Maxon Packaged & EBMRV CYCLOMAX Low NOx Burner

Size: px
Start display at page:

Download "Maxon Packaged & EBMRV CYCLOMAX Low NOx Burner"

Transcription

1 Bulletin 28 Maxon Packaged & EBMRV CYCLOMAX Low NOx Burner Packaged Version EBMRV Version Provides clean combustion with NOx emission levels below 2 ppm ( mg/m 3 ) and CO levels less than 7 ppm (9 mg/m 3 ) at 3% O 2. Lower emissions possible based on specific application. Contact your Maxon sales representative for more information. Nozzle-mixing gas burner for use with natural gas or propane Packaged version available in sizes up to 3,7, Btu/hr (11 kw) EBMRV version available in 4 sizes up to 7,4, Btu/hr (22 kw) Packaged version operates on low gas pressure 16" w.c. (4 mbar) or less Simple installation, adjustment and start-up Turndown averages 1:1 (1:1 on smaller sizes) Designed specifically for oven-type applications with cross velocities up to 4 fpm (2 m/s) Packaged version handles oven conditions from 2" w.c. ( mbar) suction to 2" w.c. ( mbar) back pressure EBMRV version offers good performance with a much wider range of suction or back pressure applications CORPORATION 21 East 18th Street, P.O. Box 268, Muncie, Indiana, Phone: (76) Fax (76)

2 GAS SS Page 282 Maxon Packaged & EBMRV CYCLOMAX Low NOx Burner Principle of Operation The clean-burning design of the Maxon Packaged and EBMRV CYCLOMAX Low NOx Burners produce extremely low emissions of both NOx and CO. The patented burner nozzle creates a swirling flame within the combustion sleeve. The recirculation pattern allows the burner to produce very low levels of CO and unburned hydrocarbons. On the Packaged versions, the air/fuel shaft maintains the proper air-fuel ratio for low emissions throughout the firing range. For best results, the fuel pressures upstream of the burner should not change by more than 3" w.c. (7. mbar) as the burner throttles from high to low fire. The EBMRV versions are field-adjusted to the proper air-fuel ratios by using a Maxon MICRO- RATIO Valve. The flame is almost completely contained inside the combustion sleeve. The gases exiting the sleeve are essentially those of complete combustion. EBMRV versions use Maxon FG Blowers and MICRO-RATIO Valves, and are capable of doubling the capacity of the Packaged versions. Blower Component Identification Filter/Silencer Packaged Version Nozzle Air Inlet Body Gas Inlet Body Gas Bypass (.4M &.8M only) Gas Bridge Pilot Spark Ignitor Combustion Sleeve Gas Manifold Main Housing Pilot Tube Scanner Pipe Back Plate EBMRV Version Nozzle Main Housing Air Inlet Adapter Back Plate Threaded Gas Inlet Pilot Spark Ignitor Combustion Sleeve Gas Manifold Pilot Scanner Tube Pipe 9/3 CORPORATION 21 East 18th Street, P.O. Box 268, Muncie, Indiana, Phone: (76) Fax (76)

3 Packaged & EBMRV CYCLOMAX Burners Page 283 Burner Application Details Packaged Versions CYCLOMAX Burners were designed for low to moderate temperature oven-type applications only. They may be used in any oven whose combustion chamber temperature is 8 F (427 C) or less. NOTE: CYCLOMAX Burners should not be used in any application where there is a static (no moving air) condition. Packaged CYCLOMAX Burners include a low horsepower combustion air blower in your choice of the voltages listed below. Packaged C YCLOMAX Burner Model Horsepower.4M.8M 1.6M 2.7M 3.7M 1/2 HP 1/2 HP 3/4 HP 2 HP 3 HP 28-23/46/3/6 1/2 HP 1/2 HP 3/4 HP 2 HP 3 HP 7/3/6 1/2 HP 1/2 HP 3/4 HP 2 HP 3 HP IMPORTANT: The combustion air blower must be in operation any time the air stream temperature is above 2 F (93 C). If not, damage to the blower, burner and piping is possible. To adjust the Packaged burner, set the gas pressure according to the values shown in the table below. During adjustment, observe the flame if possible. The flame should be blue and it should be totally contained inside the combustion sleeve, especially at low firing rates. Blue flame outside of the combustion sleeve is caused by combustion that is either too rich or too lean and will result in high levels of CO. Yellow or orange flames are normally an indicator of a too-rich flame. Higher oven suction will require higher gas pressure to the burner for optimum performance. Higher back pressure will require less gas pressure to the burner for optimum performance. The values listed in the table below are for a near balanced condition. IMPORTANT: The pilot must be interrupted in order to obtain the emissions listed in the following table. Continuous pilot is not recommended. P ackaged CYCLOMAX Natural Gas Capacities and Specifications (6 Hz) Burner Size.4M.8M 1.6M 2.7M 3.7M R ecommended Gas Pressure " w.c M aximum Capacity ( 1's Btu/hr) M inimum Capacity ( 1's Btu/hr) P ilot Capacity ( 1's Btu/hr) Turndown Up to 1: 1 Up to 1: 1 Up to 1: 1 Up to 1: 1 Up to 1: 1 Emission Turndown based on high fire 1: 1 1: 1 3.: 1 6: 1 4: 1 M aximum Air Pressure " w.c A ir Flow SCFM ( Maximum) N Ox ( corrected to 3% oxygen) C O ( corrected to 3% oxygen) S ound Level ( without silencer) db(a) F lame Length ( ft) NOTE: On the packaged unit, gas pressure is measured at the pressure tap on the gas valve body (not the backplate). The backplate pressure tap is for the EBMRV version. 9/3

4 Page 284 Packaged & EBMRV CYCLOMAX Burners Burner Application Details EBMRV Versions Maxon CYCLOMAX Burners are available in four external blower versions. By using the specified external blower, it is possible to double the capacity of the burner over the Packaged version. Emissions are similar to the burner operating with a packaged fan. With the EBMRV versions, there is slightly more flame outside of the can and this makes the burner more sensitive to cross velocity. The external blower versions are very similar to the packaged versions except they do not include gas or air internal control devices. A threaded EB Air Adapter allows the MICRO-RATIO Valve to be mounted. The recommended (minimum) FG Blower is shown in the chart below. If you use a butterfly style gas valve on the MICRO-RATIO Valve, turndown could be affected. Poppet style gas valves should be used. If your air piping is unusually long and/or contains many fittings, please review your blower size to compensate for higher pressure drops through the air piping. Set the MICRO-RATIO Valve to obtain the gas and air pressures shown on the graphs on pages The following table lists the recommended MICRO-RATIO Valve and FG Blower selections. The values in the table below are guidelines. To meet your capacity and turndown needs, pressures must be set to match the graphs on pages IMPORTANT: The EBMRV versions, like the packaged versions, should be operated with interrupted pilot. Emissions can be 2% higher if the pilot is left on continuously and combustion sleeve life is reduced. IMPORTANT: Whenever the combustion chamber temperature is above 2 F (93 C), air should be flowing through the burner. If not, damage to gaskets in the burner could result and increase the chance for leaks. Burner Size EB2MRV CM EB3MRV CM EB4MRV CM EBMRV CM M aximum Capacity ( Btu/hr) 1,6, 3,2,,4, 7,4, M ICRO-RATIO V alve 1 " P x M 3" 1." P x M 4" 2." P x M 6" 2." P x M 6" Minimum FG Blower Recommended C C C C C YCLOMAX EB Versions Natural Gas Capacities and Specification (6 Hz) Burner Size EB2MRV CM EB3MRV CM EB4MRV CM EBMRV CM M aximum Capacity ( Btu/hr) 1,6, 3,2,,4, 7,4, M inimum Capacity ( Btu/hr) 1, 18, 2, 18, P ilot Capacity ( Btu/hr) 1, 1, 18, 2, G as Pressure at Maximum Firing Rate ("w.c.) A ir Pressure at Maximum Firing Rate ("w.c.) Turndown 1: 1 1: 1 1: 1 1: 1 Emission Turndown based on high fire 1: 1 13: 1 1: 1 12: 1 A ir Flow at Maximum ( SCFM) T ypical Gas Pressure Upstream of MICRO-RATIO V alve ( psi) 1. to 2 2 to 3 2 to to 3. Typical NOx 3% O ( low cross velocity) < 2 < 2 < 2 <2 2 Typical CO 3% O ( low cross velocity) < 7 < 7 < 7 <7 2 Typical NOx 3% O ( high cross velocity) < 2 < 2 < 2 <2 2 Typical CO 3% O ( high cross velocity) < 1 < 1 < 2 <1 2 F lame Length ( ft) NOTE: Operation above the recommended gas pressure for a given air pressure will result in higher NOx and lower CO. Operation below the recommended gas pressure curves will result in lower NOx and higher CO. Use of propane as a fuel will result in higher emissions. Oven cross velocities and back pressures have a slight affect on the optimum pressures to set.

5 Packaged & EBMRV CYCLOMAX Burners Page 28 EB2MRV - Natural Gas Burner Application Details 4 KBtu/hr Gas Pressure "wc Air Pressure "wc 4 EB2MRV - Propane 16 KBtu/hr Gas Pressure "wc Air Pressure "wc 1/99

6 Page 286 Packaged & EBMRV CYCLOMAX Burners EB3MRV - Natural Gas Burner Application Details Gas Pressure "wc KBtu/hr Air Pressure "wc EB3MRV - Propane 2 KBtu/hr 2 32 Gas Pressure "wc Air Pressure "wc

7 Packaged & EBMRV CYCLOMAX Burners Page 287 Burner Application Details EB4MRV - Natural Gas 4 KBtu/hr Air Pressure "wc EB4MRV - Propane 2 KBtu/hr Air Pressure "wc 2 1 1/99

8 Page 288 Packaged & EBMRV CYCLOMAX Burners Burner Application Details EBMRV - Natural Gas 3 KBtu/hr Air Pressure "wc EBMRV - Propane 2 KBtu/hr Air Pressure "wc 3 2 1

9 SIZE M CYCLOMAX LOW NOX GAS BURNER FACTORY ORDER# R A X O N ASBY# MAXON CORPORATION MUNCIE IN.USA WARNING! R PATENT PENDING Packaged & EBMRV CYCLOMAX Burners Page 289 Dimensions (in inches) Dimensions Packaged Versions S M 1/4" NPT Gas Pressure Test Connection 1/4" NPT Hi/Lo Pressure Switch Connection P K T dia. L dia. N Main Gas Inlet Foam Filter Foam Silencer/Filter A B Hi Fire Switch Position (optional) /8" (.62) dia. burner mounting holes 8 holes equally spaced Pilot Gas 3/8" NPT Spark Ignitor 1/2" NPT E dia. R R dia. dia. F.37 G H J C rad. D dia. Observation Port 22 4 Scanner 3/4" NPT D imensions (in inches) Burner Size A B C D E F G H J K L M N NPT P R S T.4M " M " M " M /4" M /2" /4

10 T FLAME DETECTOR I N H S E A R L E L EB TEST CONN SPARK IGN. R M A X O N R CYCLOMAX LOW NOX GAS BURNER PATENT PENDING SIZE ASBY# FACTORY ORDER# MAXON CORPORATION MUNCIE IN.USA WARNING! EB TEST CONN R M A X O N R CYCLOMAX LOW NOX GAS BURNER PATENT PENDING SIZE ASBY# FACTORY ORDER# MAXON CORPORATION MUNCIE IN.USA PILOT WARNING! SPARK IGN. T FLAME DETECTOR I N H S E A R L E L PILOT Page 281 Packaged & EBMRV CYCLOMAX Burners Dimensions (in inches) Dimensions EBMRV Version EB2MRV & EB3MRV 4" NPT Combustion Air Inlet 1/4" NPT Air Pressure Test Connection dia. 1. dia Spark Ignitor Removal Clearance 1-1/2" NPT Main Gas Inlet dia. 1/4" NPT Gas Pressure Test Connection 6.32 rad. /8" (.62) dia. Burner Mtg. Holes 8 holes equally spaced 22 4 Pilot Gas 3/8" NPT Spark Ignitor 1/2" NPT Scanner 3/4" NPT Observation Port EB4MRV & EBMRV 6" NPT Combustion Air Inlet 1/4" NPT Air Pressure Test Connection " NPT Main Gas Inlet dia. A 13.2 dia Spark Ignitor Removal Clearance /4" NPT Gas Pressure Test Connection 7.73 rad. Scanner 3/4" NPT dia. Observation Port Pilot Gas 3/8" NPT Spark Ignitor 1/2" NPT /8" (.62) dia. Burner Mtg. Holes 8 holes equally spaced Dimension "A" for EB4MRV 28.7 for EBMRV

11 Packaged & EBMRV CYCLOMAX Burners Page 28-S-1 Installation Instructions Packaged Versions Please read all installation and start-up instructions before working with the burner. IMPORTANT: Do not discard packing material until all loose items are accounted for. Some components may be shipped separately from your Packaged CYCLOMAX Burner to prevent damage in transit. Do not discard packing until you have accounted for all loose items. The burner is only a part of your complete combustion system. Additional pipe train accessories and control components will be required for a complete system installation. The sketch below shows a typical gas train as might be used with the burner. Packaged CYCLOMAX Burner comes complete with its own combustion air blower. The burner also provides fuel flow control and a fuel/air mixing device. The Packaged CYCLOMAX Burner should not be exposed to direct radiant heat or positioned where it might draw in inert gases. If such conditions exist, consider filters, relocation, and/or use of the EBMRV CYCLOMAX Burner with an external air supply. CAUTION: Installation should be undertaken only by trained personnel familiar with combustion systems, with control/safety circuitry, and with knowledge of the overall installation. Instructions provided by the company or individuals responsible for the manufacture and overall installation of the complete system incorporating Maxon burners take precedence over these provided by Maxon. If there are any conflicts in these instructions, contact Maxon before proceeding. Electrical service must match the voltage, phase and cycle of all electrical system components and be compatible with burner nameplate ratings. Gas and air supply piping must be large enough to provide for the full flow and pressures shown in the catalog for your particular burner when it is operating at its full-rated capacity. Clean fuel lines are essential to preventing the blockage of burner gas ports and pipe train components. Dirty fuel lines may require special filters. Main shut-off cock should be upstream of both the main gas regulator and pilot take-off line. Main gas regulator is essential to maintaining a uniform system supply pressure. If one pipe train supplies multiple burners, provide a separate regulator in the branch leading to each burner system. Size the regulator for full system capacity at the required pressure, carefully considering pipe train losses. If the regulator has more than 3 wc (7. mbar) of droop*, two-stage regulation is recommended. Follow the instructions attached to the regulator and be sure to remove any shipping pin or block. *Droop is defined as the increase in gas pressure (due to imperfections in a gas pressure regulator) as the burner is throttled from high fire where the desired gas pressure is set. Pilot take-off should be upstream of the main gas regulator, but downstream of the main gas shut-off cock. It normally includes its own pilot gas regulator, a solenoid valve and shut-off cock. A pilot adjustable orifice at the pilot inlet simplifies adjustment. The pilot must be interrupted in order to obtain low emission levels. Continuous pilot is not recommended. NOTE: The.4m size burner is lit on main gas. It does not have a separate pilot. Plumbing and electrical wiring must allow the pilot to be interrupted. Pilot take-off should be upstream of the main gas regulator. Pilot piping must be large enough to provide for the full flow and pressures shown in the catalog for your particular burner size. External support of the gas piping is recommended. Fuel shut-off valves (when properly connected to a control system) shut the fuel supply off when a hazardous operating condition is sensed. Manual reset valves require operator attendance each time the system is started up (or restarted after a trip-out). Motorized shut-off valves permit automatic startrestart when used with an appropriate control system. /3 Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice. INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES mcorporation MUNCIE, INDIANA, USA

12 Page 28-S-2 Packaged & EBMRV CYCLOMAX Burners Installation Instructions Packaged Versions Test connections are essential for proper burner adjustment and operation and are included in the Packaged CYCLOMAX Burner. Test connections must be plugged except when readings are being taken. Burner mounting requires a stud pattern on a flat surface that matches the mounting holes on the main housing of the CYCLOMAX Burner (see dimension drawing on page 289). After placing the burner in position, add lock washers and nuts. Tighten securely. Connect the gas supply to the burner at the threaded inlet on the gas valve body. Recommended gas pressure at the burner is shown below for each burner size. Recommended Gas Pressure "wc Burner Natural Gas Size.4M.8M 1.6M 2.7M 3.7M 6 Hz Hz Recommended Gas Pressure mbar Burner Natural Gas Size.4M.8M 1.6M 2.7M 3.7M 6 Hz Hz The Packaged CYCLOMAX Burner can be mounted in several positions. Some accessories, such as control motors, can limit the mounting options. Burners are typically installed through an insulated wall that could be several inches thick. The mounting hole diameter should be approximately 1 to 1-1/2 inches (2,4 to 38,1 mm) larger than Dimension R on page 289. If the combustion air fan is supplied with a filter, the filter must be kept clean. A dirty air filter can result in inadequate combustion air flow to the burner and higher emissions. Decreased air pressure could indicate that the filter is becoming plugged. NOTE: To make the burner lighter and easier to handle, the blower can be removed before the burner is mounted. A -volt full-sine-wave spark ignition transformer should be used. Make sure the spark ignitor is in the proper position by loosening the ignitor nut and pushing the ceramic insulator as far in as possible. Hold the insulator in place as the nut is retightened. Improper positioning of the ignitor will result in difficulty in lighting the burner. Connect all remaining electrical and mechanical components. Maintenance Instructions If it is ever necessary to remove the fuel shaft from the burner, be sure to use anti-seize lube or a light grease on the fuel shaft during reassembly. Apply the grease to the O-rings only do not apply it to the cutout area. Too much grease can plug the area in the fuel shaft that affects the gas flow. mcorporation MUNCIE, INDIANA, USA INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.

13 Packaged & EBMRV CYCLOMAX Burners Page 28-S-3 Start-up Instructions Packaged Versions Read all instructions before proceeding and familiarize yourself with the system s components. Verify that your equipment has been correctly installed. CAUTION: Initial adjustment and light-off should be undertaken only by trained personnel familiar with combustion systems, with control/safety circuitry, and with knowledge of the overall installation. Instructions provided by the company or individuals responsible for the manufacture and overall installation of a complete system incorporating Maxon burners take precedence over these provided by Maxon. If Maxon instructions conflict with any rules or regulations, contact Maxon before attempting start-up. The integral air-fuel shaft keeps the air-fuel ratio in the proper range throughout the firing range. Proper air-fuel ratio control depends on a constant pressure upstream of the shaft. Regulators with less than 3" wc (7. mbar) droop should be used. A pneumatic or electric control motor can be mounted to the air-fuel shaft and establish firing rates according to system demands. Gas pressure test connections are essential for burner adjustment and are provided in the burner. Do not attempt to use test connections in pipe elbows or tees, as internal turbulence can give erroneous readings. Test connections not being used must be plugged. For initial system start-up 1. Close all burner fuel valves and/or cocks. Make preliminary adjustments to regulators. Remove pilot regulator adjusting screw cover and turn screw down to near mid-range condition. Close pilot gas adjustable orifice screw by turning it clockwise until it stops, and then back it out (counterclockwise) 2 to 3 turns. 2. Check all electric circuitry and verify that all safety devices and interlocks are functioning within their respective settings/ranges. Marginallyset pressure switches can result in numerous nuisance trips and can delay start-up. Be sure all manifolds are tightly sealed and that test ports are plugged if not being used. 3. Check that all duct and chamber dampers are properly positioned and locked into operating positions. 4. Start all system related fans and blowers. Check for proper motor rotation and impeller direction. Verify that all safety interlocks are working. Allow air handling equipment to run for an adequate purge of manifolds and combustion chamber plenums.. Initial start-up adjustment can more easily be accomplished in a manual control mode. Disconnect the automatic control motor s linkage from the burner s control valve by loosening the control motor s connecting rod from the valve s toggle linkage. 6. Once the burner is installed and all safety devices are in place, the burner is ready to be fired. Position the burner at its minimum firing rate. Do not exceed minimum (overtravel), as the gas and air valves will start to re-open. The.4M size does not have a pilot; it is lit on main gas. For other sizes, pilot pressure can be as low as 6 to 12" wc (14.9 to 29.9 mbar) under ideal conditions, but a higher pilot pressure will facilitate start-up under stubborn lighting conditions. Maxon recommends that the pilot take-off be upstream of the main gas regulator. Ideal pilot flow ranges from about 7 SCFH (.2 m 3 /min) on the 8, Btu/hr (117 kw) size to about 12 SCFH (.6 m 3 /min) on the largest size (for natural gas). 7. If the burner fails to light, it could be due to trapped air in the gas line. Keep trying until the gas purges the air. If the burner fails to light after repeated attempts, check to see if the spark ignitor is pushed all the way in. For the.4m burner, adjust the gas bypass until a stable minimum flame at a gas pressure close to (or slightly higher than) what is desired at high fire is achieved. If working with a.4m burner and it is lit and stable on main gas at minimum, proceed to Step Confirm that the pilot is lit before proceeding to the next step. /3 Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice. INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES mcorporation MUNCIE, INDIANA, USA

14 Page 28-S-4 Packaged & EBMRV CYCLOMAX Burners Start-up Instructions Packaged Versions 9. With burner at minimum position, turn on the main gas. The.4M and.8m sizes have a gas bypass with an adjustable orifice which can be adjusted to allow more gas to flow around the fuel shaft at minimum. Shut off the pilot and confirm that the burner is still lit. Adjust the main gas regulator to 3" wc (7. mbar) more than the recommended value. 1. Slowly increase the firing rate. As firing rate increases, the pressure upstream of the burner may decrease somewhat because of regulator droop. 11. Bring the burner up to high fire, increasing regulator pressure if necessary. 12. Readjust the regulator to the recommended gas pressure upstream of the burner (see page 28- S-2). NOTE: Do not overtravel when going up to high fire. 13. Once the burner is lit and has been fired throughout the range, slowly bring it down to minimum and verify that the gas pressure does not increase by more than 3" wc (7. mbar) as the burner is throttled down. High suction applications can require higher gas pressures to the burner because more air is pulled through the system. High back pressure conditions can require that the gas pressure be set lower than the values listed on page 28-S-2. mcorporation MUNCIE, INDIANA, USA INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.

15 Packaged & EBMRV CYCLOMAX Burners Page 28-S- Installation Instructions EBMRV Versions Please read all installation and start-up instructions before working with the burner. IMPORTANT: Do not discard packing material until all loose items are accounted for. Some components may be shipped separately from your EBMRV CYCLOMAX Burner to prevent damage in transit. Do not discard packing until you have accounted for all loose items. The burner is only a part of your complete combustion system. Additional pipe train accessories and control components will be required for a complete system installation. MICRO-RATIO Control Valve (Style P gas valve and M- style butterfly air valve) and FG Blower must be ordered separately. See CYCLOMAX (section 28) and FG Blower (section 92) catalog literature for selection guidelines for choosing the appropriate blower for your burner and capacity requirements. Do not position the EBMRV CYCLOMAX Burner or the FG Blower where they will be exposed to direct radiant heat or the blower could draw in inert gases. If such conditions exist, consider filters or relocation. CAUTION: Installation should be undertaken only by trained personnel familiar with combustion systems, with control/safety circuitry, and with knowledge of the overall installation. Instructions provided by the company or individuals responsible for the manufacture and overall installation of a complete system incorporating Maxon burners take precedence over these provided by Maxon. If there are any conflicts in these instructions, contact Maxon before proceeding. Electrical service must match the voltage, phase and cycle of all electrical system components and must be compatible with burner nameplate ratings. Gas and air supply piping must be large enough to provide for the full flow and pressures shown in the catalog for your particular burner when it is operating at its full rated capacity. Attempt to minimize the pressure drop from the blower to the burner. If air supply piping is unusually long and/or incorporates many fittings through which large pressure drops could occur, choose a higher capacity blower. Do not use air piping smaller than 3 (76 mm) on the EB2MRV 4 (12 mm) on EB3MRV, or 6 (12 mm) on the EB4MRV and EBMRV. Testing has shown that with three 9 elbows and 1 feet (348 mm) of straight pipe, rated capacities can be obtained with these sizes. Gas supply piping should be the same size (or larger) than the size of the poppet gas valve: 1 (2.4 mm) for EB2MRV 1. (38 mm) for EB3MRV 2. (63 mm) for EB4MRV and EBMRV Pipe/duct the MICRO-RATIO Valve to the air inlet and attach the gas line from the MICRO-RATIO Valve to the threaded gas inlet on the burner back plate. Smaller gas piping can be used, but will require higher gas pressure to compensate for the additional pressure drop. Clean fuel lines are essential to prevent the blockage of burner gas ports and pipe train components.dirty fuel lines may require special filters. If an uneven flame is observed (dark spots on the sleeve, no flame in a particular region, etc.), one or more of the gas ports may be plugged. An uneven flame will cause higher emissions. Good flame uniformity allows for optimum performance of the burner. Main shut-off cock should be upstream of the main gas regulator and the pilot line take-off. Main gas regulator is essential to keep the pressure upstream of the MICRO-RATIO Valve constant once the burner is set to the recommended gas pressure versus air pressure curve. If one pipe train supplies multiple burners, provide a separate regulator to the MICRO-RATIO Valve of each burner system. Size the regulator for full system capacity at the required pressure upstream of the MICRO- RATIO Valve. Pressure to the MICRO-RATIO Valve should be 1 psi (69 mbar) higher than the high fire gas pressure at the burner. Follow the instructions attached to the regulator and be sure to remove any shipping pin or block. Pilot take-off should be upstream of the main gas regulator but downstream of the main gas shut-off cock. It normally includes a pilot gas regulator, solenoid valve, and shut-off cock. A pilot adjustable orifice at the pilot inlet simplifies adjustment. Plumbing and electrical wiring must allow the pilot to be interrupted. 1/99 Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice. INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES mcorporation MUNCIE, INDIANA, USA

16 Page 28-S-6 Packaged & EBMRV CYCLOMAX Burners Installation Instructions EBMRV Versions Pilot piping must be large enough to provide the full flow and pressures required for lighting the burner. Pilots will light over a wide range of pressures. Compensate for higher pressures by closing the adjustable orifice. Unless available pilot pressure is significantly higher than the burner operating pressure, use the following guidelines for sizing the pilot gas piping: EB2MRV & EB3MRV use at least 1/2 (12.7 mm) dia. pilot piping EB4MRV & EBMRV use at least 3/4 (19 mm) dia. pilot piping External support of both the air and gas piping is recommended. Fuel shut-off valves (when properly connected to a control system) shut the fuel supply off when a hazardous operating condition is sensed. Manual reset valves require operator attendance each time the system is started up (or restarted after a trip-out). Motorized shut-off valves permit automatic startrestart when used with an appropriate control system. The control valves which may be used with the EBMRV CYCLOMAX Burner are not intended for tight shut-off. Flame sensing can be accomplished only with a UV scanner. Cooling air to the UV scanner should not be required. Test connections are essential for proper set-up of the EBMRV CYCLOMAX Burners. The two test connections for the EBMRV version are located on the burner back plate (gas pressure) and on the circumference of the burner main housing (air pressure). Test connections must be plugged except when readings are being taken. Include observation ports in the combustion chamber design to provide a view of the flame. This will simplify start-up and adjustment procedures. Burner mounting requires a stud pattern on a flat surface that matches the mounting holes on the main housing of the CYCLOMAX Burner (see dimensional drawings on pages 289 and 281). Place the burner in position and add lock washers and nuts. Tighten securely. Connect the air valve of the MICRO-RATIO Valve assembly to the threaded inlet of the EBMRV adapter on the burner. Connect the gas valve of the MICRO-RATIO Valve assembly to the threaded inlet on the back plate of the burner. Adjust the linkage of the MICRO-RATIO Valve to achieve reliable light-off and adequate air to support both the pilot and main flames. The air valve should be set at to 1 degrees open when the gas valve is at minimum to get reliable lighting. Connect the FG Blower to the inlet of the MICRO- RATIO air valve. Minimize the piping between the blower, valve and burner to reduce pressure drop. The EBMRV CYCLOMAX Burner can be mounted in a variety of positions, but is most conveniently mounted with both inlets facing upward on the side of an oven. Downfiring is permitted. Burners are typically installed through an insulated wall. The mounting hole diameter should be approximately 1 to 1-1/2 inches (2,4 to 38,1 mm) larger than Dimension R on page 289. If using a filter with the FG Blower, check periodically to see if the filter is becoming plugged. If a drop in air pressure or change in flame appearance is observed, the filter may be plugged. Inadequate air flow to the burner can result in higher emissions. A volt, full-wave spark ignition transformer should be used. Verify that the spark ignitor is in the proper position by loosening the ignitor nut and pushing the ceramic in as far as possible. Keep forward pressure on the ceramic as the nut is being re-tightened. Improper positioning of the ignitor will cause difficulty in lighting the burner. Connect all remaining electrical and mechanical components. mcorporation MUNCIE, INDIANA, USA INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.

17 Packaged & EBMRV CYCLOMAX Burners Page 28-S-7 Start-up Instructions EBMRV Versions Read all instructions before proceeding and familiarize yourself with the system s components. Verify that the equipment has been correctly installed. CAUTION: Initial adjustment and light-off should be undertaken only by trained personnel familiar with combustion systems, with control/safety circuitry, and with knowledge of the overall installation. Instructions provided by the company or individuals responsible for the manufacture and overall installation of a complete system incorporating Maxon burners take precedence over these provided by Maxon. If Maxon instructions conflict with any rules or regulations, contact Maxon before attempting start-up. Gas and air pressure test connections are essential for proper burner adjustment. Test connections must be plugged except when readings are being taken. For initial system start-up: 1. Close all burner fuel valves and/or cocks. Make preliminary adjustments to regulators. Remove pilot regulator adjusting screw cover and turn screw down to near mid-range position. Turn pilot gas adjustable orifice screw clockwise until it closes, then turn screw counter-clockwise two or three turns. 2. Check all electric circuitry. Verify that all safety devices and interlocks are operable and functioning within their respective ranges. Be sure all manifolds are tight and verify that test connections are plugged if not being used. 3. Check that all duct and chamber dampers are properly positioned and locked into operating positions. 4. Start all system-related fans and blowers. Check for proper motor rotation and impeller direction. Verify that all safety interlocks are working. Allow air handling equipment to run for a sufficient purge time.. Initial start-up adjustment should only be done in a manual control mode. Disconnect any control motors from the MICRO-RATIO Valve linkage using an allen wrench to disconnect the control motor s connecting rod from the valve s toggle linkage. NOTE: The EBMRV CYCLOMAX Burners are designed to be used with Maxon MICRO-RATIO Valves. The gas valve has a multiple screw adjusting cam which is used to adjust the gas pressure at each setting to correspond with the appropriate air pressure for each position. The numbers on the external position indicating strip correspond to a series of adjusting screws which should be initially set to give the desired contour to the cam. Control valves are easily adapted to automatic operation with an electric or pneumatic control motor. Maxon offers a broad range of CB & L (connecting bracket and linkage) assemblies to properly position and align the control motors when used with Maxon control valves. Maxon CB & L assemblies are designed to position the control operator, not to support its weight. User must provide auxiliary support in the form of wall brackets, floor stands, turnbuckle hangers, etc., to support the weight and size of the operator. 6. Measure air pressure by connecting a manometer to the air pressure test connection which is located on the burner s main housing approximately 4 (12 mm) back from the burner mounting flange. 7. Measure gas pressure by connecting a manometer to the gas pressure test connection on the back plate of the burner. NOTE: Maxon offers a test connection kit which provides a convenient means of connecting plastic tubing to the burner test port connections. Kit should be removed after intial start-up and the test ports should be plugged for normal operations. 8. Open the MICRO-RATIO air valve slightly to provide enough air to support reliable light-off. 1/99 Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice. INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES mcorporation MUNCIE, INDIANA, USA

18 Page 28-S-8 Packaged & EBMRV CYCLOMAX Burners Start-up Instructions EBMRV Versions 9. Establish the maximum combustion air pressure by moving the air valve crank assembly toward the higher positions until the desired air pressure is reached. This occurs around 9 degrees, unless the burner and/or blower are greatly oversized. 1. Reconnect the fuel valve to the air valve. Having marked the minimum and maximum settings, adjust the linkage and travel of the stroke. Set the air and gas pressures throughout the entire range. 11. Re-check and verify that air handling devices are still operating. CAUTION: If flame is extinguished any time during steps 12 through 18, immediately shutoff gas and return MICRO-RATIO Valve to minimum position. Allow adequate purge time for safety reasons. Re-light the pilot (if necessary) and reopen gas valve and turn screw last adjusted in slightly further before returning to that firing position. Refine adjustment if necessary. 12. Light the pilot. With pilot gas solenoid (or manual cock) closed, open the main fuel supply valve(s). Energize spark ignitor and open pilot gas solenoid (or manual cock). Observe ignition of pilot. Pilot should be set at the minimum gas flow which will support reliable ignition. Adjust pilot using adjustable orifice and/or pilot gas regulator. 13. Shut off the spark ignition and pilot and confirm easy re-ignition several times. 14. With pilot gas on and spark ignition off, turn on the main gas. With the main gas flowing, verify that flame is visible all around the burner nozzle. If not, adjust the minimum adjusting screw of the MICRO-RATIO Valve until flame appears stable. Shut off pilot. 1. With the burner still set at minimum, adjust all other screws on the cam to form a smooth ramp. NOTE: A preliminary setting can be established with all the remaining adjusting screws. Generally, each succeeding screw needs to be screwed in approximately one full turn deeper than its preceding screw. A smooth stair-step gradient pre-set at this point from low to high will simplify the remaining adjustment steps. 16. Slowly move the MICRO-RATIO Valve to next position. Adjust as necessary to maintain ignition and the type of flame desired. Flame should be a steady blue color and should only fill approximately 2% of the can at lower firing rates. Observe the air pressure and adjust gas pressure to appropriate value shown in charts/graphs. 17. Repeat Step 16 with the remaining adjustment screws until high fire position is reached. If a flameout occurs, allow purge time and return to Step Adj. Screws (under cover) Handle for Manual Operation Position Indicator Pointer Locking Screw for manual operation 12 in the adjustment procedure. At each setting, use the adjustment screw to set the gas pressure to the appropriate value corresponding to air pressure reading. Refer to charts and graphs in this catalog section. 18. Cycle the burner to verify that pressures are within the recommended ranges. The position of each screw on the MICRO-RATIO Valve affects the adjacent screws. It can take two or three passes through the ranges to get the burner gas pressures set to the desired values with repeatability. When high fire position is reached with the MICRO-RATIO Valve, slowly move the valve to the position immediately below high fire, read the air pressure, observe the gas pressure, and adjust the appropriate screw if necessary. Move the valve down to the next setting and repeat this procedure with each of the remaining adjustment screws until minimum fire is reached. After the initial adjustment pass, adjust only the screw corresponding to the actual position of the MICRO-RATIO Valve and the NEXT adjacent screw to be adjusted (either up or down the ramp). If possible, do not adjust the previous screw. Two passes through the firing range is enough. Some sensitive applications may require three passes with adjustments to get the ramp smooth enough to produce repeatable gas pressures at each setting. mcorporation MUNCIE, INDIANA, USA INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.

19 Packaged & EBMRV CYCLOMAX Burners Page 28-S-9 Start-up Instructions EBMRV Versions CAUTION: If high temperature limit trips before adjustment is complete, cycle burner back to minimum and allow the system to cool down before attempting to make any further adjustment. 19. Observe the gas supply pressure during adjustment. As firing rate is increased, the gas supply pressure will drop off and could go below recommended levels. It may be necessary to adjust the regulator. If so, all positions on the screw carrier of the MICRO-RATIO Valve will need to be re-adjusted. Flame Appearance: While increasing the burner setting, continue to make adjustments to keep the flame stable. A flame that is too lean will be transparent and will lift away from the nozzle. A flame that is too rich will be yellow and will burn on the outside of the can. A rich flame looks lazy. It will be darker than a lean flame and appear purple in color. When adjusted properly, the flame will appear bright blue in color. At low oven temperatures, the can color should be visible as a slight glowing effect. At moderate to high oven temperatures, the can should appear as a uniform medium red in color. Generally, a too lean flame condition creates high CO and low NOx, and a too rich flame condition will create lower CO but higher NOx. The best reference for CO and NOx levels is the charts on pages 283 and 284. The optimum pressures can vary according to the characteristics of the natural gas used as well as furnace back pressure or suction conditions. 2. When all screws have been adjusted and initial repeatability is verified, re-check pressures with unit at operating temperature. Refine settings if outside of the recommended ranges shown on the graphs. 21. System should have an interrupted pilot. Verify that pilot is shut-off. Operation with the pilot on causes flame non-uniformity, significantly higher emissions and can shorten can life. 22. When burner performance is satisfactory, reconnect the linkage from the control motor to the MICRO-RATIO gas valve. 23. Check out overall system operation by cycling the burner, observing the air and gas pressures, re-igniting the burner, etc. Recheck all safety interlocks for proper setting and operation. After air and gas pressures have been verified and are within recommended ranges, shut the burner down, remove all fittings and tubing from the test connections and plug the test ports with pipe plugs. CAUTION: Test every UV installation for dangerous spark excitation from ignitors, other burners, and direct or reflected UV radiation. 24. Shut system down and close all fuel valves. Allow an approved post-purge period before shutting down all fans. Replace all equipment covers and caps and tighten all linkage set screws. 2. Instruct operating personnel on proper start-up, operation and shut-down of system. Establish written instructions for reference. NOTE: It is good practice to check the air and gas pressures regularly. If the gas supply to the MICRO-RATIO Valve changes significantly, the adjusting screws will need to be re-adjusted. If a filter is becoming plugged, a routine check of the air and gas pressures can uncover problems before they become serious. Poor burner performance will result if pressures are set incorrectly. 1/99 Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice. INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES mcorporation MUNCIE, INDIANA, USA

20 Page 28-S-1 Packaged & EBMRV CYCLOMAX Burners Notes mcorporation MUNCIE, INDIANA, USA INDUSTRIAL COMBUSTION EQUIPMENT AND VALVES Maxon practices a policy of continuous product improvement. It reserves the right to alter specifications without prior notice.

Burner Application Details Packaged Versions

Burner Application Details Packaged Versions Packaged & BMV CYCOMAX Burners Page 83 Packaged Versions CYCOMAX Burners were designed for low to moderate temperature oven-type applications only. They may be used in any oven whose combustion chamber

More information

Installation Instructions

Installation Instructions Page 5750-S-1 Installation Instructions General These mounting instructions for Circular INCINO- PAK Burners are in addition to the specific instructions offered for other Maxon component items: Shut-Off

More information

Installation Instructions

Installation Instructions PREMIX Blower Mixers Page 3100-S-1 Installation Instructions General Instructions Important: Do not discard packing materials until all loose items are accounted for. To prevent damage in transit, spark

More information

Installation and Maintenance Instructions

Installation and Maintenance Instructions RAMFIRE Burners Page 4300-S-1 Air Inlet Arrangement Installation and Maintenance Instructions RAMFIRE Burners are furnished in standard position illustrated at right. Since burner block is round, the entire

More information

Installation and Maintenance Instructions

Installation and Maintenance Instructions VORTIFLARE Radial Flame Burners Page 4400-S-1 Air Inlet Arrangement Installation and Maintenance Instructions VORTIFLARE Burners are furnished in standard position illustrated at right. Since burner block

More information

Installation and Maintenance Instructions

Installation and Maintenance Instructions KINEMAX Burners Page 4200-S-1 Air Inlet Arrangement Installation and Maintenance Instructions KINEMAX Burners are furnished in standard position illustrated at right. Since burner block is round, the entire

More information

Typical Piping Layouts for PREMIX Blower Mixer Systems

Typical Piping Layouts for PREMIX Blower Mixer Systems PREMIX Blower s Page 3103 Block & Bleed system is frequently required by insurance authorities. Typical Piping Layouts for PREMIX Blower Systems Maxon assumes no responsibility for the use or misuse of

More information

MAXON M-PAKT Ultra Low NOx Burners. Technical Catalog

MAXON M-PAKT Ultra Low NOx Burners. Technical Catalog MAXON M-PAKT Ultra Low NOx Burners Technical Catalog TABLE OF CONTENTS Product description... 1 Features and benefits... 1 Typical emissions... 1 Model Numbers... 2 Specifications of M-PAKT Burners...

More information

VENTITE Inspirator Mixers

VENTITE Inspirator Mixers Bulletin 30 VENTITE Inspirator Mixers Premix Burner Systems Use kinetic energy of higher gas pressures to provide air/gas mixture for all Maxon premix-type burner systems Uses most clean fuel gases 00-

More information

Design and Application Details MICRO-RATIO Valves

Design and Application Details MICRO-RATIO Valves Flow Control Valves Page 7003 Design and Application Details MICRO-RATIO Valves Principle of Operation MICRO-RATIO Valve assemblies typically consist of a fixed-gradient air butterfly valve mechanically

More information

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION

XDF BURNERS DUAL FUEL EXCESS AIR BURNER FEATURES DESCRIPTION EXCESS AIR OPERATION DUAL FUEL EXCESS AIR BURNER MODEL: 3610, 3651 Revision: 0 FEATURES Burns all fuel gases or light oils Nozzle mix design for on ratio control or excess air 350% excess air all sizes on gas or oil Turndown

More information

IPG IGNITION GAS PILOTS BACK-LOADED GAS

IPG IGNITION GAS PILOTS BACK-LOADED GAS INSTRUCTIONS IPG IGNITION GAS PILOTS BACK-LOADED GAS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components

More information

GM Series Dual-Block Multi-Function Gas Control Valves

GM Series Dual-Block Multi-Function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM Issue Date 0297 GM Series Dual-Block Multi-Function Gas Control Valves Figure 1: GM Series

More information

MAXON M-PAKT ULTRA LOW NOx BURNERS

MAXON M-PAKT ULTRA LOW NOx BURNERS ULTRA LOW NOx BURNERS TECHNICAL CATALOG 3M-0007-0 TABLE OF CONTENTS Product description... 3 Features and benefits... 3 Typical emissions... 3 Model Numbers... Specifications of M-PAKT Burners... Materials

More information

Installation Instructions

Installation Instructions LP and High Altitude LP Gas Conversion Kit For United States Installations Installation Instructions For Model Series *G6/PGF1 Furnaces, *L1/PGC1 Furnaces, and *R4/PPG1 Gas/Electric Appliances using Honeywell

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date August 19, 2008 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS 1NP0680 - PROPANE CONVERSION FOR USE WITH MODELS: PM8, PC8, PM9, PC9, FL9M, FL9C, FC9M, FC9C This conversion kit is to be installed by a qualified service agency

More information

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve

G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Installation Instructions Issue Date March 13, 2013 G196 Series BASOTROL Redundant Combination Gas Valve with Manual Shutoff Valve Application The G196 valves are suitable for use with natural gas, Liquefied

More information

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS

Installation Instructions WARNING: WARNING: WARNING: LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS LP AND HIGH ALTITUDE LP GAS CONVERSION KIT FOR UNITED STATES INSTALLATIONS Installation Instructions For Model Series *G7/*GC2 Furnaces and Appliances Using Honeywell Gas Valves. BEFORE THE CONVERSION

More information

installation instructions

installation instructions installation instructions GAS CONVERSION KIT PROPANE-TO-NATURAL P/N 315572-71201 4GAD 6GAD Cancels: IIK 4G-50-4 IIK 4G-50-5 7/15/91 NOTE: Read the entire instructions before starting the installation.

More information

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h

INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h INSTALLATION & MAINTENANCE MANUAL FOR RIVERSIDE HYDRONICS BG400 GAS BURNER 140,000 thru 1,400,000 Btu/h CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. RIVERSIDE HYDRONICS

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! INLET PRESS TAP WHITE-RODGERS 36E93-304 Delay-Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT ALPKT57- INSTALLATION INSTRUCTIONS PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements... Table of Contents INSTALLATION

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 80% AFUE Gas Furnace, BGS80 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information

ACCESSORY KIT INSTALLATION MANUAL

ACCESSORY KIT INSTALLATION MANUAL ACCESSORY KIT INSTALLATION MANUAL LP (PROPANE) CONVERSION KIT 1NP0366 FOR USE WITH MODELS: G8C & GF8 This conversion kit shall be installed by a qualified service agency in accordance with these instructions

More information

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF

SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED 36RB 36IRB VULCAN C36RB C36IRB WOLF SERVICE MANUAL SALAMANDER BROILERS RADIANT AND INFRARED VULCAN 36RB 36IRB WOLF C36RB C36IRB This Manual is prepared for the use of trained Vulcan Service Technicians and should not be used by those not

More information

G96 Series BASOTROL Dual Operator Valve

G96 Series BASOTROL Dual Operator Valve Installation Instructions 9. Issue Date February 22, 2013 G96 Series BASOTROL Dual Operator Valve Applications The G96 valves are combination, dual operator, automatic valves available with or without

More information

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E96-314 DSI, HSI & Proven Pilot Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL

More information

Natural Gas to L.P. Gas Conversion Kit

Natural Gas to L.P. Gas Conversion Kit Natural Gas to L.P. Gas Conversion Kit For Bosch 96% AFUE Gas Furnace, BGH96 Model Installation Instructions 3124627 2 Natural Gas to L.P. Gas Conversion Kit Installation Instructions Data subject to change

More information

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners

Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners BULLETIN MT2035-07/05 Modulating Valves for Atmospheric, Infrared, and Direct Fired Burners M/MR Series M411, M511, M611 M420, M520, M620, MR410, MR510, MR610 MR212D, MR212E, MR212G and MR212J (Flanged),

More information

Installation Instructions For Natural Gas Conversion

Installation Instructions For Natural Gas Conversion Installation Instructions For Natural Gas Conversion (Kit Part No. 1175405) This kit is designed to convert PGX4 and PX4 Two -Stage Gas units for use with Natural Gas. Table 1 Heating Value at Altitude

More information

G92 Series BASOTROL Automatic Pilot Gas Valve

G92 Series BASOTROL Automatic Pilot Gas Valve Installation Instructions Issue Date September 17, 2008 G92 Series BASOTROL Automatic Pilot Gas Valve Installation IMPORTANT: Only qualified personnel should install or service BASO Gas Products. These

More information

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS

36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS 36C/36D HSI, DSI Proven Pilot Gas Valves INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet)

Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) Natural Gas High-Altitude Conversion Kit For Installations in the United States (2,001 10,000 Feet) INSTALLATION INSTRUCTIONS For R7 Series Light Commercial Packaged Gas Electric Units IIMPORTANT: Please

More information

36H SERIES Combination Gas Valve

36H SERIES Combination Gas Valve FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION The 36H series combination gas valve is

More information

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302

SL G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 SL 40-399 G3 - Fuel Conversion to Propane (NG to LP) P-Kit 302 If converting from Propane to Natural Gas, order the Natural Gas Conversion Parts Kit (IBC Part # P-303) from your authorized IBC Distributor.

More information

SL G3. Warning

SL G3. Warning Important: If converting from Propane to Natural Gas - order the Natural Gas Conversion Parts Kit (IBC Part # P-307) from your authorized IBC Distributor. Use the Propane Gas conversion parts kit if the

More information

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage.

Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. Operating instructions GB VD Burners Incorrect installation, adjustment, or misuse of this burner could result severe personal injury, or substantial property damage. To the Equipment Owner: Please read

More information

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only

WARNING: Installation Instructions. Natural Gas High Altitude Conversion Kit United States Installations Only Natural Gas High Altitude Conversion Kit United States Installations Only Installation Instructions Light Commercial Packaged Gas Electric Units R7TQ Series 6, - 7 1/2, & 10 Ton (2,001 FT - 10,000 FT)

More information

ACCESSORY KIT INSTALLATION INSTRUCTIONS

ACCESSORY KIT INSTALLATION INSTRUCTIONS ACCESSORY KIT INSTALLATION INSTRUCTIONS PROPANE CONVERSION - INDUCED COMBUSTION FURNACES 1NP0501 FOR USE WITH 95% MODELS: TG9S, GG9S (130,000 BTU ONLY) FOR USE WITH 80% MODELS: TG(8,L)S, GG(8,L)S (130,000

More information

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS

36E DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WTE-RODGERS 36E54-214 DSI and HSI Two-Stage Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves

UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GM-20/25 GM-40/45 Issue Date 1298 UL Listed GM-20/25 and GM-40/45 Series Dual-block Multi-function

More information

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235)

INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) P/N 126905-01 Rev. B 11/2016 INSTALLATION INSTRUCTIONS MANUAL ON/OFF SAFETY VALVE/PILOT KIT MODEL GA9050A-1 (F0235) For All Single, Dual and Triple Burner Natural and Propane/LP Gas Logs P126905-01 For

More information

INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h

INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h INSTALLATION & MAINTENANCE MANUAL FOR PVI FIREPOWER BG600 GAS BURNER 1,200,000 thru 2,400,000 Btu/h CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a seasonal

More information

Propane Conversion Kit Instructions

Propane Conversion Kit Instructions 604 8 0/ US/CA For heating engineers Propane Conversion Kit Instructions Logano G4 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G4 X gas-fired boilers

More information

/2004 US/CA

/2004 US/CA 630 9765 0/004 US/CA For the contractor Propane Conversion Kit Instructions Sealed Combustion Gas Boiler Logano GA44 This kit and instructions are for converting the GA44 model boilers from Natural Gas

More information

Pressure Dump Valve Service Kit for Series 2300 Units

Pressure Dump Valve Service Kit for Series 2300 Units Instruction Sheet Pressure Dump Valve Service Kit for Series 00 Units. Overview The Nordson pressure dump valve is used to relieve hydraulic pressure instantly in Series 00 applicator tanks when the unit

More information

Installation Instructions

Installation Instructions 48011HW NATURAL GAS TO PROPANE CONVERSION KIT 58HDX, 359AAV, PG9YAB, PG9YAA Installation Instructions SAFETY REQUIREMENTS Installing and servicing heating equipment can be hazardous due to gas and electrical

More information

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves

GS-20/25 and GS-40/45 Series Single-block Multi-function Gas Control Valves Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin GS-20/25 GS-40/45 Issue Date 1298 GS-20/25 and GS-40/45 Series Single-block Multi-function Gas

More information

Float Operated Level Controllers

Float Operated Level Controllers CONTENTS Float Operated Level Controllers IM0015 Nov. 2014 PAGE Introduction 1 Scope 1 Description 1 Specification 1 Control Installation 2 INTRODUCTION Side Mount Back Mount Prior to installing, the instructions

More information

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual

Welker Sampler. Model GSS-1. Installation, Operation, and Maintenance Manual Installation, Operation, and Maintenance Manual Welker Sampler Model GSS-1 The information in this manual has been carefully checked for accuracy and is intended to be used as a guide to operations. Correct

More information

BBG BETA BURNER GAS SERIES

BBG BETA BURNER GAS SERIES BBG BETA BURNER GAS SERIES INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components by

More information

North American Orifice Metering System

North American Orifice Metering System Combustion North American Orifice Metering System 8697 and M8697 Metering Orifices accurately measure gas flows to industrial burners. They are compact, inexpensive, and can be installed in individual

More information

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM

FOR INSTALLING CO 2 BLENDER KIT (P/N IN BEER SYSTEM IMI CORNELIUS INC One Cornelius Place Anoka, MN 55303-623 Telephone (800) 238-3600 Facsimile (612) 22-326 INSTALLATION INSTRUCTIONS FOR INSTALLING CO 2 BLENDER KIT (P/N 111612000 IN BEER SYSTEM SECONDARY

More information

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator.

RHPS Series RD(H)F40 User Manual. Read the complete manual before installing and using the regulator. RHPS Series RD(H)F40 User Manual Read the complete manual before installing and using the regulator. 2 WARNING Before removing a regulator from the system for service, you must depressurize system purge

More information

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS

36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS INLET PRESS TAP WHITE-RODGERS 36E03 and 36E38 DSI and HSI Step Opening Combination Gas Valve INSTALLATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Operation Manual Piston Sensed Gas Pressure Regulators

Operation Manual Piston Sensed Gas Pressure Regulators 687 Technology Way Napa, CA 94558 Phone: (707) 259-0102 FAX: (707) 259-0117 www.aptech-online.com Operation Manual Piston Sensed Gas Pressure Regulators (Models KT9, KT10, Welded KT10, KT12) Table of Contents:

More information

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction.

The conversion of new certified central heating gas appliances must conform to directions outlined in this instruction. ACCESSORY KIT INSTALLATION INSTRUCTIONS HIGH ALTITUDE APPLICATION CONVERSION MID-EFFICIENCY SINGLE-STAGE INDUCED COMBUSTION FURNACES MODELS: P*HU/G8T-UH/L8T-UH/FL8 UPFLOW / HORIZONTAL P*DN/G8T-DN/L8T-DN

More information

Instructions for High Altitude Conversion

Instructions for High Altitude Conversion 6304 38 0/ US/CA For heating engineers Instructions for High Altitude Conversion Logano G334 X gas-fired boiler This conversion kit and the accompanying instructions are for conversion of G334 X gas-fired

More information

Model: 43T. Bermad Pressure Relief Valve

Model: 43T. Bermad Pressure Relief Valve Model: 43T Bermad Pressure Relief Valve Installation Operation Maintenance Manual () Rev.C1_01.08.17 Page 1 of 10 Safety First BERMAD believes that the safety of personnel working with and around our equipment

More information

Installation, Operation and Maintenance Manual for Back Pressure Regulator

Installation, Operation and Maintenance Manual for Back Pressure Regulator Installation, Operation and Maintenance Manual for Back Pressure Regulator Model 8860 2009 Groth Corporation IOM-8860 Rev. B 12541 Ref. ID: 95565 Page 2 of 13 Table of Contents I. INTRODUCTION 3 II. DESIGN

More information

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1

TECHNICAL DATA MAINTENANCE AIR COMPRESSOR MODEL G-1 Dry 131h 1. DESCRIPTION The Viking Model G-1 Maintenance Air Compressor is an electric motor-driven, aircooled, single-stage, oil-less compressor. The unit is equipped with a check valve and provides a

More information

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , &

Assembly Drawing: W-311B-A01, or as applicable Parts List: W-311B-A01-1, or as applicable Special Tools: , , & REDQ Regulators Model 411B Barstock Design Powreactor Dome Regulator OPERATION AND MAINTENANCE Contents Scope..............................1 Installation..........................1 General Description....................1

More information

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301

SL G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301 SL 26-260 G3 - Fuel Conversion to Natural Gas (LP to NG) P-Kit 301 Note If converting from Natural Gas to Propane, order the Natural Gas Conversion Parts Kit (IBC Part # P-300) from your authorized IBC

More information

SPECIFICATIONS ATTENTION

SPECIFICATIONS ATTENTION VPS 504 S06 Installation Manual - P/N 80122 - Ed. 01/09 VPS 504 S06 and S05 Valve Proving System Installation Instructions VPS 1 6 Gases Natural gas, air and other inert gases. NOT suitable for butane

More information

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5.

MUELLER. A Wall Type. Indicator Post. Reliable Connections. General Information 2. Technical Data/ Dimensions 3. Installation 4-5. Installation Instructions manual MUELLER table of contents PAGE A-20814 Wall Type General Information 2 Technical Data/ Dimensions Installation 4-5 Maintenance 6 Parts 7 Indicator Post! WARNING: 1. Read

More information

BBC BETA BURNERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel.

BBC BETA BURNERS. WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. INSTRUCTIONS BBC BETA BURNERS NOTE These instructions are intended for BBC burners firing gas or light oil. For heavy oil BBC applications using compressed air atomization, see.1 WARNING These instructions

More information

Installation Guide No. 111, 8/26/05. Winnox Burners. WX Series. Version 1.00

Installation Guide No. 111, 8/26/05. Winnox Burners. WX Series. Version 1.00 Installation Guide No. 111, 8/26/05 Winnox Burners WX Series Version 1.00 COPYRIGHT Copyright 2005 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation and

More information

Propane Conversion Kit Instruction

Propane Conversion Kit Instruction Propane Conversion Kit Instruction Condensing gas boiler Required Input Rates Logamax plus GB62-80 kw 270,000 btu/hr Logamax plus GB62-00 kw 35,000 btu/hr This kit and instructions are for converting the

More information

RD(H)20/25 Pressure-Reducing Regulator User Manual

RD(H)20/25 Pressure-Reducing Regulator User Manual RD(H)20/25 Pressure-Reducing Regulator User Manual Read the complete manual before installing and using the regulator. 2 Safe Product Selection When selecting a product, the total system design must be

More information

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual

Type S301 & S302 Gas Regulators INTRODUCTION INSTALLATION. Scope of Manual. Description. Specifications. Type S301 and S302. Instruction Manual Fisher Controls Instruction Manual Type S301 & S302 Gas Regulators October 1981 Form 5180 WARNING Fisher regulators must be installed, operated, and maintained in accordance with federal, state, and local

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 6C8-5 Combination Gas Control INSTALLATI INSTRUCTIS Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS

More information

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function Technical Instructions Document No. 155-752 SKP25 U.. Description Only when assembled to Series VG Gas valves SKP25

More information

FLOMIXERS SELECTION DATA ALL GASES

FLOMIXERS SELECTION DATA ALL GASES MODEL: 2301 Revision: 0 BULLETIN 2301-2311 FLOMIXERS are proportional mixing devices that utilize the energy of a stream of air at pressures up to several pounds to (1) entrain a combustible gas, and (2)

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS Type 36C04, 36C14 Step-Opening Combination Gas Control (24 Volt, 120 Volt & 750 mv Models) INSTALLATI INSTRUCTIS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW

More information

SZ, RZ & SRZ Series*

SZ, RZ & SRZ Series* SZ, RZ & SRZ Series* Instruction and Operation Manual FOR GAS ONLY SYSTEMS MANUFACTURED BY JOHN ZINK COMPANY, L.L.C. WARNING! BURNER MUST BE INSTALLED, MAINTAINED, AND OPERATED BY TRAINED PERSONNEL. DO

More information

BURNERS NOZZLE MIX SINGLE TUNNEL MULTIPLE TUNNEL

BURNERS NOZZLE MIX SINGLE TUNNEL MULTIPLE TUNNEL MODEL: 3501 - Single Tunnel 3506 - Multiple Tunnel Revision: 0 BULLETIN 3501 & 3506 8001 NM FEATURES High heat inputs - intense combustion Excellent flame stability Wide turndown range - greater than 10:1

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

BUTTERFLY VALVES Series 800

BUTTERFLY VALVES Series 800 BUTTERFLY VALVES Series 800 WARNING Before proceeding read ALL instructions and become familiar with the equipment and associated drawings. Follow ALL applicable safety regulations and codes for pressurized

More information

Installation Guide 111 2/26/2010. Eclipse Winnox Burners WX Series Version 2

Installation Guide 111 2/26/2010. Eclipse Winnox Burners WX Series Version 2 Installation Guide 111 2/26/2010 Eclipse Winnox Burners WX Series Version 2 Copyright Copyright 2005 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Propane Gas Conversion Kit WGCK-1 Instructions for 0-6,000 Feet Elevation Installations This propane gas conversion kit is to be used only when converting the following furnace

More information

RIX COMPRESSORS. MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230. November 21, 2002 APPLICABILITY [ A]

RIX COMPRESSORS. MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230. November 21, 2002 APPLICABILITY [ A] RIX COMPRESSORS MICROBOOST Owner s Manual CONFIGURATION A MB-115 MB-230 November 21, 2002 APPLICABILITY [ A] INTRODUCTION Safety This electromechanical equipment is designed to produce high pressure gas.

More information

Dual Solenoid Gas Valve Installation

Dual Solenoid Gas Valve Installation Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing FLYNN Gas Products. Carefully follow all instructions in this bulletin and all instructions

More information

BURNERS NOZZLE MIX SINGLE TUNNEL MULTIPLE TUNNEL

BURNERS NOZZLE MIX SINGLE TUNNEL MULTIPLE TUNNEL MODEL: 3501 Single Tunnel 3506 - Multiple Tunnel Revision: 0 BULLETIN 3501 & 3506 BURNERS NOZZLE MIX 8001 NM FEATURES APPLICATIONS High heat inputs - intense combustion Excellent flame stability Wide turndown

More information

Instruction Manual 742 5/1/2009. Eclipse Ratio Regulators ES Series Version 1

Instruction Manual 742 5/1/2009. Eclipse Ratio Regulators ES Series Version 1 Instruction Manual 742 5/1/2009 Eclipse Ratio Regulators ES Series Version 1 Copyright Copyright 1997 by Eclipse, Inc. All rights reserved worldwide. This publication is protected by federal regulation

More information

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves.

Discontinued. Powers Controls. Technical Instructions Document No P25 RV Rev. 1, May, RV 201 Pressure Reducing Valves. Powers Controls RV 201 Pressure Reducing Valves Description Features Product Numbers Dual Pressure PRV Technical Instructions Document No. 155-049P25 RV 201-1 Single Pressure PRV The RV 201 Pressure Reducing

More information

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1*

INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* INSTRUCTIONS FOR CONVERTING CONDENSING GAS MOBILE HOME FURNACES MODEL SERIES: CMA3*, CMC1*, VMA3*, VMC1* THIS KIT CONTAINS: AOPS7741 (NATURAL TO PROPANE CONVERSION PARTS FOR MODEL SIZE, 50) AOPS7742(NATURAL

More information

Thank You for Attending Today s Webinar. Today s Featured Speaker

Thank You for Attending Today s Webinar. Today s Featured Speaker Thank You for Attending Today s Webinar Your Host Mike DeLacluyse President Lesman Instrument Company miked@lesman.com Today s Featured Speaker A.J. Piskor Combustion & Controls Specialist Lesman Instrument

More information

KC Series Gas Components and Supply Design Guide

KC Series Gas Components and Supply Design Guide Technical Bulletin KC Series Gas Components and Supply Design Guide GF-1030 General AERCO KC Series gas fired potable water heaters and boilers are modulating input devices that require an adequate volume

More information

BGA158 Series CE Approved Class A Shutoff Gas Valve

BGA158 Series CE Approved Class A Shutoff Gas Valve Installation Instructions BGA158 Issue Date August 24, 2011 BGA158 Series CE Approved Class A Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated gas valve that

More information

Bermad Pressure Reducing. Model: 42T

Bermad Pressure Reducing. Model: 42T Bermad Pressure Reducing Pilot Operated Pressure Control Valve Model: 42T Installation Operation Maintenance Manual (IOM) REV. 27.7.17 Page 1 of 12 Safety First BERMAD believes that the safety of personnel

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL Series 4300 Engineered Performance TABLE OF CONTENTS 0 INTRODUCTION 1 1 Scope 1 2 Description 1 3 Specifications 1 0 INSTALLATION 1 1 Mounting 1 2 Piping 1 1 Connecting Process Pressure 2 2 Vent Connections

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 36C53 Combination Gas Valves (24 Volt Model) INSTALLATI INSTRUCTIS Electrical Rating: Voltage: 24 Volts, (30 Volts Max.), 60 Hz. Current Rating: 0.23 Amps Type of Gas Natural Gas Pressure

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS For Burner Kit replacement of 553010021 Burners in GUI, GDI & GNI Gas Furnaces Using Natural Gas Please read these instructions completely before attempting installation. SAFETY

More information

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205.

HUPF Series DESCRIPTION APPLICATION INSTRUCTION SHEET GAS PRESSURE REGULATOR WITH INCORPORATED FILTER EN1C-0003NL05 R1205. HUPF Series GAS PRESSURE REGULATOR WITH INCORPORATED FILTER INSTRUCTION SHEET DESCRIPTION Spring-loaded regulator with inlet pressure compensation and zero shut-off. The outlet pressure is kept constant

More information

GM-7000 Series CE Approved Gas Control Valve

GM-7000 Series CE Approved Gas Control Valve Installation Instructions GM-7000 Issue Date November 9, 2012 GM-7000 Series CE Approved Gas Control Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

MUELLER A A Non-Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3.

MUELLER A A Non-Adjustable. Vertical Indicator Posts. Reliable Connections. General Information 2. Technical Data 3. Installation Instructions manual MUELLER table of contents PAGE A-20808 General Information 2 Technical Data 3 Dimensions 4 A-20809 Non-Adjustable Installation 5-6 Parts 7 Maintenance 8 Vertical Indicator

More information

LRS(H)4 Pressure-Reducing Regulator User Manual

LRS(H)4 Pressure-Reducing Regulator User Manual LRS(H)4 Pressure-Reducing Regulator User Manual Read the complete manual before installing and using the regulator. 2 Safe Product Selection When selecting a product, the total system design must be considered

More information

BGA158 Series CE Approved Class B Shutoff Gas Valve

BGA158 Series CE Approved Class B Shutoff Gas Valve Installation Instructions BGA158 Issue Date March 22, 2016 BGA158 Series CE Approved Class B Shutoff Gas Valve Applications The BGA158 Series shutoff gas valve is an electrically operated shutoff valve

More information

Instruction Manual No. 742, 8/98

Instruction Manual No. 742, 8/98 Instruction Manual No. 742, 8/98 Eclipse Ratio Regulators ES Series COPYRIGHT Copyright I997 by Eclipse Combustion, Inc. All rights reserved worldwide. This publication is protected by federal regulation

More information