ADVANCED CONFIGURATION Multiple Tanks control unit S-Module Tanktronic
More informationMaster Control Systems, Inc. Variable Speed Fire Pump Controllers
Master Control Systems, Inc. Variable Speed Fire Pump Controllers Meets NFPA 20-2013 UL/FM Listed and Approved for fire protections 1 Why Variable Speed? Huge Sprinkler System and Standpipe Cost Savings
More informationAquavar SOLO 2 Frequently Asked Questions
Aquavar SOLO 2 Frequently Asked Questions How do I size the Aquavar SOLO 2 for the appropriate pump/motor combination? Can I use a 208 Volt motor? Can I run the Aquavar SOLO 2 up to 80HZ? What are the
More information42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only)
42045 Heavy Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor Only) 42047 Heavy Duty ADA Base Model Kit: 110/145 PSI (ADA Compressor Only) 45052 Constant Duty ADA Base Model Kit: 85/105 PSI (ADA Compressor
More informationSimple Time-to-Failure Estimation Techniques for Reliability and Maintenance of Equipment
F E A T U R E A R T I C L E Simple Time-to-Failure Estimation Techniques for Reliability and Maintenance of Equipment Key Words: Reliability and maintenance, time-to-failure estimation, reactive maintenance
More informationReturn to Session Menu DYNAMIC POSITIONING CONFERENCE QUALITY ASSURANCE SESSION. The Meaning of LIFE. Richard Purser GL Noble Denton
Return to Session Menu DYNAMIC POSITIONING CONFERENCE October 15-16, 2013 QUALITY ASSURANCE SESSION The Meaning of LIFE Richard Purser GL Noble Denton The Meaning of Life 15 th October 2013 What is the
More informationSYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA
SYSCO BUCKHEAD BEEF CHARLOTTE, NORTH CAROLINA August, 2016 Infrared Inspection Report Sysco Buckhead Beef 3516 Green Park Circle Charlotte, North Carolina, 28217 Company Contact Mark McNeely Project: 15120816
More informationSAFETY PRECAUTIONS FOR THE BLACK BEARD S BEACH WATER PARK
SAFETY PRECAUTIONS FOR THE BLACK BEARD S BEACH WATER PARK The following safety precautions are for the Black Beard s Beach Water Park and are based on the Operations Manual Warranties & As-Builts for the
More informationWireless I/O, Connecting Remote Sensors in a Wide Range of Environments
Gas Well Deliquification Workshop Sheraton Hotel, February 19 22, 2012 Wireless I/O, Connecting Remote Sensors in a Wide Range of Environments Glenn Longley, Sr. Product Manager FreeWave Technologies Agenda
More informationSYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND
SYSCO ST JOHN'S MOUNT PEARL, NEWFOUNDLAND October, 2016 Infrared Inspection Report Sysco St. John s 10 Old Placentia Road Mount Pearl, NF A1N 4P5 Company Contact: David Shaw Project: C261016 2605 CHARTER
More informationPERFORM Operating Document
PERFORM Operating Document Use and Maintenance of CO 2 Incubator PC-POD-CA-007-v02 Revision History Version Reason for Revision Date 01 New POD 30-Sep-13 02 Minor revisions for section 2.3, 3.1, 4.3. 14-April-16
More informationSensoric 4-20 ma Transmitter Board Operation Manual
Sensoric 4-20 ma Transmitter Board Operation Manual 1 Content Features Operation Manual Technical Data Mechanical Dimensions Remarks & Contact information 2 Features Soldered sensor cell (non replaceable)
More informationThe Path to LUBRICATION EXCELLENCE
The Path to LUBRICATION EXCELLENCE TABLE OF CONTENTS CHAPTER 3 Traditional Time-Based Lubrication CHAPTER 1 When Bearings Fail Prematurely CHAPTER 2 The Challenge For Maintenance Professionals CHAPTER
More informationGasSense NDIR User Manual
INDEX INDEX... 1 1. OVERVIEW... 2 2. TECHNICAL DATA... 3 3. SPECIFICATIONS... 4 4. PRODUCT DESCRIPTION... 5 4.1 Mechanical details... 5 4.2 Piping... 7 4.3 Connections... 7 5. INSTALLATION... 10 6. CALIBRATION
More informationBUBBLER CONTROL SYSTEM
BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air
More information2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic. Pressure Measurement Engineered solutions for all applications
Application Description AG/266PILD-EN Rev. C 2600T Series Pressure Transmitters Plugged Impulse Line Detection Diagnostic Pressure Measurement Engineered solutions for all applications Increase plant productivity
More informationTest pumps. Pressure sources. Good reasons for proper and reliable calibration
Test pumps Pressure is one of the most commonly measured quantities in engineering, which is why exact and reliable pressure measurement is especially important. However, the characteristics of the even
More informationRULES PUBLICATION NO. 119/P
RULES PUBLICATION NO. 119/P PERIODIC SURVEYS OF FUEL INSTALLATIONS ON SHIPS OTHER THAN LIQUEFIED GAS CARRIERS UTILIZING GAS OR OTHER LOW FLASH POINT FUELS 2019 January Publications P (Additional Rule Requirements)
More informationIMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS CAUTION - To reduce risk of electrical shock: - Do not disassemble. Do not attempt repairs or modifications. Refer to qualified service agencies for all service and repairs.
More informationApplication of CHE100 in Frequency Conversion Alteration of Air Compressor System
Application of CHE100 in Frequency Conversion Alteration of Air Compressor System Abstract: This paper describes application of CHE100 in frequency conversion alteration of the air compressor system and
More information200 PSI COMPRESSORS - MODEL NUMBERS
200 PSI COMPRESSORS - MODEL NUMBERS 380C AIR COMPRESSOR KIT PART NO. 38033 480C AIR COMPRESSOR KIT PART NO. 48043 380C 480C IMPORTANT: It is essential that you and any other operator of this product read
More informationAUTOMATIC GAS MANIFOLDS
AUTOMATIC GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com
More informationHydro Plant Risk Assessment Guide
September 2006 Hydro Plant Risk Assessment Guide Appendix E10: Compressed Air System Condition Assessment E10. 1 GENERAL Compressed air systems are key components at hydroelectric power plants. Compressed
More information