Installation, Operation & Maintenance Instructions

Size: px
Start display at page:

Download "Installation, Operation & Maintenance Instructions"

Transcription

1 Installation, Operation & Maintenance Instructions PressVal Micron Pressurisation Units Ltd Northgate Newark Notts NG24 1JN Tel: (01636) Fax: (01636) PressVal Micron Rev 1

2 Contents 1. Introduction 3 2. Description 4 3. Delivery & Nameplates 5 4. Technical Details Installation Details Pressure Settings Commissioning Operation and Fault Codes Maintenance Wiring diagrams Notes

3 1. Introduction These instructions have been written to give a brief description of the PressVal Micron pressurisation units their installation, commissioning, operation and subsequent maintenance. The installation of pressurisation units and their ancillary equipment is normally carried out by the Heating Engineer, and for the purpose of this manual he is regarded as the installer, and, as such, it is his responsibility to ensure that he has read and understood the contents of this manual before installing the boiler. It is essential that each unit has all services connected to it before commissioning. The installation should be in accordance with current I.E.E. Regulations, relevant British Standard and Codes of Practice, Building Regulations and Local Authority Bylaws. Engineers will normally commission the pressurisation unit and if the heating engineer is present at the time, he will be instructed on the day-to-day operation of the unit. If this is not possible, or additional training is required, this can be arranged through. The units pressure settings are recorded on the commissioning report and a copy of this will be issued for retention with this manual (see example). A note should be entered below by the person responsible for the plant, giving the pressurisation unit model, reference K number, WO number, Serial No. These numbers are indicated on the nameplate which is located on the front of the break tank, inside the cabinet. For completion by Plantroom Attendant Unit Model: Serial No: K No: WO No: Commissioning Date For technical, servicing or parts enquiries, telephone, fax or to quoting the model(s) & K number, as above

4 2. Description. Description Application PressVal pressurisation equipment is designed to provide automatic make-up and pressure for sealed heating, chiller, and condensor systems. General Details The PressVal Micron pressurisation unit is a microprocessor controlled unit. Single and twin pump options are available to work up to the following pressures: Pump Pump Maximum Model Type Pressure 125 Single Twin Single Twin Single Twin 3.0 Expansion vessels Standard expansion vessels with fixed diaphragm are available as follows: Vessel Vessel Maximum Volume Configuration Pressure litres Vertical 6 bar litres Vertical 10 bar Non standard expansion vessels with interchangeable diaphram, inspection cover and pressure gauge are available as follows: Vessel Vessel Maximum Volume Configuration Pressure litres Vertical 6 bar litres Vertical 10 bar litres Horizontal 6 bar litres Horizontal 10 bar Details of the expansion vessels are shown on pages 9 and 10 Equipment Configurations PressVal Micron equipment is supplied in the following configurations: FS Micron Pressurisation unit with free standing expansion vessels. 4 PressVal Micron SM Micron Pressurisation unit and expansion vessels all skid mounted PressVal Micron CH Micron Pressurisation unit and expansion vessels all fitted within a cabinet. PressVal Micron PressVal Micron Mini Micron Wall mounted pressurisation unit with separate expansion vessels for small systems. PressVal Micron Controller PressVal Micron Features All enclosed type unit with polyester powder coated finish in colours. No side access required to cabinet. Quick release removeable door and electrical access panel. WRC listed controls and fittings. Break tank filter. Type A air gap. Illuminated on/off switch. Combined lockshield / drain valves. Centrifugal pump on 125 & 225 units, Turbine pump on 180 & 280 units 1/50/ v supply Power supply 12v ac for all controls. Safe low voltage Relay switching 230v ac 8 amp Dual or single pump control Pump monitoring for no current or too much current draw. 4 Digit display with scrolling, to display status and alarm modes. Internal alarm with mute function. Hi/Lo water detection with alarm and auto reset. No volt free out Hi pressure alarm with volt free Lo pressure alarm with volt free Pump trip volt free x 2 Sensor fail volt free Logging for no of times each pumps has run, number of alarms and number of times power fail. Main setpoint with adjustable diff Hi and Lo alarm setpoints with manual reset. Max time run for pumps Alternates pumps each time its activated. Password entry Visual pressure reading. All volt free outputs can also be powered with a rating upto 8 amps for warning lamps or alarms. If 1 pumps fails the other will cut in displaying P1 fail P2 go activating the P1 trip relay. If P2 fails the unit locks out and goes into full alarm mode.

5 3. Delivery & Nameplates Delivery The pressurisation unit and its associated equipment are normally delivered by our own transport on a mutually agreed date. The unit can be offloaded by a crane lorry if specifically booked at the time of ordering, (this is normally an extra). The equipment is normally supplied on a pallet for offloading via a fork lift truck. It can be craned off using slings. On delivery, the installer should check all items against the delivery note and should then store them in a safe and dry place. The model type and size is detailed on the units nameplate. A copy of this is stuck to the packaging for easy reference. A typical nameplate is detailed right. From the model reference you can work out the specification of the unit: Nameplates Ltd. Northgate, Newark, Notts. NG24 1JN Tel: (01636) Fax: (01636) Model: PressVal FS Micron 425/ Serial No. HFS Contract No. K64000 Supply: 1ph / 50Hz / 230V WO No. WO Made in UK Model: PressVal FS Micron 425/ Product Range Configuration Type of Control Expansion vessel volume (litres) Expansion vessel gas charge (bar) Number of pumps Maximum Cold fill pressure (metres wg) Each expansion vessel will have its own data plate. An example of which is shown on the right. Ltd. Northgate, Newark, Notts. NG24 1JN Tel: (01636) Fax: (01636) Type: PressVal 425/1.0 Volume: 425 litres Gas charge: 1.0 bar Max working pressure: 6 bar Max temperature: 70 o C Standard: BS4814 Serial number: K64000 Date of supply: 02/04 Made in UK

6 4. Technical Details PressVal FS Micron Models PressVal FS Micron 35 PressVal FS Micron 50 PressVal FS Micron 80 PressVal FS Micron 110 PressVal FS Micron 140 PressVal Micron D PressVal FS Micron 200 C PressVal FS Micron 300 PressVal FS Micron 425 PressVal FS Micron 600 PressVal FS Micron 800 PressVal FS Micron 1000 A Front View B E F Side View Models PressVal FS Micron 2x425 PressVal FS Micron 2x600 PressVal Micron D PressVal FS Micron 2x800 C PressVal FS Micron 2x1000 A Front View B E F Side View PressVal FS Micron Type x425 2x600 2x800 2x1000 Dimensions: A B C D E F Dry Weight: (125 single pump unit) (225 twin pump unit) (180 single pump unit) (280 twin pump unit) (Expansion vessel - 6 bar) Service connections (rear view) Connections (All units) 1. System connection 1/2 bsp M 2. Expansion vessel connection 1/2 bsp F 3. Cold mains connection 1/2 bsp M 4. Overflow 22mm 5. Cable entry Clearance / Access (All units) Rear clearance: 100mm is required at the back of the pressurisation unit to pipe up. Front clearance: 600mm is required in front of the pressurisation unit for access to the unit. Side clearance: No side clearance required Top clearance: 400mm is required above the pressurisation unit for access to the electrical panel.

7 4. Technical Details PressVal SM Micron Models PressVal Micron PressVal SM Micron 80 PressVal SM Micron 110 C PressVal SM Micron 140 PressVal SM Micron 200 PressVal SM Micron 300 PressVal Micron D B E A F Models PressVal SM Micron 25 PressVal SM Micron 50 PressVal SM Micron 425 PressVal SM Micron 600 PressVal SM Micron 800 PressVal SM Micron 1000 A B E F C Models PressVal SM Micron 2x425 D PressVal SM Micron 2x600 PressVal SM Micron 2x800 PressVal Micron C PressVal SM Micron 2x1000 B E A F PressVal SM Micron Type x425 2x600 2x800 2x1000 Dimensions: A B C D E F Dry Weight: (125 single pump unit) (225 twin pump unit) (180 single pump unit) (280 twin pump unit) Service connections (rear view) Connections (All units) 1. System connection 1/2 bsp M 2. Expansion vessel connection 1/2 bsp F 3. Cold mains connection 1/2 bsp M 4. Overflow 22mm 5. Cable entry Clearance / Access (All units) Rear clearance: 100mm is required at the back of the pressurisation unit to pipe up. Front clearance: 600mm is required in front of the pressurisation unit for access to the unit. Side clearance: No side clearance required Top clearance: 400mm is required above the pressurisation unit for access to the electrical panel.

8 4. Technical Details PressVal CH Micron PressVal Micron PressVal Micron Connections (All units) 1. System connection 1/2 bsp M 2. Cold mains connection 1/2 bsp M 3. Overflow 22mm A B C 1 4. Electrical terminal box Clearance / Access (All units) Front clearance: 600mm is required in front of the pressurisation unit for access to the unit. Rear clearance: No rear clearance required** Side clearance: No side clearance required** Top clearance: No top clearance required** ** Note clearance for pipe work and electrical cables will have to allowed for. Entry into the unit is left for the contractor to decide. PressVal CH Micron Type Dimensions: A B C Dry Weight: (125 single pump unit) (225 twin pump unit) (180 single pump unit) (280 twin pump unit) PressVal Mini Micron 4 Connections (All units) 1. System connection 1/4 bsp M 2. Cold mains connection 1/2 bsp M Overflow 22mm 4. Cable entry Clearance / Access (All units) Front clearance: 600mm is required in front of the pressurisation unit for access to the unit. Rear clearance: No rear clearance required Side clearance: 100mm left side clearance required to pipe up Top clearance: 300mm top clearance required for electrics Only suitable for use with expansion vessels up to 300 litres Electrical details: 1ph / 50Hz / 230V 48 W motor, Fuse 3A Dry Weight: 6kg 8

9 4. Technical Details PressVal standard expansion ves- D C D H D C H C H PressVal 2 to 25 Standard Range PressVal 35 to 80 PressVal 110 to 1000 PressVal Model Volume (litres) Max pressure (bar) Max temperature ( o C) 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* System Conn (C) (bsp) 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/ Dimensions: Diameter (D) (mm) Height (H) (mm) Dry weight (kg) High Pressure Range PressVal Model Volume (litres) Max pressure (bar) Max temperature ( o C) 70* 70* 70* 70* 70* 70* 70* 70* System Conn (C) (bsp) Dimensions: Diameter (D) (mm) Height (H) (mm) Dry weight (kg) Specification Steel Construction: To BS 4814:1990 Sizes up to 80 litre: Deep Drawn with separate clench joint as defined in BS 4814:1990 Sizes 110 to 1000: All welded Diaphragm: Flexible rubber with stress free rolling action * Max temp: Temperature of fluid in contact with diaphragm. The use of these vessels in systems operating at higher temperatures can be achived with the use of an intermediate vessel. Sizes up to 25 litres: Mounting brackets available on request. Recommended piping for expansion vessels. AAV Drain Cock Lock Shield Valve Antigravity loop

10 4. Technical Details PressVal non standard expansion vessels OD PressVal VHH (vertical) and HHH (horizontal) expansion vessels are complete with interchangeable diaphragm, inspection cover and pressure gauge. PressVal VHH Vessel size (litres) System connection (C) 80 DN DN DN100 H H OD PressVal HHH C C L Non standard vertical expansion vessels PressVal Model VHH Volume (litres) Max pressure (bar) Max temperature ( o C) 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* Diameter (D) (mm) Height (H) (mm) Dry weight (kg) Non standard vertical expansion vessels PressVal Model VHH Volume (litres) Max pressure (bar) Max temperature ( o C) 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* Diameter (D) (mm) Height (H) (mm) Dry weight (kg) Non standard horizontal expansion vessels PressVal Model HHH Volume (litres) Max pressure (bar) Max temperature ( o C) 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* Diameter (D) (mm) Height (H) (mm) Length (L) (mm) Dry weight (kg) Non standard horizontal expansion vessels PressVal Model HHH Volume (litres) Max pressure (bar) Max temperature ( o C) 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* 70* Diameter (D) (mm) Height (H) (mm) Length (L) (mm) Dry weight (kg)

11 4. Technical Details PressVal intermediate vessels D H Please Note that intermediate vessels are only required on systems operating above 90 o C boiler flow temperature. Small systems may have sufficient volume in the pipe work to the expansion vessel, on these occasions an intermediate vessel may not be required. For confirmation please call Technical. C PressVal V Intermediate vessels PressVal Model V Volume (litres) Max pressure (bar) Max temperature ( o C) Diameter (D) (mm) Height (H) (mm) Connection (C) (bsp/pn6/16) 1.1/2 1.1/ Dry weight (kg) PressVal Model V Volume (litres) Max pressure (bar) Max temperature ( o C) Diameter (D) (mm) Height (H) (mm) Connection (C) (bsp/pn16) 1.1/2 1.1/ Dry weight (kg) Description PressVal Intermediate Vessels provide effective temperature reduction of expanded water in systems operating above 90 C. Installed between the system return and the expansion vessel(s), the PressVal Intermediate Vessel prevents high temperature expansion water coming into contact with the expansion vessel diaphragm. Please note that to aid heat dissipation, the intermediate vessel, together with the pipework to and from it, should not be insulated. For HTHW systems, use a Nitro pressurisation unit, details on request. Key Features Vessels up to 7 Bar g and 120 C are constructed to BS 853. Vessels above 7 Bar g and/or 120 C are constructed to PD5500:2000. Tall slim design encourages thermal stratification with the inlet at the top and the outlet at the bottom to prevent natural circulation. Test certificates available. System connections shown in table are general and may change to suit installation. Other vessels are also available, i.e. storage and chilled water buffer vessels. Other vessels and volumes can be made to suit specific needs. Sizing Intermediate vessel volume (litres) = % of expansion volume at highest system temperature (see table below) Flow temperature % of expansion o C volume

12 5. Installation Details Regulations and Standards covering Sealed System Equipment: HSE-PM5 Guidance Document. Water Bye-Laws. HSE Pressure Systems and Transportable Gas Container Regulations. (Expansion vessels do not currently require any routine inspection or checking under the written scheme of examination). Code of Practice: Refer to B.S Pressure equipment directive 12

13 6. Pressure Settings Before you can commission the Press- Val Micron pressurisation unit you will need to know the following pressure settings: Cold fill pressure. High cut out pressure. Low cut out pressure. Cold fill pressure. The cold fill pressure is the initial pressure that the pump needs to generate to pressurize a system at its highest point. On LTHW systems this should be set at 0.3 bar above the static height pressure, this extra pressure will allow any air to be expelled from the highest point of the system. For example a system with a static height of 10 metres has an approximate static pressure of 1.0 bar. So the cold fill pressure should be set at 1.30 bar. On MTHW systems operating above 100 o C it is necessary to ensure that the water at the highest point in the system does not flash off to steam. Therefore it is necessary to add an anti-flash margin pressure on to the static height pressure. The table right shows the antiflash pressure at differing flow temperatures. For example on a system with a static height of 10 metres and operating at 120 o C flow, the cold fill pressure would be 3.30 bar High pressure cut out. The high pressure cut out setting is the maximum pressure that the system will run at before it locks out. This is a safety feature to prevent over pressurizing a system. The high pressure cut out should be set 0.3 bar below the safety valve setting. Low pressure cut out. The low pressure cut out setting is the minimum pressure that the system will run at before it locks out. This is a safety feature to prevent the system from running without sufficient water in it. The low pressure cut out should be set 0.3 bar below the cold fill pressure. Operating pressure. On a pressurized system the pressure will vary between the high and low pressure settings. This is dependent on the mean system temperature. Maximum operating pressure. The maximum operating pressure of a system is the lowest maximum operating pressure that any component in the system is suitable for. This may be the boiler or a vessel or an indirect calorifier etc. Final (hot) operating pressure. The final (hot) operating pressure depends on how the expansion vessel(s) have been sized. The smaller the expansion vessel volume is the greater the final working pressure will be. On systems where the cold fill pressure is close to the maximum operating pressure you can expect to see a large expansion vessel volume in relation to the system volume. To check the size of the expansion vessels you can use the following calculation: Expansion coefficient Vessel Size VE Expansion vessel size System water content x Coefficient of expansion = Expansion vessel efficiency Expansion vessel efficiency Final pressure - Cold fill pressure = (bar abs) Final pressure Coefficient of expansion Please note that for systems containing antifreeze the coefficient of expansion will increase. Details of the different expansion coefficients can be found in BS7074. Ant-flash Margin at flow Temp o C Bar

14 7. Commissioning Technical details Power Supply: AC 12v +/-10% 50/60 Hz Pressure Sensor: simulated with a Trimmer/ DC12V supply Range of Measurements: Bar Alarm Outputs: All normally open, AC 250v 8A Boiler Interlock: Normally Closed, AC 250v 8A Audible Alarm: Internal Buzzer Suitable for plantroom temps: 0-50 o C Suitable for plantroom humidity: 30-85% without condensation Control Unit Power to the unit is controlled via a on/off switch located next to the controller. This is not an integral part. The unit becomes live once power is supplied. The unit will not register until the system is full of water and pressure is sensed at the transducer. It will give the reading below and sound an audible alarm. This prevents the unit being used to fill the system. Once the system is filled the unit can be programmed Key Key Function 1 Displays pressure value/ Parameter memorization 2 Buzzer mute / Instrument reset / Pump 1 override 3 Parameter value increase by 0.1 bar 4 Parameter valve decrease by 0.1 bar Gaining access to the programme and stored information. To enter the programme mode and to set the unit up a password needs to be entered. The password is common on all units Press + & - keys. Simultaneously and hold for 2 seconds. Then release. Then enter the code shown on right using the + & - and set keys again. The first reading is the number of times pump 1 has run. This scrolls on the screen. It can register up to 999 starts 14

15 7. Commissioning By pressing the Set Key you will move to the next reading. This is Pump 2. As the unit autocycles this will be different to pump 1. It will be within 1 digit unless pump 1 has been operated manually. The unit will always start on pump 1 after power failure as well. Pump 2 cannot be operated manually By pressing the Set Key you will move to the next reading. This is the number of alarms registered. This can register up to 9999 alarms By pressing the Set Key you will move to the next reading. This is the number of power interruptions registered. This can register up to 9999 interruptions.

16 7. Commissioning By pressing the Set Key you will move to the first setting: Fill pressure. It is prefixed with letter P By using the +/- key the correct pressure can be entered To accept the setting and move to the next setting press the set key. At this point if the p1 Override is pressed the pump will run By pressing the Set Key you will move to the next setting: High pressure alarm It is prefixed with letter H By using the +/- key the correct pressure can be entered To accept the setting and move to the next setting press the set key. By pressing the Set Key you will move to the next setting: Low pressure alarm It is prefixed with letter L By using the +/- key the correct pressure can be entered To accept the setting and move to the next setting press the set key By pressing the Set Key you will move to the next setting: Pump on/off differential It is prefixed with letter D By using the +/- key the correct differential can be entered It can be altered any amount as long as it does not conflict with any other setting To accept the setting and move to the next setting press the set key 16

17 7. Commissioning By pressing the Set Key you will move to the next setting: Max Pump run time It is prefixed with the letters DELP By using the +/- key the correct value can be entered in 10 minute increments It can be set between mins. Setting at 0 disables the function. RECOMMEND SETTING 10 MINUTES To accept the setting press set. The unit will then scroll SYS GO and start to operate

18 8. Operation & Fault Codes Operation To display the actual working pressure press the Actual pressure button. The pressure will be shown in bar g. To override pump 1 press P.1 OVERRIDE button. Pump 1 should run. Fault Codes L.P. Fault occurs if a leak is too great for the pump to keep up the unit will go into Low pressure lock out. If wired back to the boilers / BMS system this will shut down the boiler / chiller / condenser plant. Check the pressure settings and check for leaks within the system. H.P. Fault occurs if the pressure in the system rises above the high pressure setting. Check the pressure settings and system temperature. Check expansion vessel sizing. Ensure diaphragm is not leaking. Check expasion vessel gas charge, you will need to isolate and drain the vessel down before checking the pressure. L.H.2.O. Low water in break tank. Check incoming water mains. Check ball / float valve. 18

19 8. Operation & Fault Codes Fault Codes H.H2O. High water in break tank. Check ball / float valve. P.1.Fail Fault occurs if pump number one fails. Check the pump. P.2.Fail Fault occurs if pump number one fails. Check the pump. DEL.P1 or P2. Max pump run time has elapsed for either pump 1 or 2. Check system for major leaks. ERR.1 Full fault condition. Check system pressure. Check sensors. Cjeck pumps. Check water supply. Check electrical supply. To reset switch unit of and on.

20 9. General Microprocessor Information FUNCTIONS OF THE KEYS SET KEY Allows to store data in the EEPROM during parameter programming, to pass on to next parameter for programming, and to exit from the instrument SETUP mode BUZZER MUTE / RESET / P 1. OVERRIDE KEY Press and release during an alarm condition to stop buzzer Press for about two seconds to reset instrument (not in the parameter programming mode) Press during parameter programming to activate the PUMP 1 override mode (message: P1 GO) Note: this can only be done with parameters P., H., L., and d. SETUP + KEY No function during normal controller activity Increases the parameter value by 0,1 bar during parameter programming By parameter del.p. increases the parameter value in 10 minute-steps to a max of 990 minutes SETUP KEY No function during normal controller activity Decreases the parameter value by 0,1 bar during parameter programming By parameter del.p. decreases the parameter value in 10 minute-steps to a minimum of 00 minutes (disables the parameter) SETUP + and SETUP KEYS pressed simultaneously Depress simultaneously, and then release to enter the parameter configuration menu. In this phase any alarms are deactivated and all relay contacts are open. Exiting the parameter configuration phase with the SET key also resets the instrument. PARAMETER CONFIGURATION Code Description Limits Resolution Description P. Mid Set Point 0.0 (H.-0.1) 0.1 bar This is the ideal pressure that must be reached after an intervention of pump 1 or 2. H. High pressure (P.+0.1) bar This is the maximum limit pressure value of the water in the system. L. Low pressure 0.0 (P.-0.1) 0.1 bar This is the minimum limit pressure value of the water in the system. d. Differential 0.0 L. 0.1 bar This is the value which, when subtracted from the Mid Set Point P., fixes the intervention threshold limit value of the controller. del.p. Max pump activity time min 10 minute-step increases to max 990 minutes 20

21 9. General Microprocessor Information TROUBLE SHOOTING ALARM MESSAGES (Note: the alarm messages listed below are the single alarms that can appear together with other alarms and in that case are then the sum of each alarm condition) Alarm Messages Cause Controller Intervention H. H2O Float intervention at MAX FLOAT LEVEL Opens the relay of PUMP 1 or PUMP 2. L. H2O Float intervention at MIN FLOAT LEVEL Opens the relay of PUMP 1 or PUMP 2. H.P. Exceeding the upper plant water pressure limit Activates the acoustic signal, closes the High PRESSURE relay, opens the BOILER relay. L.P. Exceeding the lower plant water pressure limit Activates the acoustic signal, closes the LOW PRESSURE relay, opens the BOILER relay. P.1 FAIL Pump 1 failure Closes the PUMP 1 FAILURE relay (however, the plant is operating correctly). P.2 FAIL Pump 2 failure Closes the PUMP 2 FAILURE relay (however, the plant is operating correctly). P.1 FAIL P.2 FAIL Both pumps are defect Activates the acoustic signal, closes the PUMP 1 FAILURE relay, closes the PUMP 2 FAILURE relay, opens the relay of PUMP 1 or PUMP 2, opens the BOILER relay. del. P1 del.p. parameter time setting reached Activates the acoustic signal, opens the relay of PUMP 1, opens the BOILER relay. del. P2 del.p. parameter time setting reached Activates the acoustic signal, Besides the alarm signals, the controller can give six warning messages as indicated below. WARNING MESSAGES Warning Messages SYS. GO Meaning Normal plant operation, closes the boiler relay P.1 GO PUMP 1 running, closes the boiler relay P.2 GO PUMP 2 running, closes the boiler relay Err. Err. 1 Cod. Wrong password Sensor failure, closes the sensor failure relay Appears for 1 second before password insertion

22 9. General Microprocessor Information Procedures or decrease this value, press the + or pushbutton; once the correct value has been reached, press SET to confirm this value and this value, press the + or pushbutton; once the correct value has been reached, press SET to confirm this value and to pass on 10. L. _._ (the formerly selected two numbers) will be displayed that refer to the Low Pressure parameter. To increase or decrease this value, press the + or pushbutton; once the correct value has been reached, press SET to confirm this value and to pass on 11. d. _._ (the formerly selected two numbers) will be displayed that refer to the Differential parameter. To increase or decrease this value, press the + or pushbutton; once the correct value has been reached, press SET to confirm this value and to pass on to 12. del.p. will be displayed for 1 second and the max time (in 10 minute-step increases to max 990 minutes) of pump activity can = password for access to the parameter menu. 2. Password input procedure: a) simultaneously depress + and pushbuttons briefly; b) on release the Cod. will be displayed; c) four zeros ( 0000 ) will be displayed and the first one in the blinking mode; d) use the + or pushbutton to select the correct value; e) push the SET button to confirm the value; f) now the second 0 will blink; g) proceed like in d), e); h) now the third 0 will blink; etc, etc. 3. If the password is wrong, Err. will be displayed. 4. If the password is correct, P1 will be displayed for 1 second, and then the number of PUMP 1 start-up times. (To reset this number to 0000, press the RESET pushbutton for 1 second). 5. By pressing SET, P2 will be displayed for 1 second and then the number of PUMP 2 start-up times. (To reset this number to 0000, press the RESET button for 1 second). 6. By pressing SET, ALL. will be displayed for 1 second and then the number of times the controller had an alarm. (To reset this number to 0000, press the RESET button for 1 second). 7. By pressing SET, L.PO. will be displayed for 1 second and then the number of power black outs. (To reset this number to 0000, press the RESET button for 1 second). 8. By pressing SET, P. _._ (the formerly selected two numbers) will be displayed that refer to the Mid Set Point parameter. To increase to pass on to the successive parameter. 9. H. _._ (the formerly selected two numbers) will be displayed that refer to the High Pressure parameter. To increase or decrease to the successive parameter. to the successive parameter. the successive parameter. be set by pressing the + or pushbutton; once the correct value has been reached, press SET to confirm. When setting the value to 00 the parameter is disabled. Jumper Select the type of pumps to be controlled by either removing or inserting the jumper, i.e., - REMOVE the jumper when using the big pumps (Model: 12HS MkIII 230V a.c. - current limit values: Min 700 ma, Max not considered) - INSERT the jumper when using the small pumps (Model: EP7 - current limit values: Min 200 ma, Max 500 ma) This selection can be made by either - shutting down the power supply to the controller and then removing or inserting the jumper, or - by removing or inserting the jumper when the controller is turned on and then pressing the RESET pushbutton. Default parameter values (by EEPROM data loss) P.1 = 0000, P.2 = 0000, ALL. = 0000, L.PO. = 0000, P. = 1.0, H. = 1.5, L. = 0.5, d. = 0.2, del.p. = Maintenance Maintenance period PressVal pressurisation equipment should be periodically checked once per heating season. Maintenance checks The following checks should be carried out: 1) Drain down expansion vessels and test gas charge in vessel. This should be the same as detailed on the expansion vessel dataplate. Over time the gas charge in the vessel will permiate through the diagragm. If the gas charge is less than the stated pressure pump air back in the vessel using a compressor. 2) Check ball valve operates 3) Check pumps operate. This can be done by isolating the unit on its lock shield valve and opening the drain valve. 4) Check number of times the pumps have operated by following the comssioning procedure. 5) Check settings are the same as on the commissioning report. 6) Check level sensors operate by draining down the break tank. 22

23 11. Wiring Diagram (Single Pump Units) White Brown Yellow

24 11. Wiring Diagram (Twin Pump Units) White Brown Yellow 24

25 12. Notes

26 12. Notes 26

27 12. Notes

28 England Ltd Northgate Newark Notts NG24 1JN Tel: (01636) Fax: (01636) website: PressVal Micron Rev 1

PressVal Pressurisation Units. Packaged Pressurisation Units with expansion vessels for heating systems.

PressVal Pressurisation Units. Packaged Pressurisation Units with expansion vessels for heating systems. PressVal Packaged with expansion s for heating systems. lamco Basepak LEXILLER lamco Basepak LEXILLER POWER AULT MUTE/ RESET SYSTEM OK lamco ON / O lamco Basepak LEXILLER PressVal SM skid mounted units

More information

System Pressure Manager Standard & System Pressure Manager Plus

System Pressure Manager Standard & System Pressure Manager Plus System Pressure Manager Standard & System Pressure Manager Plus Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING,

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Models: EPS Single Pump EPT Twin Pump EPS-HP EPT-HP Single Pump High Pressure Twin Pump High Pressure

More information

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION

ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION ECONORESS ELECTRONIC EPS & EPT - ENHANCED PRESSURISATION SET INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION OCT2010 STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 020 87833050

More information

Electronic Single and Twin Pump System Pressure Managers

Electronic Single and Twin Pump System Pressure Managers Electronic Single and Twin Pump System Pressure Managers Installation, Commissioning & Servicing Instructions Note: THESE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING, COMMISSIONING, OPERATING

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Digital Range Models: DS 126 Single Pump / Single System DT 126 Twin Pump / Single System DS 160

More information

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units

Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Installation, Operation and Maintenance Instructions for Electronically Controlled Pressurisation Units Micro-S / Micro-S Digital Wall Hung Unit Please fulfil all listed requirements prior to and during

More information

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03

TABLE OF CONTENTS TECHNICAL DOCUMENTATION 03 INSPIRED EF F ICIENCY PRESSURISATION UNITS MAXI P R ESSUR I SAT I O N U NI T S T E CH N I CAL D O CUMEN T A T I O N I SSUE 1 0 /1 7 R e v. 0 1 TABLE OF CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. 9. Technical Data

More information

matrix installation guide

matrix installation guide matrix installation guide Matrix pressurisation units These installation, commissioning and servicing instructions are intend for use with the matrix compact and standard pressurisation units. efore commencing

More information

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22

Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Arrow Valves Ltd Installation Instructions / Operating & Maintenance Manual Midi-Fill Digital Pressurisation Unit Models MFD15 & MFD22 Tel 01442 823 123 Fax 01442 823 234 www.arrowvalves.co.uk Model shown

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The HDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

Ventam 85 Installation & Commissioning Instructions

Ventam 85 Installation & Commissioning Instructions Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoeburyness Essex SS3 9QY Phone 01702 382 307 Fax 01702 382 340 Ventam 85 Installation & Commissioning Instructions 1 General The Ventam

More information

JET Mini Mechanical Pressurisation Equipment

JET Mini Mechanical Pressurisation Equipment JET Mini Mechanical Pressurisation Equipment Mini Models (130HL, 230HL) Operation & Maintenance Manual Rev 2.2 We reserve the right to change designs and technical specifications of our products. Rev 2.2

More information

CCT-7320/ROC-2313 Reverse Osmosis Controller

CCT-7320/ROC-2313 Reverse Osmosis Controller CCT-7320/ROC-2313 Reverse Osmosis Controller 1 General The instrument is a combined control instrument of a reverse osmosis controller and an on-line conductivity instrument. It can perform the operation

More information

Installation, operating and maintenance Instructions for Seemag bypass level indicator

Installation, operating and maintenance Instructions for Seemag bypass level indicator Issue: S Date: 05-09-14 Type G35 General information The Seetru bypass magnetic level indicator, abbreviate SEEMAG, serves to show the filling level of fluids in tanks, basins, tubes etc. The Seemag operates

More information

In Vessel Composter Installation & Commissioning Manual

In Vessel Composter Installation & Commissioning Manual In Vessel Composter Installation & Commissioning Manual Contents Customer responsibilities Transportation Lifting Delivery Pre-installation requirements Installation Drainage Ventilation Levelling Unpacking

More information

BUBBLER CONTROL SYSTEM

BUBBLER CONTROL SYSTEM BUBBLER CONTROL SYSTEM Description: The LDBCS is a fully automatic bubbler system, which does liquid level measurements in water and wastewater applications. It is a dual air compressor system with, air

More information

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES

CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES I N S T R U C T I O N - M A N U A L CONDUCTIVITY POINT/S LEVEL SWITCH JAYCEEAQUA 4000 SERIES FUNCTION: Conductivity level limit switches are based on the principle of measuring level through the electrical

More information

Flamco Flamco-Fill STA Flamco-Fill STM

Flamco Flamco-Fill STA Flamco-Fill STM STA STM Typ STA 5936 Typ STM 5937 GB Installation and operating instructions 1999, 2 Contents GB UK Limited P.O. Box 9, Washway Lane, St. Helens, Merseyside WA10 6FE United Kingdom Telephone: 01744 744744

More information

MP15 Jockey Pump Controller

MP15 Jockey Pump Controller Setup and Operating Instructions MP15 Jockey Pump Controller This manual provides general information, installation, operation, maintenance, and system setup information for Metron Model MP15 Jockey Pump

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Operation & Maintenance Manual Vacuum Degassing Pressure Step Degasser (MidiPSD 150, PSD 250, PSD 280, PSD 2160) Combined Vacuum Degassing With Pressurisation Equipment Combination Degasser and Pressurisation

More information

Flamco Pressurisation/Dosing/Degasser Equipment PressDS Plus

Flamco Pressurisation/Dosing/Degasser Equipment PressDS Plus Flamco Pressurisation/Dosing/Degasser Equipment PressDS Plus PressDS Plus Models (225, 250, 280) Operation & Maintenance Manual Rev 1.0 We reserve the right to change designs and technical specifications

More information

Budget Range Operators Handbook

Budget Range Operators Handbook Budget Range Operators Handbook BAMBI AIR COMPRESSORS LTD 152 Thimble Mill Lane Heartlands Birmingham B7 5HT United Kingdom Tel: 0121 322 2299 Fax: 0121 322 2297 Email: sales@bambi-air.co.uk www.bambi-air.co.uk

More information

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation.

Gas Check. Short testing time, with automatic start-up if no leakage was detected from previous operation. Quality Products at Competitive Prices Gas Check Automatic testing of the down-stream installation to check that all valves are closed and that pipework and fittings are gas tight before each system start-up.

More information

mikrofill PRESSURISATION UNIT

mikrofill PRESSURISATION UNIT IN SPIR E D PRESSURISATION E F F I CI E NCY UNIT MIKR O F IL L 3 P R E SSUR I SAT I O N U NI T mikrofill PRESSURISATION UNIT INTRODUCTION Renowned for developing innovative products, Mikrofill has built

More information

Flamco Flexcon M-P Pump automat

Flamco Flexcon M-P Pump automat Flexcon M-P Pump automat 0664 Flex MP-eps GB Installation and operating instructions 1999, Flamco 2 Installation and operating instructions Flexcon M-P pump automat Dear customer, GB With the purchase

More information

Reverse Osmosis System Installation Guide and Operation Manual.

Reverse Osmosis System Installation Guide and Operation Manual. Reverse Osmosis System Installation Guide and Operation Manual. Table of Contents 1 Introduction...2 2 Installation...3 2.1 Feed water connection...3 2.2 Permeate and concentrate plumbing...3 2.3 Electrical

More information

ACV-10 Automatic Control Valve

ACV-10 Automatic Control Valve ACV-10 Automatic Control Valve Installation, Operation & Maintenance General: The Archer Instruments ACV-10 is a precision automatic feed rate control valve for use in vacuum systems feeding Chlorine,

More information

AUTOMATIC GAS MANIFOLDS

AUTOMATIC GAS MANIFOLDS AUTOMATIC GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

OC Panel High Limit Aquastat Kit, Manual Reset p/n

OC Panel High Limit Aquastat Kit, Manual Reset p/n OC Panel High Limit Aquastat Kit, Manual Reset p/n 233202 Instruction Sheet APPLICATION The OC (Option Control) Panel High Limit Aquastat Kit provides electronic temperature sensing in a UL limit-rated

More information

EDUCATION DEPARTMENT ACCU-TEST

EDUCATION DEPARTMENT ACCU-TEST ABN 17 100 208 964 EDUCATION DEPARTMENT ACCU-TEST GAS SAFETY SHUT OFF SYSTEM Operating & Installation Manual Head Office (Melbourne) Sydney Brisbane (Distributor) 1/5 Samantha Court 2/14 Welder Road 17

More information

Electro Controls. Level WattsIndustries.co.uk

Electro Controls. Level WattsIndustries.co.uk Electro Controls Level - 2017 WattsIndustries.co.uk levels Section 19 LIQUID LEVEL SWITCHES HORIZONTAL ELL.. Volt free contacts To monitor liquid level in tanks and switch pumps or an alarm in the event

More information

1. PARTS INTRODUCTION ELECTRICAL NOTES INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10.

1. PARTS INTRODUCTION ELECTRICAL NOTES INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10. CONTENTS 1. PARTS 3. 2. INTRODUCTION 4. 3. ELECTRICAL NOTES 5. 4. INSTALLATION 5/6. 5. START UP 6/7. 6. MAINTENANCE 7/8/9. 7. PRESSURE SWITCH ADJUSTMENTS 9/10. 8. ELECTRICAL CONNECTIONS 10/11. 9. SPECIFICATIONS

More information

Mainsboost Charger Installation, Operation & Maintenance Instructions

Mainsboost Charger Installation, Operation & Maintenance Instructions mainsboost Mainsboost Charger Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the home owner as it contains important guarantee, maintenance and safety information

More information

TECHNICAL DATA. Q = C v P S

TECHNICAL DATA. Q = C v P S Page 1 of 13 1. DESCRIPTION The Viking 6 Model G-6000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1)

JOLLY2. Installation user s manual. 6 different operating modes selectable. version 3.3. DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) ENGLISH ENGLISH ENGLISH ENGLISH Installation user s manual Warning! electrical scheme modified JANUARY 2005 version 3.3 JOLLY2 DATA TO BE FILLED OUT BY THE INSTALLER (Page 1) 6 different operating modes

More information

Expansion Vessels for Potable Installations

Expansion Vessels for Potable Installations 4. Expansion Vessels for Potable Installations Domestic installations lose millions of litres of potable water due to expansion water leaking from the vent and expansion pipe. Flamco s Airfix diaphragm

More information

Aquavar SOLO 2 Frequently Asked Questions

Aquavar SOLO 2 Frequently Asked Questions Aquavar SOLO 2 Frequently Asked Questions How do I size the Aquavar SOLO 2 for the appropriate pump/motor combination? Can I use a 208 Volt motor? Can I run the Aquavar SOLO 2 up to 80HZ? What are the

More information

Operating Instructions Part No

Operating Instructions Part No DIGITAL AUTOMATIC TYRE INFLATOR Operating Instructions Part No. 11.0545 Thank you for selecting this Jamec Pem Automatic Tyre Inflator. Please read this manual before carrying out any installation or service

More information

Commercial Softeners. Installation, Operation & Maintenance Guide. Manual 002.1

Commercial Softeners. Installation, Operation & Maintenance Guide. Manual 002.1 Commercial Softeners Installation, Operation & Maintenance Guide Manual 002.1 Contents Page 1. Unpacking Instructions 3 2. Installation 3 Pre-installation checks Fitting the bottom distribution system

More information

Chesil - Electronic Pressurisation Unit

Chesil - Electronic Pressurisation Unit Chesil - Electronic Pressurisation Unit Equipment For Commercial/Light Industrial Central Heating Installations. Installation, Commissioning and Servicing Instructions IMPORTANT NOTE THESE INSTRUCTIONS

More information

Duplex Commercial Softeners

Duplex Commercial Softeners Duplex Commercial Softeners Installation, Operation & Maintenance Guide Manual 003.1 Contents Page 1. Unpacking Instructions 3 2. Installation 4 Pre-installation checks Fitting the bottom distribution

More information

Controller for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW User guide

Controller for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW User guide Controller for boilers Galan - regulator for management of heating elements and circuit SolarSentinel-DBTW User guide SHORT DESCRIPTION: 1. Device is applicable to: Burners, Electric boiler, Electric heaters,

More information

Job Sheet 1. Geothermal Energy

Job Sheet 1. Geothermal Energy Job Sheet 1 Geothermal Energy OBJECTIVES In this job sheet, you will become familiar with the training system components. You will operate your training system in heating and cooling mode and observe the

More information

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY

TECHNICAL DATA 3 MODEL G-3000 DRY VALVE RISER ASSEMBLY Page 1 of 13 1. DESCRIPTION The Viking 3 Model G-3000 Dry Valve Riser Assembly is equipped with a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

GENERIC MANUAL - FOR REFERENCE ONLY. ALL BESPOKE UNITS WILL HAVE PROJECT SPECIFIC DETAILS

GENERIC MANUAL - FOR REFERENCE ONLY. ALL BESPOKE UNITS WILL HAVE PROJECT SPECIFIC DETAILS GENERIC MANUAL - FOR REFERENCE ONLY. ALL BESPOKE UNITS WILL HAVE PROJECT SPECIFIC DETAILS EnwaMatic Bespoke BS 300 Contents Declaration of conformity: 2 Pressure test certificate: 3 Contacts: 4 Installation

More information

TECHNICAL DATA. Q= Cv S

TECHNICAL DATA. Q= Cv S Page 1 of 13 1. DESCRIPTION The Viking 4 inch Model G-4000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry

More information

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13

TECHNICAL DATA Q = C. v P S. 2 Model G-2000 Dry valve. Page 1 of 13 Page 1 of 13 1. Description The Viking 2 Model G-2000 Dry Valve Riser Assembly consists of a small profile, light weight, pilot operated valve that is used to separate the water supply from the dry sprinkler

More information

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats

Installation, Operating, Maintenance and Safety Instructions for. Pressurised water systems for boats FLOMAX-SYSTEM DOC532/11 Installation, Operating, Maintenance and Safety Instructions for FLOMAX-SYSTEM Pressurised water systems for boats CW343A FloMax System 12 volt d.c. CW344A FloMax System 24 volt

More information

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply

OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply OIL SUPPLY SYSTEMS ABOVE 45kW OUTPUT 4.1 Oil Supply 4.1.1 General The primary function of a system for handling fuel oil is to transfer oil from the storage tank to the oil burner at specified conditions

More information

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND

CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND Configuration # : 41G20F0 CONTROL LOGIC DESCRIPTION DOCUMENT IC-410ND Input/output table: Inputs Qty Outputs Qty Inside Temperature Probe 3 Inflatable Balloon 8 Chimney Temperature Probe 1 Chimney Activator

More information

Spirax Compact FREME Flash Recovery Energy Management Equipment

Spirax Compact FREME Flash Recovery Energy Management Equipment IM-UK-cFREME UK Issue 1 Spirax Compact FREME Flash Recovery Energy Management Equipment Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4.

More information

Blowdown vessels Meeting the requirements of HSE PM60

Blowdown vessels Meeting the requirements of HSE PM60 Blowdown vessels Meeting the requirements of HSE PM60 BDV60 blowdown vessels A complete range of equipment for the safe disposal of boiler blowdown Boiler blowdown Steam boilers must be blown down to remove

More information

AutoChanger Installation & User Guide Issue 2

AutoChanger Installation & User Guide Issue 2 1 INDEX Page 1. Introduction... 3 2. AutoChanger Components Guide 4 3. Installation. 5-11 a) Installation Guidelines.. 5 b) Installation Retrofit... 6-11 c) Installation New... 11 4. AutoChanger User Guide

More information

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz

GRUNDFOS DATA BOOKLET. Hydro Solo-E. Complete pressure boosting systems 50/60 Hz GRUNDFOS DATA BOOKLET Complete pressure boosting systems 5/6 z Contents Product data Performance range 3 Operating conditions Inlet pressure Type key Product range 5 Construction 5 Installation 5 Mechanical

More information

INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May

INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May INSTRUCTION MANUAL FOR MODEL 7360V VERTICAL CURING CHAMBER Revision E May 2015 98-0520 S/N 2001 N. Indianwood Ave. Tulsa, Oklahoma 74012 U.S.A. TEL: (918) 250-7200 FAX: (918) 459-0165 E-mail: chandler.sales@ametek.com

More information

Booster Set (Vertical Twin) Installation, Operation & Maintenance Instructions

Booster Set (Vertical Twin) Installation, Operation & Maintenance Instructions Booster Set (Vertical Twin) Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the owner as it contains important guarantee, maintenance and safety information

More information

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. .

SAPCON. User Manual. Capacitance Continuous Level Indicator. . Introduction. . General Description. . Principle of Operation. . User Manual Capacitance Continuous Level Indicator Comprehensive User s Manual. Introduction. General Description. Principle of Operation. Specifications. Connection Diagrams. Quick Calibration Chart.

More information

MOYNO FLUID DETECTION CONTROL SERVICE MANUAL. Section: ACCESSORIES. Page: 1 of 8 Date: May 1, 1998 GENERAL

MOYNO FLUID DETECTION CONTROL SERVICE MANUAL. Section: ACCESSORIES. Page: 1 of 8 Date: May 1, 1998 GENERAL MOYNO Section: ACCESSORIES Page: 1 of 8 Date: May 1, 1998 SERVICE MANUAL FLUID DETECTION CONTROL GENERAL The Moyno Fluid Detection Control prevents unnecessary loss of production time or repair costs to

More information

Operating Instructions Part No

Operating Instructions Part No DIGITAL AUTOMATIC TYRE INFLATOR Operating Instructions Part No. 11.0578 Thank you for selecting this Jamec Pem Automatic Tyre Inflator. Please read this manual before carrying out any installation or service

More information

Multiple Pressure Booster Systems With Variable Speed Controller Type BL

Multiple Pressure Booster Systems With Variable Speed Controller Type BL Multiple Pressure Booster Systems With Variable Speed Controller Type BL General Characteristics - Single or multistage pumps - Horizontal or vertical mounting - Total head 30m ~ 250m - Material construction:

More information

Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger

Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger OM008 Installation, Operation and Maintenance Instructions for Pacific PA Non-Storage Heat Exchanger The operating and maintenance instructions contained within this package are for Pacific water/water

More information

DIGITAL AUTOMATIC TYRE INFLATOR

DIGITAL AUTOMATIC TYRE INFLATOR DIGITAL AUTOMATIC TYRE INFLATOR Instruction Manual PSI Part No. 11.0556 Digital Automatic Tyre Inflator (Portable) Thank you for selecting our Digital Automatic Tyre Inflator (Portable), please read this

More information

SPECIFICATIONS APCEPH1

SPECIFICATIONS APCEPH1 APCEPH1 ph CONTROLLER SPECIFICATIONS APCEPH1 Input voltage 120 Volts AC Maximum amperage 14.5 amps @ 120 VAC ph Accuracy +/- 0.2 ph ph Control range Adjustable 4.5 8.5 ph Weight < 1 lbs Dimensions 3" x

More information

TANKTRONIC. STANDARD CONFIGURATION Single Tank. ADVANCED CONFIGURATION Multiple Tanks. Twin Tank (common valve) Twin Tank (separate valves) Vent box

TANKTRONIC. STANDARD CONFIGURATION Single Tank. ADVANCED CONFIGURATION Multiple Tanks. Twin Tank (common valve) Twin Tank (separate valves) Vent box TANKTRONIC STANDARD CONFIGURATION Single Tank control unit Twin Tank (common valve) control unit Twin Tank (separate valves) control unit ADVANCED CONFIGURATION Multiple Tanks control unit S-Module Tanktronic

More information

SCIENCE LAB UTILITY CONTROLS

SCIENCE LAB UTILITY CONTROLS SCIENCE LAB UTILITY CONTROLS INCORPORATING GAS PRESSURE PROVING GAS PRESSURE PROVING EQUIPMENT - ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY THE MERLIN RANGE DESIGNED FOR EDUCATIONAL LABORATORIES

More information

100L AIR COMPRESSOR MODEL NO: TIGER 16/1010 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS01/13

100L AIR COMPRESSOR MODEL NO: TIGER 16/1010 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS01/13 100L AIR COMPRESSOR MODEL NO: TIGER 16/1010 PART NO: 2244025 OPERATION & MAINTENANCE INSTRUCTIONS LS01/13 INTRODUCTION Thank you for purchasing this product. Before attempting to use this product, please

More information

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions

UBEC 1AT. AUTO TANK Fill System Installation, Operation, & Setup Instructions Document Number: XE-ATA5PM-R1A UBEC 1AT AUTO TANK Fill System 08899155 Installation, Operation, & Setup Instructions Rev170906-EB-FRC PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM

More information

AUTROL 217 Expansion and pressurization Systems

AUTROL 217 Expansion and pressurization Systems Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Control units. Installation and operating instructions Series: DP-Control

Control units. Installation and operating instructions Series: DP-Control Control units Installation and operating instructions Series: DP-Control Table of Contents 1 Manual introduction 1.1 Preface... 4 1.2 Icons and symbols... 4 2 Identification, service and technical support

More information

Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats

Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats MAXI-SYSTEM DOC50/ Installation, Operating, Maintenance and Safety Instructions for MAXI-SYSTEM Pressurised water systems for boats CW CW Maxi-System.9+ volt d.c. Maxi-System.9+ volt d.c. CW99A Maxi-System

More information

Installation, use and maintenance instructions. Gas burner (5)

Installation, use and maintenance instructions. Gas burner (5) Installation, use and maintenance instructions Gas burner MODEL GAS 4 TYPE 516 T80 291 (5) TECHNICAL FEATURES Thermal output 180-470 kw 154.800-404.200 kcal/h Fuel Natural gas Pci 8-10 kwh/m 3 = 7000-8600

More information

Renewables. Tribune HE Unvented Hot Water Cylinders Installation and Maintenance Instructions. Issue 17 July 2012

Renewables. Tribune HE Unvented Hot Water Cylinders Installation and Maintenance Instructions. Issue 17 July 2012 Renewables Tribune HE Unvented Hot Water Cylinders Installation and Maintenance Instructions Issue 17 July 2012 IMPORTANT NOTE TO THE INSTALLER Read these instructions before commencing installation. Unvented

More information

Quantum Contract Pressurisation Unit Operation & Maintenance Manual. Model: QC-35

Quantum Contract Pressurisation Unit Operation & Maintenance Manual. Model: QC-35 Quantum Contract Pressurisation Unit Operation & Maintenance Manual Model: QC-35 1: nstallation Location The following should be considered when choosing the position of the pump set: The area should be

More information

Operations Manual. Internal automatic Pressure control for orbital tube welding. By Exel Orbital Systems, Inc. Page

Operations Manual. Internal automatic Pressure control for orbital tube welding. By Exel Orbital Systems, Inc. Page Operations Manual Internal automatic Pressure control for orbital tube welding. By Exel Orbital Systems, Inc. Page SG1 Overview and Dimensions 5.25 / 133 mm PS Power Supply Connection 4.06 / 103 mm Top

More information

MD R a n g e O p e r a t o r s H a n d b o o k

MD R a n g e O p e r a t o r s H a n d b o o k MD R a n g e O p e r a t o r s H a n d b o o k Covering Models:- MD35/20 MD75/80 MD75/0 MD75/0V MD75/250 MD75/250V MD0/500 MD225/1000 BAMBI AIR COMPRESSORS LTD 2 Thimble Mill Lane Heartlands Birmingham

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE11C150, VE15C150, VE18C150 PART NO: 2226005, 2226000, 2226015 OPERATION & MAINTENANCE INSTRUCTIONS LS0615 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

Mainsboost Installation, Operation & Maintenance Instructions

Mainsboost Installation, Operation & Maintenance Instructions mainsboost Mainsboost Installation, Operation & Maintenance Instructions Please leave this instruction booklet with the home owner as it contains important guarantee, maintenance and safety information

More information

MANUAL GAS MANIFOLDS

MANUAL GAS MANIFOLDS MANUAL GAS MANIFOLDS Phoenix Pipeline Products Limited. Unit 8, McKenzie Industrial Park, Tel No.: 44 (0) 161 428 7200 Bird Hall Lane, Fax No.: 44 (0) 161 428 7010 Stockport, Email: info@p3-phoenix.com

More information

24L AIR COMPRESSOR MODEL NO: TIGER 11/250 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS01/13

24L AIR COMPRESSOR MODEL NO: TIGER 11/250 PART NO: OPERATION & MAINTENANCE INSTRUCTIONS LS01/13 24L AIR COMPRESSOR MODEL NO: TIGER 11/250 PART NO: 2244010 OPERATION & MAINTENANCE INSTRUCTIONS LS01/13 INTRODUCTION Thank you for purchasing this product. Before attempting to use this product, please

More information

Temperature Controller CC24-7 ULTRA USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

Temperature Controller CC24-7 ULTRA USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517) Temperature Controller USER S MANUAL Aerotech, Inc. FORM: QM1387 4215 Legion Dr. Mason, MI 48854-1036 USA October 2010 Ph. (517) 676-7070 Fax (517) 676-7078 FOR CUSTOMER USE Enter the serial number located

More information

PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION

PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION PROVENGAS AUTOMATIC PROVING SYSTEMS FOR GAS INSTALLATION Provengas Labsafe PGLS001 Provengas Cooksafe PGCS003 2 Provengas Labsafe has been designed as a gas pressure proving system for use in schools and

More information

SINGLE VALVE WITH LOW-FLOW BYPASS

SINGLE VALVE WITH LOW-FLOW BYPASS CONTROL VALVES Pressure Reducing Valve Sizing Guide Sizing pilot operated reducing valves is not a complicated process. It starts with determining requirements and following these guidelines in valve size

More information

Manual Actuated Boiler Blowdown Valves

Manual Actuated Boiler Blowdown Valves Manual Actuated Boiler Blowdown Valves Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Operation 5. Maintenance 6. Spare parts p.1 1. Safety

More information

User Manual. Nitrogen generator N2 LCMS 1

User Manual. Nitrogen generator N2 LCMS 1 User Manual Nitrogen generator N2 LCMS 1 Sommario 1. Introduction 3 2. Safety 4 3. Description of the generator 6 4. Installation 8 5. Disassembly and transport 11 6. Use 12 7. Maintenance 17 8. Troubleshooting

More information

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide

AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide AcornVac Vacuum Plumbing Systems - Trouble Shooting Guide 1. Accumulators Problem Accumulator is overflowing If Accumulator continues to overflow Correction 1. Push and hold the manual activation button

More information

The Univentor 1250 Anaesthesia Unit

The Univentor 1250 Anaesthesia Unit THE UNIVENTOR 1200/1250 ANAESTHESIA UNIT The Univentor 1250 Anaesthesia Unit TABLE OF CONTENTS EDITION 1 Section 1 - WARRANTY & SERVICE 1.1. WARRANTY 2 1.2. DAMAGED SHIPMENTS 2 1.3. SERVICE 2 Section 2

More information

SMV-001 Thermostatic Shower Mixer Valve Installation Instructions & Adjustment Settings

SMV-001 Thermostatic Shower Mixer Valve Installation Instructions & Adjustment Settings SMV-001 Thermostatic Shower Mixer Valve Installation Instructions & Adjustment Settings 38 READ ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. LEAVE THIS BOOKLET WITH THE END USER FOR FUTURE REFERENCE

More information

User s manual. Nitrogen generator Laser Cut

User s manual. Nitrogen generator Laser Cut User s manual Nitrogen generator Laser Cut Table of contents 1. Introduction 3 2. Safety 4 3. Description of the generator 6 4. Installation 10 5. Operating instructions 16 6. Maintenance 30 7. Troubleshooting

More information

VERTICAL AIR COMPRESSORS

VERTICAL AIR COMPRESSORS VERTICAL AIR COMPRESSORS MODEL NO: VE15C150, VE18C150, VE25C150 PART NO: 2226010, 2226020, 2226025 OPERATION & MAINTENANCE INSTRUCTIONS LS0715 INTRODUCTION Thank you for purchasing this CLARKE Vertical

More information

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection

SG36KTL-M Quick Installation Guide. 1 Unpacking and Inspection SG36KTL-M Quick Installation Guide This guide provides a general instruction of the installation procedures of SG36KTL-M. In no case shall this guide substitute for the user manual or related notes on

More information

1020 Industrial Drive, Orlinda, TN fax

1020 Industrial Drive, Orlinda, TN fax Operation Manual Tank Distribution System A-UPT Series 615-654-4441 sales@specialtyh2o.com 615-654-4449 fax TABLE OF CONTENTS Section 1 GENERAL 1.2 Warnings and Cautions... 1 1.2 Theory of Operation...

More information

NIV EAU MATIC ST User Manual Made in Canada

NIV EAU MATIC ST User Manual Made in Canada NIV EAU MATIC ST User Manual Made in Canada www.niveaumatic.com info@niveaumatic.com -2- Table of contents Introduction Section 1 Page 4 Installation Section 2 Pages 5 to 10 2.1 Control box 2.2 Sensor

More information

Sterisil Ac+ Installation & Operating Manual

Sterisil Ac+ Installation & Operating Manual Sterisil Ac+ Installation & Operating Manual 719 622 7200 Sterisil.com Arbor Dental Associates 2 Table of Contents Introduction 4 Sterisil Ac + Features 5 Installation Instructions 6 Maintenance 10 Troubleshooting

More information

The CWE / HWE-R Series: Overview. Frame and cabinet covering

The CWE / HWE-R Series: Overview. Frame and cabinet covering Table Of Contents The CWE / HWE-R Series: Overview...... 1 Frame and cabinet covering... 1 Refrigerant gas...... 2 Compressors...... 2 Condensers...... 2 Fans... 3 Evaporator...... 3 Refrigerant circuit......

More information

Touch Screen Guide. OG-1500 and OG Part # T011

Touch Screen Guide. OG-1500 and OG Part # T011 Touch Screen Guide OG-1500 and OG-2000 Part # 9000000.T011 Effective 11/2010 External View Internal View 1. Transducer Banks 2. Oxygen Sensor 3. PLC These are the two manifolds with three (3) transducers

More information

24L AIR COMPRESSOR OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: RANGER 7/240 PART NO: LS0913

24L AIR COMPRESSOR OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: RANGER 7/240 PART NO: LS0913 24L AIR COMPRESSOR MODEL NO: RANGER 7/240 PART NO: 2242000 OPERATION & MAINTENANCE INSTRUCTIONS LS0913 INTRODUCTION Thank you for purchasing this CLARKE 24L Air Compressor. Please read this manual fully

More information

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel

Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel OM006 Installation, Operation and Maintenance Instructions for Mild Steel Buffer Vessel The operating and maintenance instructions contained within this package are for standard mild steel buffer vessels

More information

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which

TECHNICAL DATA. System water supply pressure enters the priming chamber of the deluge valve (A.1) through the 1/4 (8 mm) priming line, which January 27, 2012 307a 1. (Refer to Figures 1-3.) A Viking Non-Interlocked Preaction system utilizes a Viking Deluge Valve to control water flow into system piping equipped with closed sprinklers. Under

More information

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels

Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels OM003 Installation, Operation and Maintenance Instructions for Direct Hot Water Storage Vessels The operating and maintenance instructions contained within this package are for standard storage vessels

More information