Operating Instructions
|
|
- Darlene Stokes
- 5 years ago
- Views:
Transcription
1 Operating Instructions Before operating the thin film evaporator, please be aware of all safety concerns associated with this experiment: Burn hazard from the column and steam lines, Chemical hazards associated with ethylene glycol. 1. Preparation for Start-up Make sure that the product tanks and their sight glasses are empty. If necessary, pump the tank content to the feed tanks on the 2 nd floor (see Section 3) and empty the tank sight glasses (see Section 4). Go to the 2 nd floor and select the tank to be used as a feed source (note that some of the tanks are used for storage of pure EG). Mix the content of the selected feed tank o Make sure that all valves are closed except the inlet and outlet valves for the selected tank, the main outlet valve, and the suction and discharge valves of the mixing pump (see Figure 1). o Turn the mixing pump on by using a switch on the electric panel o Turn the mixing pump off after about 10 minutes. Close the pump suction and discharge valves. Figure 1. Feed tanks on the 2 nd floor (left) and piping around the feed mixing pump (right). On the 1 st floor, check that the enclosure for the inline refractometers is pressurized (see Figure 2). The enclosure is required to be pressurized by clean dry air to ensure that there are no flammable 1
2 gases near electronic equipment contained in the enclosure. If pressure in the enclosure is too low, the low pressure alarm will go off. If this happens, adjust the air valve on the enclosure control panel until the pressure gauge indicates Safe. Figure 2. System components near the enclosure for inline refractometers: (a) side view and (b) front view. 2
3 2. Start-up Turn on the cooling water for heat exchangers and condensers by slowly turning the main water valve shown in Figure 3. Make sure that the water valve is fully open. If necessary, adjust rotameters for water flows to individual heat exchangers and condensers (the rotameters are located on the back of the evaporator stand). Figure 3. South side view of the TFE. Turn on the seal water for the TFE rotor and set it to 2.5 GPM using the rotameter located on the right side of the TFE system (see Figure 3). Turn on the electric switch for the votator (see Figure 2). 3
4 Figure 4. Steam and air lines. Preheat the evaporator: slowly open the blue TFE steam valve (see Figure 4). 1. Make sure to wear a heat-resistant glove the steam line is hot! 2. It is important to open the valve slowly to prevent thermal shock to the system. The gap between the rotor blades and inner walls of the evaporator is very narrow (0.75 mm) and thermal shock may cause distortion of the system. 3. Start with opening the steam valve so that the steam pressure is approximately 5 psi. 4. Continue to slowly open the valve so that the pressure changes at a rate of about 20 psi per minute. 5. Stop when the steam pressure reached 75 psi. Open the main feed valves located on near the power switch (see Figure 2). Check calibration of the inline refractometers by briefly sending feed flow through all of three them. 1. Use the 3-way valves located below the refractometer enclosure (see Figure 2) to change direction of the flow. Direction of the flow is indicated by the short end of the valve handle, as shown in Figure Verify that all three refractometers read the same value. 3. Return the 3-way valves into their original positions to allow the product flow into the product refractometers. 4. Take a feed sample using the sample port shown in Figure 2a. 5. Measure the sample composition using the tabletop refractometer and compare the result with the measurements of the inline refractometers. 4
5 Figure 5. 3-way valve with the short end of the handle pointing (a) to the right and (b) to the left. The dashed red lines indicate the path of the fluid flow corresponding to the position of the valve handle. On the first day of the lab: Calibrate the feed rotameter; use the feed control valves to adjust the feed flow rate (see Figure 6). Use the feed control valves to set a desired feed flow rate for your experiment. Figure 6. Feed control valves and rotameter. Important: Never feed liquid into the evaporator without the rotor turning. Doing so may cause: 1. Uneven heating around a stationary rotor, which may cause deformation of the rotor. 2. Accumulation of liquid in the process area, which will generate an extra resistance to the rotor when it starts turning, which may damage the system. 5
6 Open the steam injector valve (see Figure 3) to generate vacuum in the system. Do this slowly to avoid shocking the system with a rapid pressure change. 1. Make sure to wear a heat-resistant glove! 2. Use the pressure gauge located above the product tanks (see Figure 7) to set the desired system vacuum pressure. Figure 7. Vacuum gauge. 3. While the system is running: Measure and record product concentration and temperature every 5 minutes (for both the top and bottom products). o o The product concentration is measured by inline refractometers. Don t forget to convert Brix % to ethylene glycol concentration! The product temperature should be read using a thermocouple reader. Make sure that the thermocouple type displayed by the reader is K. If it s not, press the TYPE button on the reader until K is displayed. Record liquid level in the product tanks every 5 minutes After reaching a steady-state, measure the flow rate of the steam condensate using the bucket and stopwatch method. 6
7 4. Recycling products After an experimental run is complete, it is necessary to recycle the content of the product tanks back to the feed tank. In order to do this, at least one of the group members should go to the 2 nd floor while other group members should remain on the 1 st floor. Liquid transfer requires communication between the 1 st and the 2 nd floors. Please use 2-way radios (available in the control room) for this purpose. On the 2 nd floor: Make sure that 1. The 2 nd floor return valve is open (see Figure 8) 2. The inlet valve for the feed tank is open (see Figure 1). Important: there is a line for deionized (DI) water next to the return line on the 2 nd floor (see Figure 8). Make sure to open the valve on the return (and not the DI water) line. The DI water line should be used by the lab technician only. Figure 8. Product return and DI water lines near the feed tanks on the 2 nd floor. Wait for a signal from the 1 st floor. Once you receive a signal, open the deadman valve on the return line (see Figure 9). In order to keep this valve open, it is necessary to hold on to its handle. Once the handle is released, the valve returns to the closed position. Monitor the level of the feed tanks while the fluid is being transferred. If you see that one of the tanks is overflowing, release the deadman valve. Figure 9. Deadman valve on the return line (2 nd floor). 7
8 On the 1 st floor: If the system is in operation, reduce the vacuum pressure to below 8 in Hg. This is required for proper operation of the return pump (see below). Open the main return valve located next to the power switch (see Figure 2) and the return valves located next to the product tanks (see Figure 10). Figure 10. Product tanks, return line, and return pump. Inform the person on the 2 nd floor that you are about to start the return pump. Make sure that they are ready to open the deadman valve before turning the pump on. The return pump is air-operated. Turn it on by opening the on/off air valve located next to the return pump (see Figure 10). Adjust the air control valve so that the pump makes about 2 clicks per second. Once the tanks are empty, close the return valves and turn off air supply for the return pump. 8
9 5. Taking a product sample or emptying sight glass while the evaporator is under vacuum Note: This procedure should only be performed if one of the inline refractometers is faulty. The purpose of this procedure is to take a sample that can be analyzed using a desktop refractometer. Close the sight glass valves (see Figure 11). o This isolates the sight glass from the product tank Open the vent valve on the sight glass o This lets atmospheric air into the sight glass Open the sample port valve and take a sample (or drain the sight glass completely) Figure 11. Product tank. After the necessary amount of fluid is taken from the sight glass: o Close the sample port valve o Close the vent valve o Reestablish the connection between the sight glass and the tank: Slightly open the bottom sight glass valve. Slowly open the top sight glass valve until it is fully open. This will return the sight glass to the same pressure as the tank and, if the tank is not empty, you should see liquid filling up the sight glass. Slowly open the bottom sight glass valve until it is fully open. o It is important to follow this procedure for reestablishing connection between the sight glass and the tank. Opening the valves out of order or too quickly may result in a fast and turbulent flow from the tank to the sight glass, which will activate a check valve 1, which will prevent the liquid level in the sight glass from reaching the liquid level in the tank. 1 The purpose of the check valve is to prevent a large spill in case the sight glass is broken. A broken sight glass will lead to a fast flow from the tank to the sight glass and will activate the check valve, thus preventing spilling the entire content of the tank. 9
10 6. Shut down Close the blue steam valve. Keep the steam mains valve open at all times (see Figure 4). This is necessary to for automatic condensate purge from the steam line. Keep the feed valve open for several minutes. The liquid flowing through the evaporator will help condense steam remaining in the evaporator jacket. You should see reduction in the steam pressure on the gauge shown in Figure 4. Wait until the steam pressure has reduced to about 5 psi. Close the steam injector valve. Close the feed valve and wait until the flows into the product tanks stop. Turn off the votator motor. Turn off cooling water for the heat exchangers and condensers and the seal water for the TFE rotor (see Figure 3). Pump the liquid contained in the product tanks back to the feed tank on the 2 nd floor (see Section 4). 10
Armfield Distillation Column Operation Guidelines
Armfield Distillation Column Operation Guidelines 11-2016 R.Cox Safety SAFETY GLASSES ARE REQUIRED WHEN OPERATING THE DISTILLATION COLUMN Wear gloves when mixing alcohol feedstock The column will become
More informationOperating Instructions
Operating Instructions Preparation for Start-up 1. If the computer system is logged off, log into the computer system. Log into the operator account on the computer. Please ask your TA for username and
More information1. Study the performance of a binary distillation column operated in batch mode.
Goals for batch distillation using the East distillation column: 1. Study the performance of a binary distillation column operated in batch mode. 2. Determine the overall and local efficiency of the column
More informationAcornVac Vacuum Plumbing Systems - Trouble Shooting Guide
AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide 1. Accumulators Problem Accumulator is overflowing If Accumulator continues to overflow Correction 1. Push and hold the manual activation button
More informationCHEMICAL ENGINEERING LABORATORY CHEG 239W. Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller
CHEMICAL ENGINEERING LABORATORY CHEG 239W Control of a Steam-Heated Mixing Tank with a Pneumatic Process Controller Objective The experiment involves tuning a commercial process controller for temperature
More informationGas Absorption Draft Standard Operating Procedure
Gas Absorption Draft Standard Operating Procedure R.C. 9-14 Scope Page 1 Equipment Overview Page 1 Safety Page 2 Operating Procedure Page 4 Equipment Description Page 16 Gas Absorption Experiment Draft
More informationManual for continuous distillation
Manual for continuous distillation 1. Week 1: Objectives: Run the column at total reflux. When steady state is reached, take the sample from the top and bottom of the column in order to determine the overall
More informationANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS
Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This
More informationThermocirc Installation and Maintenance Instructions
1570072/2 IM-P157-36 ST Issue 2 Thermocirc Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation 6 Maintenance
More informationOperating Instructions
Operating Instructions Note: 1. Never let the centrifugal pump run dry. 2. Make sure that there is at least one open path for water flow in the pipe network before turning the pump on. Never run the pump
More informationDF1 and DF2 Diffusers
1550650/4 IM-P155-07 ST Issue 4 and Diffusers Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Operation 6. Maintenance
More informationEquipment Operating Procedure Glove Box
Equipment Operating Procedure Glove Box Page 1 0.0 Changing the Compressed Gas Cylinder 1. Complete Compressed Gas Cylinder training from EHS website before manually exchanging gas cylinders. In order
More informationGAS DEHYDRATION SYSTEM
GAS DEHYDRATION SYSTEM High pressure gases from the Gas Compressors (CBA-4070/4020) flow to the Glycol Contactor (MAF-1150). In the Contactor, gas flows through trays, contacting the lean glycol that is
More informationHill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide
Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide Secondary Coolant System Start-Up Procedures June 2006 Produced by the Hill PHOENIX Learning Center DISCLAIMER This
More informationOPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS MODEL GS2000 / GS2001 OIL-LESS REFRIGERANT RECOVERY UNIT NATIONAL REFRIGERATION PRODUCTS 985 WHEELER WAY LANGHORNE, PA 19047 (215) 638-8909 FAX (215) 638-9270 R01099 GS2000.DOC NRP-OM-GS2000
More informationMST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap
1250650/6 IM-P125-07 ST Issue 6 MST21 Stainless Steel Balanced Pressure Thermostatic Steam Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation
More informationTrion PECVD SOP IMPORTANT: NO PLASTIC, TAPE, RESISTS, OR THERMAL PASTE ARE ALLOWED IN THE CHAMBER
Trion PECVD SOP IMPORTANT: NO PLASTIC, TAPE, RESISTS, OR THERMAL PASTE ARE ALLOWED IN THE CHAMBER CAUTION: THE CHAMBER PLATE GETS EXTREMELY HOT Start Up Procedure 1) Open bottle and regulator for Helium,
More informationAE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions
0176050/3 IM-P017-11 ST Issue 3 AE50S Automatic Air and Gas Vent for Liquid Systems Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4
More informationPumpAgents.com - Click here for Pricing/Ordering Nominal psi (bar) Cut-In Cut-Out
PumpAgents.com - Click here for Pricing/Ordering Model 31670-Series Dual Max 7.5 GPM (28 LPM) AUTOMATIC TWO STAGE WATER SYSTEM WITH ACCUMULATOR TANK AND PUMPGARD STRAINER IDEAL FOR PLEASURE AND COMMERCIAL
More informationInert Air (N2) Systems Manual
INSTRUCTION MANUAL Inert Air (N2) Systems Manual N2-MANUAL 2.10 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT. GENERAL INFORMATION Positive pressure nitrogen gas pressurizing
More informationTHERMAL EVAPORATION UNIT (for Al evaporation)
THERMAL EVAPORATION UNIT (for Al evaporation) System Owner: NeerajPanwar 9619507210 panwar.iitr@gmail.com System Operator: 1. Bhimraj Sable 9930189878 bhimrajsable71@gmail.com Authorized User: 1. Ramesh
More informationAdsorption Unit Operating Procedures: CO2 Adsorption on to Activated Carbon
Adsorption Unit Operating Procedures: CO2 Adsorption on to Activated Carbon Background Safety Concerns Description of the Unit Switching the Unit On Preparation of the Unit Configuration of the Unit for
More informationSCA Series Inverted Bucket Steam Traps
0770050/5 IM-P077-06 ST Issue 5 SCA Series Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning
More informationSpirax Compact FREME Flash Recovery Energy Management Equipment
IM-UK-cFREME UK Issue 1 Spirax Compact FREME Flash Recovery Energy Management Equipment Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4.
More informationGAS COMPRESSION SYSTEM
GAS COMPRESSION SYSTEM The gas compression system at HI 376 A consists of two natural gas turbine-driven Compressors (CBA-4020/4070). Both Compressors are needed for the volume of gas being compressed.
More informationTD45 Thermodynamic Steam Trap Installation and Maintenance Instructions
0685255/1 IM-P068-47 ST Issue 1 TD45 Thermodynamic Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation 4 Commissioning 5 Operation
More informationChapter 3 EXPERIMENTAL: EQUIPMENT, SET-UP, AND PROCEDURE
Chapter 3 EXPERIMENTAL: EQUIPMENT, SET-UP, AND PROCEDURE 72 3.0 Introduction The experimental work was carried out in three stages. First stage: a laboratory scale single nozzle horizontal jet ejector
More informationBulletin TCR-104 & 109 Filling and adding to the Glycol pressure system
Bulletin 061013 TCR-104 & 109 Filling and adding to the Glycol pressure system 1. Glycol System and air On this model the glycol system is a closed system, the glycol is not exposed to the air. No external
More informationGAS DEHYDRATION SYSTEM
GAS DEHYDRATION SYSTEM High pressure and compressed gases flow to the Glycol Contactor (MAF-3110). In the Contactor, gas flows through trays, contacting the lean glycol that is flowing across the trays
More informationUBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions
1270750/7 IM-P127-02 ST Issue 7 UBP32 Sealed Balanced Pressure Thermostatic Steam Trap for use with PC_ Pipeline Connectors Installation and Maintenance Instructions 1 General safety information 2 General
More informationSERIES 30. Spring Operated Tank Blanketing Valve PROTECTOSEAL.
SERIES 30 PROTECTOSEAL 1 2" NPT inlet and outlet standard Direct acting valve mechanism Optional flanged or threaded inlet and outlet connections available Inlet gas pressures from 10 PSIG to 200 PSIG
More informationHEAT EXCHANGE AND TRANSFER, INC. 500 Superior Street Carnegie, PA (412) Fax: (412)
SECTION Bypass Oil Sampling Station (B.O.S.S 1000) GENERAL.......................... SAFETY........................... Hazards............................... Personal Protective Equipment........... PRODUCT
More informationUSM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions
6250250/1 IM-P625-03 ST Issue 1 USM21 Sealed Bimetallic Steam Trap for use with Pipeline Connectors Installation and Maintenance Instructions 1. General safety information 2. General product information
More informationUIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors
1130050/4 IM-P113-02 ST Issue 4 UIB30 and UIB30H Sealed Inverted Bucket Steam Traps for use with Pipeline Connectors Installation and Maintenance Instructions 1. Safety information 2. General product information
More informationUsing P-T Analysis As A Service Tool
Using P-T Analysis As A Service Tool Manufacturers of refrigerants, controls, other suppliers distribute hundreds of thouss of pressure-temperature charts to the trade every year. It would be rare indeed
More informationSERIES 10. Pilot Operated Tank Blanketing Valve, 2" PROTECTOSEAL.
SERIES 10 PROTECTOSEAL 2" NPT inlet and outlet standard Pilot operated design provides tight operating band Optional inlet and outlet connections available Inlet gas pressures from 40 PSIG to 130 PSIG
More informationMEMORIAL UNIVERSITY OF NEWFOUNDLAND Faculty of Engineering and Applied Science FLUID MECHANICS LABORATORY PIPE FRICTION
MEMORIAL UNIVERSITY OF NEWFOUNDLAND Faculty of Engineering and Applied Science FLUID MECHANICS LABORATORY PIPE FRICTION Objective To estimate the fluid pressure drops and roughness specifications for copper
More informationOperating Procedures for Metal Evaporator I
Operating Procedures for Metal Evaporator I Metal Evaporator I is intended as a tool and a training device. Understanding the operation of this equipment should give you a basic knowledge of vacuum and
More informationBlue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION
Blue River Technologies Port-A-Poly Mixer w/2.5 GPH LMI Pump And Secondary Water Dilution Line INSTALLATION AND OPERATION Install your Blue River Technologies Port-A-Poly mixing system in a clean dry area.
More informationGuideline No.M-05(201510) M-05 AIR COMPRESSOR. Issued date: 20 October China Classification Society
Guideline No.M-05(201510) M-05 AIR COMPRESSOR Issued date: 20 October 2015 China Classification Society Foreword This Guideline constitutes the CCS rules, and establishes the applicable technical requirements
More informationKKT Training Series: ECO Series, Preventative Maintenance
KKT Training Series: ECO Series, Preventative Maintenance p.m. process The preventative maintenance is a scheduled event with one hour of downtime. We must ensure the following procedure is performed:
More information6301 TYPE CAST IRON SAFETY VALVES
Pressure (bar) 6301 TYPE CAST IRON SAFETY VALVES FEATURES The 6301 type safety valve is a device designed to protect installations against possible overpressure. It operates automatically and closes when
More informationStandard Operating Procedure
Page 1 of 10 Vigor Glove Box Standard Operating Procedure Lab: ESB 154 Department: Materials Science and Engineering PI: Paul V. Braun Written By: Subing (Alan) Qu Section 1: Overview Type of SOP: Process
More informationFX134, FX1234, FX3030 Problem and Solutions
FX134, FX1234, FX3030 Problem and Solutions Unit Will Not Power Up Turn the power switch on. The unit LCD will display revision program and filter life within 3 to 5 seconds after turning on unit. If this
More informationOPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC East Market Street York, PA Manual P/N
OPERATION MANUAL RTI RHS650 RTI TECHNOLOGIES, INC. 4075 East Market Street York, PA 17402 Manual P/N 035-80589-02 Table of Contents Components... 2 Test... 4 Recovery/Recycling... 5 Evacuation... 7 Charging...
More information2. Determine how the mass transfer rate is affected by gas flow rate and liquid flow rate.
Goals for Gas Absorption Experiment: 1. Evaluate the performance of packed gas-liquid absorption tower. 2. Determine how the mass transfer rate is affected by gas flow rate and liquid flow rate. 3. Consider
More informationR E D I C O N T R O L S
R E D I C O N T R O L S Operation & Maintenance Manual Portable Service Purger for Low Pressure Chillers Model: PSP-LP-1B For Refrigerants R-11, R-113, R-114 & R-123 & Other Similar Refrigerants File Literature
More informationTD10, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions
6875/3 IM-P68-31 ST Issue 3 TD1, TD52M and TD259 Thermodynamic Steam Traps Installation and Maintenance Instructions 1 General safety information TD1 2 General product information 3 Installation 4 Commissioning
More informationPART 1 GENERAL..2 Components of the gas chlorination system include, but are not limited to the following:
PART 1 GENERAL 1.1 DESCRIPTION.1 This section includes the supply, delivery and installation, testing and placement into operation of a gas chlorination system, and appurtenances as specified herein and
More informationCPE562 Chemical Process Control HOMEWORK #1 PROCESS & INSTRUMENTATION DIAGRAM
Faculty of Chemical Engineering CPE562 Chemical Process Control HOMEWORK #1 PROCESS & INSTRUMENTATION DIAGRAM SUBMISSION DATE: 1 OCT. 2012 Question 1 Name the following equipments based on standard P&ID
More informationGenie Supreme TM Model 123HP Installation & Operation Instructions
Genie Supreme TM Model 123HP Installation & Operation Instructions Manufacturing Contact Information A+ Corporation, LLC Call for expert product application assistance: 41041 Black Bayou Rd. Gonzales,
More informationGenie Supreme Model 123 Installation & Operation Instructions
Genie Supreme Model 123 Installation & Operation Instructions Manufacturing Contact Information A+ Corporation, LLC Call for expert product application assistance: 41041 Black Bayou Rd. Gonzales, LA 70737
More informationWater Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems
Water Mist Systems Inspection, Testing, and Maintenance of Water Mist Systems Name of Property: Address: Phone Number: Inspector: Contract No.: Date: This Report Covers: Monthly Quarterly Annual Other
More informationCover Page for Lab Report Group Portion. Head Losses in Pipes
Cover Page for Lab Report Group Portion Head Losses in Pipes Prepared by Professor J. M. Cimbala, Penn State University Latest revision: 02 February 2012 Name 1: Name 2: Name 3: [Name 4: ] Date: Section
More informationINSTALLATION INSTRUCTIONS Non-Pressurized Tank. Non-Pressurized Tank Part Number: AFCG1PT
INSTALLATION INSTRUCTIONS Non-Pressurized Tank Non-Pressurized Tank Part Number: AFCG1PT Table of Contents General Desc on 2 Ins n 3 Flushing and Purging 5 Start-up 7 Adding or Checking Fluid 8 Replacing
More information5890II GC Standard Operating Procedure 9/2/2005
5890II GC Standard Operating Procedure 9/2/2005 This procedure is for the analysis of natural gas using the HP 5890II GC with the Restek ShinCarbon column. Detector Type: TCD Column Type: Restek Micropacked,
More informationDelayed Coker Safe Sampling Tar or Spalled Coke
Delayed Coker Safe Sampling Tar or Spalled Coke Presented by Mitch Moloney of ExxonMobil mitchell.j.moloney@exxonmobil.com @ Galveston TX coking.com May-2013 a MJ Moloney - ExxonMobil May-2012 coking.com
More informationGAS DEHYDRATION SYSTEM
GAS DEHYDRATION SYSTEM High pressure and compressed gases flow through the Gas Scrubber (MBF-4540) to the Glycol Contactor (MAF-0900). In the Contactor, gas flows through trays, contacting the lean glycol
More informationPOWER FLUSH KIT INSTRUCTIONS
1 GENERAL INFORMATION POWER FLUSH KIT INSTRUCTIONS ACE Power Flush is an ozone-safe solvent engineered specifically for flushing refrigeration and air conditioning systems. Used exactly like the old R-11
More informationFT16 Ball Float Steam Trap Installation and Maintenance Instructions
1430050/1 IM-P143-04 ST Issue 1 FT16 Ball Float Steam Trap Installation and Maintenance Instructions 1 General safety information 2 General product information 3 Installation ½" and ¾" shown 4 Commissioning
More information1020 Industrial Drive, Orlinda, TN fax
Operation Manual Tank Distribution System A-UPT Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.2 Warnings and Cautions... 1 1.2 Theory of Operation...
More informationAE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems
0170651/ 10 IM-P017-08 ST Issue 10 AE30 Automatic Air Eliminators / Air and Gas Vents for Liquid Systems Installation and Maintenance Instructions 1. Safety information 2. General product information 3.
More informationBT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications
1800350/6 IM-P180-12 ST Issue 6 BT6HC Hygienic Sanitary Balanced Pressure Steam Trap for High Capacity and CIP/SIP Applications Installation and Maintenance Instructions 1. Safety information 2. General
More informationOperating Guidelines for PermSelect Modules Liquid Contacting
Operating Guidelines for PermSelect Modules Liquid Contacting PermSelect PDMSXA-2500 (0.25m 2 ) PermSelect PDMSXA-7500 (0.75m 2 ) PermSelect PDMSXA-1.0 (1m 2 ) PermSelect PDMSXA-2.1 (2.1m 2 ) PermSelect
More informationAmerican Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM
American Society of Sanitary Engineering PRODUCT (SEAL) LISTING PROGRAM ASSE STANDARD #1019 - REVISED: 2011 Wall Hydrant with Backflow Protection and Freeze Resistance MANUFACTURER: CONTACT PERSON: E-MAIL:
More informationUniversity of Minnesota Nano Center Standard Operating Procedure
University of Minnesota Nano Center Standard Operating Procedure Equipment Name: Controlled Atmosphere Glove Box Model: Labconco Protector Location: PAN 185 Badger Name: Not on Badger Revision Number:
More informationCryogenics is the science of ultra low temperatures. Low temperatures are achieved by the liquefaction of gases.
CRYOGENICS SAFETY Introduction Cryogenics is the science of ultra low temperatures. Low temperatures are achieved by the liquefaction of gases. The gases which are most widely used in industry and research
More informationRG6000. Refrigerant Recovery Machine. Operating Manual. 99 Washington Street Melrose, MA Phone Toll Free
TM Refrigerant Recovery Machine RG6000 1 Operating Manual 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com Safety Precautions WARNING
More informationPetro-Chemical & Analyzer Sampling Systems
Petro-Chemical & Analyzer Sampling Systems Pressure control solutions for your industry. The Tescom brand offers a comprehensive range of regulators, valves and changeover systems that are ideal for analyzer
More informationAVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions
1234150/3 IM-P123-17 ST Issue 3 AVS32 Stainless Steel Air Vent for Steam Systems Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4.
More informationLab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow
Georgia Institute of Technology School of Earth and Atmospheric Sciences EAS 4641, Spring 2008 Lab 3 Introduction to Quantitative Analysis: Pumps and Measurements of Flow Purpose of Lab 3: 1) To gain a
More informationDri-Line Mk3 Monnier Compressed Air Drain Trap
5044050/2 IM-P504-24 CH Issue 2 Dri-Line Mk3 Monnier Compressed Air Drain Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation and Operation
More informationLAKOS Waterworks. PWC Series Sand Separators. Installation & Operation Manual LS-829 (10/12)
LAKOS Waterworks PWC Series Sand Separators Installation & Operation Manual LS-829 (10/12) Table of Contents Separator Operation... 3 Individual Model Details.... 4 Flow vs. Pressure Loss Chart 4 Installation
More informationPetro-Chemical & Analyzer Sampling Systems
Petro-Chemical & Analyzer Sampling Systems Pressure control solutions for your industry. The Tescom brand offers a comprehensive range of regulators, valves and changeover systems that are ideal for analyzer
More informationThe Discussion of this exercise covers the following points:
Exercise 5-3 Wet Reference Leg EXERCISE OBJECTIVE Learn to measure the level in a vessel using a wet reference leg. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Measuring
More informationBLOCK II HYDROGENATION (COMPRESSORS) OUTSIDE LOGSHEETS C-200A TIME: NORM COND PSV SET DIVIDER BLOCK (DB) RESERVOIR LEVEL
BLOCK II HYDROGENATION (COMORS) DATE: C-200A DIVIDER BLOCK (DB) RESERVOIR TIME: NORM SET DB RESERVOIR TEMP (Range 80-105ºF) DB PROFLOW DISPLAY (ALARM OR NORMAL?) DB NEOMAG INDICATORS (CYCLING?) DB PIN
More informationCAST IRON SAFETY VALVE TYPE 6301
CHARACTERISTICS The 6301 safety valve is dedicated to protect the equipment from potential overpressure. This is an automatic device that closes when the pressure conditions are back to normal. It is a
More informationOPERATOR S MANUAL Ar-Gone Weld Gas Analyzer
July 2011 OPERATOR S MANUAL Ar-Gone Weld Gas Analyzer WARNING! Before operating this product, read and understand this Operator s Manual. Become familiar with the potential hazards of this unit. Contact
More informationAnother convenient term is gauge pressure, which is a pressure measured above barometric pressure.
VACUUM Theory and Applications Vacuum may be defined as the complete emptiness of a given volume. It is impossible to obtain a perfect vacuum, but it is possible to obtain a level of vacuum, defined as
More informationMFP14-PPU (Vented) Automatic Packaged Pump Units
681060/2 IM-P681-02 ST Issue 2 MFP14-PPU (ented) Automatic Packaged Pump Units Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Single MFP14 - PPU installation
More informationVacuum Pumpdown and Venting Procedure, CRaTER Thermal Vacuum System. Dwg. No
Rev. ECO Description Checked Approval Date 01 32- Release M. Smith Vacuum Pumpdown and Venting Procedure, CRaTER Thermal Vacuum System Dwg. No. 32-06003.05 Revision 01 June 18, 2007 1 1. Introduction 1.1.
More informationOXY FUEL SYSTEM SET UP & SHUT DOWN PROCEDURE CHECKLIST ACETYLENE FUEL GAS
OXY FUEL SYSTEM SET UP & SHUT DOWN PROCEDURE CHECKLIST ACETYLENE FUEL GAS Items needed for demonstrations: Fire extinguisher PPE (Personal Protective Equipment): o Lab coats/welding jackets o Leather gloves
More informationOIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply
OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions
More informationA/C SYSTEM DIAGNOSIS
A/C SYSTEM DIAGNOSIS 1988 Jeep Cherokee 1988 AIR CONDITIONING & HEAT A/C General Servicing Diagnostic Procedures Jeep; All Models DIAGNOSTIC PROCEDURES Diagnosis is an important first step in A/C system
More informationExhibit 4. Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N)
1 APPLICABILITY Exhibit 4 Determination of Static Pressure Performance of the Healy Clean Air Separator (Executive Orders VR-201-N and VR-202-N) Definitions common to all certification and test procedures
More informationApplication Worksheet
Application Worksheet All dimensions are nominal. Dimensions in [ ] are in millimeters. Service Conditions Medium Through Valve: Required C v : Temperature Maximum: Minimum: Normal: Flow Maximum: Minimum:
More informationThanks for choosing EJAI SOLAR product
SPLIIT SOLAR WATER HEATER (( YYJ--S01 SERIIES )) IINSTALLATIION MANUAL www.ejaisolar.com ZHEJIANG EJAI SOLAR TECHNOLOGY CO.,LTD. 1 Thanks for choosing EJAI SOLAR product Content 1. Important Information....2
More informationInstructions for High Altitude Conversion
6304 38 0/ US/CA For heating engineers Instructions for High Altitude Conversion Logano G334 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G334 X gas-fired
More informationGUIDELINES FOR CONDUCTING HYDROGENATION REACTIONS
Page 1 of 5 GUIDELINES FOR CONDUCTING 1. Definition of Hydrogenation and Hydrogenolysis Reactions Hydrogenation reactions are synthetic transformations involving hydrogen, metallic catalysts (such as nickel,
More informationM45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions
BAC 13310 IM-P133-42 ST Issue 2 M45 ISO Ball Valve DN25 to 150 Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning 5.
More informationMSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection
1170850/1 IM-P117-36 ST Issue 1 MSC-P and MSC-N Manifolds for Steam Distribution and Condensate Collection Installation and Maintenance Instructions 1. Safety information 2. General product information
More informationFocus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels
Inerting Control Systems by NTRON PROCESS ANALYZER DIVISION of NEUTRONICS INC. EXTON. PA. 19341 RJN Rev. A June 2001 Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert
More informationExercise 5-2. Bubblers EXERCISE OBJECTIVE DISCUSSION OUTLINE. Bubblers DISCUSSION. Learn to measure the level in a vessel using a bubbler.
Exercise 5-2 Bubblers EXERCISE OBJECTIVE Learn to measure the level in a vessel using a bubbler. DISCUSSION OUTLINE The Discussion of this exercise covers the following points: Bubblers How to measure
More informationEXPERIMENT 2 LEVEL CONTROL SYSTEM
EXPERIMENT 2 LEVEL CONTROL SYSTEM 1.0 OBJECTIVE To study the response of level control process in open tank using the PID controller. 2.0 INTRODUCTION TO THE APPARATUS (MODEL WLF922). a) The process consists
More informationGA-300 Gas Analyzer. Technical Note. Overview. Front Panel. iworx Systems, Inc. GA-300
Technical Note GA-300 Overview The GA-300 CO2 and O2 Gas Analyzer is easy to use, robust, and adaptable to human, animal, and plant applications. The GA-300 has two analog outputs to allow recording and
More informationProduct Sheet Spraymist Unit
Product Sheet Spraymist Unit DESCRIPTION The Spraymist unit is perfectly adapted for use with differents liquids for applications as metalcutting, drilling, grinding, cooling or wetting processes and chain
More informationSHHH AIR COMPRESSOR Model Nos. SHHH5/24 - SHHH5/50 - SHHH7/100
SHHH AIR COMPRESSOR Model Nos. SHHH5/24 - SHHH5/50 - SHHH7/100 OPERATING & MAINTENANCE INSTRUCTIONS 0306 Thank you for purchasing this CLARKE Shhh Air silent running air compressor Before attempting to
More informationTSS21 Sealed Thermostatic Steam Tracer Trap
1255050/4 IM-P125-10 ST Issue 4 TSS21 Sealed Thermostatic Steam Tracer Trap Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
More informationOperating Instructions Models and Hydrostatic Test Pumps
Operating Instructions Models 33100 and 33101 Hydrostatic Test Pumps 33100 DIMENSIONS: WEIGHT: PUMP: MOTOR: CONTROL: GAUGE: DISCHARGE HOSE: 16 (40cm) L x 22 (55cm) W x 18 (45cm) H 87 lbs., 39.5 kg Triplex
More informationTROUBLESHOOTING GUIDELINES
TROUBLESHOOTING GUIDELINES PROBLEM: Performance 1. The most common problem in this area comes from inadequate flow to the LAKOS Separator(s). All LAKOS Separators operate within a prescribed flow range
More information