1 FLAMMABLE MIXTURE ANALYSIS FOR HAZARDOUS AREA CLASSIFICATION Allan Bozek P.Eng, MBA Member IEEE EngWorks Inc. 1620, 49 th Avenue SW Calgary, Canada T2T2T7 Vince Rowe, P.Eng Member IEEE Marex Canada Ltd. 1550, 555-4th Avenue SW Calgary, Canada T2P 3E7 Abstract - The properties of flammable mixtures as they apply to a hazardous area classification analysis are discussed. Mathematical formula and application rules of thumb are provided to help estimate the relative density, group classification, autoignition temperature, material flashpoint and the flammability of a mixture. Application guidelines are provided on how to apply the results in the context of a hazardous area classification analysis. Index Terms Hazardous area classification, flammable mixture analysis, density, group classification, autoignition, flashpoint, flammability. I. INTRODUCTION The vast majority of flammable materials handled in oil, gas and petrochemical facilities consist of flammable mixtures of various compositions. Performing a hazardous area classification risk assessment requires an understanding of the behavior of flammable mixtures and how they might influence the extent, group classification and autoignition temperature of the classified area. Unfortunately, very little guidance is given on mixture analysis by the various industry recognized standards and recommended practices on area classification. The search for the proper chemical relationships and formula can be frustrating. The mixture analysis must be performed with help of chemical textbooks and other references not specifically written for the purpose of a hazardous area classification analysis. The purpose of this paper is to provide guidance on how to analyze the properties of flammable mixtures as they apply to a hazardous area classification. The key flammable material parameters and the test methods used to determine the properties of pure flammable materials are discussed. In the absence of actual test results, a series of mathematical relationships and application rules of thumb are provided for estimating the properties of flammable mixtures. Application guidelines are also provided to assist in documenting the results within the context of a hazardous area classification analysis. II. HAZARDOUS AREA CLASSIFICATION OVERVIEW A hazardous area classification analysis is a structured risk assessment process used to determine the probability of a flammable atmosphere being present during normal or abnormal operations. The analysis divides the facility layout into zones of risk which are then used to determine the appropriate equipment and wiring methods for safe operation. The probability that a flammable atmosphere exists is dependent on the chemical properties of the flammable materials present, as well as the grade and rate of release. The extent of the hazard will be influenced by the behavior of the flammable material under normal ambient pressure and temperature conditions, the degree of ventilation within an area, the geometry and velocity of the release and the physical topography of an area. There are several methods for classifying an area once the flammable materials and physical parameters are identified. The most common way is to use the direct example approach where the facility is classified using diagrams that depict typical situations. This method of classification is incorporated into most industry recommended practices for hazardous area classification. A second method uses the point source approach to classify facilities. Potential release sources are identified and a formal calculation is performed to determine the extent of a classified area. The point source approach is more rigorous and thus requires more detailed information on the nature of the flammable materials to obtain a reasonable conclusion. III. PROPERTIES OF FLAMMABLE MATERIALS To assess the risk and the extent of the hazard, several key properties of the flammable material must be determined. They include: A. Vapor Pressure and Flashpoint The hazard posed by flammable materials is influenced by how easily it will mix with air and potentially form a flammable mixture. This is a function of vapor pressure and temperature. Flammable gases have a very low vapor pressure and as such are always in a gaseous state at ambient temperatures. Flammable liquids in contrast, are in a state of transition between a liquid and a gas. The hazard posed by a flammable liquid is a function of how easily it changes state from a liquid to a vapor at ambient temperatures. The temperature at which a liquid provides sufficient vapor to form a flammable mixture on the surface of the liquid is termed its flashpoint. This is the key parameter used to classify the potential hazard associated with flammable liquids. The flashpoint of a flammable material is determined experimentally using two recognized methods as illustrated in Fig. 1 and 2. The open cup flashpoint test procedure requires heating the flammable material in an open cup and periodically using an open flame to ignite the surface vapor. When there is sufficient vapor to sustain combustion, the flashpoint temperature is recorded.

2 The closed cup flashpoint test procedure is similar to the open cup flashpoint test except the flammable material is sealed within a closed cup environment. The closed cup flashpoint test typically results in a lower flashpoint temperature than observed with the open cup test. The flashpoint temperatures most often quoted for flammable materials in various publications are derived using the closed cup method. Flashpoint is used as a basis for categorizing the volatility of flammable liquids. NFPA 30 [1] categorizes flammable materials into three classes based on their flashpoint and boiling point vapor pressure (Table I). Class I materials are those that readily flash to atmosphere at ambient temperatures and pressures. They are considered highly volatile and require due consideration with respect to an area classification. Class II materials typically do not flash at temperatures that would normally be considered ambient. From an area classification perspective, Class II flammable materials are considered when they are stored or handled at temperatures above their flashpoint. Class III materials are only a consideration when they are exposed to very high process temperatures and typically do not factor into a hazardous area classification. In all cases, the properties of the flammable material and the process conditions must be assessed prior to defining the degree and extent of a classified area. Part 15 (IP15) of the British Institute of Petroleum Model Code of Safe Practice in the Petroleum Industry has a similar classification for petroleum liquids based on flashpoint. The petroleum classes defined in Table II are used in conjunction with a series of typical diagrams that define the degree and extent of a classified area. IP15 takes into account the process conditions and adjusts the extent of the classification based on if the material is handled above or below its flashpoint temperature. It also makes reference to situations where the fluid cannot be easily classified by flashpoint and addresses the potential hazards associated with flammable mists and sprays. Under these circumstances, a judgment call must be made as to the fluid category and the characteristics of the potential hazard. The point source method of area classification is normally used in these situations [2]. TABLE I NFPA CLASSIFICATION OF FLAMMABLE/COMBUSTIBLE MATERIALS NFPA Flashpoint (ºC) Examples Class BP = Boiling Point IA < 22.8, (BP < 37.8) Ethyl Ether, Pentane IB <22.8, (BP > 37.8) Acetone, Gasoline IC 22.8 and < 37.8 Naphtha, Xylene II >37.8 and < 60 Fuel Oil, Kerosene IIIA 60 and < 93 Ethylene Glycol IIIB 93 Asphalt, Transformer Oil Flammable Liquid Flame Bunsen Burner Fig. 1 Open Cup Flashpoint Test Apparatus Test Cup Thermometer Thermometer Liquid Bath Heating Vessel Agitator Open Cup with Flammable Liquid Bath Thermometer Flame Fig. 2 Closed Cup Flashpoint Test Apparatus TABLE II IP15 PETROLEUM CLASSES IP Class Flashpoint (ºC) Application 0 NA LPGs I <21 Flam. at ambient conditions II(1) 21 and 55 Handled below FP II(2) 21 and 55 Handled above FP III(1) >55 to 100 Handled below FP III(2) >55 to 100 Handled above FP Unclassified 100 B. Relative Vapor Density The relative vapor density of a flammable gas/vapor is a key parameter when using the direct example approach method of area classification. The diagrams selected for a particular situation are dependent on the relative density of

3 the gas/vapor as compared to air under standard ambient temperature-pressure conditions. For practical applications, a gas/vapor mixture that has a relative vapor density of 0.8 is regarded as lighter-than-air and a release would rapidly rise and collect in the upper levels of a confined area. Gas/vapor mixtures that have a relative vapor density greater than 1.2 are regarded as heavier-than-air and will collect at ground level. In theory, heavier-than-air flammable mixtures can travel long distances and result in large areas of potential hazard. Gas/vapor mixtures with a relative vapor density of between 0.8 and 1.2 can exhibit properties of both lighter-than-air and heavier-than-air behavioral characteristics so both possibilities should be considered [3] [4]. While gas/vapor density may have an influence on the extent of a classification in enclosed areas under ideal conditions, recent experiments using dispersion modeling have shown that the relative density has little influence on the extent of a hazard in a pressurized release. In these circumstances, the angle of release and how close the release point is to the ground has a larger effect. The extent of a flammable region is determined more by the direction and the velocity of the release than by the density of the gas or vapor released [5]. C. Group Classification of Flammable Materials The group classification assigned to a hazardous location determines the explosionproof or flameproof enclosure design requirements and the performance specifications for intrinsically safe circuits. The design of an explosionproof or flameproof enclosures is dependent on flamepath tolerances which are in-turn based on the Maximum Experimental Safe Gap (MESG) distance defined for a given flammable gas or vapor. The smaller the MESG defined for a material, the longer the flamepath required to cool the hot gases discharged from an explosionproof assembly during an ignition event. Typically, the longer the flamepath required, the more expensive the enclosure. The group classifications for flammable gases/vapors are determined experimentally based on the MESG determined under test conditions. The NEC group classifications for flammable materials are based on tests performed by Underwriter Laboratories using a Westerberg Explosion Test Vessel (WETV). The WETV consists of two chambers, one within the other, and each filled with a stochiometric explosive mixture. The mixtures are separated by an adjustable 25mm wide joint gap assembly. The flammable atmosphere is ignited in the inner chamber and allowed to propagate to the outside chamber. The opening of the joint gap assembly is reduced until an internal chamber ignition does not propagate to the external chamber. The opening of the 25mm wide joint gap at that point is the MESG. The group classification for the flammable material is then assigned based on Table III. The IEC group classifications are performed in a similar fashion. The size and shape of the explosion chamber differs from the WETV but the results are statistically similar. The IEC group classification of materials as it relates to MESG is also provided in Table III. TABLE III GROUP CLASSIFICATION CRITERIA NEC Gas Grouping IEC Gas Grouping Group MESG (mm) MIC ratio Group MESG (mm) MIC Ratio A Acetylene B IIC C >0.45 >0.40 >0.50 >0.45 IIB D >0.75 >0.80 IIA >0.90 >0.80 The group classification for a flammable material can also be based on the minimum ignition current (MIC) required to ignite the material under stochiometric conditions within a specified test apparatus. This is derived experimentally with the results often expressed as a ratio to the minimum ignition energy required for methane. Table III provides the group classifications based on the minimum ignition current ratio (MIC ratio) as compared to methane. D. Lower and Upper Flammable Limits Flammable gases and vapors are flammable only when they are between their lower flammable limits (LFL) and their upper flammable limits (UFL). For area classification purposes, the LFL is of greater concern as the hazard can be reduced by controlling the level of ventilation to dilute the flammable gas to a concentration well below the LFL. The LFL is a key parameter required for all hazardous area classification ventilation and point source calculations. Hot Air Electrode Ignition Vessel Manifold Fig. 3 Flammable Limits Test Apparatus The %LFL and %UFL values for pure substances are derived experimentally using the apparatus described in ASTM E and illustrated in Fig. 3. The concentration of the flammable material is gradually increased until an ignition is observed. The % volume to air is recorded as the lower flammable limit. The concentration is further increased and ignited until the mixture no longer ignites. The % concentration is then recorded as the upper flammable limit. Air Flammable Gas Mixture Air Manifold

4 E. Autoignition Temperature (AIT) The autoignition temperature of a flammable material is required to determine maximum safe operating surface temperature for equipment installed in a hazardous location. The maximum surface operating temperature for electrical equipment is defined by a temperature code. The temperature code is used to determine if the equipment item is suitable for installation based on the AIT defined for the hazardous location. There are a number of definitions for autoignition temperature in current use. For example, API RP500 defines AIT as: The minimum temperature required, at normal atmospheric pressure, to initiate or cause self sustained combustion (independent of any externally heated element). [3] API RP505 defines AIT as: The lowest temperature of a heated surface at which, under specified conditions, the ignition of a flammable substance in the form of a gas or vapor mixture with air will occur. [4] The API RP505 definition is a modification of the definition in IEC which is: Ignition temperature The lowest temperature at which ignition occurs when the method prescribed in this standard is used. [7] The test method used in IEC consists of heating a 200ml Erlenmeyer flask in a hot air furnace as illustrated in Fig. 4. The flask is heated to the desired temperature, at which point a liquid or gaseous sample is injected into the flask. If no flame is observed within 5 minutes, the test is repeated until the minimum temperature at which ignition occurs is determined. The process is repeated until a degree of correlation exists between several identical tests. This correlated value is then defined as the autoignition temperature for the flammable material. ASTM E659 Standard Test Method for Autoignition Temperature of Liquid Chemicals defines AIT as: The minimum temperature at which Autoignition occurs under the specified conditions of test. [8] The test method described in standard ATSM E659 is similar to the test procedure used in IEC with the exception of the volume and the shape of the flask used. Published AIT tables are usually based on the laboratory procedures outlined in IEC and ASTM E659. The prescribed methods are relatively simple and the results are repeatable, however, they are only accurate for the conditions under which the testing is performed. Autoignition temperatures can be influenced by the volume, shape and the material composition of the test apparatus, the method and rate of heating, the flame detection method as well as the percent gas/vapor/air composition of the sample [9]. The published AIT tables typically reference the lowest AIT observed under controlled laboratory conditions. Industry experience however indicates that the actual minimum temperature at which ignition occurs is much higher. API RP 2216 Ignition Risk of Hydrocarbon Liquids and Vapors by Hot Surfaces in Open Air concluded that the minimum temperature (referred to as the minimum hot surface ignition temperature) should not be assumed unless the surface temperature is approximately 360 F (182 C) above the published AIT [10]. It should be noted that there is no standardized test for hot surface ignition temperature. The temperature at which hot surface ignition occurs is not a fundamental fluid property and is influenced by a number of factors including ambient conditions as well as the size, geometry and properties of the hot surface itself. Hot surface ignition data cannot easily be extrapolated to different situations and the use of a general rule of thumb based on a minimum autoignition temperature can be very inaccurate [11]. Fig. 5 illustrates the relationship between vapor pressure, upper and lower flammability limits, autoignition and hot surface ignition temperature. Fig. 4 IEC Autoignition Temperature Test Apparatus V a p o r P r e s s u r e Viewing Line 200 ml Erlenmeyer Heater Elements Mixture Vapor Pressure Curve Flash Point Temperature Published Autoignition Temperature Mirror To Instrument Monitors Autoignition Zone Lower Flammable Limit Mixture/Surface Temperature Fig. 5 Autoignition and Hot Surface Ignition Temperature as a Function of Temperature and Vapor Pressure IV. INDUSTRY REFERENCES Flame Arrestor Thermocouple Electric Furnace To Heater Controls Upper Flammable Limit Syringe Hot Surface Ignition Zone (Curve may shift based on less ideal conditions) Inflatable Reservoir Most area classification standards and recommended practices do not incorporate a list of flammable material properties. A secondary publication must usually be referenced to obtain the necessary data. The one notable exception is NFPA 497 Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas which incorporates a list of flammable material properties within the context of the document [12].

5 Historically, API 500 and 505 has referenced NFPA 325 Guide to Fire Hazard Properties of Flammable Liquids, Gases and Volatile Solids as the recommended source of information for flammable material properties. The document was originally intended for fire prevention purposes and does not incorporate information on MESG, MIC ratio or minimum ignition energy data required for determining the group classification of a flammable material. As of 1998, NFPA 325 is no longer in print and has been superseded by the NFPA Fire Protection Guide to Hazardous Materials [13]. The document combines information from nine different NFPA reference documents on hazardous materials. With NFPA 325 no longer being published, the 2007 edition of API 500 and 505 now make reference to NFPA 497 as the recommended source of information for flammable material properties. NFPA 497 provides a complete list of chemical parameters including the NFPA flammable material classification, flashpoint, autoignition temperature, vapor pressure, density, group classification and the MESG and MIE/MIC for a list of commonly found flammable materials used in chemical process facilities. The list, although not comprehensive, includes most flammable materials commonly found in upstream production, transportation and refinery facilities. Area classifications performed using IEC [14] are referred to IEC Electrical Apparatus for Explosive Gas Atmospheres Part 20 Data for Flammable Gases and Vapours [15] for a list of flammable material properties. IEC was created specifically for hazardous area classification purposes and includes a complete set of data for performing an analysis. There are minor differences between the data published in NFPA 497 and IEC The differences are related to the variation in test procedures and apparatus used. TABLE IV provides an overview of the differences between the reference publications for a cross sample of flammable materials. Other sources of flammable material property information include MSDS (Material Safety Data Sheets US OSHA) and WHMIS (Workplace Hazardous Materials Information System Canada) material data sheets and a number of chemical reference texts that tabulate the properties of flammable materials. MSDS and WHMIS data can be valuable because they often provide information on chemicals and products not normally listed in industry chemical references. They however omit MIC and MESG information required for the group classification of a flammable material. TABLE IV FLAMMABLE PROPERTIES COMPARISON BETWEEN NFPA 497 and IEC Flammable AIT Ref. %LFL %UFL Material ºC MESG Methane NFPA IEC Pentane NFPA IEC Hydrogen NFPA IEC Hydrogen NFPA Sulfide IEC V. PROPERTIES OF MIXTURES In a perfect world, a hazardous area classification would be completed using the information provided in the various area classification standards and recommended practices and the properties listed in the hazardous material references. All process materials would be of a homogenous nature with their properties and flammable characteristics well defined. Unfortunately, real world process facilities combine process streams with different materials thus affecting the properties and characteristics of the combined mixture. This would not be an issue if the tests for flashpoint, MESG, %LEL and autoignition could be done for a mixture the same way it is done for a pure substance. This is however impractical in the context of plant design where the cost and effort associated simulating and testing each process stream does not justify the end result. Some mathematical means of estimating the properties of a flammable mixture is required to properly assess the nature of the hazard and define the extent of the classified zones. Fortunately there are some mathematical relationships that can be used to help predict the properties of flammable mixtures. A. Base assumptions To estimate the properties of a flammable mixture, a number of key assumptions are required. The first assumption is that the mixture is in a gas or vapor state upon release and it does not exist as mist or spray. The properties of flammable mists and sprays are extremely difficult to model and must be treated as a unique case for area classification purposes [5]. The second assumption is that the flammable materials remain in mixture. The behavior of ideal vs. non-ideal mixtures will impact the accuracy of this assumption to a degree but not enough to render the approximation invalid. B. Estimating Mixture Relative Density As previously discussed, the relative density of a mixture must be estimated to determine if it is heavier-than-air, lighterthan-air or of neutral buoyancy. The information is necessary to determine what direct example approach diagram is appropriate for a particular situation. The relative density of a mixture is calculated based on the molar weight of the mixture as it compares to the molar weight of air. The molar weight of air is grams/mole at 0 C at sea level. The following formula is the basis for the calculation: where RD air = n Mi,x i i (1) RD air = Relative density of the mixture compared to air M i = molar weight of the individual constituent x i = corresponding mole fraction

6 The results are then compared to the values in TABLE V and then applied to the appropriate area classification diagram. TABLE V RELATIVE DENSITY CATEGORIZATION RD air < 0.8 Lighter than air 0.8 RD air 1.2 Neutral buoyancy RD air > 1.2 Heavier than air Consider the mixture illustrated in TABLE VI. Calculate the molar weight of the mixture and determine if it is lighter or heavier than air. TABLE VI EXAMPLE: ESTIMATING RELATIVE DENSITY Material M i x i M i x i Methane % 8.02 Ethane % 3.0 H 2 S % 5.11 Nitrogen % 4.2 Heptane % 5.0 Octane % 5.71 Total 100% The molar weight calculated for the mixture is When divided by the molar weight of air (28.96) the mixture has a relative density of 1.07 indicating the mixture has neutral buoyancy. This information would then be used to judge the extent of the transient vapor zone associated with the appropriate area classification diagram. It should be noted that most industry references for flammable materials do not provide information on the molar weight of materials. A chemistry textbook must be referenced to source this information. C. Estimating the Group Classification of Mixtures Determining the group classification of a mixture is essential for determining the appropriate hazardous location electrical equipment specifications. For most upstream production and downstream refinery facilities handling hydrocarbon mixtures, the group classification is typically group D under the division system and group IIA under the zone system of area classification. The two flammable materials that most often influence the group classification of a hydrocarbon processing facility are H 2 S and hydrogen. API RP500, RP505 and IP15 provide some guidance in determining the group classification of facilities handling H 2 S and hydrogen. Generally, a group C or IIB group classification is not justified unless H 2 S comprises at least 25% of the flammable mixture stream. A group B or IIC classification is not justified unless the hydrogen component of a flammable stream exceeds 30%. For most hydrocarbon processing facilities, the H 2 S and hydrogen rule of thumb guidelines are sufficient to determine the group classification. For chemical processing facilities handling flammable mixtures other than hydrocarbons, the group classification is more complex. In these situations, Le Chatelier s principle can be applied. Le Chatelier studied the influence of pressure, temperature and concentration on systems at equilibrium. Le Chatelier postulated that when a system at equilibrium is disturbed, the system will counteract as far as possible, the effect of the disturbance on the system. This principle is applied to estimating the MESG and subsequent group classification of a flammable mixture. The mathematical relationship for estimating MESG using Le Chatelier s principle is as follows: Consider the example of a flammable mixture consisting of 50% Diethyl Ether, a Group C, (IIB) classified material as illustrated in TABLE VII. TABLE VII ESTIMATING MESG EXAMPLE Material x i MESG (mm) Group Diethyl Ether 50% 0.83 C, (IIB) Methanol 20% 0.92 D, (IIA) Nitrogen 15% - Isopropyl Ether 10% 0.94 D, (IIA) Methyl Ether 5% 0.84 C, (IIB) Applying Le Chatelier s principle to the mixture: MESG mix = MESG mix = i MESG i where MESG mix = Estimated MESG of the mixture MESG i = MESG of the individual constituent x i = corresponding mole fraction MESG mix = Using TABLE III, the gas mixture is thus classified group D, (IIA). It is interesting to note that the MESG value obtained for the mixture using Le Chatelier s principle has a value greater than all MESGs for each of the individual material components. This is due to the effect nitrogen gas has on calculating the MESG of the mixture. Inert gases will influence the MESG of a mixture by reducing the oxidant quality of the mixture. Le Chatelier s principle will tend to overemphasize the effect of the inert gas on the MESG of an inert-flammable gas mixture and will produce odd results when used with mixtures that contain a large percentage of inert gas. The same is true of mixtures that contain oxygen in excess of a nominal 21% concentration. The higher concentration of oxygen increases the volatility of the ignition producing higher pressures which in turn render the MESG test values for the individual components invalid. Materials such as carbon monoxide or carbon disulfide that do not incorporate hydrogen bonds can also result in erroneous results. Laboratory test results has shown that Le Chatelier s principle is reasonably 1 1 x i (2)

7 accurate provided the following situations are avoided: [16][17] 1. Flammable mixtures where a significant portion of the gas is an inert. 2. Mixtures that incorporate oxygen as one of the components. 3. Mixtures that contain greater than 5% carbon monoxide. 4. Mixtures that contain acetylene. D. Estimating LFL and UFL of Mixtures Estimating the lower flammable limit of a mixture is required for point source calculation methods and for determining the level of adequate ventilation in an enclosed area using the fugitive emissions calculation procedure described in appendix B of API RP 500 and 505. Upper flammable limits are seldom used as a basis for area classification. The LFL of a mixture may be estimated by applying a derivation of Le Chatelier s principle. The derivation uses only the flammable components of the mixture with their mole fractions adjusted to their relative percentage of the flammable mix as follows: where %LFL mix = %LFL i = x iflam = Consider the flammable mixture example previously used for estimating MESG. TABLE VIII EXAMPLE: ESTIMATING %LFL Material x i x iflam LFL Diethyl Ether 50% 58.8% 1.7% Methanol 20% 23.5% 6.0% Nitrogen 15% - Isopropyl Ether 10% 11.8% 1.4% Methyl Ether 5% 5.9% 3.4% 100% 100% %LFL mix = %LFL mix = %LFL mix = 2% i The UFL of a mixture can also estimated using Le Chatelier s principle in a similar way. 1 x iflam %LFL i Estimated LEL of the mixture %LFL of the individual constituent Corresponding mole fraction on a flammable bases 1 X (3) Le Chatelier s principle provides flammability limits that are close to the experimental values of simple hydrocarbon mixtures with sufficient accuracy for most area classification analysis. The approximation is valid with mixtures in air at ambient pressures [18]. E. Flammability of Mixtures There are often situations where gas or fluid mixtures contain flammables in low concentrations. The question arises whether the mixture as a whole is flammable and therefore must be considered as part of an area classification. To determine the flammability of a mixture, an assessment must be made to determine if the mixture contains sufficient flammables to exceed the lower flammable limit of the mixture as a whole. The calculation procedure is relatively easy for mixtures in a gaseous state. It is more complex for fluid mixtures where the flammable components may flash to atmosphere based on ambient, operating or storage temperatures. 1) Flammability of a Gas Stream: The flammability of a process gas stream may be determined by first estimating the %LFL of the mixture using Le Chatelier s principle and then comparing the %LFL to the total %flammables contained in the mixture. If the %flammables exceed the %LFL, the mixture is considered flammable [19]. Consider the example in TABLE IX where a relatively small percentage of flammables make up a gas mixture: TABLE IX EXAMPLE: DETERMINING THE FLAMMABILITY OF A GAS STREAM Material % Vol x iflam LFL Methane % 5.0% Butane % 1.9% Ethane % 3.0% Air % Estimating the %LFL for the mixture using Le Chatelier s principle: %LFL mix = The flammable percent volume of the mixture is: %Flam mix = 3% + 1.5% + 1% = 5.5% X 100 = 3.2% Since the %Flam mix exceeds the %LFL mix the mixture is considered flammable and must be considered within the context of an area classification. 2) Flammability of a Process Fluid Stream: Determining the flammability of a process fluid stream requires estimating the flashpoint of the mixture. A common industry practice for estimating the flashpoint of mixtures is to

8 use the lowest published flashpoint for any of the pure components. If the flashpoint temperature for the single lowest pure component in the mixture is exceeded at ambient, process or storage handling conditions, the mixture is considered flammable. This assumption is thought to provide a conservative value for the flashpoint of a mixture however; further research has shown that this assumption is not always valid. Mixtures can exhibit lower flashpoints than any of the pure component values depending on if the mixture is classed as ideal or nonideal. An ideal mixture is defined as a mixture where all molecular interactions are the same as if the individual components were in their pure state at the same pressure and temperature as the mixture [20]. The mixture will follow the properties of Raoult s law which allows the thermodynamic properties of the mixture to be predicted based on the properties of the individual components. Using this principle, the vapor pressure and flashpoint of a mixture can be estimated diagrammatically as illustrated in Fig 6. The vapor pressure or the flashpoint of a mixture is directly influenced by the mole fraction of the individual constituents of the mixture. P sat A P sat B Vapour Pressure x i (mole fraction) T f,b Flashpoint x i (mole fraction) Fig. 6 Vapor Pressure and Flashpoint Behavior of Ideal Mixtures T f,a Mixtures that exhibit ideal behavior include water-alcohol and heptane-hexane hydrocarbon mixtures. Non-ideal mixtures deviate from Raoult s law in a positive or negative manner depending on the molecular attraction of the mixture components. Fig. 7 illustrates the behavior of a mixture that deviates in positive manner from Raoult s law. Note that under certain conditions, the flashpoint of the mixture may be less than the flashpoint of either component in the mixture. Most mixtures exhibit non-ideal behavior to a degree. Methanol hydrocarbon mixtures are highly non-ideal and have been shown to exhibit flashpoint temperature lower than either component. This complicates the development of a simple rule of thumb for determining the flammability of a fluid mixture. Unless a mixture can be positively confirmed to exhibit ideal behavior in accordance with Raoult s law, the mixture must be assumed to be flammable with the flashpoint lower than what is published for any of the flammable components. The only reliable way of determining the flashpoint and hence the flammability of a fluid mixture is by test procedure. P sat A Actual Vapour Pressure Ideal x i (mole fraction) Fig. 7 Vapor Pressure and Flashpoint Behavior of Non-Ideal Mixtures F. Autoignition Temperature T f,b P sat B Ideal Actual Flashpoint x i (mole fraction) T f,a Estimating an AIT for a mixture is a challenging problem due to the complex nature of the autoignition-combustion process. There are no established mathematical relationships to help in this regard. The only way to determine the AIT of a mixture is by laboratory test. If AIT data for a mixture is not available and the situation precludes testing, often the lowest AIT of any pure component in the flammable mixture is used as the AIT. This typically results in a very conservative AIT value and may not reflect the true nature of the hazard. A rule of thumb often used to estimating the AIT of hydrocarbon mixtures is to take the lowest AIT of any component exceeding 5% (by volume) of the total mixture. This is based on the assumption that the autoignition temperature of a mixture will be influenced more by the properties of the major components than by the minor components in the mixture. This assumption has not been verified and additional research in this area is required. Rules in the NEC and the CEC require the maximum surface operating temperature of electrical equipment to be less than the ignition temperature of the specific gas or vapor in a hazardous area. While the rules do not specify the use of AIT s (as opposed to hot surface ignition temperature), the use of published AIT s has been standard practice. In some situations it may make sense to use a temperature other than the published AIT based on documented engineering judgment. A real life example involves the installation of MI heat tracing on high temperature process piping in heavy oil upgrader facilities. In these situations, it is common for process piping to operate at elevated temperatures in the range of 325 C in areas where diluents (predominantly hexane - AIT 215 C), are present. Historically, the heat trace design would have been limited to a maximum surface operating temperature of 215 C on a pipe that normally operates at 325 C. This results in multiple passes of a lower wattage electric heat trace to limit the maximum surface operating temperature of the tracer to less than 215 C. Recent upgrader facility designs have made documented engineering decisions to allow the maximum design temperature of the heat trace to be as high as the operating temperature of the hot piping. This allows more flexibility in the design of the heat trace system and typically reduces the number of tracer circuits required to meet the process piping heating requirements.

9 VI. APPLICATION GUIDELINES The hazardous area classification for a facility is usually documented using layout drawings and details that define the degree and extent of the classified areas. The drawings also provide pertinent information on the group classification and autoignition temperature defined for the facility. For complex facilities that incorporate a variety of flammable mixture streams, the drawings are usually supplemented by an engineering document that summarizes the basis for the area classification. The hazardous area classification study report should include: 1) A description of the process and the flammable materials handled. 2) A list of the codes, standards, recommended practices and material references used in the analysis. 3) A list of assumptions used to classify the facility including the basis for normal and abnormal operations. This would also include a section on flammable mixtures and how their material properties were estimated. 4) A hazardous materials worksheet that documents the properties of the flammable materials handled within the facility. The flashpoint, group classification, autoignition temperature, LFL/UFL and hazard classification is summarized for each process stream. 5) A source of release worksheet that identifies the most likely release points within a facility. 6) The basis for the group classification and autoignition temperature for the overall facility. 7) A summary of any fugitive emission and ventilation calculations. 8) Recommendations for gas detector placement including information on what flammable gases are to be detected and the calibration procedure required for gas detector maintenance. 9) A list of recommendations for operation and maintenance activities performed in classified areas. 10) The area classification layout drawings should incorporate a note that references the study report as the bases for the area classification design. The hazardous area classification study report provides essential information for understanding the basis for the original hazardous area classification and for planning any future modifications to the area classification design for the facility. VII. CONCLUSION Performing a hazardous area classification risk analysis requires an understanding of how flammable mixtures behave. In an ideal world, the properties of a flammable mixture would be determined by test procedure; however, this is impractical in most cases. Methods are required to estimate the properties of flammable mixtures to support a hazardous area classification analysis. Predicting the relative vapor density of a mixture is a simple calculation that compares the molar weight of the mixture to the molar weight of air at ambient temperatures and pressures. Determining the group classification, estimating the LFL, UFL, and predicting the flammability of a gas mixture can be done using Le Chatelier s principle. The complex nature of the autoignition process precludes the use of a simple mathematical model or industry rule of thumb that can be used to estimate the AIT of a flammable mixture. Additional research is required to develop a basis for an industry accepted practice for estimating the autoignition temperature of flammable mixtures. X. REFERENCES [1] NFPA 30, Flammable and Combustible Liquids Code, National Fire Protection Association, Quincy, MA., [2] Institute of Petroleum, Model Code of Safe Practice Part 15, Area Classification Code for Installations Handling Flammable Fluids, 3rd Edition, Energy Institute (2003), Portland Press. [3] ANSI/API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, American Petroleum Institute, Washington, DC, [4] ANSI/API RP 505, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Zone 0, Zone 1, and Zone 2, American Petroleum Institute, Washington, DC, [5] Propst, John, E., Volatility and Mists Electrical Area Classification's Important Variables, IEEE Transactions on Industry Applications, Vol. 36, No. 2, March/April [6] ASTM E , Standard Test Method for Concentration Limits of Flammability of Chemicals, American Society for Testing and Materials, Conshohocken, PA, [7] IEC , Electrical Apparatus for Explosive Gas Atmospheres Part 4: Method of Test for Ignition Temperature, International Electrotechnical Commission, Geneva, Switzerland [8] ASTM E659-78, Standard Test Method for Autoignition Temperature of Liquid Chemicals, American Society for Testing and Materials, Conshohocken, PA, [9] NFPA 325, Guide to Fire Hazard Properties of Flammable Liquids, Gases and Volatile Solids, National Fire Protection Association Quincy, MA., [10] API RP 2216, Ignition Risk of Hydrocarbon Liquids and Vapors by Hot Surfaces in Open Air, American Petroleum Institute, Washington, DC, 2003.

10 [11] Colwell, J.D., Reza, A., Hot Surface Ignition of Automotive and Aviation Fluids, Fire Technology, 41, , [12] NFPA 497, Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas, National Fire Protection Association Quincy, MA., [13] Fire Protection Guide to Hazardous Materials, National Fire Protection Association, Quincy, MA., [14] IEC , Electrical Apparatus for Explosive Gas Atmospheres Part 10 Classification of Hazardous Areas, International Electrotechnical Commission, Geneva, Switzerland, [15] IEC , Electrical Apparatus for Explosive Gas Atmospheres Part 20 Data for Flammable Gases and Vapours, related to the use of Electrical Apparatus, International Electrotechnical Commission, Geneva, Switzerland, [16] Briesch, Edward, NEC Group Classification of Mixtures, American Institute of Chemical Engineers, 34 th Loss Prevention Symposium, Atlanta, Georgia, March 8, [17] Report on Proposals NFPA 497, Report of the Committee on Electrical Equipment in Chemical Atmospheres, F2007. [18] Hristova, M., Tchaoushev, S., Calculation of Flash Points and Flammability Limits of Substances and Mixtures, Journal of the University of Chemical Technology and Metallurgy, 41, 3, Pg , [19] Crowl, Daniel, A., Understanding Explosions, American Institute of Chemical Engineers, New York, New York, 2003 [20] Perry s, Chilton, Kirkpatrick, Perry s Chemical Engineers Handbook, McGraw-Hill Inc. New York, New York, H. VITA Allan Bozek, P.Eng., MBA, is a Principal with EngWorks Inc. providing consulting engineering services to the oil and gas industry. He is a registered professional engineer in the provinces of Alberta and British Columbia, Canada and has been a member of the IEEE since Allan s areas of expertise include hazardous area classification, power systems design, protective relaying and grounding for large scale industrial and petrochemical facilities. Mr. Bozek graduated from the University of Waterloo in 1986 with BASc in Systems Design Engineering and a MBA from the University of Calgary in Allan may be contacted at ABozek@EngWorks.ca Vince Rowe retired from Shell Canada in 1994 and continues to be active in the Oil and Gas industry as a consultant. He provides training on electrical installations and maintenance in classified locations. He is a partner with Marex Canada Limited and a member of the steering committee for the Canadian Electrical Code. He is Chairman of the Hazardous Location and Electric Heating sections and one of the initiators of the Objective Based Industrial Electrical code for Canadian Industry. Mr. Rowe graduated from the University of Manitoba in 1960 with a Bsc in Electrical Engineering. Vince may be contacted at Vince.Rowe@shaw.ca

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Electrical Equipment

More information

Fires and Explosions: What You Need to Know to Prevent Them

Fires and Explosions: What You Need to Know to Prevent Them Fires and Explosions: What You Need to Know to Prevent Them CSChE PSM Symposium Edmonton, Alberta 2007 Gerry Phillips, GC Phillips Consulting Ltd. Norman Nibber, Independent Risk Control Objectives Understand

More information

Session #: Selection of Explosion Protected Equipment for Hazardous Locations

Session #: Selection of Explosion Protected Equipment for Hazardous Locations Abstract Session #: (Arial 16) Selection of Explosion Protected Equipment for Hazardous Locations Pieter Coetzee Explosion Prevention Consultant Registered person How can we mitigate the risks of explosions

More information

Temperature Influence on the Flammability Limits of Heat Treating Atmospheres

Temperature Influence on the Flammability Limits of Heat Treating Atmospheres Temperature Influence on the Flammability Limits of Heat Treating Atmospheres John Dwyer, Jr., James G. Hansel, Tom Philips Air Products and Chemicals, Inc., Allentown, PA Abstract The flammability limits

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 12 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

Hazardous (Classified) Locations

Hazardous (Classified) Locations Hazardous (Classified) Locations Presented by: John Chambers UL HazLoc operations Presented at: Safety & You in 2002 2002 Safety Conference Flexible Packaging Association (FPA) 1 AREA CLASSIFICATIONS Class

More information

1. Add a new Annex B.8 to read as follows:

1. Add a new Annex B.8 to read as follows: NFPA 69-2014 Edition Standard on Explosion Prevention Systems TIA Log No.: 1212 Reference: Annex B.8 (new) Comment Closing Date: February 19, 2016 Submitter: Martin Clouthier, Clouthier Risk Engineering,

More information

Applications Note: Use of "pentane equivalent" calibration gas mixtures

Applications Note: Use of pentane equivalent calibration gas mixtures Introduction The gas that is used to verify accuracy is every bit as important as the detector itself when it comes to worker safety. Choosing (and using) the right mixture is critical to the success of

More information

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT OVERVIEW ASSESSING THE RISK RELATIONSHIP BETWEEN FIRES AND EXPLOSIONS CLASSIFYING HAZARDOUS AREAS INTO ZONES

More information

Describe Flammable Gas Measurement

Describe Flammable Gas Measurement Training Module Describe Flammable 100% 90% C 80% No Combustion 70% 60% 50% 40% 30% 20% UEL B Combustion No Combustion 10% 0% LEL A Human Development HDC Human Development All rights reserved. No part

More information

Title of Paper Interpretation of IP15 in Process Plant Design: a Commonsense Approach ---------------------------------------------------------------------------------------------------------------------------

More information

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display.

Thermo Probe, Inc. TP-5 TP-7 TP-8. Instruction Manual English. Switch. Display. Carry Strap. Probe. Ground Clip. Switch. Display. Display Thermo, Inc. Instruction Manual English TP-5 Display TP-7 Display TP-8 1-1 Thermo, Inc. Instructions for use- Models TP-5, TP-7, and TP-8 The manual describes basic function and use of Thermo instruments

More information

The Omron STI Hazardous Location

The Omron STI Hazardous Location Hazardous Location Rating Systems for Interlock Switches The Omron STI Hazardous Location Rated Safety Interlock Switches presented in this catalog are classified by the European standard as Ex, ExdIIc

More information

MEMORANDUM. SUBJECT: NFPA 69 Proposed Tentative Interim Amendment (TIA) No.1212

MEMORANDUM. SUBJECT: NFPA 69 Proposed Tentative Interim Amendment (TIA) No.1212 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Explosion Protection Systems

More information

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS

1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS 1.8 INDUSTRIAL PROCESS WEIGHING IN HAZARDOUS AREAS EXPLOSION PROTECTION In addition to the type approval and certification of industrial weighing systems concerned with accuracy, equipment that is also

More information

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances.

PURE SUBSTANCE. Nitrogen and gaseous air are pure substances. CLASS Third Units PURE SUBSTANCE Pure substance: A substance that has a fixed chemical composition throughout. Air is a mixture of several gases, but it is considered to be a pure substance. Nitrogen and

More information

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438

CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO Walnut Lake Rd th Street Houston TX Garner, IA 50438 CALCULATING THE SPEED OF SOUND IN NATURAL GAS USING AGA REPORT NO. 10 Jerry Paul Smith Joel Clancy JPS Measurement Consultants, Inc Colorado Engineering Experiment Station, Inc (CEESI) 13002 Walnut Lake

More information

Intrinsic safety 101 hazardous locations

Intrinsic safety 101 hazardous locations Intrinsic safety 101 hazardous locations Protection methods, containment, segregation, and prevention By Robert Schosker This article answers the question, Why worry about hazardous locations? The area

More information

Fit for Purpose Compositional Input for Allocation Using Equations of State Thomas Hurstell, Letton Hall Group

Fit for Purpose Compositional Input for Allocation Using Equations of State Thomas Hurstell, Letton Hall Group UPM 15030 Fit for Purpose al Input for Allocation Using Equations of State Thomas Hurstell, Letton Hall Group Abstract Methods are presented to develop compositional input for use in allocation systems

More information

Atmospheric Hazards. Hazardous Atmosphere 3/29/2017. Oxygen deficiency and enrichment Flammable gases and vapors Toxic contaminants

Atmospheric Hazards. Hazardous Atmosphere 3/29/2017. Oxygen deficiency and enrichment Flammable gases and vapors Toxic contaminants 2017 Wisconsin Safety Council Safety & Health Conference, Presentation by Tim Gackle, OSHA Training Institute April 11, 2017 Atmospheric Hazards Oxygen deficiency and enrichment Flammable gases and vapors

More information

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary

LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary ADH 1/7/014 LOW PRESSURE EFFUSION OF GASES adapted by Luke Hanley and Mike Trenary This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the

More information

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12

LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/12 LOW PRESSURE EFFUSION OF GASES revised by Igor Bolotin 03/05/ This experiment will introduce you to the kinetic properties of low-pressure gases. You will make observations on the rates with which selected

More information

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E

Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics. Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E Dangerous Substances & Explosive Atmospheres Regulation 2002 The Basics Richard Cowen Dip SH, Dip RSA, CMIOSH, MIIRSM, FRSPH, GI Fire E DSEAR Regulations 2002 Sets minimum requirements for the protection

More information

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres

NZQA registered unit standard version 3 Page 1 of 7. Plan electrical installations for explosive atmospheres Page 1 of 7 Title Plan electrical installations for explosive atmospheres Level 5 Credits 8 Purpose This unit standard is intended for use in the training and assessment of people who work with electrical

More information

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION

AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION AIDGC PRESENTATION MARCH 2006 HAZARDOUS AREAS STANDARDS & CLASSIFICATION Jeff Strath Principal Engineer Paterson Flood Engineers Pty Ltd www.pfe.com.au INTRODUCTION This presentation provides an overview

More information

Interchangeability Criteria.

Interchangeability Criteria. Interchangeability Criteria. A substitute gas should burn satisfactorily with negligible change in burner performance on all types of burners without the need for special adjustment. The important requirements

More information

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels

Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert Gas Blanketing of Chemical Process Vessels Inerting Control Systems by NTRON PROCESS ANALYZER DIVISION of NEUTRONICS INC. EXTON. PA. 19341 RJN Rev. A June 2001 Focus on VOC Emissions Reduction Using an Oxygen Based Inerting Control System For Inert

More information

ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994

ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994 ENGINEERING STANDARD FOR HAZARDOUS AREA ORIGINAL EDITION DEC. 1994 This Standard is the property of Iranian Ministry of Petroleum. All rights are reserved to the owner. Neither whole nor any part of this

More information

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces

PSSI 36 General Confined Spaces, Tunnels, Culverts and Similar Spaces 1. SCOPE This document now includes provision for safe access to cable tunnels and culverts previously covered in PSSI 37 which is now withdrawn. The term Confined Space is defined in the Confined Spaces

More information

Technical Manual. Sensepoint XCD Gas Detector

Technical Manual. Sensepoint XCD Gas Detector Technical Manual Sensepoint XCD Gas Detector 19 Cross Interference and Cross Calibration 19.1 Cross Interference Table for Toxic and Oxygen This table shows the relative cross sensitivity of the Sensepoint

More information

A. What are the three states of matter chemists work with?

A. What are the three states of matter chemists work with? Chapter 10 and 12 The Behavior of Gases Chapter 10 The States of Matter A. What are the three states of matter chemists work with? Section 10.1 Pg 267 B. We will explain the behavior of gases using the

More information

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the

METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS. 1.2 Scope. This method is applicable for the 1151 METHOD 21 - DETERMINATION OF VOLATILE ORGANIC COMPOUND LEAKS 1.0 Scope and Application. 1.1 Analytes. Analyte Volatile Organic Compounds (VOC) CAS No. No CAS number assigned 1.2 Scope. This method

More information

Session 13: Fundamentals of Area Classification Studies

Session 13: Fundamentals of Area Classification Studies Session 13: Fundamentals of Area Classification Studies Jaco Venter Explolabs Consulting 1 Introduction An accurate area classification study is of the utmost importance for selecting suitable explosion

More information

USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases)

USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases) (June 27, 2002) USER'S MANUAL HOT-WIRE TYPE GAS SENSOR NAP-100A SERIES ( NET10A(R) ) (For All Combustible Gases) 1. General Being designed for light industrial applications, NAP-100A series also available

More information

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany

EXPLOSION PROTECTION USING THE DATABASE. Maria Molnarne. formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany EXPLOSION PROTECTION USING THE DATABASE Maria Molnarne formerly at BAM Federal Institute for Materials Research and Testing, Berlin, Germany Department - Chemical Safety Engineering Outline Database CHEMSAFE

More information

Misuse of Combustible Gas Meters

Misuse of Combustible Gas Meters Misuse of Combustible Gas Meters An incident investigation raised concerns that users of combustible gas meters may be greatly underestimating fire and explosion hazards. Errors result when meters calibrated

More information

Absorption - The process of contacting a vapor and gas stream with an absorbing liquid to remove specific materials from the gas stream.

Absorption - The process of contacting a vapor and gas stream with an absorbing liquid to remove specific materials from the gas stream. Sufe Design and Optvation ofpi-oc.ess Vents and Emission Contid $wteins by Center for Chemical Process Safety Copyright 0 2006 John Wiley & Sons, Tnc. APPENDIX B GLOSSARY Absorption - The process of contacting

More information

1.2.7 Hazard Communication

1.2.7 Hazard Communication 1.2.7 Hazard Communication YOUR ORGANIZATION STANDARD OPERATING PROCEDURES/GUIDELINES TITLE: Hazard Communication NUMBER: 1.2.7 PREPARED BY: SECTION/TOPIC: Member Health and Assistance Programs ISSUE DATE:

More information

17. CARGO MEASUREMENT AND CALCULATION

17. CARGO MEASUREMENT AND CALCULATION Page 1 17. CARGO MEASUREMENT AND CALCULATION 17.1 GENERAL Liquefied gas cargoes are measured and calculated in a similar manner to that of other bulk liquid cargoes such as crude oils and petroleum products.

More information

You should be able to: Describe Equipment Barometer Manometer. 5.1 Pressure Read and outline 5.1 Define Barometer

You should be able to: Describe Equipment Barometer Manometer. 5.1 Pressure Read and outline 5.1 Define Barometer A P CHEMISTRY - Unit 5: Gases Unit 5: Gases Gases are distinguished from other forms of matter, not only by their power of indefinite expansion so as to fill any vessel, however large, and by the great

More information

Flammable Environments Guideline

Flammable Environments Guideline GUIDE Flammable Environments Guideline 2014-0004 The Canadian Association of Petroleum Producers (CAPP) represents companies, large and small, that explore for, develop and produce natural gas and crude

More information

Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI

Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI Thermodynamics ERT 206 Properties of Pure Substance HANNA ILYANI ZULHAIMI Outline: Pure Substance Phases of pure substance Phase change process of pure substance Saturation temperature and saturation pressure

More information

Calibration Requirements for Direct Reading Confined Space Gas Detectors

Calibration Requirements for Direct Reading Confined Space Gas Detectors : Calibration Requirements for Direct Reading Confined Space Gas Detectors However, the definition of bump test has always been a little slippery. Some manufacturers differentiate between a bump test that

More information

USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT

USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT USE OF THE EXCEEDANCE CURVE APPROACH IN OCCUPIED BUILDING RISK ASSESSMENT Kieran J Glynn, Advisor Major Accident Risk, BP, UK The exceedance curve approach was developed following the issue of the 2003

More information

Benefits of Detailed CFD Ventilation Analysis During Early Design Phases. Josué Quilliou Gexcon Consulting

Benefits of Detailed CFD Ventilation Analysis During Early Design Phases. Josué Quilliou Gexcon Consulting Benefits of Detailed CFD Ventilation Analysis During Early Design Phases Josué Quilliou Gexcon Consulting 12 95 NORSOK S-001: Natural ventilation in hazardous areas shall be as good as possible and shall

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 6974-4 First edition 2000-04-01 Natural gas Determination of composition with defined uncertainty by gas chromatography Part 4: Determination of nitrogen, carbon dioxide and

More information

OUTGASSING PHENOMENON IN FLASH POINT TESTING FOR FIRE SAFETY EVALUATION

OUTGASSING PHENOMENON IN FLASH POINT TESTING FOR FIRE SAFETY EVALUATION OUTGASSING PHENOMENON IN FLASH POINT TESTING FOR FIRE SAFETY EVALUATION Gregory E. Gorbett CFEI, CVFI, Christine Kennedy CFEI, Kathryn C. Kennedy CFEI, Patrick M. Kennedy CFEI, CFPS John A. Kennedy and

More information

1 PIPESYS Application

1 PIPESYS Application PIPESYS Application 1-1 1 PIPESYS Application 1.1 Gas Condensate Gathering System In this PIPESYS Application, the performance of a small gascondensate gathering system is modelled. Figure 1.1 shows the

More information

PRAGMATIC ASSESSMENT OF EXPLOSION RISKS TO THE CONTROL ROOM BUILDING OF A VINYL CHLORIDE PLANT

PRAGMATIC ASSESSMENT OF EXPLOSION RISKS TO THE CONTROL ROOM BUILDING OF A VINYL CHLORIDE PLANT PRAGMATIC ASSESSMENT OF EXPLOSION RISKS TO THE CONTROL ROOM BUILDING OF A VINYL CHLORIDE PLANT L.P. Sluijs 1, B.J. Haitsma 1 and P. Beaufort 2 1 Vectra Group Ltd. 2 Shin-Etsu (contact details: Vectra Group

More information

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus

NZQA registered unit standard version 2 Page 1 of 7. Conduct a conformity assessment of explosion-protected apparatus Page 1 of 7 Title Conduct a conformity assessment of explosion-protected apparatus Level 6 Credits 9 Purpose This unit standard covers the assessment and certification of explosion-protected apparatus

More information

Workplace Safety and Health (Major Hazard Installations) Regulations 2017 S 202/2017

Workplace Safety and Health (Major Hazard Installations) Regulations 2017 S 202/2017 Workplace Safety and Health (Major Hazard Installations) Regulations 2017 S 202/2017 THE SCHEDULES FIRST SCHEDULE DANGEROUS SUBSTANCES Regulation 2(1) and Second and Fifth Schedules PART 1 NAME OF DANGEROUS

More information

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter

Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Nitrogen subtraction on reported CO 2 emission using ultrasonic flare gas meter Kjell-Eivind Frøysa, Christian Michelsen Research AS, Bergen, Norway Henning Ekerhovd, StatoilHydro ASA, Kollsnes, Norway

More information

U. S. OIL & REFINING CO. M A T E R I A L S A F E T Y D A T A S H E E T

U. S. OIL & REFINING CO. M A T E R I A L S A F E T Y D A T A S H E E T U. S. OIL & REFINING CO. M A T E R I A L S A F E T Y D A T A S H E E T Page 1 of 5 MIXED BUTANE MSDS No. 611100 Revised 8/10/98 U. S. OIL & REFINING CO. EMERGENCY ASSISTANCE: 3001 Marshall Ave. COMPANY:

More information

NZQA registered unit standard version 1 Page 1 of 8. Conduct detailed inspection of electrical installations for explosive atmospheres

NZQA registered unit standard version 1 Page 1 of 8. Conduct detailed inspection of electrical installations for explosive atmospheres Page 1 of 8 Title Conduct detailed inspection of electrical installations for explosive atmospheres Level 5 Credits 5 Purpose This unit standard is intended for use in the training and assessment of people

More information

HYDROGEN - METHANE MIXTURES : DISPERSION AND STRATIFICATION STUDIES

HYDROGEN - METHANE MIXTURES : DISPERSION AND STRATIFICATION STUDIES HYDROGEN - METHANE MIXTURES : DISPERSION AND STRATIFICATION STUDIES A. Marangon, M.N. Carcassi Department of Mechanical, Nuclear and Production Engineering, University of Pisa, Via Largo Lucio Lazzarino,

More information

METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER

METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER 1250 METHOD 25A - DETERMINATION OF TOTAL GASEOUS ORGANIC CONCENTRATION USING A FLAME IONIZATION ANALYZER 1.0 Scope and Application. 1.1 Analytes. Analyte CAS No. Sensitivity Total Organic Compounds N/A

More information

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV

CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV CHAPTER 16 %UHDWKLQJ*DV0L[LQJ3URFHGXUHV 16-1 INTRODUCTION 16-1.1 Purpose. The purpose of this chapter is to familiarize divers with the techniques used to mix divers breathing gas. 16-1.2 Scope. This chapter

More information

PROPERTIES OF GASES. [MH5; Ch 5, (only)]

PROPERTIES OF GASES. [MH5; Ch 5, (only)] PROPERTIES OF GASES [MH5; Ch 5, 5.1-5.5 (only)] FEATURES OF A GAS Molecules in a gas are a long way apart (under normal conditions). Molecules in a gas are in rapid motion in all directions. The forces

More information

White Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology:

White Paper. Chemical Sensor vs NDIR - Overview: NDIR Technology: Title: Comparison of Chemical Sensor and NDIR Technologies TSN Number: 25 File:\\MII- SRV1\Metron\Bridge_Analyzers\Customer_Service_Documentation\White_Papers\25_G en EGA NDIR vs Chemical Sensor.docx Created

More information

1. PRODUCT INFORMATION

1. PRODUCT INFORMATION Page 1 of 6 Date Prepared: January 10, 2004 Supersedes: January 09, 2004 MSDS Number: 6436 1. PRODUCT INFORMATION Product Identifier: Application and Use: Aviation synthetic lubricant Product Description:

More information

Chem 110 General Principles of Chemistry

Chem 110 General Principles of Chemistry CHEM110 Worksheet - Gases Chem 110 General Principles of Chemistry Chapter 9 Gases (pages 337-373) In this chapter we - first contrast gases with liquids and solids and then discuss gas pressure. - review

More information

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS

ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS XIX IMEKO World Congress Fundamental and Applied Metrology September 6, 9, Lisbon, Portugal ENVIRONMENTAL AND POLLUTANTS GAS ANALYZERS Ana Madeira, Florbela A. Dias and Eduarda Filipe 3 Instituto Português

More information

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS

ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS ACCUMULATION OF HYDROGEN RELEASED INTO A VENTED ENCLOSURE - EXPERIMENTAL RESULTS Hooker, P. 1, Willoughby, D. 2, Hall, J. 3 and Hoyes, J. 4 1 Major Hazards Unit, HSL, Harpur Hill, Buxton, SK17 9JN, U.K,

More information

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS

MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS MODERN APPROACH FOR CONDITION MONITORING OF POWER TRANSFORMERS USING DISSOLVED GAS ANALYSIS Zohra Khan 1, Avinash Paranjpe 2 1 ME Student, Electrical Power System, PES COE/ Dr. B.A.M. University, (India)

More information

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools

Protective Atmospheres, Measurement Technologies and Troubleshooting Tools Protective Atmospheres, Measurement Technologies and Troubleshooting Tools Furnace atmospheres are critical to meet metallurgical specifications defined by control processes. The makeup of a furnace s

More information

Gas Pressure. Pressure is the force exerted per unit area by gas molecules as they strike the surfaces around them.

Gas Pressure. Pressure is the force exerted per unit area by gas molecules as they strike the surfaces around them. Chapter 5 Gases Gas Gases are composed of particles that are moving around very fast in their container(s). These particles moves in straight lines until they collides with either the container wall or

More information

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus

Hazardous Location Coding System - NEC 500. Type of Protection. XP = Explosionproof. IS = Intrinsically Safe Apparatus Hazardous Location Equipment - United States Equipment listed in this category for Hazardous (Classified) Locations is also suitable for installations in areas that are unclassified locations and, unless

More information

4. Using the kinetic molecular theory, explain why a gas can be easily compressed, while a liquid and a solid cannot?

4. Using the kinetic molecular theory, explain why a gas can be easily compressed, while a liquid and a solid cannot? Name Period HW 1 Worksheet (Goals 1-4) - Kinetic Molecular Theory 1. Describe how gases, liquids, and solids compare using the following table. Solids Liquids Gases Volume (definite or indefinite) Molecular

More information

Calibration and Bump Test Requirements for Direct Reading Portable Gas Monitors

Calibration and Bump Test Requirements for Direct Reading Portable Gas Monitors : Calibration and Bump Test Requirements for Direct Reading Portable Gas Monitors Manufacturers and regulatory agencies agree the safest and most conservative approach is to perform a functional test by

More information

Fractional Vaporization of Ignitable Liquids -Flash Point and Ignitability Issues-

Fractional Vaporization of Ignitable Liquids -Flash Point and Ignitability Issues- Fractional Vaporization of Ignitable Liquids -Flash Point and Ignitability Issues- Patrick M. Kennedy, CFEI, CFPS, MIFireE Andrew T. Armstrong, Ph.D., FABC, FAAFS March, 2006 Presentation for the ISFI

More information

ASTM D86 - Procedural Outline

ASTM D86 - Procedural Outline ASTM D86 - Procedural Outline Standard Test Method for Distillation of Petroleum Products and Liquid Fuels at Atmospheric Pressure The following summarizes the procedural steps required for performing

More information

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof

Hazardous Location Coding System - For Division. Class I / II / III, Division 1 / 2 Type of Protection. XP = Explosionproof Hazardous Location Equipment - Canada Equipment listed in this category for Hazardous Locations is also suitable for installations in areas that are non-hazardous locations and, unless referenced in the

More information

Optimization of Separator Train in Oil Industry

Optimization of Separator Train in Oil Industry Optimization of Separator Train in Oil Industry Pawan jain a M.E. Petroleum Engineering, Maharashtra Institute of Technology, Pune-411038 ---------------------------------------------------------------------***---------------------------------------------------------------------

More information

1. PRODUCT INFORMATION

1. PRODUCT INFORMATION Page 1 of 6 Date Prepared: March 22, 2003 Supersedes: November 08, 2002 MSDS Number: 15046 1. PRODUCT INFORMATION Product Identifier: ESSOLUBE HDX PLUS ENGINE OIL 10W-30 Application and Use: Mineral oil

More information

ISO INTERNATIONAL STANDARD

ISO INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO 10156 Third edition 2010-04-01 Gases and gas mixtures Determination of fire potential and oxidizing ability for the selection of cylinder valve outlets Gaz et mélanges de gaz

More information

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS

PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS PART II RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF VESSELS IDENTIFIED BY THEIR MISSIONS TITLE 104 CARRIAGE OF DANGEROUS GOODS SECTION 7 ELECTRICITY CHAPTERS A APPROACH B DOCUMENTS, REGULATIONS AND

More information

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS Annex 3, page 2 ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 15 INERT GAS SYSTEMS The text of existing chapter 15 is replaced by the following: "1 Application This

More information

VALVE MANUFACTURERS ASSOCIATION API 622 API 624

VALVE MANUFACTURERS ASSOCIATION API 622 API 624 VALVE MANUFACTURERS ASSOCIATION API 622 API 624 Written by Rich Davis Manager Business Development Western Hemisphere & China Flexitallic L.P., Deer Park, Texas Presented By: Steve Butler, Shell Global

More information

States of Matter. Q 7. Calculate the average of kinetic energy, in joules of the molecules in 8.0 g of methane at 27 o C. (IIT JEE Marks)

States of Matter. Q 7. Calculate the average of kinetic energy, in joules of the molecules in 8.0 g of methane at 27 o C. (IIT JEE Marks) Q 1. States of Matter Calculate density of NH 3 at 30 o C and 5 atm pressure Q 2. (IIT JEE 1978 3 Marks) 3.7 g of a gas at 25 o C occupied the same volume as 0.184g of hydrogen at 17 o C and at the same

More information

Chemistry HP Unit 6 Gases. Learning Targets (Your exam at the end of Unit 6 will assess the following:) 6. Gases

Chemistry HP Unit 6 Gases. Learning Targets (Your exam at the end of Unit 6 will assess the following:) 6. Gases Chemistry HP Unit 6 Gases Learning Targets (Your exam at the end of Unit 6 will assess the following:) 6. Gases 6-1. Define pressure using a mathematical equation. 6-2. Perform calculations involving pressure,

More information

NSPS SUBPART Ka Check-off Form JULY 11, LAFAYETTE ROAD NO., ST. PAUL, MN

NSPS SUBPART Ka Check-off Form JULY 11, LAFAYETTE ROAD NO., ST. PAUL, MN 520 LAFAYETTE ROAD NO., ST. PAUL, MN 55155-4194 NSPS FORM NSPS-Ka NSPS SUBPART Ka Check-off Form JULY 11, 2005 I. Introduction An owner or operator may fill in this form in replacement of a highlighted

More information

acrolein, acetaldehyde and acetone( cm -1 ); methanol (1306 cm -1 ); ethylene (949 cm -1 ); and isoprene (893 cm -1 ).

acrolein, acetaldehyde and acetone( cm -1 ); methanol (1306 cm -1 ); ethylene (949 cm -1 ); and isoprene (893 cm -1 ). acrolein, acetaldehyde and acetone(1550 1800 cm -1 ); methanol (1306 cm -1 ); ethylene (949 cm -1 ); and isoprene (893 cm -1 ). 5 Figure 4a 6 Figure 4b Figure 4c 7 Figure 5 Questions in Student Handout

More information

Insulation. SOLKANE 365 SOLKANE 365/227 Flammability characteristics and handling. Solvay Special Chemicals

Insulation. SOLKANE 365 SOLKANE 365/227 Flammability characteristics and handling. Solvay Special Chemicals Insulation SOLKANE 365 SOLKANE 365/227 Flammability characteristics and handling Solvay Special Chemicals Introduction Solkane 365mfc has been developed by SOLVAY as a liquid blowing agent for rigid polyurethane

More information

Kinetic-Molecular Theory

Kinetic-Molecular Theory GASES Chapter Eleven Kinetic-Molecular Theory! Recall that our only previous description of gases stated that gases completely fill and take the shape of their containers.! The Kinetic-Molecular Theory

More information

"CONFINED SPACE ENTRY... A REFRESHER PROGRAM"

CONFINED SPACE ENTRY... A REFRESHER PROGRAM MAJOR PROGRAM POINTS "CONFINED SPACE ENTRY... A REFRESHER PROGRAM" Training for THE OSHA PERMIT-REQUIRED CONFINED SPACES STANDARD Quality Safety and Health Products, for Today...and Tomorrow OUTLINE OF

More information

General information on explosion protection

General information on explosion protection 427 Why explosion protection? Explosion protection for electrical and mechanical machinery is an important precautionary measure to ensure the safety of persons and all kinds of production, storage and

More information

ISO INTERNATIONAL STANDARD. Welding consumables Gases and gas mixtures for fusion welding and allied processes

ISO INTERNATIONAL STANDARD. Welding consumables Gases and gas mixtures for fusion welding and allied processes INTERNATIONAL STANDARD ISO 14175 Second edition 2008-03-01 Welding consumables Gases and gas mixtures for fusion welding and allied processes Produits consommables pour le soudage Gaz et mélanges gazeux

More information

MATERIAL SAFETY DATA SHEET

MATERIAL SAFETY DATA SHEET Sasol Solvents Trading as Sasol Chemicals North America LLC 900 Threadneedle Houston, Texas 77079 MATERIAL SAFETY DATA SHEET EMERGENCY NUMBERS: CHEMTREC (800) 424-9300 MSDS or Product Information: 281

More information

J. David Hailey Ph.D. Vice President, Business Development COSA Xentaur 7125 North Loop East Houston, TX 77028

J. David Hailey Ph.D. Vice President, Business Development COSA Xentaur 7125 North Loop East Houston, TX 77028 METHODOLOGY FOR RESIDUAL OXYGEN CALORIMETRY J. David Hailey Ph.D. Vice President, Business Development COSA Xentaur 7125 North Loop East Houston, TX 77028 KEYWORDS Combustion Air Requirement Index (CARI)

More information

PUBLIC COMPANY ORLEN LIETUVA OCCUPATIONAL HEALTH AND SAFETY PROCEDURE BDS-12 USE OF PORTABLE GAS ANALYZERS I. GENERAL

PUBLIC COMPANY ORLEN LIETUVA OCCUPATIONAL HEALTH AND SAFETY PROCEDURE BDS-12 USE OF PORTABLE GAS ANALYZERS I. GENERAL PUBLIC COMPANY ORLEN LIETUVA APPROVED BY Deputy Director of Quality, Labor Safety and Environmental Control Director 30 November 2017 Order No TV1(1.2-1)-457 OCCUPATIONAL HEALTH AND SAFETY PROCEDURE BDS-12

More information

DSEAR-Classification of Hazardous Areas (Zoning) and Selection of Equipment

DSEAR-Classification of Hazardous Areas (Zoning) and Selection of Equipment OHSS: Classification of Hazardous areas (Zoning) and selection of equipment Guidance 202 DSEAR-Classification of Hazardous Areas (Zoning) and Selection of Equipment Contents Overview... 2 Assessing the

More information

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES

I.CHEM.E. SYMPOSIUM SERIES NO. 97 BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES BUOYANCY-DRIVEN NATURAL VENTILATION OP ENCLOSED SPACES M. R. Marshall* and P. L. Stewart-Darling* A simple mathematical model for the buoyancy driven ventilation of an enclosed space, using a two-pipe

More information

ASTM UPDATE to COQA. COQA Meeting Feb San Antonio. RJ (Bob) Falkiner SR (Steve) David GJ (Jay) Grills W (Wayne) Kriel

ASTM UPDATE to COQA. COQA Meeting Feb San Antonio. RJ (Bob) Falkiner SR (Steve) David GJ (Jay) Grills W (Wayne) Kriel ASTM UPDATE to COQA COQA Meeting Feb 21 2018 San Antonio RJ (Bob) Falkiner SR (Steve) David GJ (Jay) Grills W (Wayne) Kriel WHAT HAS CHANGED IN THE LAST 5 YEARS? CCQTA TVP / RVP PROJECT INITIATED IN FEB

More information

DURING the course of certain investigations it became

DURING the course of certain investigations it became VOLUMETRIC DETERMINATION OF ETHER OR CYCLOPROPANE, CARBON DIOXIDE, NITROUS OXIDE AND OXYGEN IN ANESTHETIC MIXTURES By F. J. PRIME DURING the course of certain investigations it became necessary to be able

More information

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE

COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE COAL MINES TECHNICAL SERVICES, GAS DETECTION RELATED SERVICES FOR MINES RESCUE Peter Mason Manager, Coal Mines Technical Services, a division of Mines Rescue Pty Ltd, Australia ABSTRACT The NSW Mines Rescue

More information

Transport of gas tanks for motor vehicles

Transport of gas tanks for motor vehicles Committee of Experts on the Transport of Dangerous Goods and on the Globally Harmonized System of Classification and Labelling of Chemicals Transport of gas tanks for motor vehicles Submitted by the expert

More information

THE SIGNIFICANCE OF HAZARD ENDPOINTS IN QUANTITATIVE RISK ANALYSIS

THE SIGNIFICANCE OF HAZARD ENDPOINTS IN QUANTITATIVE RISK ANALYSIS THE SIGNIFICANCE OF HAZARD ENDPOINTS IN QUANTITATIVE RISK ANALYSIS John B. Cornwell and Jeffrey D. Marx Presented At 6 Process Plant Safety Symposium Houston, Texas April -2, 6 Presented By Quest Consultants

More information

Guide to Gases and Vapours

Guide to Gases and Vapours Guide to Gases and Vapours Properties of dangerous Gases and Vapours Flammable and toxic gases and vapours may occur in many places. To deal with the toxic risk and the danger of explosion this is what

More information

FIRE AND EXPLOSION HAZARD MANAGEMENT

FIRE AND EXPLOSION HAZARD MANAGEMENT FIRE AND EXPLOSION HAZARD MANAGEMENT Toolbox Talk Practical Applications (Part 2) Setting the standard in oil and gas safety 1 WHAT SHOULD I KNOW ABOUT FIRES AND EXPLOSIONS» One-size-fits-all solution

More information

NZQA registered unit standard version 3 Page 1 of 6

NZQA registered unit standard version 3 Page 1 of 6 Page 1 of 6 Title Report on the integrity of explosion-protected electrical apparatus in explosive atmospheres Level 3 Credits 3 Purpose This unit standard covers the explosion-protection aspects of plant

More information