1 Operating life time Normal expeted servie life (expressed in the number of yles over the full adjustment range) is appr. 1 million for the pressure swith. This may be extended to 2.5 million yles max. if only a part of the adjustment range is used (about 20%). Operating Instrutions Single/Dual Metal Diaphragm Pressure Swithes Type D1S/D2S and D1X/D2X Swith sensor life may also be effeted negatively by: Media not ompatible with the wetted materials. Too high swith yling speed or more than 20 yles per minute. System yling pressure exeeding the top of the adjustable range. The proof pressure must never be exeeded, otherwise the swith may be damaged. Careful seletion of the pressur e range an have a positive effet on the servie life of the swith. 1 Intended Appliations Safety Instrutions... 2 Standards... 4 Warranty/Guaranty... 5 Installation/Commissioning Maintenane/Cleaning Tehnial Data... 9 Barksdale GmbH Dorn-Assenheimer Straße 27 D-6120 Reihelsheim Phone: +49 (605) Fax: +49 (605) and info@barksdale.de Internet: Art. no.: Index N, Speifiations are subjet to hanges without notie! 12 1
2 1 Intended Appliations The pressure swithes are speifially applied for monitoring and ontrolling of operations using maximum and minimum pressures. A miro swith triggers an eletrial signal when minimum or maximum pressure are reahed. DANGER The swith may only be used in the speified fields of appliation (see type label). The temperature has to be within the speified ranges, the pressure values and the eletrial rating must not exeed the values speified. Observe also the appliable national safety instrutions for assembly, ommissioning and operation of the swith. The swith is not designed to be used as the only safety relevant element in pressurized systems aording to DGR 97/2/EC. Without speial provisions/ations, pressure swithes must not be used for ombustable gas or pure hydrogen appliations. 2 Safety Instrutions The safety instrutions are intended to protet the user from dangerous situations and/or material damage. In the operating instrutions the seriousness of the potential risk is designated by the following signal words: DANGER Refers to imminent danger to men. Nonobservane may result in fatal injuries. Refers to important information essential to the user. Standards Disposal The equipment must be disposed of orretly in aordane with the loal regulations for eletri/eletroni equipment. The equipment must not be disposed of with the household garbage! The standards applied during development, manufature and onfiguration are listed in the CE onformity and manufaturer's delaration. 4 Warranty/Guaranty Warranty Our sope of delivery and servies is governed by the legal warranties and warranty periods. Terms of guaranty We guaranty for funtion and material of the single- / dual- pressure swith under normal operating and maintenane onditions in aordane with the statutory provisions. Loss of guaranty The agreed guaranty period will expire in ase of: hanges or modifiations to the swith/housing/fitting inorret use, inorret installation or inorret handling or operation ontrary to the provisions of these operating instrutions. No liability is assumed for any damage resulting therefrom, or any onsequential damage. Refers to a reognizable danger. Nonobservane may result in fatal injuries, and destroy the equipment or plant parts. CAUTION Refers to a danger. Nonobservane may result in light injuries and material damage to the equipment and/or to the plant. 2
3 5 Installation/Commissioning DANGER Only install or uninstall the swith when deenergized (eletrially and hydraulially/pneumatially). Pressure onnetion and eletrial onnetion must be arried out by trained or instruted personnel aording to state-of-the-art standards. The swith must only be installed in systems where the maximum pressure P max is not exeeded (see type label). CAUTION Contat Protetion The miro swithes used are normally suitable for both diret and alternating urrent operation. Indutive, apaitive and lamp loads may, however, onsiderably redue the life expetany of a miro swith and, under extreme irumstanes, even damage the ontats. Depending on the appliation spark suppression and urrent limiting is reommended (see sueeding figures). R1 C able R2 R R R Alternating pressure - vauum appliations are not authorized in swith types whih are suitable for both vauum and pressure appliations. Pressure peaks and pressure shoks exeeding the maximum operating pressure are inadmissible. The maximum operating pressure is the upper final value of the adjustable range or, if speified, the pressure indiated as maximum operating pressure. Exeeding the max. operating pressure affets the performane and the life span of the produt and may damage it. Pressure swithes must be mounted vibrationless. Chek the swith regularly for funtioning. If the swith does not work properly, stop operation immediately! All pressure swithes are tested for proper funtioning before they leave the fatory. The fatory proof pressures are stated on the type label. Fig. 1: Protetion in ase of apaitive loads R1: Protetion against starting urrent rushes R2,R: Protetion against high disharge urrents U = Diode Fig. : Protetion in ase of ontinuous urrent and indutive load by reovery diode Fig. 2: Lamp load provided with resistane in parallel or series onnetion to swith of ondensators U R Fig. 4: Protetion in ase of alternating urrent and indutive load by RC-link 4 5
4 Set point adjustment Fatory-Provided: pressure (temperature) swith point setting We onfirm for pressure (temperature) swithes that have been fatory set the setting will be detailed on the label name plate. Warranty is not appliable for any hanges that may our due to transportation or installation. For ritial appliations we reommend the setting is heked and re-set if eessary after installation and wirding of the pressure (temperature) swith. In pressure swithes, a displaement of the pressure sensing element ours with a hange in pressure. Following the displaement of the pressure sensing element operates a miroswith. Upon delivery of the produt, the set points are likely to be found in the middle of the adjustable range. On request, fix set points may be adjusted by our fatory. In this event, the point will be indiated on the type plate or any separate plate, i = inreasing, d = dereasing. The set point is adjusted by turning the adjustment srew. To reah the adjustment srew for pressure swithes with housing, remove the over (see Fig. 8). Preise adjustment of set point to atuate on inreasing pressure Lower system pressure to 0 bar. Inrease pressure slowly and hek if miro swith is atuated at desired swith pressure. If neessary, readjust by turning the adjustment srew Repeat preeding steps until miroswith operates at desired swith pressure. Preise adjustment of set point to atuate on dereasing pressure Inrease pressure up to a point learly above the desired swith pressure (at least, swith pressure plus max. hysteresis; not above max. operating pressure). Lower pressure slowly and hek if miro swith is atuated at desired swith pressure. If neessary, readjust by turning the adjustment srew Repeat preeding steps until miroswith operates at desired swith pressure. Following the adjustment of all set points, eah set point must be heked and, if neessary, be readjusted. The adjustment of several set points ours for eah set point as speified above. Wiring Code for all Types (Contat status at atm. pressure) Allow pressure swith to reah the desired swith pressure. Turn adjustment srew lokwise or ounterlokwise to atuate the miro swith. NC NO Power iruit C = purple Power iruit C = brown In ase of overpressure: + In ase of vauum: + Counterlokwise rotation: Clokwise rotation: Counterlokwise rotation: Clokwise rotation: set point inreasing set point dereasing set point dereasing set point inreasing NC NO at vauum NC/NO vie versa Fig. 5: Wiring Code NC = blue NO = red NC = orange NO = blak Please onsult the wiring diagram for the ontat status at atmospheri pressure (see Fig. 5). Partiularly important for small pressures! Set point adjustment must be performed in installation position. 6 7
5 Use in Hazardous Loations The pressure swith type D1X/D2X is designed and approved for the protetion lass "intrinsi safety i" and "explosion-proof enlosure d". The pressure swith type D1S/D2S has none of the approvals stated above. The intrinsially safe swithes marked as Ex ia must be operated with a ertified swith amplifier (see Fig. 6). DX swithes with explosion proof enlosures are designed and ertified to be used aording to UL, CSA and ATEX regulations. Design onditions, approval data and instrutions must be observed arefully. The wiring between swith and Ex i isolation amplifier must meet the loal safety requirements. The ustomer must provide for a highly ondutive onnetion between swith and grounding. With option Ex i: The models having light-alloy (aluminium) enlosures or enlosure parts must be proteted against all impat or frition whih an ignite the explosive atmosphere. Unproteted area Ex ia area 7 Tehnial Data See data sheet Dimensions in mm (inh) (1.89) approx. 7 leads about 450 (17.72) long Proess onnetion approx. 55 Mounting bore 5 (0.197) 29 (1.14) 58 (2.28) D1S 45 (1.77) 90 (.54) 45 (1.77) 90 (.54) D2S 90 (.54) (0.9) (0.9) 45 (1.77) Slotted hex 45 (1.77) adjustment srew size 8 Ciruit * Ciruit * 90 (.54) NO 28 (1.1) approx (0.24) * Slotted hex adjustment srew size 8 NC GRD Fig. 7: Metal diaphragm pressure swith type D1S.../D2S... Zener barrier type Swith amplifier NAMUR Fig. 6: Operation of pressure swithes in intrinsially safe areas 6 Maintenane/Cleaning Maintenane The pressure swith is maintenane free. Cheking the set points lies within the disretion of the user. The usual preventive maintenane work in aordane with the PED and ATEX guidelines must always be arried out. Small setpoint drifts may our during the initial use of the swith (run-in period). To minimize the setpoint drift we an perform a run-in (ageing) proess in our works on request. Larger or ontinuing setpoints drifts during the normal use of the swith may indiate that the measuring system is not used orretly within the speified limits, exeeding the design riteria or is worn-out. This might lead to metal fatigue of the measuring system and it therefore should be replaed before an ultimate rupture of the metal diaphragm might take plae. Please onsult your supplier or Barksdale diretly for guidelines 8 9
6 D1X D2X Adjustable ranges Terminal lip 45 Ground onnetion 51 (2.01) 77 (.0) 2 (0.906) Conduit onnetion ½NPT 166 (6.55) 11 (0.4) Ciruit * Conduit onnetion ¾NPT 67 (2.64) 2 (0.906) 166 (6.55) Ciruit * 11.5 (0.41) (0.4) Pressure range ode Adjustable range Inreasing pressure Dereasing pressure Max. operating pressure Proof pressure (short term) Max. hysteresis of swith types (end of range) H, GH M, GM 197 (7.756) 120 (4.724) 51 (2.01) 21 (0.827) 21 (0.827) Proess onnetion ø8 (1.496) ¼" NPT Proess onnetion ¼" NPT Conduit onnetion ½NPT * Slotted hex adjustment srew size 8 Fig. 8: Metal diaphragm differential pressure swith type D1X.../D2X... Approval data for Ex i swithes (D1X/D2X) Approval: II 1 GD Ex ia IIC T6 Ga Ex ia IIIC T0 C Da Certifiate no.: ISSeP08ATEX016X/1 Permissible ambient temperature: -40 C +75 C Eletrial data for intrinsially safe appliation: Ui = 28V Ci = 40 pf Ii = 50 ma Li = 4 µh Standards applied: IEC : 2011, IEC : 2011, IEC : 2006 Approval data for Ex d swithes (D1X/D2X) Approval: 71 (2.795) Adjustment srew* II 2 G II 2 D Certifiate no.: ISSeP08ATEX024X/ Permissible ambient -40 C +75 C temperature: Ex db IIC T6 Gb Ex tb IIIC T80 C Db IP66 Standards applied: IEC : A11:201 IEC :2014 IEC : (0.4) ø125 (4.92) 11 (0.4) ø125 (4.92) Proess onnetion ¼" NPT Conduit onnetion ½" NPT Overpressure Vauum 2SS SS SS SS SS SS SS Eletrial Ratings Miro swith H M GH Speial Charateristis Miroswith with silver ontats Miroswith with silver ontats Miroswith with gold plated ontats for low voltage and low urrent Volt AC 50/60 Hz Ind. A Res. A Volt DC 6 to Ind. A Res. A Notes 0,50 0,5 Small hysteresis; high AC / low DC loads 5,00 1,00 0,25 15,0 2,0 0,4 Medium hysteresis; high AC and DC loads ,00 1,00 low hange-bak values GM , 0, Medium hysteresis We reommend to use a prefuse of the maximum urrent rating from the table above aording to the load swithed. We reommend gold plated ontats for all intrinsially safe and other appliations with low voltage/power. 11
Operating Instructions Single/Dual Bourdon Tube Pressure Switches Type BS/BT/BX
pproval data for Ex i swithes (BT and BX) pproval: II 1 G D Ex ia IIC T6 Ex ia D 20 T0 Operating Instrutions Single/Dual Bourdon Tube Pressure Swithes Type BS/BT/BX Certifiate no.: ISSeP08TEX016X Permissible
More informationBKR: 3-way ball valve with female thread, PN 40
Regulating valves, ombined with atuator CV5.60 en Produt Data Sheet BKR015...050 BKR: 3-way ball valve with female thread, PN 40 ow energy effiieny is improved Preision ontrol and working without losses
More informationBKR: 3-way ball valve with female thread, PN 40
Regulating valves, ombined with atuator PDS 56.091 en Produt Data Sheet BKR015...050 BKR: 3-way ball valve with female thread, PN 40 ow energy effiieny is improved Preision ontrol and working without losses
More informationBKTA: 3-way change-over ball valve (T) with male thread, PN 40
BKTA: 3-way hange-over ball valve (T) with male thread, PN 40 ow energy effiieny is improved Effiieny means preise hangeover with minimum leakage Features 3-way hange-over ball valve with T-bore for use
More informationBUL: 3-way unit valve, PN 16
Produt data sheet 55.009 BU: 3-way unit valve, PN 16 Improving energy effiieny inear mixture and no loss through leakage in the ontrol passage for energy-effiient regulation Features Flat-sealing standard
More information55.109/1. BUT: Three-way unit valve, PN 16. Sauter Components
55.109/1 UT: Three-way unit valve, PN 16 How energy effiieny is improved Linear mixture and no leak losses in the ontrol passage for energy-effiient regulators. reas of appliation Regulating valve for
More informationBKR: 3-way regulating ball valve with female thread, PN 40
Produt data sheet 5.1 56.091 BKR: 3-way regulating ball valve with female thread, PN 40 ow energy effiieny is improved Effiieny means preise ontrol and working with minimum leakage Features 3-way regulating
More informationVKR: 2-way regulating ball valve with female thread, PN 40
Produt data sheet 7.1 56.090 VKR: 2-way regulating ball valve with female thread, PN 40 ow energy effiieny is improved Effiieny means preise ontrol and working with minimum leakage Features 2-way regulating
More informationM-5071/1111. Electronic Pressure Switch PSW14 series
M-507/ Electronic Pressure Switch PSW4 series S TABLE OF CONTENTS Electronic Pressure Switch PSW4 Series Intended Applications... Safety Instructions... 3 Standards... 4 Warranty/Guaranty... 5 Installation/Commissioning...
More informationSauter Components
55.009/1 U: Unit threeway valve, PN 1 How energy effiieny is improved inear mixing and no losses through leakage for energyeffiient ontrol. reas of appliation Control valve for ontrolling heating zones,
More informationINSTRUCTION HANDBOOK OM2
INSTRUCTION HANDBOOK OM2 Pakaging mahine for sanitary napkins Mahine-No.: 2622668.11.01 Year of onstrution: 2007 Version 1 dated 2007-12-03 Keep for further referene! Manufaturer addresses / Customer servie
More informationVaccine Storage and Handling Guidelines
Vaine Storage and Handling Guidelines Table of Contents 2 Introdution 3 Definitions 3 The Importane of the Cold Chain 3 Proteting Ontario s Vaine Supply 4 Maintaining Vaine Poteny and Minimizing Wastage
More informationInductive slot sensor
0102 Model Number Features 3.5 mm slot width Usable up to SIL 3 acc. to IEC 61508 Nonferrous targets Application Danger! In safety-related applications the sensor must be operated with a qualified fail
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 1.5 mm
0102 Model Number Features 1.5 mm flush Accessories BF 8 Mounting flange, 8 mm Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 1.5 mm Installation flush
More informationTechnical Data. Dimensions
0102 Model Number Features 10 mm flush Shielded PUR cable for oil and gas sector Accessories BF 30 Mounting flange, 30 mm Technical Data specifications Switching function Normally closed (NC) Output type
More informationTechnical Data. Dimensions
00 Model Number Features Comfort series 30 mm non-flush Accessories MHW 0 Modular mounting bracket V-G Female connector, M, 4-pin, field attachable V-W-N-M-PUR Female cordset, M, -pin, NAMUR, PUR cable
More information76.111/1. BUD: Flanged three-way valves, PN 6. Sauter Components
76.111/1 BUD: Flanged three-way valves, PN 6 ow energy effiieny is improved urate ontrol with high reliability. reas of appliation Continuous ontrol of old/hot water and air in losed networks 1) and flow
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 65 GW2 40 35 9 5 GW1 14 11 9 5.4 M20 x 1.5 0102 Model Number S M12 x 1.5 Features 77.5 LED V Direct mounting on standard actuators Compact and stable housing with terminal compartment connection
More informationTechnical Data. General specifications. Rated operating distance s n 5 mm
0102 Model Number Features 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-18 Quick mounting bracket with dead stop BF 18 Mounting flange, 18 mm Technical Data specifications Switching
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 2 mm
0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories EXG-12 Quick mounting bracket with dead stop BF 12 Mounting flange, 12 mm Technical Data specifications Switching
More informationTechnical Data. Dimensions
00 Model Number Features mm flush Usable up to SIL acc. to IEC 6508 Accessories V-G Female connector, M, -pin, field attachable V-W Female connector, M, -pin, field attachable V-G-N-M-PUR Female cordset,
More informationGeneral Technical Data and Calculations
18 Bosh Rexroth AG R31EN 232 (26.4) General Produt Desription General Tehnial Data and Calulations Fores and load moments In Rexroth the running traks are arranged at a ompression angle of 45. This results
More informationTechnical Data. General specifications. Rated operating distance s n 2 mm
0102 Model Number Features 2 mm flush Usable up to SIL 2 acc. to IEC 61508 Technical Data specifications Switching function Normally closed (NC) Output type NAMUR Rated operating distance s n 2 mm Installation
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 5 mm
00 Model Number Features 5 mm flush Usable up to SIL acc. to IEC 6508 Accessories V-G Female connector, M, -pin, field attachable V-W Female connector, M, -pin, field attachable V-G-N-M-PUR Female cordset,
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 15 mm non-flush Stainless steel housing Accessories BF 30 Mounting flange, 30 mm Technical Data specifications Switching element function NAMUR, NC Rated operating
More informationDimensions. Technical Data General specifications Switching element function Rated operating distance s n 10 mm
Dimensions M30x1,5 5 40 37 0102 Model Number 36 LED Features Comfort series 10 mm embeddable Connection BN BU Accessories BF 30 Mounting flange, 30 mm L+ L- Technical Data specifications Switching element
More informationGAS PRESSURE REGULATOR RMG 512
SERVING THE GAS INDUSTRY WORLDWIDE General Desription GAS PRESSURE REGULATOR RMG 512 RMG REGEL + MESSTECHNIK GMBH Appliation, Features, Tehnial data Appliation for offtake stations in gas transmission
More informationTechnical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection
0102 Model Number Features Direct mounting on standard actuators Compact and stable housing Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up to SIL2 acc. to IEC 61508 Accessories
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable
More informationDimensions. Technical Data General specifications Switching element function Rated operating distance s n 5 mm
Dimensions M18x1 37 40 4 0102 24 LED Model Number Features 5 mm embeddable Usable up to SIL2 acc. to IEC 61508 Connection BN BU Accessories L+ L- EXG-18 Quick mounting bracket with dead stop BF 18 Mounting
More informationTechnical Data. Dimensions
0102 Model Number Features 6 mm flush Usable up to SIL 3 acc. to IEC 61508 Application Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs,
More informationTechnical Data. Dimensions
0102 Model Number Features Comfort series 5 mm flush Usable up to SIL 2 acc. to IEC 61508 Accessories BF 18 Mounting flange, 18 mm EXG-18 Quick mounting bracket with dead stop Technical Data specifications
More informationTechnical Data. Dimensions
0102 Model Number Features 2 mm flush Usable up to SIL2 acc. to IEC 61508 Technical Data specifications Switching element function NAMUR, NC Rated operating distance s n 2 mm Installation flush Output
More informationRESPIRATORY PROTECTIVE EQUIPMENT
RESPIRATORY PROTECTIVE EQUIPMENT SETTING Correspondene to: Dr R M Howie, 12 Morningside Close, Edinburgh EH10 4DB, UK; robin.howie@ btlik.om T RMHowie Oup Environ Med 2005; 62:423 428. doi: 10.1136/oem.2002.004424
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 7 36 5 33.5 9 5.4 30 65 0102 Model Number Features Direct mounting on standard actuators Fixed setting Satisfies machinery directive Compact and stable housing EC-Type Examination Certificate
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 17.
The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 17. Please refer to the publiation in its entirety for omplete details on this produt inluding
More informationCompact differential pressure switch Flameproof enclosure Ex d Models DE, DEC
Mechatronic pressure measurement Compact differential pressure switch Flameproof enclosure Ex d Models DE, DEC WIKA data sheet PV 35.41 Process Compact Series Applications Differential pressure monitoring
More informationmanual h/p/cosmos discovery 4.0 Instruction- & Service manual Manufacturer h/p/cosmos sports & medical gmbh h/p/cosmos discovery 4.
manual h/p/osmos disovery 4.0 Instrution- & Servie manual Manufaturer h/p/osmos disovery 4.0 h/p/osmos sports & medial gmbh Firmware version 3.01.3 Am Sportplatz 8 DE 83365 ussdorf-traunstein Germany phone
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 65 9 5 14 40 35 11 9 5.4 M20 x 1.5 0102 S Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting Satisfies
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.
The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 16. Please refer to the publiation in its entirety for omplete details on this produt inluding
More informationThe following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.1.
The following exerpt are pages from the North Amerian Produt Tehnial Guide, Volume 2: Anhor Fastening, Edition 16.1. Please refer to the publiation in its entirety for omplete details on this produt inluding
More informationEMPLOYER SAMPLE PROCEDURES FOR HEAT ILLNESS PREVENTION
EMPLOYER SAMPLE PROCEDURES FOR HEAT ILLNESS PREVENTION FEB 2010 California Employers with any outdoor plaes of employment must omply with the Heat Illness Prevention Standard T8 CCR 3395. These proedures
More informationDimensions. Technical Data General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm
Dimensions 65 9 5 40 35 14 11 9 5.4 M20 x 1.5 0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting Satisfies machinery
More informationPressure Switches Application Guideline
Pressure Switches Application Guideline Product Overview The Fema Pressure Switch product portfolio provides devices suitable for many applications. The portfolio contains Special functions and equipment
More informationAnalysis of a Twin Screw Expander for ORC Systems using Computational Fluid Dynamics with a Real Gas Model
Purdue University Purdue e-pubs International Compressor Engineering Conferene Shool of Mehanial Engineering 2014 Analysis of a Twin Srew Expander for ORC Systems using Computational Fluid Dynamis with
More informationLMP 307. Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % / 0.
LMP 07 Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 % / 0. % FSO Nominal pressure from 0... mho up to 0... 50 mho Output signals -wire: 4... 0 ma -wire: 0...
More informationRTA Series 1 4 Poles Coded Rotary Switches
1 4 Poles oded Switches Features/Benefits PB or hand soldering versions Bushing mounting Multiple poles Decimal and hexadecimal codes Screwdriver slot or extended actuator RoHS ompliant Typical Applications
More information1 Overview. Pressure Measurement Transmitters for basic requirements. 1/16 Siemens FI SITRANS P220 for gauge pressure
Siemens AG 204 Overview The pressure transmitter SITRANS P220 measures the gauge pressure of liquids, gases and vapors. Stainless steel measuring cell, fully welded Measuring ranges 2.5 to 600 bar (36.3
More informationSITRANS P measuring instruments for pressure
SITRANS P measuring instruments for pressure Z series for gage pressure Siemens AG 008 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and
More informationRTA Series 1 4 Poles Coded Rotary Switches
1 4 Poles oded Switches Features/Benefits PB or hand soldering versions Bushing mounting Multiple poles Decimal and hexadecimal codes Screwdriver slot or extended actuator RoHS ompliant Typical Applications
More informationPressure switch, Differential pressure switch and Thermostat RT-E
Data sheet Pressure switch, Differential pressure switch and Thermostat RT-E The RT-E series consist of pressure and differential pressure switches as well as thermostats. The units are designed for industrial
More informationPressure control, differental pressure control and thermostat Type RT
MAKING MODERN LIVING POSSIBLE Technical brochure Pressure control, differental pressure control and thermostat Type RT Hydrocarbons www.danfoss.com/hydrocarbons Contents Page Introduction...3 Approvals...3
More informationInstallation Instructions
Low -Ambient Pressure Switch 0201R22 0301410 Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY ONSIDERATIONS Improper installation, adjustment,
More informationHigh-performance submersible pressure transmitter For level measurement Model LH-20
Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater
More informationITS 300 & 500 SERIES POSITION MONITORING INSTALLATION AND OPERATION MANUAL
ITS 300 & 500 SERIES POSITION MONITORING ITS 300 & 500 SERIES POSITION MONITORING INSTALLATION AND OPERATION MANUAL (Explosion proof Ex d II T6) (Doc no: ITS00312-M) 74-6, hun Ui-Dong, Won Mi-Gu, Bucheon
More information1 Overview. Pressure Measurement Single-range transmitters for general applications. 1/16 Siemens FI US Edition
Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.
More informationPneumatic pressure switch 20DD
Sensor system: stainless steel 0,2 to 6 bar Microswitch with gold plated contacts (suitable for intrinsically safe operation) High accuracy (max. scattering < 1,5%) Excellent sealing properties (better
More informationPressure switch KP-E. Data sheet
Data sheet Pressure switch KP-E KP-E pressure switches for use in refrigeration and air conditioning systems are equipped with SPDT gold plated contacts and stainless steel bellows. The high pressure switches
More informationQPL... Pressure Switches. Siemens Building Technologies HVAC Products
7 221 Pressure Switches QPL... The pressure switches are used for monitoring gas or air pressures. When the pressure falls below the switching point, the associated electrical circuit will open or switch
More informationPilot HON 625. Entwurf. Product information. serving the gas industry worldwide
Pilot HON 62 Entwurf Product information serving the gas industry worldwide Pilot HON 62 Application, characteristics Application Pilot for the gas pressure regulator HON 02 Pilot for outlet pressure control
More informationElectropneumatic Positioner and Pneumatic Positioner Type 3760 JIS
Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. An electric standardized signal of 4 to 20 ma or
More informationRoboGolf (aka RoboPutting) Robofest 2016 Game
RooGolf (aka RooPutting) Roofest 201 Game 12-2-2015 V1.1 (Kik-off version. Offiial Version will e availale on Jan 8, 201) 4 3 2 1 a A. Game Synopsis Figure 1. RooGolf Playing Field (Jr. Division) There
More informationPressure Switch for gas and air GGAO-A4
Pressure Switch for gas and air GGAO-A4 CSA Certified CSA C22.2 No. LR 53222 Certification file # 201527 Commonwealth of Massachusetts Approved Product Approval code G3-0106-191 Gas pressure switch Codes
More informationHigh-performance submersible pressure transmitter For level measurement Model LH-20
Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater
More informationRules of Hockey5s including explanations
Rules of Hokey5s inluding explanations Effetive from 1 January 2015 (updated 18 May 2015) Copyright FIH 2015 The International Hokey Federation Rue du Valentin 61 CH 1004, Lausanne Switzerland Telephone:
More informationOSAT Series. Intrinsically Safe Infrared Temperature Sensor Operator's Guide
OSAT Series Intrinsically Safe Infrared Temperature Sensor Operator's Guide Issue L Jan 2017 Introduction OSAT Series intrinsically safe non-contact infrared temperature sensors measure the temperature
More informationPressure Measurement. Transmitters for basic requirements SITRANS P Z for gauge pressure. 2/4 Siemens FI Overview
f gauge pressure Siemens AG 010 Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection
More informationEXHIBITOR MANUAL. Organiser
EXHIBITOR MANUAL 2018 Organiser ABOUT THE EXHIBITION Exhibition Name : 22nd EAST MEDITERRANEAN INTERNATIONAL TOURISM & TRAVEL EXHIBITION - EMITT Exhibition Conept : International Tourism and Travel Exhibition
More informationTechnical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection
0102 Model Number Features Direct mounting on standard actuators Compact and stable housing with terminal compartment connection Fixed setting EC-Type Examination Certificate TÜV99 ATEX 1479X Usable up
More informationIKGAtl Kenneth Grubb Associates Ltd
IKGAtl Kenneth Grubb Assoiates Ltd BURO HAPPOLD COPPERHOUSE SLUICE GATE DOCUMENT REVISION RECORD Doument Number: Number of Pages: Doument Title: Saved as: C0395/006/DOC 31 REPORT ON THE MECHANICAL SURVEY
More informationMonitoring device NTS 30
P R O D U C T I N F O R M A T I O N Electronic level- and temperature monitoring device Monitoring device NTS 30 Contents Description Description... 2 Operating... 3 Design and electrical data... 4 Circuit
More informationOwners Manual Models 4430BF3, 4430BF2 & 4430BF1 Floor Mounted Tri-Level Bottle Filling Tubular Fountain
Owners Manual Models 4430F3, 4430F2 & 4430F1 Floor Mounted Tri-Level ottle Filling Tubular Fountain MODEL 4430F1L MODEL 4430F2UM INSTALLER 4430F Fountains are among the easiest to install Fountains on
More information2 Overview. SITRANS P measuring instruments for pressure. Transmitters for gage and absolute pressure. Z series for gage pressure
Z series for gage pressure Overview Design The main components of the pressure transmitter are: Brass housing with silicon measuring cell and electronics plate Process connection Electrical connection
More informationSITRANS. Pressure transmitter SITRANS P, Z series for gauge and absolute pressure. Introduction. Safety instructions 2.
Introduction 1 Safety instructions 2 SITRANS Pressure transmitter SITRANS P, Z series for gauge and absolute pressure 7MF1564 Description 3 Assembly and connection 4 Technical data 5 Dimensional drawings
More informationGas Pressure Regulator HON 502
Gas Pressure Regulator HON 502 Product information serving the gas industry worldwide Gas Pressure regulator HON 502 Application, Characteristics, Technical Data Application for offtake stations in gas
More informationElectropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765
Electropneumatic Positioner Type 4763 Pneumatic Positioner Type 4765 Application Single-acting positioner for attachment to pneumatic control valves. Supplied with either an electric input signal from
More informationPressure Measurement Single-range transmitters for general applications
Siemens AG 206 Overview Design Device structure without explosion protection The pressure transmitter consists of a piezoresistive measuring cell with a diaphragm installed in a stainless steel enclosure.
More informationExplosion proof pressure switch Model: P953 series
Explosion proof pressure switch Model: P953 series Spec. sheet no. PD09-08 Service intended P953 diaphragm type differential pressure switch can be used in a variety of process lines. Internal micro switch
More informationHigh-performance submersible pressure transmitter For level measurement Model LH-20
Electronic pressure measurement High-performance submersible pressure transmitter For level measurement Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements Groundwater
More informationMechanical pressure switches
18 Technical features / Advantages Diecast aluminium housing IP 54 or IP 65 version also available Wall mounting or directly on the pressure line Switching element (microswitch) Lead sealable setpoint
More informationPressure Switches. Assembly and Operating Instructions. Important safety information!
Assembly and Operating Instructions Pressure Switches Basic models Additional functions DCM... -203-574 DNM... -205-575 DNS... -206-576 VCM..., VNM... -307-577 VNS... -213-513 DDCM... -217...-563 Ex-...
More informationInstruction Manual Differential Pressure Transmitter
DE61 Instruction Manual Differential Pressure Transmitter Table of Contents 1. Safety Instructions 2. Intended Applications 3. Product Description and Functions 4. Installation 5. Commissioning 6. Maintenance
More informationGeneral Specifications
General Speifiations Model GC8000 Proess Gas Chromatograph GS 11B08A01-01E GENERAL A Proess Gas Chromatograph analyzes a vapor or volatile liquid sample and then separates the various hemial omponents
More informationMechanical Pressure Switches for overpressure, vacuum pressure and differential pressure
Mechanical Pressure Switches for overpressure, vacuum pressure and differential pressure Switching range: -250 +100 mbar, 1 16 mbar to 16 63 bar Temperature: max. 70 C Material: Copper, brass, stainless
More informationOPTIBAR P 1010 C Technical Datasheet
Technical Datasheet Pressure transmitter with recessed diaphragm for general applications Wide variety thanks to modular design Measuring ranges up to 250 bar / 3750 psi High overload and temperature stability
More informationUser s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] IM 01C25A00-12E
User s Manual EJX/EJA-E Series NEPSI Certification [Option code: /NF2, /NS21, /NS24 and /NS25] 12th Edition 1 1. Introduction Thank you for purchasing the DPharp electronic pressure transmitter. This manual
More information4/2 way Pneumatic Solenoid Valve
4/2 way Pneumatic Solenoid Valve Compact design Push-over solenoid coil Exhaust air can be regulated Tube, threaded and sub-base connections Type combined with Seat valve version Type 2508 Type 2510/11
More informationRules of Beach Hockey including explanations
Rules of Beah Hokey inluding explanations Effetive from 1 June 2016 (updated 31 May 2016) Copyright FIH 2016 The International Hokey Federation Rue du Valentin 61 CH 1004, Lausanne Switzerland Telephone:
More informationPressure Switch Pressure Limiter
Assembly and Operating Instructions Pressure Switch Pressure Limiter Basic models Additional functions DCM......-203 DNM......-205 DNS......-206 VCM...,VNM......-307 VNS......-213 Important safety information!
More informationPressure Switch for gas and air
Switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. 13 and No. 0 Certification file # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF Commonwealth
More informationTechnical Datasheet. D Series SMART Pressure Transmitter Model: DPC D-Series. Key Features. Series Overview. Product applications
Technical Datasheet D Series SMART Pressure Transmitter Model: DPC-2000 Key Features ATEX - Flameproof and Intrinsically Safe IECEx - Flameproof and Intrinsically Safe SIL 2 certificate Compliant to NAMUR
More informationOperating Instructions
LPL Series LED Pendant Lighting Operating Instructions IM0102 COOPER Electronic Technologies (Shanghai) Co., Ltd. No. 955 Shengli Road, East Area of Zhangjiang High-Tech Park, Shanghai 201201 China 1.
More informationMiniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 800
KROHNE 1/22 7.236.22. GR Miniature flowmeters DK 46, DKR 46 DK 47, DK 48, DK 8 Variable area flowmeters Vortex flowmeters Flow controllers Electromagnetic flowmeters Ultrasonic flowmeters Mass flowmeters
More informationInstallation Instructions
Installation Instructions Low-Ambient Pressure Switch KSALA0201R22 KSALA0301410 NOTE: Read the entire instruction manual before starting the installation. SAFETY ONSIDERATIONS Improper installation, adjustment,
More informationPressure switch for gas and air
Pressure switch for gas and air GAO-A4 GMH-A4 GML-A4 UL Listed UL 353 File # MH 16628 CSA Certified CSA C22.2 No. LR 53222 Certification # 201527 FM Approved Class 3510, 3530 File # J.I. 1Y919.AF GXX_A4
More informationElectropneumatic Positioner and Pneumatic Positioner Type 3760 JIS
Electropneumatic Positioner and Pneumatic Positioner Type 3760 Application Single-acting positioners for direct attachment to pneumatic control valves. Supplied with an electric input signal of 4 to 20
More informationOrifice Plate Flow Meter
Orifice Plate Flow Meter FOFT Measuring Principle The principle of measuring the differential pressure is based on the fact that a differential pressure is created across that section of a pipe where its
More informationRules of Hockey5 including explanations
Rules of Hokey5 inluding explanations Effetive from 1 September 2012 Copyright FIH 2012 The International Hokey Federation Rue du Valentin 61 CH 1004, Lausanne Switzerland Telephone: ++41 21 641 0606 Fax:
More informationHigh-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20
Electronic pressure measurement High-performance submersible pressure transmitter For level measurement in hazardous areas Model LH-20 WIKA data sheet PE 81.56 Applications Deep well and borehole measurements
More informationAir Sensor. SAC Ex. Manual ATEX. AQ Elteknik AB
Air Sensor SAC Ex Manual AQ Elteknik AB ATEX Air Sensor SAC Ex ATEX Certified model Manual version 2.1 April 2014 AQ Elteknik AB 2 Table of contents 1. Manufacturer information... 4 Manufacture Declaration
More information