HV Spiker Kit - CSTE. 30 th April 2014

Size: px
Start display at page:

Download "HV Spiker Kit - CSTE. 30 th April 2014"

Transcription

1 HV Spiker Kit - CSTE 30 th April 2014

2 Safety Working With Cables As a cable jointer, safety is paramount when working daily with live electricity. When working with cables it is essential to know whether a cable is dead or alive. 2 or more buried cables remote from terminations can present a hazard - Which Cable is dead? - How Can I be certain? The identification of a particular cable circuit can be uncertain. This can be the case where a cable diversion is required for new works such as a road or other utilities work. We can offer equipment that allows you to have confidence that the cable you are working on is dead. Spiker Kit CSTE with over 30 yrs service experience. page 2

3 ESSENTIAL SAFETY RULES. 1. Only a competent engineer can operate this equipment and is required to comply with his or her company Health & Safety regulations. 2. A responsible person must have taken all reasonable steps to ensure that the cable to be spiked is dead. 3. HSE Safe Working Practices States Where underground cables cannot be positively identified and proved dead at the point of work, it may be necessary to spike the cable 4. HV circuits/cables can retain stored energy (eg capacitance). Spiking cables limits the risk of possible incorrectly earthed circuits or wrongly identified cables that may be connected to potentially charged stored energy circuits. page 3

4 ESSENTIAL SAFETY RULES. 5. Connection of the spiker earth point to a good site earth is essential. 6. Always operate the spiker at the full distance that the hydraulic hose allows and at a safe distance from (point 3.) 7. Never attempt to spike a cable of larger diameter than specified. 8. Always ensure that the spiker blade has reached the correct depth by using the indicator situated on the device. 9. It is important to note that on small cables it is possible to spike through the cable and damage to the safety device and spiker could occur, so measuring the depth of the spike is essential. page 4

5 Spiker Kit - CSTE Spiker Hydraulic Ram Unit Clamp Release Screws A very Robust Storage Case with Humidity Control Spike Depth Indicator Earth cable minimum 6m long Diamond Shaped Chisel Head Insulated Hydraulic Hose 6m long Hydraulic Hand Pump page 5

6 Spiker Kit CSTE Cables Single and three core mains Cable 11kV 11kV XLPE power cables for power networks, underground, outdoors and in cable ducting. 11kV cables are certified - BS6622 and BS EN/IEC Sheathed in a durable PVC sheathing. The CSTE spiker must not be used on cables above 11kV as such cables may exceed the mechanical features of the cutting blade. When piercing single core cable the spike and clamp must remain earthed to allow short circuit to earth. Conventional cable spiker guns will spike 3 core polymeric cables, although a jacking attachment is required to facilitate the removal of the spike from the cable. page 6

7 Spiker Kit - CSTE The Bowthorpe Spiker Kit is a safety device Designed to prove that a cable an engineer is working on is not live. The CSTE Does not require an explosive cartridge Is a robust design. Suitable for up to 102mm overall diameter cable An independent insulated earth supplied 6m x 50 sqmm The CSTE uses a fully insulated hydraulic hose which is 6m long Regular maintenance of the CSTE is required. Sharp spike required No oil leaks page 7

8 Spiker Kit CSTE - Assembly Fig 1 details the clamping arrangement for the cable Unscrewing the clamp allows the ram and spiker mechanism to be removed. (Fig 2) Ensure the spike is fully retracted prior to clamping into final position. The cable can then be placed in the V shaped tray and the ram and spiker mechanism can be placed around the cable and clamped into position. Fig 1 Fig 2 page 8

9 Spiker Kit - CSTE Copper Earth point is provided A The standard earth cable is 6M long and must be fitted to A (Longer lengths can be provided on request) The cable must be fitted to a suitable earth point which is checked before use. The selected earth point must be effective. Where no effective earth is available within 6M an extra earth lead of the same cross sectional area and current carrying capability must be added to reach a sound earth point The CSTE has a mechanical dial which indicates the travel of the spiker down into the cable (Fig 4) page 9

10 Spiker Kit - CSTE Note : If the cable is live a short circuit will occur. Depending on the available short-circuit current damage to the spiker kit will occur. The spiker kit should remain in position until a responsible person has confirmed that the previously live cable is now dead and has been isolated and earthed. Removal of the kit following a short-circuit event should be done with care and all parts inspected for damage. After an event the CSTE will need to be serviced. page 10

11 CSTE Operating Instructions page 11

12 EVERY CONNECTION COUNTS

MV-105 MEDIUM VOLTAGE CABLE. 5kV, 8kV, 15kV, 25kV & 35kV

MV-105 MEDIUM VOLTAGE CABLE. 5kV, 8kV, 15kV, 25kV & 35kV MV-05 MEDIUM VOLTAGE CABLE 5kV, 8kV, 5kV, 5kV & 5kV MV-05 MEDIUM VOLTAGE POWER CABLE 5kV % INSULATION LEVEL 8kV 00% INSULATION LEVEL Conductor conforming to ASTM B and Class B Compact stranded in accordance

More information

Vacuum Excavation in the vicinity of the Wellington Electricity Network

Vacuum Excavation in the vicinity of the Wellington Electricity Network Vacuum Excavation in the vicinity of the Network. Document no: ENG-116 Document Rev: 1 Issue Status: Final Issue Date: 14/05/2015 Page 1 of 9 Contents 1. PURPOSE... 3 2. POLICY... 3 3. SCOPE... 3 4. REFERENCES...

More information

750 Cable Cutter INSTRUCTION MANUAL

750 Cable Cutter INSTRUCTION MANUAL INSTRUCTION MANUAL 750 Cable Cutter Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register this product at www.greenlee.com

More information

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0) Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk SOFT LINE CUTTER SL55 PRODUCT CODE No. 980504 INSTRUCTIONS FOR INSTALLATION,

More information

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures

SAFETY QUALITY TECHNOLOGY. Guidance on Safe Isolation Procedures SAFETY QUALITY TECHNOLOGY Guidance on Safe Isolation Procedures Introduction Every year, people working on construction sites suffer electric shock and burn injuries some of which, tragically, are fatal.

More information

35 TON HYDRAULIC PUNCH WARNING

35 TON HYDRAULIC PUNCH WARNING OPERATORS GUIDE REL-35T-PNC 35 TON HYDRAULIC PUNCH NOTICE Sizes, weights and tool specifications listed in this manual are subject to change without notice. Please consult factory for information and updates.

More information

DT400/436 Tee Connector Installation Instructions

DT400/436 Tee Connector Installation Instructions Connectors Lorem ipsum and dolor Splices sit Amat Effective September 2014 Supersedes IS550-30-1 March 2011 MN650001EN DT400/436 Tee Connector Installation Instructions DISCLAIMER OF WARRANTIES AND LIMITATION

More information

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER

SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SAFETY MANUAL FOR FLAMMABLE PRODUCT TRANSFER SUPPLIMENT TO eom IMPORTANT READ THIS MANUAL BEFORE PRODUCT INSTALLATION, OPERATION, INSPECTION & MAINTENANCE Tougher and more rigid guidelines are being established

More information

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0) Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk SOFTLINE CUTTER SL80 PRODUCT CODE No. 980248 INSTRUCTIONS FOR INSTALLATION,

More information

709 and 710 Stud Punches

709 and 710 Stud Punches INSTRUCTION MANUAL 709 and 710 Stud Punches Read and understand all of the instructions and safety information in this manual before operating of servicing this tool. IMPORTANT SAFETY INFORMATION 709 and

More information

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0) Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk WIRE ROPE CUTTER WCS75HDZ PRODUCT CODE No. 980482 INSTRUCTIONS FOR

More information

DK ton, Double-acting, Die-type Crimping Tool

DK ton, Double-acting, Die-type Crimping Tool INSTRUCTION MANUAL DK6040 60-ton, Double-acting, Die-type Crimping Tool Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register

More information

LED 14W POLO BULKHEAD WITH MICROWAVE SENSOR

LED 14W POLO BULKHEAD WITH MICROWAVE SENSOR INTRODUCTION The LED 14W POLO Bulkhead is a modern lowcost and energy efficient fitting ideal for domestic and utility applications. SPECIFICATION LED 1150lm IP54 220-240V IK09 4000K 50/ 60Hz >82 Ra 14W

More information

Operating Instructions

Operating Instructions Operating Instructions Light-metal Ex d enclosures / flameproof enclosure > 8265/0 Empty enclosure > 8265/4 Control panel, integrated in Ex e enclosure > 8265/5 Control panel Table of Contents 1 Table

More information

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031)

IEC April Authorized Sole Agent : PT. Wisma Niagatama Perkasa. Phone : (031) Fax. : (031) IEC 62271-200 April 2004 Authorized Sole Agent : PT. Wisma Niagatama Perkasa Phone : (031) 5041242 Fax. : (031) 5044580 IEC 62271-200 Introduction Scope This standard specifies requirements for factory-assembled

More information

Further technical information is available on

Further technical information is available on 1 of 5 Manufacture address : Bartec Technor AS Dusavikveien 39 4007 Stavanger Norway Further technical information is available on www.bartec-technor.no Note on instructions When working in hazardous areas,

More information

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0) Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk HOSE/UMBILICAL CUTTER HCV100 PRODUCT CODE No. 980292 INSTRUCTIONS

More information

Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands

Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems. J.C.M. VAN ROSSUM * Prysmian Group NL The Netherlands 21, rue d Artois, F-75008 PARIS CIGRE US National Committee 2012 Grid of the Future Symposium http : //www.cigre.org Using Perfluorocarbon Tracers (PFT) for detecting oil leakages in LPOF cable systems

More information

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers

DEH Instructions. Three-Phase, Platform-Mounted Distribution Transformers g DEH 40050 Instructions Three-Phase, Platform-Mounted Distribution Transformers Introduction The equipment covered by these instructions should be operated and serviced only by competent technicians familiar

More information

Check with local zoning official for property line distance requirements.

Check with local zoning official for property line distance requirements. RESIDENTIAL POOL PLAN SUBMITTAL GUIDELINES The following guidelines are intended to assist municipal residents with the permit acquisition process with regard to pools, spas and hot tubs for single family

More information

HANDBOOK. Squeeze Off Unit SOU 250. Please refer any queries to:

HANDBOOK. Squeeze Off Unit SOU 250. Please refer any queries to: HANDBOOK Squeeze Off Unit SOU 250 Please refer any queries to: Hy Ram Engineering Co Ltd Pelham Street Mansfield Nottinghamshire NG18 2EY Telephone No: (01623) 422982 Please note all queries should state

More information

Battery-powered Micro Cutters

Battery-powered Micro Cutters SERVICE MANUAL ES32ML ES32FML EBS12ML Battery-powered Micro Cutters Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Register this

More information

SAMPLE WRITTEN PROGRAM for Control of Hazardous Energy LOCKOUT TAGOUT

SAMPLE WRITTEN PROGRAM for Control of Hazardous Energy LOCKOUT TAGOUT SAMPLE WRITTEN PROGRAM for Control of Hazardous Energy LOCKOUT TAGOUT SAMPLE WRITTEN PROGRAM The objective of this procedure is to establish a means of positive control to prevent the accidental starting

More information

REL-46 WARNING NOTICE 15 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD. Compatible with RELIABLE R15 and P Style dies. REL-46 Manual

REL-46 WARNING NOTICE 15 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD. Compatible with RELIABLE R15 and P Style dies. REL-46 Manual OPERATORS ORS GUIDE REL-46 15 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD Compatible with RELIABLE R15 and P Style dies. RELIABLE EQUIPMENT & SERVICE CO., INC. 301 Ivyland Road Warminster, PA 18974

More information

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6

2-1- Shipping Receiving Lifting Location on Site Installation Stages 6 NEUTRAL GROUNDING RESISTORS INSTALLATION, OPERATION & MAINTENANCE MANUAL Contents 1- SAFETY INSTRUCTIONS... 3 1-1- Compliance with Instructions in this Manual. 3 1-2- Guidance Notes Installation.... 3

More information

REV0709. Parts List. Hydraulic Cylinder Model MODEL C SINGLE-ACTING, SPRING RETURN HYDRAULIC CYLINDER. Max. Capacity: 55.2 Tons at 10,000 PSI

REV0709. Parts List. Hydraulic Cylinder Model MODEL C SINGLE-ACTING, SPRING RETURN HYDRAULIC CYLINDER. Max. Capacity: 55.2 Tons at 10,000 PSI REV0709 Parts List Hydraulic Cylinder Model 10312 MODEL C SINGLE-ACTING, SPRING RETURN HYDRAULIC CYLINDER Max. Capacity: 55.2 Tons at 10,000 PSI REV0709 Item No. Part No. No. Req d Description 1 10606

More information

YSLY-JZ YSLY-OZ. Low voltage - Energy, cabling, signalling and control

YSLY-JZ YSLY-OZ. Low voltage - Energy, cabling, signalling and control Low voltage - Energy, cabling, signalling and control YSLY-JZ YSLY-OZ Construction: VDE Reg. n 7509 according to VDE 0281 Teil 13 according to DIN EN 50525-2-51 Flame propagation: DIN EN 60332-1-2 Low

More information

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL

Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Operating Instructions for BAIR22-6 AIR-POWERED CRIMPING TOOL Read and understand all of the instructions and safety information in this manual before operating or servicing this tool. Table of Contents

More information

HYDRAULIC PUNCH DRIVER 38456, 38520, 7306 / 7306SB, 7310 / 7310SB, 7506, 7606SB, 7610SB, 7625 / 7625Pg / 7625PgSB, 7646 / 7646Pg / 7646PgSB

HYDRAULIC PUNCH DRIVER 38456, 38520, 7306 / 7306SB, 7310 / 7310SB, 7506, 7606SB, 7610SB, 7625 / 7625Pg / 7625PgSB, 7646 / 7646Pg / 7646PgSB INSTRUCTION MANUAL HYDRAULIC PUNCH DRIVER 38456, 38520, 7306 / 7306SB, 7310 / 7310SB, 7506, 7606SB, 7610SB, 7625 / 7625Pg / 7625PgSB, 7646 / 7646Pg / 7646PgSB Read and understand all of the instructions

More information

GATOR Battery-powered Pistol Grip Cable Cutters

GATOR Battery-powered Pistol Grip Cable Cutters OPERATION MANUAL Serialnummer (ESG45L shown) GATOR Battery-powered Pistol Grip Cable Cutters Read and understand all of the instructions and safety information in this manual before operating or servicing

More information

REL-510H WARNING NOTICE 12 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD

REL-510H WARNING NOTICE 12 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD OPERATORS ORS GUIDE REL-510H 12 TON SINGLE ACTING REMOTE HYDRAULIC CRIMPING HEAD Compatible with U style and RELIABLE R12 shell type 12 ton compression dies. RELIABLE EQUIPMENT & SERVICE CO., INC. 92 Steamwhistle

More information

CABLE ENTRIES IN HAZARDOUS AREAS CORRECT SELECTION, INSTALLATION AND MAINTENANCE

CABLE ENTRIES IN HAZARDOUS AREAS CORRECT SELECTION, INSTALLATION AND MAINTENANCE CABLE ENTRIES IN HAZARDOUS AREAS CORRECT SELECTION, INSTALLATION AND MAINTENANCE Compiled by: Arthur Cameron NOT SO CORRECT SELECTION AND INSTALLATION OF CABLE GLANDS AND JUNCTION BOXES IN HAZARDOUS AREAS

More information

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and

Bulletin Swimming pool, hot tub and spa installations Rules , , , , , and Bulletin 68-7-11 Swimming pool, hot tub and spa installations Rules 68-000, 68-056, 68-058, 68-064, 68-068, 68-302 and 68-404 Scope (1) Swimming pools - general (2) Grounding & bonding (a) Bonding for

More information

Control of Hazardous Energy Program (Lockout/Tagout)

Control of Hazardous Energy Program (Lockout/Tagout) Control of Hazardous Energy Program (Lockout/Tagout) 1 The Control of Hazardous Energy (Lockout/Tagout) Program 1910.147 The following lockout/tagout program is provided to assist employees in complying

More information

User Information Sheet 015

User Information Sheet 015 User Information Sheet 015 Formerly LPGA Guidance NO.84 March 2007 Inspection and Maintenance of LPG Pipework at Commercial and Industrial Premises 1. Introduction LPG pipework may, under certain conditions,

More information

Arran LED Floodlight Luminaire

Arran LED Floodlight Luminaire Arran LED Floodlight Luminaire INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS Important: Please read these instructions carefully before installing or maintaining this equipment. Good electrical

More information

Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices

Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices Translation Principles of testing and certification for insulating hose assemblies on cable cutting devices Status as of 2014-01 Principles of testing Insulating hose assemblies on cable cutting devices

More information

Field Instruction. The purpose of this instruction is to inform all Horizon Power workers of the safety requirements when working from a EWP.

Field Instruction. The purpose of this instruction is to inform all Horizon Power workers of the safety requirements when working from a EWP. 2.7 Safety Requirements When Working from an EWP Purpose The purpose of this instruction is to inform all Horizon Power workers of the safety requirements when working from a EWP. Scope The scope of this

More information

Applications and Considerations Section 11

Applications and Considerations Section 11 11 Applications and Considerations Section 11 www.hubbellpowersystems.com E-mail: hpsliterature@hps.hubbell.com Phone: 573-682-5521 Fax: 573-682-8714 210 North Allen Centralia, MO 65240, USA Copyright

More information

Operating Instructions

Operating Instructions Operating Instructions Ex d Enclosures in Light Metal / Flameproof Encapsulation > 8265/0 Empty Enclosure > 8265/4 controller, installed in Ex e enclosure > 8265/5 controller Contents 1 Contents 1 Contents...2

More information

Power Unit 075. Maintain Substation Circuit Breakers

Power Unit 075. Maintain Substation Circuit Breakers Power Unit 075 Maintain Substation Circuit Breakers The specification details the required skills, knowledge and behaviours to establish competence to carry out the maintenance of high voltage power circuit

More information

PDY TON HYDRAULIC CRIMPING TOOL WARNING

PDY TON HYDRAULIC CRIMPING TOOL WARNING OPERATORS ORS GUIDE PDY-1220 12 TON HYDRAULIC CRIMPING TOOL All information found in this guide must be read and understood before use or testing of this tool. Failure to read and understand these warnings

More information

Hydraulic Punch Drivers

Hydraulic Punch Drivers SERVICE MANUAL 7804SB / 7806SB Quick Draw 7704SB / 7706SB Quick Draw Flex Quick Draw Hydraulic Punch Drivers Serial Codes AHJ and YZ Read and understand all of the instructions and safety information in

More information

Safety Powder Spray Systems

Safety Powder Spray Systems Instruction Sheet P/N 107 952C Safety Powder Spray Systems 1. Introduction This section contains general safety instructions for using your Nordson equipment. Task- and equipment-specific warnings are

More information

W E NE E D TO TA LK A BOUT COLD FLOW. The Problem With The Cold Flow Standard.

W E NE E D TO TA LK A BOUT COLD FLOW. The Problem With The Cold Flow Standard. W E NE E D TO TA LK A BOUT COLD FLOW The Problem With The Cold Flow Standard www.ehawke.com CONTENTS 03 COLD FLOW AND THE STANDARDS The Cold Flow Standard misnomer The Problem with Compression and Displacement

More information

CS10 # Network Safety Performance Objectives (2016)

CS10 # Network Safety Performance Objectives (2016) CS10 #4384287 Network Safety Performance Objectives (2016) Context & Purpose The Horizon Power Network Safety Objectives (2016) (Objective Statement) has been prepared for each of network safety performance

More information

SEMME2135 Assisting in modifying and adding electrical circuits in yachts and boats

SEMME2135 Assisting in modifying and adding electrical circuits in yachts and boats Assisting in modifying and adding electrical circuits in yachts and boats Overview This standard identifies the competences you need to assist with the modification or addition of electrical circuits in

More information

Datasheet ANSI Type K & T Exposed Welded Tip Thermocouples (ANSI Colour Code)

Datasheet ANSI Type K & T Exposed Welded Tip Thermocouples (ANSI Colour Code) Datasheet ANSI Type K & T Exposed Welded Tip Thermocouples (ANSI Colour Code) ENGLISH Thermocouple types K & T to ANSI MC96.1 Fast response, welded exposed junction 1, 2, 5 or 10-metre-long Teflon PFA

More information

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Test instruments and recommended testing sequence 1 Outcomes of this Session describe the different

More information

Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines

Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines Part 3: Safety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines Charles Bleakley Chair, Subcommittee 7 PART 3 UNDERGROUND LINES 2 313. Inspection and tests

More information

Sample Written Program for The Control of Hazardous Energy (Lockout/Tagout)

Sample Written Program for The Control of Hazardous Energy (Lockout/Tagout) USAG Bavaria Safety Office Sample Written Program for The Control of Hazardous Energy (Lockout/Tagout) Nov 2016 1910.147 The Control of Hazardous Energy (Lockout/Tagout) The following lockout/tagout program

More information

Low Voltage Electricity System Safety Rules & Associated Safety Guidance

Low Voltage Electricity System Safety Rules & Associated Safety Guidance Annex J To Loughborough University Facilities Management (FM) Health and Safety Policy Low Voltage Electricity System Safety Rules & Associated Safety Guidance 1. Introduction a. These Safety Rules are

More information

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN

COOPER POWER SERIES. DS250 deadbreak straight connector installation instructions interface A. Connectors MN650027EN Connectors MN650027EN Effective November 2016 Supersedes January 2014 (IS550-11-1) DS250 deadbreak straight connector installation instructions interface A COOPER POWER SERIES DISCLAIMER OF WARRANTIES

More information

30T A/Manual Hydraulic Shop Press

30T A/Manual Hydraulic Shop Press 30T A/Manual Hydraulic Shop Press Operation Manual 1 1. Important Information 1.1 Safety Information 1.1.1 Hazard Symbols Used in the Manuals This manual includes the hazard symbols defined below when

More information

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations.

C&G 2395 Exam Paper June Section A-All questions carry equal marks. Answer all three questions. Show all calculations. C&G 2395 Exam Paper June 2013 Section A-All questions carry equal marks. Answer all three questions. Show all calculations. 1. The electrical installation in an industrial unit is scheduled for a periodic

More information

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN

COOPER POWER SERIES. DE250 deadbreak elbow connector installation instructions interface A. Screened Separable Connectors MN650025EN Screened Separable Connectors MN650025EN Effective November 2016 Supersedes September 2013 (IS550-10-1) DE250 deadbreak elbow connector installation instructions interface A COOPER POWER SERIES DISCLAIMER

More information

Dual fuel Gas-Oil/Gas burner

Dual fuel Gas-Oil/Gas burner Installation, use and maintenance instructions Dual fuel Gas-Oil/Gas burner MODEL GI/EMME 400 TYPE 496 T80 291 (6) TECHNICAL FEATURES Thermal power 116/232 465 kw - 100.000/200.000 400.000 kcal/h Fuels

More information

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO

FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO FIRE PREVENTION METHOD FOR 275KV OIL-FILLED CABLE IN TEPCO Atsushi Toya, Tokyo Electric Power Company, (Japan), toya.atsushi@tepco.co.jp Shinsuke Nasukawa, Tokyo Electric Power Company, (Japan), nasukawa.shinsuke@tepco.co.jp

More information

A17W49_MASEM_F_EN MANUAL

A17W49_MASEM_F_EN MANUAL AW9_MASEM_F_EN MANUAL CONTENTS Identification. Manufacturer. Product name. Year of manufacture. Area of use. Declaration of conformity Technical specification. Design. Function. Technical data. Electrical

More information

Operation and Maintenance Instructions

Operation and Maintenance Instructions Hydratight Limited Bentley Road South Darlaston West Midlands WS10 8LQ United Kingdom Tel: +44 121 50 50 600 Fax: +44 121 50 50 800 E-mail: enquiry@hydratight.com Website: www.hydratight.com TOP COLLAR

More information

HANDBOOK. Squeeze Off Unit SOU 400. Please refer any queries to:

HANDBOOK. Squeeze Off Unit SOU 400. Please refer any queries to: HANDBOOK Squeeze Off Unit SOU 400 Please refer any queries to: Hy Ram Engineering Co Ltd Pelham Street Mansfield Nottinghamshire NG18 2EY Telephone No: (01623) 422982 Please note all queries should state

More information

H4802, H4802-1, H , and Pole Tampers

H4802, H4802-1, H , and Pole Tampers SERVICE MANUAL H4802, H4802-1, H-4802-6, and 43227 Pole Tampers Serial Codes FKA, FKF, FKM, FZP, FZR, FZT, and FZV Read and understand all of the instructions and safety information in this manual before

More information

PR4 Installation, Operation & Maintenance Instructions (DOT Certification Included)

PR4 Installation, Operation & Maintenance Instructions (DOT Certification Included) PR4 Installation, Operation & Maintenance Instructions (DOT Certification Included) March 2006 Form FVC 054 Rev. 6 KEEP THIS DOCUMENT WITH THE PRODUCT UNTIL IT REACHES THE END USER. The Passive - R4 device

More information

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0) Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk WIRE ROPE CUTTER RCO40LP PRODUCT CODE No. 980503 INSTRUCTIONS FOR

More information

Maintaining electrical equipment/systems

Maintaining electrical equipment/systems Unit 037 Maintaining electrical equipment/systems Level: 2 Credit value: 15 NDAQ number: 500/9514/6 Unit aim This unit covers the skills and knowledge needed to prove the competences required to cover

More information

APPENDIX A. F107 & 380 Lines OYSTER RIVER DURHAM, NH

APPENDIX A. F107 & 380 Lines OYSTER RIVER DURHAM, NH APPENDIX A F107 & 380 Lines OYSTER RIVER DURHAM, NH 1. The design and proposed construction of this crossing is shown on the attached PSNH Transmission Business Drawing entitled DOUBLE CKT F107 & 380 BETWEEN

More information

Installation of Ballast Water Management Systems

Installation of Ballast Water Management Systems (Sept 2015) (Rev.1 May 2016) Installation of Ballast Water Management Systems 1. Application In addition to the requirements contained in BWM Convention (2004), the following requirements are applied to

More information

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL

AIR-OPERATED DOUBLE DIAPHRAGM PUMP USER S MANUAL 00, 0, 000 00, 000, 00 A. TECHNICAL INFORMATION Model 00 Inlet/Outlet " Air Inlet /" 0 / 000 /" /" 00 /" /" 000 /" /" 00 /" /" Flow Rate GPM/ 0LPM GPM/ 0LPM GPM/ LPM GPM/ LPM GPM/ 0LPM GPM/ 0LPM Maximum

More information

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0)

Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW. Tel +44 (0) Allspeeds Ltd. Royal Works, Atlas St Clayton le Moors Accrington Lancashire England BB5 5LW Tel +44 (0)1254 615100 www.allspeeds.co.uk WIRE ROPE CUTTER RCO40 PRODUCT CODE No. 980502 INSTRUCTIONS FOR INSTALLATION,

More information

Service Call: Vacuum Prevention System Testing on Category A and B Aerial Devices. Tools Required: 1. Atmospheric Vent Test Set (P/N )

Service Call: Vacuum Prevention System Testing on Category A and B Aerial Devices. Tools Required: 1. Atmospheric Vent Test Set (P/N ) Service Call: Vacuum Prevention System Testing on Category A and B Aerial Devices Tools Required: 1. Atmospheric Vent Test Set (P/N 488180) *An automotive vacuum test kit with various fittings to hook

More information

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150,

CARTRIDGE FILTERS. Models: CF50, CF75, CF100, CF150, CARTRIDGE FILTERS Models: CF50, CF75, CF00, CF50, The installation of this product should be carried out by a qualified pool technician, following the installation instructions provided in this manual.

More information

ENGLISH Datasheet IEC Miniature Thermocouple Connector Socket with Stainless Steel mounting bracket Types K, J, T, E, N, B & Copper (IEC Colour Code)

ENGLISH Datasheet IEC Miniature Thermocouple Connector Socket with Stainless Steel mounting bracket Types K, J, T, E, N, B & Copper (IEC Colour Code) ENGLISH Datasheet IEC Miniature Thermocouple Connector Socket with Stainless Steel mounting bracket Types K, J, T, E, N, B & Copper (IEC Colour Code) Miniature size in-line Thermocouple Socket with stainless

More information

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems

QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems Performing Engineering Operations QPEO2/037N Credit Value: 15 QCF Level: 2 GLH: 68 Maintaining electrical equipment/systems Learner Name: 2013 Excellence, Achievement & Learning Ltd EAL Assessment Route

More information

Operating Instructions

Operating Instructions LPL Series LED Pendant Lighting Operating Instructions IM0102 COOPER Electronic Technologies (Shanghai) Co., Ltd. No. 955 Shengli Road, East Area of Zhangjiang High-Tech Park, Shanghai 201201 China 1.

More information

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell:

Energy Control. Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: cell: Energy Control Suite 2A, 55 Frid Street Hamilton, ON L8P 4M3 office: 905.577.0303 cell: 905.977.0210 consultant@staffaid.ca www.staffaid.com Safety, Energy Control, Power Lockout & Function Test Procedures

More information

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION

MZX. Three-Port Seat Valves SPECIFICIATIONS AND GUIDE TO SELECTION 01 These seat valves are of globe construction with a linear moving spindle and a modified parabolic characterised plug operating against the upper seat which controls flow quantity to suit the load. The

More information

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY

For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum WARNING: FOR OUTDOOR USE ONLY For use with select HPC Fire Pits ONLY- refer to product catalog or website. 100K BTU Maximum : FOR OUTDOOR USE ONLY Small Tank LP Kit (STLPK) Installation & Operation Instructions Installation We suggest

More information

QPEO2/033N Credit Value: 14 QCF Level: 2 GLH: 64 Wiring and testing electrical equipment and circuits

QPEO2/033N Credit Value: 14 QCF Level: 2 GLH: 64 Wiring and testing electrical equipment and circuits Performing Engineering Operations QPEO2/033N Credit Value: 14 QCF Level: 2 GLH: 64 Wiring and testing electrical equipment and Learner Name: EAL Assessment Route Summary This EAL assessment route covers

More information

Swimming Pool Requirements

Swimming Pool Requirements Swimming Pool Requirements 8040 S. 6th Street Oak Creek, WI 53154 (414) 766-7000 www.oakcreekwi.org Revised: August 8. 2017 PERMITS A permit from the Inspection Department is required prior to putting

More information

AIR/OVER HYDRAULIC JACK 20 TON

AIR/OVER HYDRAULIC JACK 20 TON AIR/OVER HYDRAULIC JACK 0 TON 4487 ASSEMBLY AND OPERATING INSTRUCTIONS 349 Mission Oaks Blvd., Camarillo, CA 930 Visit our Web site at http://www.harborfreight.com Copyright 999 by Harbor Freight Tools.

More information

Datasheet IEC & ANSI Miniature or Standard Quick Wire Thermocouple Connector Plug & Socket Type K in IEC or ANSI Colour code

Datasheet IEC & ANSI Miniature or Standard Quick Wire Thermocouple Connector Plug & Socket Type K in IEC or ANSI Colour code Datasheet IEC & ANSI Miniature or Standard Quick Wire Thermocouple Connector Plug & Socket Type K in IEC or ANSI Colour code ENGLISH These quick connect versions allow rapid termination Miniature connector

More information

Hydraulic Piston Accumulators

Hydraulic Piston Accumulators Ride Control Engineering Services PWCE Extendavator Paul Wever Construction Equipment Co., Inc. P.O. Box 85 401 Martin Drive Goodfield, IL 61742-0085 Phone (309) 965-2005 Fax (309) 965-2905 1-800-990-PWCE

More information

INTENDED USE TECHNICAL SPECIFICATIONS

INTENDED USE TECHNICAL SPECIFICATIONS 1/2IN. HEAVY-DUTY AIR IMPACT WRENCH OWNER S MANUAL WARNING: Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions may result

More information

Arbor Terminator Press Operation Manual For IDT Connectors Order No Engineering No: AM

Arbor Terminator Press Operation Manual For IDT Connectors Order No Engineering No: AM Arbor Terminator Press Operation Manual For IDT Connectors Order No. 11-20-0815 Engineering No: AM7223-140 Description Operation Maintenance Order No: TM-011200815 Release Date: 03-08-12 UNCONTROLLED COPY

More information

TYPE 3710 CARTRIDGE SPLIT SEAL Technical Specification

TYPE 3710 CARTRIDGE SPLIT SEAL Technical Specification A Mating Ring B Mating Ring/ Retaining Ring C Mating Ring/ Clamp Ring D Mating Ring Adapter E Primary Ring F Primary Ring/ Retaining Ring G Finger Springs H Spring Retainer I Gland O-ring J Flat Gasket

More information

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY

Health & Safety Policy and Procedures Manual SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY SECTION 6 ELECTRICAL SAFETY / CONTROL OF HAZARDOUS ENERGY 1. CONTROL OF HAZARDOUS ENERGY POLICY AND PROCEDURES A. OSHA References: 29 CFR 1910.147, 29 CFR 1910.332, 29 CFR 1910.333, 29 CFR 1926.417 B.

More information

Typical Strength of Glued Connection. Typical Strength of Screwed Connection

Typical Strength of Glued Connection. Typical Strength of Screwed Connection Rodder Introduction DCD offers one of the most comprehensive range of Rodders available anywhere in the world - from the smallest 1/8 dia. Fish Tapes to the rugged 1/2 Rodders. The Rod DCD rods are manufactured

More information

KMU SUBSTATION WORKSHOP

KMU SUBSTATION WORKSHOP Rick Aguilar, Director of Job Training & Safety KMU SUBSTATION WORKSHOP JUNE 29-30, 2016 OTTAWA, KS Hazards & Safety Rules Qualified Personnel & Task-Based Hazard Mitigation Worksite Applications & Considerations

More information

Socket P2RF-05-S P2RF-08-S Clip & Release Lever Nameplate R99-11

Socket P2RF-05-S P2RF-08-S Clip & Release Lever Nameplate R99-11 Screwless Clamp Terminal Socket P2RF@@S Screwless clamping greatly contributes to reducing wiring time. No over or under tightening of cable connection so better contact reliability is achieved. Double

More information

3M Telecommunications Solutions for Networks. Quante QSA (= LSA plus) System Catalogue. Innovation

3M Telecommunications Solutions for Networks. Quante QSA (= LSA plus) System Catalogue. Innovation 3M Telecommunications Solutions for Networks Quante QSA (= LSA plus) System Catalogue Innovation IDC Modules Overview 3M Quante Cross Connect System QSA QSA Series 1 Connection modules for screw fixing

More information

SWIMMING POOL REQUIREMENTS

SWIMMING POOL REQUIREMENTS PERMITS A permit from the Inspection Department is required prior to putting up a permanent pool. A permit is required for permanent pools, such as the following: SWIMMING POOL REQUIREMENTS The pool is

More information

Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve

Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve Installation Instructions and User Guide 15mm & 22mm Thermostatic Mixing Valve TMV3 / TMV2 Combined Valve C85079 C85081 C85080 C85082 It is important that these guidance notes are read and fully understood

More information

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS

Hot Tapping Machine. OPERATIONS MANUAL and OPERATING INSTRUCTIONS 262-2040 Hot Tapping Machine For performing 1/4 6 Hot taps 285 psi or less. Municipal Water, Sewage, & Building Services Use OPERATIONS MANUAL and OPERATING INSTRUCTIONS WARNING: These instructions are

More information

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury.

AIR COMPRESSOR. Failure to follow all instructions as listed below may result in electrical shock, fire, and/or serious personal injury. 2 GALLON AIR COMPRESSOR Model: 7517 DO NOT RETURN TO STORE. Please CALL 800-348-5004 for parts and service. CALIFORNIA PROPOSITION 65 WARNING: You can create dust when you cut, sand, drill or grind materials

More information

Residential Swimming pools

Residential Swimming pools City of Republic Community Development Department Residential Swimming pools REVISION DATE: JANUARY 2017 Swimming Pool Safety Definitions: Barrier Requirements: A) Application All swimming pools over 24

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates GB142-24 84,800 btu/hr GB142-30 106,000 btu/hr GB142-45 160,900 btu/hr GB142-60 214,800 btu/hr This kit and instructions are

More information

WARNING. RELIABLE EQUIPMENT & SERVICE CO., INC. 301 Ivyland Road Warminster, PA USA Phone: Fax:

WARNING. RELIABLE EQUIPMENT & SERVICE CO., INC. 301 Ivyland Road Warminster, PA USA Phone: Fax: OPERATOR'S GUIDE Pivot style control valves may be operated with one hand, leaving the second hand free to control the head. Lever locks in the forward position for tool advance, and in the rear position

More information

EcoCell Vertical Electrophoresis Unit

EcoCell Vertical Electrophoresis Unit Instructions for EcoCell Vertical Electrophoresis Unit Cat. No.: AN 12005 Ringstr. 4 64401 Gross-Bieberau Tel. ++49-6162-809840 Fax ++49-6162-8098420 www.anamed-gele.com Warning These units are capable

More information

In Ground Buried Uplights

In Ground Buried Uplights In Ground Buried Uplights BIANCHI LIGHTING SERVICES SUTTON CLOSE, EASTCOTE Enrico Bianchi Guidance notes for the specification and application of in ground buried uplights. MIDDLESEX HA5 2JX +44 (0)794

More information

CIRCUIT BREAKER TESTING - JOB SAFETY ANALYSIS

CIRCUIT BREAKER TESTING - JOB SAFETY ANALYSIS Title: Circuit Breaker Testing Purpose and Scope: Provide guidelines for testing of Circuit Breakers. Staffing Resources: Staff will have the minimum requirement of an Electrical Fitter/Mechanic Licence

More information